Purpose and application
The MULTIeco control unit controls the lighting at the workplace
and in offices according to the level of daylight and the presence of persons to increase comfort and save energy.
MULTIeco
The control unit can be installed in luminaires (e.g. floor standing luminaires) or in suspended ceilings.
Function
Sensors measure the brightness in the section to be controlled
and switch on the connected luminaires as soon as the level
of daylight is less than an adjustable brightness switching
threshold.
The sensors also detect the presence of people.
When people are no longer present, the connected luminaires
switch off after an adjustable delay period.
Daylight-dependent switching and presence detection can be
activated and deactivated using various operating modes.
Design
The control unit is made up of the following components:
A
Control unit
Fitting instructions
G
L
MULTIeco
N
• Adjusting screw “time” (A): switch-off delay time
Sensor
F
E
B
C
• Sensor connection (B)
• DIP switch (C)
• Adjusting screw “lux” (D): brightness switching threshold
• Button connection (E)
D
• Load contact (F)
• Power supply connection (G)
Installation
Safety instructions
The control unit must only be installed and put into operation
by a qualified electrician. The applicable safety regulations and
accident prevention regulations must be observed.
WARNING!
Exposed, live cables or damaged housing.
Danger of electric shock!
• Only work on the control unit when it is deenergised.
CAUTION!
Destruction of the control unit and other devices
through incorrect mounting!
• Do not operate any other control units on the
control line.
• Use the LMS CI BOX mounting kit for ceiling
installation.
• Ensure that the external pushbutton is designed
for the mains voltage.
• Do not wire the control and pushbutton lines
with an external voltage, especially not a mains
voltage of 230 V.
• Do not exceed the maximum number of electronic control gears.
Connecting the control unit
N L
L
N
PE
L
N
Left: Individual operation with max. 2 sensors
L
N
Sensor
MULTIeco
H
MULTIeco
~
~
~
~
L
H
H Sensor
J Pushbutton
M
J
J
Right: Networked operation with up to 4 MULTIeco control units
and central presence detection
Sensor
N
QTi/QT Fit/QTP 5
EVG
L
N
K Lamp
1 2 3 4
L Y-Connector
M Y-Connector Screw
Sensor
MULTIeco
K
1 2 3 4
H
N To luminaire group 1
O To luminaire group 2
QTi/QT Fit/QTP 5
EVG
K
J
O
Page 1 of 2
Appendix
Technical data
Operating voltage
100-240 VAC / 50-60 Hz
(DC operation permissible)
Supply connection
L, N (PE not required)
Pushbutton input
Potential-free make contact, max. line
length 50 m
Sensor connection
Max. 2 sensors, max. line length 25 m
Pin assignment:
1: Supply voltage (+ 3.3 V)
2: Light measurement
3: Motion signal
4: Ground
Max. load contact
load capacity
5 A resistive load
Fuse
External 16 A
Power consumption
Operation: 1 W
Standby: < 0.5 W
Max. number of ECGs: 20 (depends on
the ECG type to be connected)
Ambient temperature 0 °C … +50 °C
Adjustable light value 20-600 lux (measured at sensor)
Protection type
IP 20
Protection class
II
Dimensions
(L x W x H)
118 x 30 x 21 mm
Hole distance for
mounting
110 mm
VI 2011
MULTIeco_ma0611en_we1.02.indd
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 - 200
(kostenpflichtig / charges apply)
Fax.: +49 (0) 1803 677 - 202
www.osram.com
The CE requirements to EN 60928 are fulfilled. The EMC requirements to EN 61547 are fulfilled.
www.osram.de
40083214053022
4008321405302
Conformity with the relevant EU directives is
confirmed by the CE symbol.
Page 2 of 2