PDF cURus UL 60950-1, CSA 60950-1

File E135493
Project 91EK524
March 31, 1992
REPORT
on
COMPONENT-POWER SUPPLIES
Vicor Corp.
Andover, MA
Copyright © 1992 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above-named company to
reproduce this Report provided it is reproduced in its entirety.
Underwriters Laboratories Inc. authorizes the above-named company to
reproduce that portion of this Report consisting of this Cover Page through
Page 3.
File E135493
Vol. 1
Sec. 3
and Report
Page 1
Issued:
Revised:
1992-03-31
2011-04-19
D E S C R I P T I O N
PRODUCT COVERED:
USR, CNR: Component - Power Supply, ComPac Series, Model No. VI-aCbcccdeee-xx. VI may be replaced by IP for all Models. Refer to Ill. 2 and
Ill.3.
ENGINEERING CONSIDERATIONS (NOT FOR UL REPRESENTATIVE USE):
*
This product was investigated for compliance with the Standard for
Information Technology Equipment, UL 60950-1, 2nd Edition, 2007-03-27
(Information Technology Equipment - Safety - Part 1: General Requirements)
CSA C22.2 No. 60950-1-07, 2nd Edition, 2007-03 (Information Technology
Equipment - Safety - Part 1: General Requirements).
Based on the March 15, 1991 Industry Review and per the manufacturer's
request. This section of this report was transferred to the category for
Power Supplies For Use In Electronic Data Processing Equipment, General
Purpose Power Supplies, and Power Supplies For Use In Information Technology
Equipment, Including Electrical Business Equipment.
File E135493
Vol. 1
Sec. 3
and Report
Page 2
Issued:
Revised:
1992-03-31
2011-04-19
Use - For use only in (or with) complete equipment where the acceptability of
the combination is determined by Underwriters Laboratories Inc.
This power supply consists of an already Recognized power supplies
mounted on a printed wiring board with additional front end circuitry.
Primary to secondary isolation is provided by these Recognized power
supplies.
Conditions of Acceptability - When installed in the end-use equipment,
considerations shall be given in the following:
*1.
This component has been judged on the basis of the required spacings in
the Standard for Information Technology Equipment, UL 60950-1, 2nd
Edition, 2007-03-27 (Information Technology Equipment - Safety - Part
1: General Requirements) CSA C22.2 No. 60950-1-07, 2nd Edition, 2007-03
(Information Technology Equipment - Safety - Part 1: General
Requirements), which would cover the component itself if submitted for
unrestricted Listing, Fourth Edition of the Standard for Information
Processing and Business Equipment, UL 478, and Power Supplies, UL 1012.
2.
This power supply shall be installed in compliance with the enclosure,
mounting, creepage, clearance, casualty, markings and segregation
requirements of the end-use application.
3.
The need for conducting leakage current tests is to be determined as
part of the end-product evaluation.
4.
This power supply has only been evaluated for use in a pollution
Degree 2 environment.
5.
Secondary outputs 2 V - 48 V comply with SELV requirements.
outputs 52 V - 95 V are non SELV outputs.
Secondary
File E135493
Vol. 1
Sec. 3
and Report
Page 3
Issued:
Revised:
1992-03-31
2011-04-19
5.
A Heating Test should be conducted in the end product.
6.
The base plate temperature of each DC/DC module should be monitored.
7.
A baseplate temperature of 85°C should not be exceeded.
8.
The input and output connectors have not been evaluated for field
connections and are only intended for connection to mating connectors of
internal wiring inside the end-use machine. The acceptability of these
and the mating connectors relative to secureness, insulating materials,
and temperature shall be considered.
9.
These units shall be provided with external primary fuses.
10.
The following is the maximum primary fuse value acceptable:
Output Power
Nominal Input, dc
Fuse Size
24 V
24 V (wide)
48 V
300 V
10 A
12 A
7 A
2 A
400 W
400 W
400 W
24 V
48 V
300 V
20 A
15 A
4 A
600 W
600 W
600 W
24 V
48 V
300 V
30 A
25 A
6 A
200
200
200
200
11.
W
W
W
W
Based on Par. 35A.1 of the Standard for Telephone Equipment, UL 1459;
these products are acceptable for use with Telephone Equipment.
File E135493 Vol. 1 Sec. 3
ILL 3
VI - a C b c c c - d e e e - f f f
ComPAC Family Tree
VI
Product Type
VI = VI (Vicor), VI = VE (Vicor RoHs), VI = IP (VJCL), VI = IE (VJCL RoHs), MI = Military
a
Module Configurations
L = 1UP Single (1module, 1 output)
M = 2UP Single (2 modules, 1 output)
N = 3UP Single (3 modules, 1 output)
P = 2UP Dual (2 modules, 2 outputs)
Q = 3UP Dual (3 modules, 2 outputs)
R = 3UP Triple (3 modules, 3 outputs)
b
Input Voltage (Vdc)
Nominal
Range
1 = 24
21-32 @
W = 24
18-36 @
3 = 48
42-60 @
N = 48
36-76 @
6 = 300
200-400 @
d
Product Grade
C = Commercial -20C to 85C
I = Industrial
-40C to 85C
M = Military
-55C to 85C
E = Economy
0C to 85C
eee
Output Power
M = 600W
P = 450W
Q = 400W
S = 300W
U = 200W
V = 150W
W = 100W
X = 75W
Y = 50W
fff
Factory assigned code
Non-safety related, any alphanumeric combination or blanks, 0-3 characters
ccc
Output voltage (Vdc) Nominal
Z = 2.0
2 = 15.0
Y = 3.3
N = 18.5
O = 5.0
3 = 24.0
X = 5.2
L = 28.0
W = 5.5
J = 36.0
V = 5.8
K = 40.0
T = 6.5
4 = 48.0
R = 7.5
H = 52.0
M = 10.0
F = 72.0
1 = 12.0
D = 85.0
P =13.8
B = 95.0
Example
VI-PC601-CUX-23
P = 2Up (2 modules, 2 outputs), 6 = 300 V Input, 0 = 5V output, 1 = 12Vdc output
C= Commercial product Grade, U = 200W output, X = 75W output, 23 = Customer Code
Max (A)
26.7
31.2
18.0
15.6
3.9