A. Input Characteristics: 1) Voltage: 200-250VAC 2) Frequency: 50/60 Hz. 3) Line Current: 32A Maximum 4) Load Capacity: 7.36 KVA 5) Overload Protection: (2) 2P/16A UL489 Circuit Breaker 6) Power Cord: 10' (3m), #10AWG(5.25mm 2 )/3 L 7) Connector: IEC309-32A IEC309-32A 8) Indicators: Power-on, LED B. Output Characteristics: 1) Voltage: 200-250VAC 2) Current: 32A (Total Combined Load) 3) Outlets: 2x 12 IEC C13 C. Mechanical Characteristics: 1) Material: CRS 2) Finish: Powder Coat, Black, Fine Texture 3) Lettering: Silk-Screen, White/Epoxy 4) Storage Temp.: -(13) - 149F (-25 - 65C) D. Operating Environment: 1.38 in / 35.1 mm 1) Temperature: 32 - 122F (0 - 50C) OPTIONAL MOUNTING POSITIONS OF STUD BRACKETS .88 in / 22.4 mm .38 in / 9.7 mm 2) Relative Humidity: 0 - 95% (Non-Condensing) 29.543 in / 750.4 mm 28.543 in / 725 mm 27.543 in / 699.6 mm 3) Elevation: 0 - 10,000FT (0 - 3000 m) E. Regulatory Conformance: 1) Safety Agency: UL/cUL, UL60950-1, CE 2) RoHS: Compliant to Directive 2002/95/EC 0 REV CHANGE NOTICE MOUNTING KIT 2X STUD MOUNT BRACKETS (SHOWN 1/2 SCALE) NOT MOUNTED ON PDU CN-000469-SPMS 3 in / 76.2 mm 1.73 in / 43.9 mm 31 in / 787.4 mm DRAWINGS IN ACCORDANCE WITH STANDARD ANSI Y14.5M-1994 . THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION AND IS COPYRIGHTED. EXCEPT WITH THE WRITTEN PERMISSION OF SPECTRUM CONTROL, INC. OR ITS SUBSIDIARIES, SUCH INFORMATION SHALL NOT BE PUBLISHED OR DISCLOSED TO OTHERS, OR USED FOR ANY PURPOSE AND THIS DOCUMENT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART. DRAWN: CarrS TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONS ±1/64 DECIMAL .XX ± .020 DECIMAL .XXX ±.010 ANGLES ± 030' DATE 5/27/2010 Spectrum Management Systems 31" 0U PDU, 24XC13 THIRD ANGLE PROJECTION SHEET: 1 OF 1 72A-132BAXEN-02 CODE IDENT NO: STATE COLLEGE, PENNSYLVANIA