72A 160BPRBN 00

A. Input Characteristics:
1) Voltage: 208VAC (+10/-15%), 3 Phase WYE
2) Frequency: 50/60 Hz.
3) Line Current: 20A Maximum (16A DERATED, NA)
1
4) Load Capacity: 7.20 KVA
5) Overload Protection: (3) 1P/20A UL489 Circuit Breaker
6) Power Cord: 10' (3m), #12AWG/5C
7) Connector: NEMA L21-20P
8) Indicators: Power-on, LED
B. Output Characteristics:
1) Voltage: 120VAC Nominal
2) Current: 16A/Phase (Total Connected Load), DERATED NA
1
3) Outlets: 3X 6 NEMA 5-20R
C. Mechanical Characteristics:
1) Material: CRS
X
2) Finish: Powder Coat, Black, Fine Texture
Y
3) Lettering: Silk-Screen, White/Epoxy
W
G
4) Storage Temp.: -(13) - 149F (-25 - 65C)
D. Operating Environment:
Z
1) Temperature: 32 - 122F (0 - 50C)
L21-20P PLUG END
2) Relative Humidity: 0 - 95% (Non-Condensing)
3) Elevation: 0 - 10,000FT (0 - 3000 m)
3.25 in / 82.6 mm
E. Regulatory Conformance:
1) Safety Agency: UL/cUL, UL60950-1, CE
1.73 in / 43.9 mm
2) RoHS: Compliant to Directive 2002/95/EC
CHANGE NOTICE
1
8983-ENG
1
REV
33 in / 838.2 mm
DRAWINGS IN ACCORDANCE WITH
STANDARD ANSI Y14.5M-1994
.
THIS DOCUMENT CONTAINS
PROPRIETARY INFORMATION AND IS
COPYRIGHTED. EXCEPT WITH THE
WRITTEN PERMISSION OF SPECTRUM
CONTROL, INC. OR ITS SUBSIDIARIES,
SUCH INFORMATION SHALL NOT BE
PUBLISHED OR DISCLOSED TO OTHERS,
OR USED FOR ANY PURPOSE AND THIS
DOCUMENT SHALL NOT BE DUPLICATED
IN WHOLE OR IN PART.
DRAWN:
CarrS
TOLERANCES UNLESS
OTHERWISE SPECIFIED:
FRACTIONS ±1/64
DECIMAL .XX ± .020
DECIMAL .XXX ±.010
ANGLES ± 030'
DATE
6/8/2009
Spectrum
Management Systems
18X 5-20R, 3PH-WYE, 0U PDU
THIRD
ANGLE
PROJECTION
SHEET:
1 OF 1
72A-160BPRBN-00
CODE IDENT
NO:
STATE COLLEGE,
PENNSYLVANIA