Gas discharge tubes 2C800

HUAAN LIMITED
(Ø20.3x4.2mm)
2-Electrode Gas Discharge Tubes
1:Dimension(mm)
Fast Delivery Time
3:Features
2:Main Applications
•AC Power Lines
•Class II (class C) - Requirements
•Surge Protection Device/Surge Protector
•100% Lead-Free(RoHs Compliant )
•Non-Radioactive
•Low capacitance (≤4pF)
•Fast Response-time,High Insulation Resistance.
4 Electrical Characteristics
Part
Number
2C800
DC
Spark-over
Voltage
@100V/s
Impulse
Spark-over
Voltage
@1.2/50us, 6KV
Nominal AC
Insulation
discharge current
Resistance
50 Hz, 0.2s,1 shots
V
V
A
>600
<1500
300
Arc
Voltage
(at 1A)
Capacitance
(1MHz)
GΩ
V
PF
>1
~30
≤4
5 Life Test
Item A
15 shots 8/20us
30KA
Item B
10 shot 10/350us
25KA
Item C
15shots 8/20us
30KA
Item A based on IEC61643-11, Item B based on customer's request .For each item new gas
discharge tubes shall be used.
Specifications are subject to change without notice
[email protected]
[email protected]
1
HUAAN LIMITED
www.huaandz.com
Tel:+86-755-27465585
HUAAN LIMITED
(Ø20.3x4.2mm)
PERFORMANCE CHARACTERISTICS
HUAAN LIMITED
Gas Discharge Tube
Cross Reference List (Ø20.3x4.2mm)
Cross Reference
HUAAN
Gas Discharge Tube
Part Number
TDK EPCOS
Surge Arrester
Part Number
2C800
D20-A800XP
B88069X7691B301
The above trademarks are belonging to the HUAAN LIMITED,TDK / EPCOS.
We do not ensure characteristics of HUAAN products just same as products of TDK / EPCOS.
Specifications are subject to change without notice
[email protected]
[email protected]
2
HUAAN LIMITED
www.huaandz.com
Tel:+86-755-27465585