3197 en

POWER QUALITY ANALYZER 3197
Power Measuring Instruments
T h e M o s t C o m p r e h e n s i ve
Portable PQA on The Market
Catch Power Quality Problems on the Fly...
Monitor for:
✔ Inrush Current
✔ Voltage Swells
✔ Voltage Dips
✔ Transient Overvoltage
✔ Interruptions
Measure and Record:
✔ Power and Power Factor
✔ Active/Reactive Energy
✔ Demand
✔ Load Changes (with graph display!)
✔ Voltage and Current
...Before They Catch You!
Measure Power and Power Quality
on Single to Three-Phase Circuits
Quickly and Effortlessly
P
Q
A
Feature 1:
Vector Multimeter
Use the wiring map, vector
map and data monitor to
c he c k for p r op e r wiring
before taking measurements
– don’t miss out on
important power data just
because of minor wiring
mistakes!
3197
A quick glance at the correct vector map will show you
if your wiring is correct
Feature 2:
QuickSet
With QuickSet, all you have to do is just
Set, Clamp and Measure!
Line frequency
Measurement Interval
Nominal Voltage
Event
Swell
thresholds
Dip
against
Interruption
nominal
Transient
voltage
:
:
:
:
:
:
Auto
Auto
Auto
110%
90%
10%
: ON
Let QuickSet help you take care
of all the time-consuming setup
procedures. All you need to
do is select your circuit, clamp
sensor and range, and then
let QuickSet do the rest of the
work for you.
Testing Parameters Automatically Defined by QuickSet
Redefine Thresholds Easily with Intuitive Key Panel
Feature 3:
Power & Power Quality
Measure all the necessary power
parameters simultaneously
Get a crystal clear
picture of the
voltage fluctuation
on all channels
Check for sudden inrush during motor startup
and diagnose breaker trips due to over current
all on the same measurement interface. View
RMS data for every half cycle over a 30 second
period on a large graph display
All items are recorded as events so that a quick
understanding can be obtained just by viewing the waveform
✓
✓
✓
✓
✓
Power & Energy
Voltage
✓ Demand
Current
✓ Load Changes
Frequency
✓ THD(voltage)
Power
Active/Reactive
✓
and Power Factor
Energy
Voltage Fluctuation (dips and swells)
2
✓
✓
✓
✓
✓
Power Quality
Inrush Current
Voltage Swells
Voltage Dips
Transient
Overvoltage
Interruptions
1
Setting Up
is as Easy as
1-2-3
Select your
wiring
2
3
QuickSet
Toggle between screens
to customize your
measurement settings
RE
C&
EVE
NT
Make detailed
settings on how and
when to measure,
and customize your
level of event
detection as desired.
Select from 5 Types of Color-coded
Input Terminal Labels to Suit Your
Application Region
U1
U2
U3
Red
Yellow
Blue
Japan, U.K.
Blue
Orange
Black
Gray
EU (new)
3
Black
Yellow
Green
Red
China
4
Blue
Black
Red
White
EU (former)
5
White
Black
Red
Blue
N. America
Obtain real-time
moving data on
voltage, current,
power, and more!
