72A 130BQ3GN 00

A. Input Characteristics:
1) Voltage: 200-220 VAC, 3 Phase Delta
2) Frequency: 50/60 Hz.
3) Line Current: 30A Maximum
4) Load Capacity: 10.8 KVA
5) Overload Protection: 3x 2P/15A, 3x 2P/20A UL489 Circuit Breaker
L21-30P
("W" IS NOT USED)
6) Power Cord: 15' (4.5m), 4C/8AWG cord
7) Connector: NEMA L21-30P
B. Output Characteristics:
1) Voltage: 208VAC
2) Current: 24A (Total Combined Load)/Phase
3) Outlets: 3x (6x IEC C13 & 4x IEC C19)
C. Mechanical Characteristics:
1) Material: CRS/G40 Galv. Coating
2) Finish: Powder Coated
3) Lettering: Silk-Screen
4) Storage Temp.: -25 to 122F (-32 to 50C)
D. Operating Environment:
DETAIL B
SCALE 2 : 1
1) Temperature: 32 to 122F (0 - 50C)
POWER ON LEDS
ONE FOR EACH BREAKER
2) Relative Humidity: 0 to 95% (Non-Condensing)
3) Elevation: 0 to 10,000FT (0 to 3000 m)
B
E. Regulatory Conformance:
1) Safety Agency: UL/cUL, FCC 15 Class A, UL60950-1
3.47 in / 88.1 mm
2) RoHS: Compliant to Directive 2002/95/EC
03
3.25 in / 82.6 mm
REV
32.50 in / 825.5 mm
TOP
6x M6 MOUTNING NUTS
REAR
0.70 in / 17.8 mm
2.00 in / 50.8 mm
CHANGE NOTICE
15.25 in / 387.4 mm
CN-001582-SPMS
30.50 in / 774.7 mm
DRAWINGS IN ACCORDANCE WITH
STANDARD ANSI Y14.5M-1994
.
THIS DOCUMENT CONTAINS
PROPRIETARY INFORMATION AND IS
COPYRIGHTED. EXCEPT WITH THE
WRITTEN PERMISSION OF SPECTRUM
CONTROL, INC. OR ITS SUBSIDIARIES,
SUCH INFORMATION SHALL NOT BE
PUBLISHED OR DISCLOSED TO OTHERS,
OR USED FOR ANY PURPOSE AND THIS
DOCUMENT SHALL NOT BE DUPLICATED
IN WHOLE OR IN PART.
DRAWN:
CarrS
TOLERANCES UNLESS
OTHERWISE SPECIFIED:
DECIMAL .X ± .050
DECIMAL .XX ± .020
DECIMAL .XXX ±.010
DATE
5/16/2010
ANGLES ± 030'
Spectrum
Management Systems
PDU,208V,30A,3P,3(6xC13;4xC19)
THIRD
ANGLE
PROJECTION
SHEET:
1 OF 1
72A-130BQ3GN-00
CODE IDENT
NO:
STATE COLLEGE,
PENNSYLVANIA