A. Input Characteristics: 1) Voltage: 120 VAC 2) Frequency: 50/60 Hz. 3) Current: 30A Maximum 4) Load Capacity: 3.60 KVA 5) Overload Protection: (2) 1P/15A UL489 Circuit Breaker 6) Power Cord: 10' (3m) 7) Connector: L5-30P B. Output Characteristics: 1) Voltage: 120 VAC N 2) Current: 15A 3) Outlets: 24X 5-20R C. Mechanical Characteristics: 1) Material: CRS/G40 Galv. Coating L 2) Finish: Powder Coat, Black, Fine Texture G 3) Silk-Screen: White/Epoxy 4) Storage Temp.: -(25) - 149C (-25 - 65C) L5-30P PLUG END D. Operating Environment: 1) Temperature: 32 - 122F (0 - 50C) 2) Relative Humidity: 0 - 95% (Non-Condensing) 3) Elevation: 0 - 10,000FT (0 - 3000 m) E. Regulatory Conformance: 1) Safety Agency: UL/cUL, FCC 15 Class A, UL60950-1 3.25 in / 82.6 mm CHANGE NOTICE 2 INFORMATONAL LABEL REV 66 in / 1676.4 mm CN-001605-SPMS 1.73 in / 43.9 mm 2) RoHS: Compliant to Directive 2002/95/EC DRAWINGS IN ACCORDANCE WITH STANDARD ANSI Y14.5M-1994 . THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION AND IS COPYRIGHTED. EXCEPT WITH THE WRITTEN PERMISSION OF SPECTRUM CONTROL, INC. OR ITS SUBSIDIARIES, SUCH INFORMATION SHALL NOT BE PUBLISHED OR DISCLOSED TO OTHERS, OR USED FOR ANY PURPOSE AND THIS DOCUMENT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART. DRAWN: CarrS TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONS ±1/64 DECIMAL .XX ± .020 DECIMAL .XXX ±.010 ANGLES ± 030' DATE 4/29/2008 Spectrum Management Systems 24X 5-20R 0U PDU THIRD ANGLE PROJECTION SHEET: 1 OF 1 72A-130BHXBN-10 CODE IDENT NO: STATE COLLEGE, PENNSYLVANIA