UL IECEX UL 13 0077U 11 20 14

IECEx Certificate
of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com
Certificate No.:
IECEx UL 13.0077U
Status:
Current
issue No.:1
Date of Issue:
2014-11-20
Applicant:
Littelfuse Philippines, Inc
Page 1 of 4
Certificate history:
Issue No. 1 (2014-1120)
Issue No. 0 (2013-1125)
Lima Technology Centre
Special Economic Zone
Lipa City-Malvar
Batangas
Philippines
Electrical Apparatus:
Optional accessory:
Intrinsic Safety Fuses, 305 and 304 Series
Type of Protection:
Intrinsic Safety "ia"
Marking:
Ex ia IIC
Approved for issue on behalf of the IECEx
Certification Body:
Erin LaRocco
Position:
Senior Project Engineer
Signature:
(for printed version)
2014-11-20
Date:
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.
Certificate issued by:
UL LLC
333 Pfingsten Road
Northbrook IL 60062-2096
United States of America
IECEx Certificate
of Conformity
Certificate No.:
IECEx UL 13.0077U
Date of Issue:
2014-11-20
Issue No.: 1
Page 2 of 4
Littelfuse Philippines, Inc
Manufacturer:
Lima Technology Centre
Special Economic Zone
Lipa City-Malvar
Batangas
Philippines
Additional Manufacturing location
(s):
This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and
found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products
covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This
certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents
as amended.
STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified
documents, was found to comply with the following standards:
IEC 60079-0 : 2011
Explosive atmospheres - Part 0: General requirements
IEC 60079-11 : 2011
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-26 : 2006
Explosive atmospheres - Part 26: Equipment with equipment protection level (EPL) Ga
Edition: 6.0
Edition: 6.0
Edition: 2
This Certificate does not indicate compliance with electrical safety and performance requirements other than those
expressly included in the Standards listed above.
TEST & ASSESSMENT REPORTS:
A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in
Test Report:
US/UL/ExTR13.0084/00
Quality Assessment Report:
GB/BAS/QAR10.0018/03
US/UL/ExTR13.0084/01
IECEx Certificate
of Conformity
Certificate No.:
IECEx UL 13.0077U
Date of Issue:
2014-11-20
Issue No.: 1
Page 3 of 4
Schedule
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
The 304 and 305 Series fuses are encapsulated fuse assemblies suitable for use in intrinsically safe apparatus
and associated apparatus.
Please see Annex for additional details and Schedule of Limitations for Ex Components.
CONDITIONS OF CERTIFICATION: NO
IECEx Certificate
of Conformity
Certificate No.:
IECEx UL 13.0077U
Date of Issue:
2014-11-20
Issue No.: 1
Page 4 of 4
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):
Issue 1: Addition of 304 Series fuse.
Annex: Annex for IECEx UL 13.0077U Issue 1.pdf
Annex for IECEx UL 13.0077U Issue 1
The 304 and 305 Series Intrinsic Safety fuses are encapsulated fuse assemblies suitable for
use in intrinsically safe apparatus and associated apparatus.
The model nomenclature is as follows:
0305
I
.050
II
M
III
R
IV
P
V
I – Series:
0304 or 304 = 304 Series
0305 or 305 = 305 Series
II – Current Rating
.050 = 0.050 A rating
.200 = 0.200 A rating
.080 = 0.080 A rating
.250 = 0.250 A rating
.100 = 0.100 A rating
.500 = 0.500 A rating
.160 = 0.160 A rating
.750 = 0.750 A rating
III – Quantity Code:
Any alphanumeric character(s) representing number of pieces in package
IV – Packaging Code (304 Series only):
Any alphanumeric character(s) representing the type of package
V – Lead-Free Code (optional):
P = Lead-free solder
Temperature range(s):
The 304 and 305 Series Intrinsic Safety fuses are suitable for use in the following ambient
temperature ranges. The limits are based on the application of 1.7 times the nominal current
rating, In, of the fuse, temperature rise characteristics and the maximum operating temperature
of the encapsulation:
Cat. No.
305 Series
304 Series
Nominal Current
Rating, In
≤ 0.200 A
0.250 A
0.500 A
0.750 A
≤ 0.200 A
0.250 A
0.500 A
0.750 A
Ambient
Temperature
Range
-40°C to +50°C
-40°C to +46°C
-40°C to +74°C
-40°C to +46°C
-40°C to +60°C
-40°C to +56°C
-40°C to +84°C
-40°C to +56°C
The following surface temperature rise values were measured on encapsulated samples of the
components when carrying a current of 1.7 times the nominal current rating, In, of the fuse:
Model
Nominal Current
Rating
Maximum Surface
Temperature Rise
≤ 0.200 A
52°C
0.250 A
58°C
0.500 A
30°C
0.750 A
41°C
≤ 0.200 A
88°C
0.250 A
52°C
0.500 A
52°C
0.750 A
45°C
305 Series
304 Series
Electrical data
The 304 and 305 Series Fuses are rated 277 V AC/DC, 1500A AC/DC breaking capacity
These fuses were measured as having the following minimum resistance values at the
following temperatures:
Model
304 and
305
Series
Ampere Rating
(A)
0.050
0.080
0.100
0.160
0.200
0.250
0.500
0.750
Resistance (Ω)
At -20°C
At -40°C
9.202
9.010
6.031
5.963
2.709
2.668
2.297
2.292
1.935
1.839
1.268
1.105
0.392
0.368
0.219
0.196
Schedule of Limitations for Ex Components

A temperature classification is not applied to Ex Components per Annex B, Note 2 of IEC 600790. The fuses have been evaluated for use in the following ambient temperature ranges:
Cat. No.
305 Series
304 Series
Nominal Current
Rating, In
Ambient
Temperature Range
≤ 0.200 A
-40°C to +50°C
0.250 A
-40°C to +46°C
0.500 A
-40°C to +74°C
0.750 A
-40°C to +46°C
≤ 0.200 A
-40°C to +60°C
0.250 A
-40°C to +56°C
0.500 A
-40°C to +84°C
0.750 A
-40°C to +56°C

Use of the fuses outside of the ambient temperature ranges specified in the table is subject to
additional investigation.

These components have been judged on the basis of spacings in accordance with Table 5 of IEC
60079-11, and are considered suitable for use in circuits with peak voltages not exceeding 375 V
based on these separation distances alone.