Monitor
Trends while
Recording
Region
Black
2
E
UR
S
A
ME
WAVEFORM
N
1
Use the correct vector
diagram to check that your
wiring is right before
measuring, particularly
useful when measuring
3-Phase circuits
WIRIN
G
Use QuickSet to automatically set
the default values for line frequency,
nominal voltage, interval, and power
quality thresholds for event detection
Type
Select your
clamp sensor
Pull Strap Through
for Ultimate Portability
AC Adapter for
Quick Recharge or
Long Recordings
Toggle between
screens using VIEW
key for instantaneous
power data
USB Port for PC
Compatibility
One-touch switching
between graph and
numerical data
Power Switch
RMS, Phase
Angle and Lead
and Lag
Full-color
waveforms and
RMS readings
Convenient Stand for
Hands-free Viewing
Rugged and Durable Casing to
withstand even the toughest
environments and uses
3
VECTOR
Record
and Inspect
Auto-Data
Compression Lets You
Record for up to 125
Days
Find the max, min
and average values
for any point using
the cursor
function
(even while measuring)
RMS
DIP/SWELL
Toggle between the trend
graphs for a complete analysis
of the power situation
Get a detailed picture
during voltage anomalies fluctuation range for all 3
channels are displayed
✓ Consumed & Regenerated Active Power
✓ Lag and Lead of Reactive Power
ENERGY
Demand Graph
and maximum and
average values
displayed in one
window
DEMAND
Display events AND
their waveforms at
the same time
DMM
Harmonic
waveforms of
voltage, current
and active power
to the 50th order
Identify
Power Quality
Problems
WAVEFORM
Switch between voltage and
current graphs, and zoom
in on the time axis at the
touch of a button
Toggle between
events for a
complete picture of
the power anomaly Store up to
50 Events
RMS voltage
fluctuations such
as swells and dips
are clearly displayed
at event detection
INRUSH
HARMONICS
"I" marks an
Inrush Event
GRAP/LIST
DETAIL
Inrush current
fluctuations are captured
in RMS at a fast 10ms
sampling rate and displayed
across a 30-second window
Record up to 20
graphs in
internal memory
4
Scroll down and
select to display the finer
details of any event
RMS
Feature 4:
Bundled PC Application
Software
Mobility, Portability Plus
Convenient Data Transfer
Right to Your PC
Two Integrated Programs for
Data Download and Viewing
Feature 5: Compact Design
Makes for Long Battery Life
St andard USB conne c tion let s you
download dat a at a snap, and
immediately view your measurements
with the DataViewer
6 Hours of Continuous
Use on a Single Recharge
Non-volatile Ni-MH rechargeable
battery pack keeps important
measurement data in memory
even after power is turned off.
Connect to
multiple 3197 units
simultaneously
using a USB hub
A PQA that TRULY fits in the palm of your hand.
Open downloaded recordings with DataViewer to manage
and process your captured power data on your PC.
Event List
Event Details
Time Plot Graph
Standard 3197 Package Fulfills All the Requirements
for Checking Voltage Anomalies
Voltage
Cords
Carrying
Case
Rechargeable
Battery Pack
Event Waveform
Settings
nEvent Detection
RMS Voltage and Current
Voltage Accuracy
Current Accuracy
Voltage (1/2) RMS
Measurement
Accuracy
Current (1/2) RMS
Measurement
Accuracy
Frequency
Accuracy
Active Power Accuracy
(for consumption and
regeneration)
Voltage Swells (Rise), Voltage
Dips (Drop), Interruptions
Inrush Current
Transient Overvoltage
±0.3% rdg. ±0.2% f.s.
+ clamp-on sensor accuracy (P.F.=1)
Reactive Power Accuracy ±1 dgt. of calculation from each measurement
(for lags and leads)
value
Effect of Power Factor
Apparent Power Accuracy
Power Factor and
Displacement Power
Factor Accuracy
(leading phase indicated)
Active or Reactive Energy
Consumption
Accuracy
Demand
Accuracy
Harmonic Analysis Orders
Harmonic Voltage,
Current and Power
Accuracy
(accuracy is not defined
for harmonic power)
Other Measurement
Items
±1.0% rdg. (50 /60Hz, P.F.=0.5)
±1 dgt. of calculation from each measurement value
±1 dgt. of calculation from each measurement value
(DPF calculated from phase difference between
fundamental voltage and current waveforms)
Selectable between consumption, regeneration,
lag and lead
±1 dgt. applied to active and reactive power
measurement accuracy
Selectable between active or reactive power
±1 dgt. applied to active and reactive power
measurement accuracy
Up to 50th (2048 points/window, rectangular)
1st to 15th order ±0.5% rdg. ±0.2% f.s.
16th to 25th order ±1.0% rdg. ±0.3% f.s.
26th to 35th order ±2.0% rdg. ±0.3% f.s.
36th to 45th order ±3.0% rdg. ±0.3% f.s.
46th to 50th order ±4.0% rdg. ±0.3% f.s.
