Specification sheet

Features:
CBI2420A
DC UPS
•
•
•
•
•
•
•
•
INPUT
OUTPUT
PROTECTION
LOAD
OUTPUT
BATTERY
OUTPUT
OTHERS
Input: Single-phase 115 - 277 VAC
Output Load: power supply 24 VDC; 20 A
Output: Battery charging 24 VDC; 20 A
Suited for the following battery types:
Open Lead Acid, Sealed Lead Acid, lead Gel and Ni-Cd (option)
Automatic diagnostic of battery status.
Switching technology, output voltage 22-18.8 VDC
Three charging levels: Boost, trickle and recovery
Protection degree IP20 - DIN rail mountable
Cat. No.
CBI2420A
Nominal Input Voltage
Voltage range
Inrush Current (Vn – In nom. Load). I2t
Frequency
Input Current (115 – 230 VAC)
Internal fuse (factory replaceable)
External Fuse (recommended) MCB curve B
115 / 230 ~ 277 VAC
90-135 / 180-305 VAC
≤35 A ≤ 5 msec
47 – 63 Hz
8.0 ~ 4.2 A
10 A
16 A
Output Voltage (Vn) / Nominal Current (In)
Output Current In
Efficiency (at 50% of rated current)
Turn-On delay after applying input voltage
Start up with Strong Load (capacitive load)
Dissipation power load max
24 VDC / 20A
20 A
≥ 91 %
1 sec. (max)
Yes, Unlimited
48 W
Short-circuit protection
Over Load protection
Over Voltage Output protection
Over Temperature protection
Yes
Yes
Yes (typ. 35 VDC)
Yes
Output voltage (at In)
Nominal current Iload
Continuous current (without battery) Iload= In
Continuous current (with battery) Iload= In+ Ibatt
Max. Current Output Load (Main) Iload (4 sec.)
Max. Current Output Load (Back Up) Iload (4 sec.)
Push Button or Remote Input Control (RTCONN cable)
Time Buffering; min (switch output off without main input)
Protection alarm against total discharge
Threshold alarm for battery almost flat
22 ~ 28.8 VDC
1.1 x In A ± 5%
20 A
40 A
60 A max.
40 A max.
Start From Battery Without Main
0.5,2,5,10,15,20,30,45,60,∞; Require SW
19-20V DC battery
20-21 V DC battery
Boost charge (25 °C) (at In)
Max. time Bust Charge
Min. time Bust Charge
Trickle charge (25 °C) (at In)
Jumper Configuration battery type (V cell) Ni-Cd (optional)
Recovery Charge
Charging current max Ibatt
Charging current limiting Iadj
Reverse battery protection
Sulfated battery check
Detection of element in short circuit
Quiescent Current
Charging Curve automatic: IUoUo
Remote Input Control (RTCONN cable)
28.8 VDC
15 h
1 min.
27.5 VDC
2.23; 2.25; 2.27; 2.30; NiCd: 1.50 (20 elem.)
2 ~ 16 VDC
20 A ± 5%
10 – 100 % / Ibatt
Yes
Yes by Jumper
Yes
≤ 5 mA
3 stage
Boost /Trickle / Recovery
Ambient temperature (operation)
De Rating Ta > 50°C
Ambient temperature Storage
Humidity at 25°C no condensation
Cooling
MTBF (IEC 61709)
-25 – +70°C
- 2.5%(In) / °C
-40 – +85°C
95%
Auto convention
> 300.000 h
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
156
CBI2420A
DC UPS
The Altech DC-UPS system is built to optimize power
management. The available power is automatically allocated
between load and battery, supplying power to the load is the first
priority. For high inrush applications the charging power will
reroute automatically to the load. In this case the maximum
available current on the load output is two times the value of the
device rated current.
Jumper for Battery Type Selection
1 2 3 4 5
6
7
1 2 3 4 5
6
7
Sealed
Lead Low
7
MAINS
LOW BATTERY
OR
OR BATTERY
BACKUP REPLACEMENT
Gel
Battery
1 2 3 4 5
6
7
TIME
BUFFERING
Gel
Battery (1)
1 2 3 4 5
6
7
BATTERY
START
NiCd NiMh (1)
1 2 3 4 5
6
Yes
Yes
Yes
1A 30 VDC/60 VAC
1mA @ 5 VDC
7
6
1
2
3
7
Fast Charge
Enable2
1 2 3 4 5
6
7
1 2 3 4 5
6
7
MAINS
OR
BACKUP
LOW BATTERY
OR BATTERY
REPLACEMENT
DIAGNOSIS
BATTERY
L N
Jumper for Functional Setting
1 2 3 4 5
+ (2) +
OUTPUT LOAD
Battery Life
Test On1
Signal Output Contacts
Main or Backup Power
Battery Power Low
Battery Fault
Max. Current Rating (Resistive Load)
Minimum Permissible Current Rating
6
– (1) –
5 6 7 8 9 10
Sealed
Lead High
1 2 3 4 5
The Battery Care concept based on algorithms that achieve rapid
and automatic charging, battery optimization during charging
time, flat batteries recovery and real time diagnostic The Real
Time Auto-diagnostic system, monitors battery faults, sulfated
battery, short circuit battery elements, reverse polarity
connection, battery disconnect. This conditions are detected and
identified by the number of blinks of the diagnosis Led.
Open
Lead
Fast Recovery
Charge (2)3
– (3) –
+ (4) +
Jumper present: life test enabled.
Jumper present: fast test enabled.
Jumper present: fast recovery charge
enabled only for size 3. Possibility to
recharge the battery also when the
voltage is close to zero with the
maximum power of the device.
RJ45 Connection Input/Output
Temp. Comp. Battery (with ext. probe)
Remote monitoring display
Can Bus
Yes - Optional
Yes - Optional
No
Environment
Insulation voltage (IN/OUT)
Insulation voltage (input / ground)
Insulation voltage (Output / ground)
Protection Class (EN/IEC 60529)
Pollution Degree Environment
Connection TB, Screw Terminal
Protection class (Ground Connected)
Dimensions (WxHxD)
5.91x4.53x5.32 in
Weight (approx.)
Battery
3000 VAC
1605 VAC
500 VAC
IP20
2
4 mm² (30-10 AWG)
Class I
150x115x135 mm
Load
Mains or Backup
Out 2
Battery Low or
Battery Replacement
Start From Battery
1.55 kg (3.5 Lbs)
Safety and EMC
IEC/EN 60335-2-29
EN60950 / UL1950 / CE
EN54-4
89/336/EEC
DIN41773
IEC 61000-6-4
IEC 61000-6-2
The Altech DC-UPS system is designed to charge and monitor all
battery types, by selecting the battery type via jumpers. The
predefined curves include Open Lead Acid, Sealed Lead Acid, Gel,
Ni-Cd (optional) battery types. The charging curve are
programmed to automatically switch between Recovery Charge,
Boost charge and Trickle charge. The continuous battery efficiency
monitoring, reduces battery damage risk and allows a safe
operation in permanent connection.
Voltage
Voltage / Current
Battery charger standard compliance
Safety standards compliance:
Fire Detection and alarm compliance
EMC Directive
Charging cycle
Emission
Immunity
Out 1
CBI
In Vac
Current
Recovery Charge
Fast / Boost Charge
Tickle / Float Charge
A compact and rugged metal case with DIN rail mounting bracket
provide an easy installation and an IP20 protection.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
157