A. Input Characteristics: 1) Voltage: 200-220 VAC, 3 Phase Delta 2) Frequency: 50/60 Hz. 3) Line Current: 30A Maximum 4) Load Capacity: 10.8 KVA 5) Overload Protection: 3x 2P/15A, 3x 2P/20A UL489 Circuit Breaker L21-30P ("W" IS NOT USED) 6) Power Cord: 15' (4.5m), 4C/8AWG cord 7) Connector: NEMA L21-30P B. Output Characteristics: 1) Voltage: 208VAC 2) Current: 24A (Total Combined Load)/Phase 3) Outlets: 3x (6x IEC C13 & 4x IEC C19) C. Mechanical Characteristics: 1) Material: CRS/G40 Galv. Coating 2) Finish: Powder Coated 3) Lettering: Silk-Screen 4) Storage Temp.: -25 to 122F (-32 to 50C) D. Operating Environment: DETAIL B SCALE 2 : 1 1) Temperature: 32 to 122F (0 - 50C) POWER ON LEDS ONE FOR EACH BREAKER 2) Relative Humidity: 0 to 95% (Non-Condensing) 3) Elevation: 0 to 10,000FT (0 to 3000 m) B E. Regulatory Conformance: 1) Safety Agency: UL/cUL, FCC 15 Class A, UL60950-1 3.47 in / 88.1 mm 2) RoHS: Compliant to Directive 2002/95/EC 03 3.25 in / 82.6 mm REV 32.50 in / 825.5 mm TOP 6x M6 MOUTNING NUTS REAR 0.70 in / 17.8 mm 2.00 in / 50.8 mm CHANGE NOTICE 15.25 in / 387.4 mm CN-001582-SPMS 30.50 in / 774.7 mm DRAWINGS IN ACCORDANCE WITH STANDARD ANSI Y14.5M-1994 . THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION AND IS COPYRIGHTED. EXCEPT WITH THE WRITTEN PERMISSION OF SPECTRUM CONTROL, INC. OR ITS SUBSIDIARIES, SUCH INFORMATION SHALL NOT BE PUBLISHED OR DISCLOSED TO OTHERS, OR USED FOR ANY PURPOSE AND THIS DOCUMENT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART. DRAWN: CarrS TOLERANCES UNLESS OTHERWISE SPECIFIED: DECIMAL .X ± .050 DECIMAL .XX ± .020 DECIMAL .XXX ±.010 DATE 5/16/2010 ANGLES ± 030' Spectrum Management Systems PDU,208V,30A,3P,3(6xC13;4xC19) THIRD ANGLE PROJECTION SHEET: 1 OF 1 72A-130BQ3GN-00 CODE IDENT NO: STATE COLLEGE, PENNSYLVANIA