(add accuracy of clamp sensor to harmonic current accuracy)
Peak Voltage and Current, K Factor, Voltage
Unbalance Factor, Max/Min/Ave of Time Series
PC Application
To measure current and power, please select one or more of our
HIOKI Clamp On Sensors detailed on the back of this catalog.
nMeasurement Specifications (Guaranteeed Accuracy Period: 1 Year)
True RMS (200 ms calculation )
±0.3% rdg. ±0.2%f.s
±0.3% rdg. ±0.2%f.s. + Clamp sensor accuracy
True RMS
(one cycle calculation refreshed every half cycle)
±0.3% rdg. ±0.2%f.s.
True RMS
(half-cycle calculation, half-cycle voltage synchronized)
±0.3% rdg. ±0.2%f.s. + Clamp sensor accuracy
Effective Measurement range: 45.00 to 66.00 Hz
±0.01 Hz ±1 dgt. (when input is at least 10% of range)
USB Cable
AC Adapter
Timer Detection
Manual Detection
Thresholds
Event Recording Lengths
Waveform
Event voltage fluctuation graph
Inrush current graph
Maximum Number of
Recordable Events
RMS value detected using voltage (1/2) measured
every half cycle
RMS value detected using current (1/2) every half cycle
Detection Range: 50 Vrms (±70.7 Vpeak equiv.) or more, 10 to 100 kHz
Detect events at preset intervals selectable from
OFF, 1, 5, 15 or 30 minutes; 1, 2 or 12 hours; or 1 day
Detect events when keys are pressed
Set to OFF or to specified value, except for
detection of transient overvoltages. (Waveform
recording not available for transients.)
20ms before detection + 200ms upon detection + 30ms after detection
0.5s before + 2.5s after detection
0.5s before + 29.5s after detection
50 event waveforms, 20 event voltage fluctuation
graphs, 1 inrush current graph, 1000 event counts
nInput Specifications
Single-phase 2-wire (1P2W), single-phase 3-wire
(1P3W), three-phase 3-wire (3P3W2M and 3P3W3M),
three-phase four-wire (3P4W and 3P4W2.5E)
Measurement Line frequency Auto-select (50/60 Hz)
Maximum Allowable Input Voltage input terminal: 780 V AC (1103 Vpeak)
Current input terminal: 1.7 V AC (2.4 Vpeak)
Voltage
Maximum Rated Voltage Voltage input terminal: CATIII 600 V AC, CATIV 300 V AC (50/60 Hz)
Current input terminal: per clamp-on sensors used
to Ground
Simultaneous digital sampling of voltage and current
Measurement Method
(sampling frequency: 10.24 kHz per channel)
Voltage Measurement
600.0V (Crest factor 2 or less)
Range
Wiring Configurations
Current Measurement
Range: Manual ranging
according to clamp sensor
(Crest factor 3 or less)
Clamp Sensor
Range
Clamp Sensor
Range
9657-10, 9675 500.0 mA/5.000 A 9661, 9667 (500A) 50.00 A/500.0 A
9694, 9695-02 5.000 A/50.000 A
9669
100.0 A/1.000 kA
9660, 9695-03 10.00 A/100.0 A 9667 (5000A) 500.0 A/5.000 kA
500mA 300.0W/600.0W/900.0W
100A 60.00kW/120.0kW/180.0kW
Power Measurement
5A 3.000kW/6.000kW/9.000kW 500A 300.0kW/600.0kW/900.0kW
Range: Depends on
combination of current range
10A 6.000kW/12.00kW/18.00kW
1kA 600.0kW/1.200MW/1.800MW
and measurement line
50A 30.00kW/60.00kW/90.00kW
5kA 3.000MW/6.000MW/9.000MW
5
n BASIC SPECIFICATIONS
n ENVIRONMENTAL AND SAFETY-RELATED SPECIFICATIONS
Display
Display languages
Display refresh rate
Clock functions
Real-Time Clock accuracy
Internal Memory Capacity
Maximum recording time
Operating
environment
Demand period
4.7-inch color STN LCD
