Datasheet

SIP 6 Series
Circuit Diagram (view on relay upper side)
3,75 6,5
14
3,75
0,4
2,1 25,4 5 8,5 5 6,5 5 6,5 5 6,5 5 4,1 0,5
3
Ø 1,3
25,4 5 8,5 5 6,5 5 6,5 5 6,5 5
6,5
14
0,5
32
2,9
12,5
1
3
[mm]
4,1
Control Contact
Contact material
AgSnO2 + 0,2 µm Au
Rated switching capacity
250 VAC 6 A AC1 1500 VA
Electr. life AC 1(360 cycles / h)
approx.100000
Inrush current max.
15 A for 20 ms
Switching voltage range
5 to 250 VDC / VAC
Switching current range*
5 mA to 6 A
Switching capacity range*
60 mW to 1500 W(VA)
Contact resistance (as delivered)
≤100 mΩ / 6 V / 100 mA
Output Contact
Contact material
AgSnO2
Rated switching capacity
250 VAC (440 VAC) 16 A AC1 4000 VA
Electr. life AC 1(360 cycles / h)
approx.250000
Inrush current max.
60 A for 20 ms
Switching voltage range
5 to 250 VDC (480 VAC)
Switching current range*
10 mA to 16 A
Switching capacity range*
120 mW to 4000 W(VA)
Contact resistance (as delivered)
≤100 mΩ / 6 V / 100 mA
*Guided values
≥0,6
≥1,2
≥1,8
≥2,4
≥4,8
≥6,0
≥11,0
≥22,0
218,0
109,0
72,0
54,5
27,2
21,8
11,8
5,9
43
44
44
33
34
34
12 23
11 24
12 22
11 21
SIP 512
SIP 422
A2
A1
A2
- Basic insulation
at 250 VAC
- Air and creepage distance
>4 mm
- Test voltage
2500 V / 50 Hz / 1 min
- Double or reinforced insulation
at 250 VAC
- Air and creepage distance
>8 mm
- Test voltage
4000 V / 50 Hz / 1 min
- Double or reinforced insulation
at 250 VAC
- Air and creepage distance
>10 mm
- Test voltage
5000 V / 50 Hz / 1 min
Test voltage contact open
1500 V / 50 Hz / 1 min
Creepage resistance
CTI 250
Pollution degree
2
Overvoltage category
III
Insulation resistance at Up 500 VDC
>100 MΩ
Additional Data
Mechanical endurance
Switching frequency, mechanical
Response time (all NO closed)
Drop-out time** (all NC closed)
Bounce time of NO contact
Bounce time of NC contact
Shock resistance 16 ms
27,5 ± 10%
110 ± 10%
248 ± 10%
440 ± 10%
1760 ± 10%
2750 ± 10%
9250 ± 13%
37000 ± 15%
>10 x 106 operations
15 Hz
typically 18 ms
typically 5 ms
typically 8 ms
typically 12 ms
NO > 10g
NC > 8g
Vibration resistance
10-200 Hz
NO > 10g
10-50 Hz
NC > 5g
50-200 Hz
NC > 3,5g
Resistance to short circuiting control contacts
1000 A SCPD 6 A gG / gL (pre-fuse)
Resistance to short circuiting output contacts
1000 A SCPD 16 A gG / gL (pre-fuse)
Ambient temperature
-40°C to +70°C
Thermal resistance
40 K / W
Temperature limit for coil
125°C
Weight
ca. 60 g
Mounting position
any
Type of protection
RT II
Solder bath temperature
270°C / 5 s
DC 1: 24V
DC 14: 24V
100
10
DC 13: 24V
1
5
Switching Current (A) →
10
16
Contact Lifetime output contacts AC
10000
AC 3: 230V
1000
AC 1: 400V
AC 3: 400V
100
AC 1: 230V
AC 15: 230V
10
1
5
Switching Current (A) →
UL 508:
A600 / R150
Maximal contact load at AC 1 with 230 V:
2 contacts with 16 A each
3 contacts with 12 A each
4 contacts with 10 A each
10
16
Load Limit Curve with Direct Current
16
8
4
2
1
0,8
0,4
1
2
0,2
0,1
0
50
100
150
200
0
20
40
60
Ambient Temperature °C →
80
Voltage (VDC) →
1) Inductive load L/R 40 ms
2) Resistive load
250
Excitation Voltage Range
2,5
Approvals
2,0
UL File E188953
Insulation class IEC 60664-1
Protection class II
Fire protection requirements
Sec. 4
250 VAC
VDE 0106
UL 94 / V0
1,5
1
1,0
2
0,5
UB
UN 0
Options, Accessories
none available
Product Key
ELESTA GmbH, Heuteilstrasse 18, Fon:
CH - 7310 Bad Ragaz, Switzerland Fax:
1000
3,0
Tests, Regulations
SIP 4 2 2 24VDC
Operations x 1000 →
54
**without spark suppression
Resistance in Ohm
at 20 °C
Nominal current
in mA
Min. pick-up
voltage at 20 °C
4,2
8,4
12,6
16,8
33,6
42,0
77,0
154,0
Drop-out voltage at
20 °C
Nominal voltage
VDC
Standard coils for direct current
(other voltages on request)
6
12
18
24
48
60
110
220
53
54
10000
Operations x 1000 →
33
64
Contact Lifetime output contacts DC
Current (A) →
43
63
64
Insulation Data
20
84,6
3,75 12,5 3,75
53
A1
Dimensions
2,1
63
Output
Contacts
- PCB Relay with forcibly guided contacts
- Protective separation between coil/control contacts and
output contacts (>8 mm) and output contacts in one row
(>10 mm)
- EN50205 type A
- Contact mounting: SIP512 Control contacts 1 NO / 1 NC
Output contacts 4 NO
SIP422 Control contacts 2 NC
Output contacts 4 NO
- High switching power
- Nominal coil power 1,3 W
- Holding coil power 0,39 W
- For railway application (EN50155) on request
Control
Contacts
Relay Key Data
Coil voltage
Soldering tags
Number of NC contacts
Number of NO contacts
Type designation
+41 (0)81 303 54 00
+41 (0)81 303 54 01
100
1) Max. excitation voltage with contact load:
control contacts ≤4 A, output contacts ≤12 A
2) Min. excitation voltage (guaranteed values) without
previous operation
© Copyright
11/2014