UPS12580 Spec Sheet -(2.35M

Powered by
UPS12580
UPS 12580 is specially designed for high efficient discharge
application. Its characteristics are high energy density, small
footprint and high discharge efficiency. It can be used for more
than 260 cycles at 100% discharge in cycle service, up to 5 years
in standby service.
Specification
Cells Per Unit
Voltage Per Unit
6
12
580W @ 5min-rate to 1.60V per PCS @25
96.7W@ 5min-rate to 1.60V per CELL @25
Capacity
Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging
Current Limit
Equalization and Cycle Service
Self Discharge
Terminal
Container Material
Approx. 2.83 kg(6.24 lbs)
130A(5sec)
Approx. 12.5m
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15 ~40 ( 5 ~104 )
Storage: -15 ~40 ( 5 ~104 )
25
3 (77
5 )
13.5 to 13.8 VDC/unit Average at 25
4.80A
(77
(77
)
) [*P]
TUV Asia Pacific Ltd.
Taiwan Branch
(77
)
TUV Asia Pacific Ltd.
Taiwan Branch
14.4 to 15.0 VDC/unit Average at 25 (77 )
CSB Batteries can be stored for more than 6 months at
25 (77 ). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
F2-Faston Tab 250
ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Dimensions :
Overall Height (H)
98.3±1.0(3.87±0.04)
Unit: mm (inch)
Container height (h)
94.0±1.0 (3.70±0.04)
CSB-manufactured VRLA
(Absorbent Glass Mat type)
batteries are UL-recognized
components under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
Length (L)
151.0±2.0 (5.95±0.08)
Width (W)
65.0±1.0 (2.56±0.04)
(http://www.csb-battery.com)
The system of manufacturer was certified
by TUV CERT according to ISO 9001,ISO 14001.
Constant Current Discharge Characteristics
Unit:A (25
,77
)
F.V/Time
2MIN
3MIN
4MIN
5MIN
6MIN
7MIN
8MIN
10MIN
15MIN
20MIN
30MIN
60MIN
90MIN
1.60V
95.1
75.5
63.4
54.1
47.2
42.3
38.5
32.3
23.0
18.3
13.2
7.42
5.31
1.67V
85.3
71.0
60.2
51.7
45.6
41.2
37.6
31.7
22.7
18.1
13.0
7.33
5.20
1.70V
81.1
68.3
58.4
50.4
44.6
40.4
37.1
31.3
22.7
18.0
12.9
7.24
5.17
1.75V
73.6
62.6
53.7
47.2
42.2
38.5
35.6
30.1
22.1
17.5
12.7
7.11
5.03
1.80V
66.1
56.8
48.8
43.2
39.3
36.3
33.2
28.4
21.1
16.9
12.4
6.92
4.91
1.85V
59.4
49.7
43.5
39.3
36.3
32.9
30.3
26.1
19.6
15.8
11.7
6.61
4.70
Constant Power Discharge Characteristics
F.V/Time
1.60V
Unit:W (25
,77
)
2MIN
3MIN
4MIN
5MIN
6MIN
7MIN
8MIN
10MIN
15MIN
20MIN
30MIN
60MIN
90MIN
908
774
663
580
516
469
427
361
261
208
150
84.2
59.3
1.67V
877
748
643
565
504
462
420
356
261
206
149
84.0
58.9
1.70V
859
730
630
556
499
453
414
353
258
206
149
83.6
58.8
1.75V
808
688
601
538
481
441
402
343
254
203
148
83.1
58.4
1.80V
750
640
568
505
458
419
383
329
245
197
145
81.7
57.6
1.85V
674
586
514
463
424
384
352
305
229
186
138
78.9
55.6
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
RA1604
UPS 12580
140
0.025
2.60
120
0.021
2.40
100
0.018
2.20
80
0.014
2.00
60
0.011
1.80
40
0.007
1.60
20
0.004
1.40
0
140
0.025
2.60
120
0.021
2.40
100
0.018
2.20
80
0.014
2.00
60
0.011
1.80
40
0.007
1.60
20
0.004
1.40
)Ratio
1PWx 5Min
1PWx2.5Min
0.012PA
3
6
9
12
15
18
68
)Ratio
1PWx 5Min
1PWx2.5Min
14.70V
2.45V
0.012PA
1PW
0
3
6
9
12
15
0.62PW
0.47PW
0.25PW 0.16PW
18
Charging Procedures
Application
Cycle Use
Standby
Charge Voltage(V/Cell)
Temperature
25 (77 )
Set Point
Allowable Range
2.45
2.40~2.50
25 (77 )
2.275
2.25~2.30
Max.Charge Current
Final Discharge
Voltage V/Cell
1.75
0.05PA
Discharge
Power(W)
0.05P>(W)
1.60
0.05 P (W)<0.125P 0.125 P (W)<0.5P
EUROPE OFFICE
Tel: +31(0)180 418 140
Fax: +31(0)180 418 327
E-mail: [email protected]
Tel: +886-2-2880-5600
Fax: +886-2-2888-3300
+86-21-5064-1046
E-mail: [email protected]
1.70
+86-10-5820-5336/5338
+86-10-58203053
Tel: +86-755-8831-6488/6396/16356
Fax: +86-755-8831-6548
E-mail: [email protected]
1.30
(W) 0.5P