English, Japanese or Chinese (Simplified)
Approx. once per second
Auto calendar, auto leap year, 24-hour format
Within 13 seconds/month
4MB
125 Days
AUTO, 1, 5, 15 and 30 min., and 1 hour (AUTO
sequentially selects 1, 2, 10, 30 seconds, 1, 5, 15
and 30 min., and 1 hour automatically)
15 min., 30 min. and 1 hour
Recordable Items
All parameters (incl. max/min/average values)
Interval Settings
n INTERFACE SPECIFICATIONS
Interface
Connection destination
USB 2.0 (Full Speed)
Computer operating on Windows 2000/XP
Temperature
and humidity
Applicable
standards
Power source
Indoors, up to 2000 m (6562-ft.) ASL
-10 to 50°C (14 to 122°F), 80% RH or less (non-condensating)
Storage
Operation 0 to 40°C (32 to 104°F), 80% RH or less (non-condensating)
EN61010, Pollution degree 2,
Measurement Categories III (600 V) and IV (300 V)
Safety
(anticipated transient overvoltage 6000 V)
EN61326 Class A
EMC
EN61000-3-2, EN61000-3-3
AC Adapter 9418-15 or Battery Pack 9459
(Maximum rated power: 23 VA (with AC adapter)
Continuous
Approx. 6 hours
operating time
(after full charge, with 5 min. auto-off LCD backlight)
with battery pack
128 W × 246 H × 63 D mm (5.04”W × 9.69”H × 2.48”D)
Dimensions and
(including stand)
mass
Approx. 1.2 kg (42.3 oz.) (with battery pack)
nCLAMP ON SENSOR SPECIFICATIONS
9694
9660
3m cord
3m cord
9661
9669
3m cord
9667
3m cord
9695-02
9695-03
CAT III 1000V
MODEL
CAT III 300V
CAT III 300V
Measurable conductor diameter
Primary current rating
Output voltage
Accuracy
CAT III 600V
φ15mm
AC 5A
AC 10mV/A
AC 100A
AC 1mV/A
2m from sensor to circuit
1m from circuit to connector
CAT III 600V
φ46mm
φ55mm, 80×20mm
φ254mm
AC 500A
AC 1mV/A
AC 1000A
AC 0.5mV/A
AC 500A/5000A
AC 500mVf.s.
CAT III 300V
CAT III 300V
φ15mm
AC 50A
AC 10mV/A
AC 100A
AC 1mV/A
Amplitude
±0.3%rdg.±0.02%f.s. ±0.3%rdg.±0.02%f.s. ±0.3%rdg.±0.01%f.s. ±1.0%rdg.±0.01%f.s. ±2.0%rdg.±1.5mV ±0.3%rdg.±0.02%f.s. ±0.3%rdg.±0.02%f.s.
(45 to 66 Hz)
Phase
within ±1°
within ±2°
within ±1°
within ±0.5°
within ±1°
within ±2°
within ±1°
(5Hz to 5kHz)
(minimum 10% input)
Frequency characteristic
(accuracy deviation)
Max. rated voltage to
earth(insulated conductor)
within ±1.0% at 40Hz to 5kHz (9669: within ±2.0%)
300Vrms
Maximum allowable
50A continuous
input (45 to 66 Hz)
Dimensions and weight 46W×135H×21Dmm, 230g
Requirements
±3dB at 10Hz to
20kHz
within ±1.0% at 40Hz to 5kHz
1000Vrms
300Vrms
300Vrms
600Vrms
600Vrms
130A continuous
550A continuous
1000A continuous 10000A continuous
46W×135H×21Dmm, 230g
77W×151H×42Dmm, 360g
100W×188H×42Dmm, 590g Sensor length 910mm, 140g
9445-02/03 AC Adapter (Option)
CLAMP ON SENSOR (100A)
CLAMP ON SENSOR (500A)
FLEXIBLE CLAMP ON SENSOR (5000A)
CLAMP ON SENSOR (1000A)
CLAMP ON SENSOR (5A)
CLAMP ON SENSOR (50A)
CLAMP ON SENSOR (100A)
CONNECTION CORD (for the 9695-02/9695-03)
CLAMP ON LEAK SENSOR (10A)
CLAMP ON LEAK SENSOR (10A)
VOLTAGE CORD (bundled with the standard 3197)
AC ADAPTER (bundled with the standard 3197)
BATTERY PACK (bundled with the standard 3197)
PQA-HiVIEW Pro PC Application Software
9660
9661
9667
9669
9694
9695-02
9695-03
9219
9657-10
9675
9438-05
9418-15
9459
9624-50
n3197 STANDARD BUNDLE CONFIGURATION
Includes all the equipment you need to measure voltage.
