SPD - Cooper Bussmann

Surge Protection Made Simple™
Photovoltaic Applications
Modular DIN Rail SPD Solutions
Description
The Cooper Bussmann® multi-pole, modular Surge Protective Device
(SPD) (with three-step DC switching device) features easy ID™ visual
indication and optional remote contact signaling (floating changeover
contact) for use in PV systems.
These complete surge protective devices are suitable for all
PV systems in accordance with UL 1449 3rd Edition and
IEC 60364-7-712. Includes a five year limited warranty.
These prewired solutions consist of a base and locking modules that
feature a combined disconnection and short-circuiting (shunting)
device with safe electrical isolation to prevent fire damage due to DC
arcs. An integrated DC fuse allows safe module replacement without
arc formation.
In case of insulation faults in the generator circuit, a reliable and
tested fault-resistant Y circuit prevents damage to the surge
protective devices.
BSPH_____YPV(R)
The green and red visual indicator flags show the module protective
status (green = good, red = replace). Apart from this visual indication,
the remote signaling option features a three terminal floating
changeover contact that can be used as a make or break contact
depending on the particular monitoring system design employed.
Dimensions - mm
Visual Status Indication
Remote Signal
Contact Available
Module Circuit Diagrams
DC+/–
DC–/+
Fuse Closed
12
11
14
Fuse Open
MOV
Thermal Disconnector
Arc
BSPH_____YPV(R)
Shown with optional remote contact signaling
Shown with optional remote contact signaling
Short-Circuit Interrupting (SCI) Technology
1
1. Original State
3. Arc Extinguishes
2
3
4
2. Disconnection Device Response
4. Safe Electrical Isolation
www.cooperbussmann.com/surge
0111
BU-SB11015
Page 1 of 2
Data Sheet 2055_A4
Ordering Information
Nominal PV System Voltage
Catalog Numbers:
(Base + Modules)
Replacement Modules:
600Vdc
Without Remote Signaling
With Remote Signaling
Outer (2)
Center (1)
1000Vdc
1200Vdc
BSPH3600YPV
BSPH31000YPV BSPH31200YPV
BSPH3600YPVR BSPH31000YPVR BSPH31200YPVR
BPH300YPV
BPH500YPV
BPH600YPV
BPM300YPV
BPM500YPV
BPM600YPV
Specifications
Nominal PV System Voltage
MCOV [UCPV]
Max System Discharge Current (8/20 µs) [Imax]
Voltage Protection Level [UP]
Voltage Protection Level at 5kA [UP]
Integrated Fuse Breaking Capacity/Interrupting Rating
Technology
Operating Temperature Range [TU]
Nominal Discharge Current (8/20 µs) [(DC+/DC-) --> PE] [In]
Response Time [tA]
Operating State/Fault Indication
Conductor Ratings and Cross-Sectional Area: Minimum
Maximum
Mounting
Enclosure Material
Degree of Protection
Capacity
Standards Information:
UL
IEC
Product Warranty
600V
1000V
1200V
700Vdc
1170Vdc
1200Vdc
40kA
40kA
30kA
_<2.5kV
_<4.0kV
_<4.5kV
_<2.0kV
_<3.5kV
_<4.0kV
30kA/1000Vdc
30kA/1000Vdc
30kA/1200Vdc
Short-Circuit Interruption (SCI) Overcurrent Protection
-40°C to +80°C
12.5kA
_<25ns
Green (good)/Red (replace)
60/75°C 1.5mm2/14AWG Solid/Flexible
60/75°C 35mm2/2AWG Stranded/25mm2/4AWG Flexible
35mm DIN Rail per EN 60715
UL 94V0 Thermoplastic
IP20
3 Modules, DIN 43880
UL 1449 3rd Edition (Type 2)*
IEC 61643-11 Type 2, IEC 61643-1 Class II
Five Years**
Remote Contact Signaling
Remote Contact Signaling Type
AC Switching Capacity (Volts/Amps)
DC Switching Capacity (Volts/Amps)
Changeover Contact
250V/0.1A
250V/0.1A; 125V/0.2A; 75V/0.5A
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Order from Catalog Numbers Above
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals
Ordering Information
Typical Application Schematics
Common
Common
Common
Equipment
Grounding
Conductor
Equipment
Grounding
Conductor
Equipment
Grounding
Conductor
Application A
Two energized poles/modes
600, 1000 & 1200Vdc systems
Application B
One energized pole/mode
600Vdc & 1000Vdc*** systems only
Steel panel wall
*Does not apply to 1200Vdc.
** See Cooper Bussmann SPD
Limited Warranty Statement
(3A1502) for details at
www.cooperbussmann.com/surge
Application C
One energized pole/mode
600Vdc & 1000Vdc*** systems only
(Max. system discharge current
(8/20 µs) [Imax] 25kA)
20
1000Vdc One energized pole/mode mounting detail.
***BSPH31000YPV(R) 1000Vdc one energized pole/mode requires the following:
1. Use a suitable electrical insulator to keep a 10mm min. safety distance from the PV-SPD and other grounded
parts in the housing as shown
2. No metal covers are in the area of the module release buttons as shown.
M5
Isolator/
insulator
No metal covers
or parts allowed
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document
are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user
with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
© 2011 Cooper Bussmann
w w w. c o o p e r b u s s m a n n . c o m
0111
BU-SB11015
Page 2 of 2
Data Sheet 2055_A4