A. Input Characteristics: 1) Voltage: 208VAC (+10/-15%), 3 Phase WYE 2) Frequency: 50/60 Hz. 3) Line Current: 20A Maximum (16A DERATED, NA) 1 4) Load Capacity: 7.20 KVA 5) Overload Protection: (3) 1P/20A UL489 Circuit Breaker 6) Power Cord: 10' (3m), #12AWG/5C 7) Connector: NEMA L21-20P 8) Indicators: Power-on, LED B. Output Characteristics: 1) Voltage: 120VAC Nominal 2) Current: 16A/Phase (Total Connected Load), DERATED NA 1 3) Outlets: 3X 6 NEMA 5-20R C. Mechanical Characteristics: 1) Material: CRS X 2) Finish: Powder Coat, Black, Fine Texture Y 3) Lettering: Silk-Screen, White/Epoxy W G 4) Storage Temp.: -(13) - 149F (-25 - 65C) D. Operating Environment: Z 1) Temperature: 32 - 122F (0 - 50C) L21-20P PLUG END 2) Relative Humidity: 0 - 95% (Non-Condensing) 3) Elevation: 0 - 10,000FT (0 - 3000 m) 3.25 in / 82.6 mm E. Regulatory Conformance: 1) Safety Agency: UL/cUL, UL60950-1, CE 1.73 in / 43.9 mm 2) RoHS: Compliant to Directive 2002/95/EC CHANGE NOTICE 1 8983-ENG 1 REV 33 in / 838.2 mm DRAWINGS IN ACCORDANCE WITH STANDARD ANSI Y14.5M-1994 . THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION AND IS COPYRIGHTED. EXCEPT WITH THE WRITTEN PERMISSION OF SPECTRUM CONTROL, INC. OR ITS SUBSIDIARIES, SUCH INFORMATION SHALL NOT BE PUBLISHED OR DISCLOSED TO OTHERS, OR USED FOR ANY PURPOSE AND THIS DOCUMENT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART. DRAWN: CarrS TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONS ±1/64 DECIMAL .XX ± .020 DECIMAL .XXX ±.010 ANGLES ± 030' DATE 6/8/2009 Spectrum Management Systems 18X 5-20R, 3PH-WYE, 0U PDU THIRD ANGLE PROJECTION SHEET: 1 OF 1 72A-160BPRBN-00 CODE IDENT NO: STATE COLLEGE, PENNSYLVANIA