A. Input Characteristics: 1) Voltage: 208VAC, 3 PHASE DELTA 2) Frequency: 50/60 Hz. 3) Current: 60 AMP 4) Load Capacity: 21.6 KVA 5) Overload Protection: (9) 2P/15A UL489 Circuit Breaker 6) Power Cord: 10' (3m) (8G/4C) 3W+PE 7) Connector: IEC309 60A PIN AND SLEEVE B. Output Characteristics: 1) Voltage: 208VAC L1 2) Current: 11.5A PER OUTLET, 11.5A PER OUTLET GROUP 3) Outlets: 3 PER BREAKER, 3 BREAKERS PER PHASE (27 x C13 TOTAL) L2 C. Mechanical Characteristics: L3 1) Material: CRS/G40 2) Finish: Powder Coat, Black, Fine Texture IEC 309 60A PIN AND SLEEVE CONNECTOR 3) Lettering: Silk-Screen, White/Epoxy 4) Storage Temp.: -(25) to 149C (-25 to 65C) D. Operating Environment: 3.25 in / 82.6 mm 1) Temperature: 32 TO 122F (0 - 50C) 2) Relative Humidity: 0 - 95% (Non-Condensing) 3) Elevation: 0 - 10,000FT (0 - 3000 m) E. Regulatory Conformance: 1) Safety Agency: UL/cUL, UL60950-1 CABLE RETENSION CLIPS 2) RoHS: Compliant to Directive 2002/95/EC 1.73 in / 43.9 mm 66 in / 1676.4 mm REV CHANGE NOTICE ECN-000734-SPMS 01 POWER LED's (ONE PER BREAKER) DRAWINGS IN ACCORDANCE WITH STANDARD ANSI Y14.5M-1994 . THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION AND IS COPYRIGHTED. EXCEPT WITH THE WRITTEN PERMISSION OF SPECTRUM CONTROL, INC. OR ITS SUBSIDIARIES, SUCH INFORMATION SHALL NOT BE PUBLISHED OR DISCLOSED TO OTHERS, OR USED FOR ANY PURPOSE AND THIS DOCUMENT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART. DRAWN: CarrS TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONS 1/64 DECIMAL .XX .020 DECIMAL .XXX .010 DATE 12/3/2009 ANGLES 0 30' Spectrum Management Systems PDU,0U,27/C13,208V,60A THIRD ANGLE PROJECTION SHEET: 1 OF 1 72A-1A1BB0EN-10 CODE IDENT NO: STATE COLLEGE, PENNSYLVANIA