72A 132BAXEN 02

A. Input Characteristics:
1) Voltage: 200-250VAC
2) Frequency: 50/60 Hz.
3) Line Current: 32A Maximum
4) Load Capacity: 7.36 KVA
5) Overload Protection: (2) 2P/16A UL489 Circuit Breaker
6) Power Cord: 10' (3m), #10AWG(5.25mm 2 )/3
L
7) Connector: IEC309-32A
IEC309-32A
8) Indicators: Power-on, LED
B. Output Characteristics:
1) Voltage: 200-250VAC
2) Current: 32A (Total Combined Load)
3) Outlets: 2x 12 IEC C13
C. Mechanical Characteristics:
1) Material: CRS
2) Finish: Powder Coat, Black, Fine Texture
3) Lettering: Silk-Screen, White/Epoxy
4) Storage Temp.: -(13) - 149F (-25 - 65C)
D. Operating Environment:
1.38 in / 35.1 mm
1) Temperature: 32 - 122F (0 - 50C)
OPTIONAL MOUNTING POSITIONS OF STUD BRACKETS
.88 in / 22.4 mm
.38 in / 9.7 mm
2) Relative Humidity: 0 - 95% (Non-Condensing)
29.543 in / 750.4 mm
28.543 in / 725 mm
27.543 in / 699.6 mm
3) Elevation: 0 - 10,000FT (0 - 3000 m)
E. Regulatory Conformance:
1) Safety Agency: UL/cUL, UL60950-1, CE
2) RoHS: Compliant to Directive 2002/95/EC
0
REV
CHANGE NOTICE
MOUNTING KIT
2X STUD MOUNT BRACKETS
(SHOWN 1/2 SCALE)
NOT MOUNTED ON PDU
CN-000469-SPMS
3 in / 76.2 mm
1.73 in / 43.9 mm
31 in / 787.4 mm
DRAWINGS IN ACCORDANCE WITH
STANDARD ANSI Y14.5M-1994
.
THIS DOCUMENT CONTAINS
PROPRIETARY INFORMATION AND IS
COPYRIGHTED. EXCEPT WITH THE
WRITTEN PERMISSION OF SPECTRUM
CONTROL, INC. OR ITS SUBSIDIARIES,
SUCH INFORMATION SHALL NOT BE
PUBLISHED OR DISCLOSED TO OTHERS,
OR USED FOR ANY PURPOSE AND THIS
DOCUMENT SHALL NOT BE DUPLICATED
IN WHOLE OR IN PART.
DRAWN:
CarrS
TOLERANCES UNLESS
OTHERWISE SPECIFIED:
FRACTIONS ±1/64
DECIMAL .XX ± .020
DECIMAL .XXX ±.010
ANGLES ± 030'
DATE
5/27/2010
Spectrum
Management Systems
31" 0U PDU, 24XC13
THIRD
ANGLE
PROJECTION
SHEET:
1 OF 1
72A-132BAXEN-02
CODE IDENT
NO:
STATE COLLEGE,