For current or power measurements, please select from our wide
assortment of clamp on sensors.
VOLTAGE CORD 9438 -05 (3m cord length), BATTERY PACK 9459, AC
ADAPTER 9418 -15 , USB Cable, Input Terminal Labels, Input Cord
Labels, 3197 Applications PC Program (CD-ROM), strap, carrying case,
measurement guide, instruction manual
9657-10
3m cord
CAT III 300V
CAT III 300V
Measurable conductor diameter
φ30mm
Primary current rating
AC 10A
AC 10A
Output voltage
Amplitude Accuracy
(45 to 66 Hz)
AC 100mV/A
AC 100mV/A
±1.0%rdg.±0.005%f.s.
±1.0%rdg.±0.05%f.s.
within ±5°
within ±3°
Phase Accuracy (50/60Hz)
φ40mm
1mA (10A on forward and return) 5mA (100A on forward and return)
Residual Current
Frequency characteristic
within ±5% at 40Hz to 5kHz within ±3% at 40Hz to 5kHz
(accuracy deviation)
Max. rated voltage to earth
Maximum allowable input
300Vrms (insulated conductor)
10A continuous
30A continuous
Dimensions and weight 60W×113H×24Dmm, 160g 74W×145H×42Dmm, 380g
Notes
Not compatible with power measurements
nSUGGESTED OPTIONS for POWER MEASUREMENTS
3P4W Circuit testing of motors and breakers:
3197 Standard Package + 9661 (500A Sensor)×3
3P4W Circuit testing of external CTs:
3197 Standard Package + 9694 (5A Sensor)×3
3P Leakage testing:
3197 Standard Package + 9675 (10A Sensor)×3
HIOKI (Shanghai) Sales & Trading Co., Ltd. :
1608-1610 Shanghai Times Square Office, 93 Huai Hai Zhong Road,
Shanghai, P.R.China POSTCODE: 200021
TEL +86-21-6391-0090/0092 FAX +86-21-6391-0360
http://www.hioki.cn / E-mail: [email protected]
HIOKI USA CORPORATION :
6 Corporate Drive, Cranbury, NJ 08512 USA
TEL +1-609-409-9109 / FAX +1-609-409-9108
http://www.hiokiusa.com / E-mail: [email protected]
51W×58H×19Dmm, 50g
3m cord
MODEL
130A continuous
9219 Connection Cord (3m; Option)
9675
nCOMPLETE LIST OF OPTIONS
HEAD OFFICE :
81 Koizumi, Ueda, Nagano, 386-1192, Japan
TEL +81-268-28-0562 / FAX +81-268-28-0568
http://www.hioki.co.jp / E-mail: [email protected]
60A continuous
DISTRIBUTED BY
Beijing Office :
TEL +86-10-5867-4080/4081 FAX +86-10-5867-4090
E-mail: [email protected]
Guangzhou Office :
TEL +86-20-38392673/2676 FAX +86-20-38392679
E-mail: [email protected]
HIOKI INDIA PRIVATE LIMITED :
Khandela House, 24 Gulmohar Colony Indore 452 018 (M.P.), India
TEL +91-731-4223901, 4223902 FAX +91-731-4223903
http://www.hioki.in / E-mail: [email protected]
All information correct as of Jun. 4, 2010. All specifications are subject to change without notice.
3197E7-06B-03K
Printed in Japan