Downloads for Isolation Power Transformers (N-66A)

P OWE R T RAN S FO R M E R
CHASSIS MOUNT : Isolation
N-66A
Electrical Specifications (@25°C)
1. Maximum Power:
250 VA
2. Input Voltage:
Parallel: 115V@50/60Hz
Series:230V@50/60Hz
3. Output Voltage:
115V + 5%
4. Full Secondary Load: 2.17 Amps RMS
5. Voltage Regulation:
5 % TYP @ full load to no load
Description:
The N-66A is power transformer for isolating equipment from direct connection to the
power line. It is constructed with nonconcentrically wound coils. The primary and
secondary are wound on separate arbors, then assembled on a laminate core
side-by-side separated by insulation. This prevents electrical connection under
normal or overload conditions between the primary and secondary windings.
A
Safety:
PRIMARY
These units are designed with 1500V isolation between winding to winding and
between winding and core. Materials and construction are rated for Class B
insulation system.
D
B
Dimensions:
F
LEADS
Unit: In inches
A
B
C
D
E
F
4.625
3.937
4.625
3.00
3.625
2.250
Weight: 11.0 Lbs.
Mounting Holes: .375 x .187”
Connections: 10.0±1” leads, 0.250±0.062” Skin & Tin
Schematic:
E
BLK
C
YEL
RED
BLU
RED
BRN
SHIELD
WHT
INPUT - Series: BLK to BRN, JUMPER YEL to BLU
Parallel: BLK to YEL, JUMPER BLK to BLU and YEL to BRN
OUTPUT: RED to RED
SHIELD: WHT
RoHS Compliance: As of manufacturing date February 2005, all standard products
meet the requirements of 2011/65/EU, known as the RoHS initiative.
SH LEAD
SEC LEAD S
* Upon printing, this document is considered “uncontrolled”. Please contact Triad Magnetics’
website for the most current version.
Web: www.TriadMagnetics.com
Phone 951-277-0757
Fax 951-277-2757
460 Harley Knox Blvd.
Perris, California 92571
Publish Date: December 4, 2013