Specification sheet

Features:
CBI4810A
DC UPS
•
•
•
•
•
•
•
•
INPUT
OUTPUT
PROTECTION
LOAD
OUTPUT
BATTERY
OUTPUT
OTHERS
Input: Single-phase 115 - 277 VAC
Output Load: power supply 48VDC; 10A
Output: Battery charging 48VDC; 10A
Suited for the following battery types:
Open Lead Acid, Sealed Lead Acid, lead Gel and Ni-Cd (option)
Automatic diagnostic of battery status.
Switching technology, output voltage 44-57.6VDC
Three charging levels: Boost, trickle and recovery
Protection degree IP20 - DIN rail mountable
Cat. No.
CBI4810A
Nominal Input Voltage
Voltage range
Inrush Current (Vn – In nom. Load). I2t
Frequency
Input Current (115 – 230 VAC)
Internal fuse (factory replaceable)
External Fuse (recommended) MCB curve B
115 / 230 ~ 277 VAC
90-135 / 180-305 VAC
≤35 A ≤ 5 msec
47 – 63 Hz
8.0 ~ 4.2 A
10 A
16 A
Output Voltage (Vn) / Nominal Current (In)
Output Current In
Efficiency (at 50% of rated current)
Turn-On delay after applying input voltage
Start up with Strong Load (capacitive load)
Dissipation power load max
48 VDC / 10A
10 A
≥ 91 %
1 sec. (max)
Yes, Unlimited
54 W
Short-circuit protection
Over Load protection
Over Voltage Output protection
Over Temperature protection
Yes
Yes
Yes (typ. 90 VDC)
Yes
Output voltage (at In)
Nominal current Iload
Continuous current (without battery) Iload= In
Continuous current (with battery) Iload= In+ Ibatt
Max. Current Output Load (Main) Iload (4 sec.)
Max. Current Output Load (Back Up) Iload (4 sec.)
Push Button or Remote Input Control (RTCONN cable)
Time Buffering; min (switch output off without main input)
Protection alarm against total discharge
Threshold alarm for battery almost flat
44 ~ 57.6 VDC
1.1 x In A ± 5%
10 A
20 A
30 A max.
20 A max.
Start From Battery Without Main
0.5,1,3,5,10,15,20,30,45,60,∞; Require SW
38-40V DC battery
40-42V DC battery
Boost charge (25 °C) (at In)
Max. time Bust Charge
Min. time Bust Charge
Trickle charge (25 °C) (at In)
Jumper Configuration battery type (V cell) Ni-Cd (optional)
Recovery Charge
Charging current max Ibatt
Charging current limiting Iadj
Reverse battery protection
Sulfated battery check
Detection of element in short circuit
Quiescent Current
Charging Curve automatic: IUoUo
Remote Input Control (RTCONN cable)
56.6 VDC
15 h
1 min.
55 VDC
2.23; 2.25; 2.27; 2.30; NiCd: 1.50 (40 elem.)
2 ~ 24 VDC
10 A ± 5%
10 – 100 % / Ibatt
Yes
Yes by Jumper
Yes
≤ 5 mA
3 stage
Boost /Trickle / Recovery
Ambient temperature (operation)
De Rating Ta > 50°C
Ambient temperature Storage
Humidity at 25°C no condensation
Cooling
MTBF (IEC 61709)
-25 – +70°C
- 2.5%(In) / °C
-40 – +85°C
95%
Auto convention
> 300.000 h
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
160
CBI4810A
DC UPS
The Altech DC-UPS system is built to optimize power
management. The available power is automatically allocated
between load and battery, supplying power to the load is the first
priority. For high inrush applications the charging power will
reroute automatically to the load. In this case the maximum
available current on the load output is two times the value of the
device rated current.
Jumper for Battery Type Selection
1 2 3 4 5
6
1 2 3 4 5
6
7
6
6
7
MAINS
LOW BATTERY
OR
OR BATTERY
BACKUP REPLACEMENT
7
TIME
BUFFERING
Gel
Battery (1)
1 2 3 4 5
6
7
BATTERY
START
NiCd NiMh (1)
1 2 3 4 5
6
7
Yes
Yes
Yes
1A 30 VDC/60 VAC
1mA @ 5 VDC
6
1
2
3
7
Fast Charge
Enable2
1 2 3 4 5
6
1 2 3 4 5
6
7
7
MAINS
OR
BACKUP
LOW BATTERY
OR BATTERY
REPLACEMENT
DIAGNOSIS
BATTERY
L N
Jumper for Functional Setting
1 2 3 4 5
+ (2) +
OUTPUT LOAD
Gel
Battery
1 2 3 4 5
– (1) –
5 6 7 8 9 10
Sealed
Lead High
Battery Life
Test On1
Signal Output Contacts
Main or Backup Power
Battery Power Low
Battery Fault
Max. Current Rating (Resistive Load)
Minimum Permissible Current Rating
Open
Lead
Sealed
Lead Low
1 2 3 4 5
The Battery Care concept based on algorithms that achieve
rapid and automatic charging, battery optimization during
charging time, flat batteries recovery and real time diagnostic
The Real Time Auto-diagnostic system, monitors battery faults,
sulfated battery, short circuit battery elements, reverse polarity
connection, battery disconnect. This conditions are detected and
identified by the number of blinks of the diagnosis Led.
7
Fast Recovery
Charge (2)3
– (3) –
+ (4) +
Jumper present: life test enabled.
Jumper present: fast test enabled.
Jumper present: fast recovery charge
enabled only for size 3. Possibility to
recharge the battery also when the
voltage is close to zero with the
maximum power of the device.
RJ45 Connection Input/Output
Temp. Comp. Battery (with ext. probe)
Remote monitoring display
Can Bus
Yes - Optional
Yes - Optional
Yes - Optional
Insulation voltage (IN/OUT)
Insulation voltage (input / ground)
Insulation voltage (Output / ground)
Protection Class (EN/IEC 60529)
Pollution Degree Environment
Connection TB, Screw Terminal
Protection class (Ground Connected)
Dimensions (WxHxD)
5.91x4.53x5.32 in
Weight (approx.)
3000 VAC
1605 VAC
500 VAC
IP20
2
4 mm² (30-10 AWG)
Class I
150x115x135 mm
Battery
Out 1
CBI
In Vac
Environment
Load
Mains or Backup
Out 2
Battery Low or
Battery Replacement
Start From Battery
1.55 kg (3.5 Lbs)
Safety and EMC
IEC/EN 60335-2-29
EN60950 / UL1950 / CE
EN54-4
89/336/EEC
DIN41773
IEC 61000-6-4
IEC 61000-6-2
The Altech DC-UPS system is designed to charge and monitor all
battery types, by selecting the battery type via jumpers. The
predefined curves include Open Lead Acid, Sealed Lead Acid, Gel,
Ni-Cd (optional) battery types. The charging curve are
programmed to automatically switch between Recovery Charge,
Boost charge and Trickle charge. The continuous battery efficiency
monitoring, reduces battery damage risk and allows a safe
operation in permanent connection.
Voltage
Voltage / Current
Battery charger standard compliance
Safety standards compliance:
Fire Detection and alarm compliance
EMC Directive
Charging cycle
Emission
Immunity
Current
Recovery Charge
Fast / Boost Charge
Tickle / Float Charge
A compact and rugged metal case with DIN rail mounting bracket
provide an easy installation and an IP20 protection.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
161