72A 190BWLEN 02

A. Input Characteristics:
1) Voltage: 208VAC +5/-15% 3PHASE DELTA
2) Frequency: 50/60 Hz.
3) Current: 30A Maximum MAX, 24A DERATED FOR NA)
4) Load Capacity: 6.24 KVA
5) Overload Protection: 6x 2P/15A UL489 Circuit Breaker
6) Power Cord: 10' (3m), 4C/8AWG cord
7) Connector: L15-30P
B. Output Characteristics:
1) Voltage: 208VAC +5/-15%
2) Current: 15A MAX (12A DERATED FOR NA) PER BREAKER/OUTLET
30A MAX (24A DERATED FOR NA) PER PHASE
3) Outlets: 12x C13
C. Mechanical Characteristics:
1) Material: CRS/G40 Galv. Coating
2) Finish: Powder Coated
3) Lettering: Silk-Screen
4) Storage Temp.: -25 to 122F (-32 to 50C)
D. Operating Environment:
1) Temperature: 32 to 122F (0 - 50C)
2) Relative Humidity: 0 to 95% (Non-Condensing)
3) Elevation: 0 to 10,000FT (0 to 3000 m)
E. Regulatory Conformance:
1) Safety Agency: UL/cUL, FCC 15 Class A, UL60950-1
5.00 in / 127 mm
2) RoHS: Compliant to Directive 2002/95/EC
1.25 in / 31.8 mm
0.25 in / 6.4 mm
FRONT
1.73 in / 43.9 mm
CHANGE NOTICE
2
REV
REAR
CN-000631-SPMS
6-32 UNC - 2B
TYP 8 (4 PER SIDE)
(REDESINGED)
3.00 in / 76.2 mm
31.51 in / 800.4 mm
31.01 in / 787.7 mm
30.01 in / 762.3 mm
29.13 in / 739.9 mm
1.00 in / 25.4 mm
DRAWINGS IN ACCORDANCE WITH
STANDARD ANSI Y14.5M-1994
.
THIS DOCUMENT CONTAINS
PROPRIETARY INFORMATION AND IS
COPYRIGHTED. EXCEPT WITH THE
WRITTEN PERMISSION OF SPECTRUM
CONTROL, INC. OR ITS SUBSIDIARIES,
SUCH INFORMATION SHALL NOT BE
PUBLISHED OR DISCLOSED TO OTHERS,
OR USED FOR ANY PURPOSE AND THIS
DOCUMENT SHALL NOT BE DUPLICATED
IN WHOLE OR IN PART.
DRAWN:
carrs
TOLERANCES UNLESS
OTHERWISE SPECIFIED:
DECIMAL .X ± .050
DECIMAL .XX ± .020
DECIMAL .XXX ±.010
DATE
6/2/2010
ANGLES ± 030'
Spectrum
Management Systems
PDU,0U,12/C13,208V3P,30A
THIRD
ANGLE
PROJECTION
SHEET:
1 OF 1
72A-190BWLEN-02
CODE IDENT
NO:
STATE COLLEGE,
PENNSYLVANIA