SH

NEW Series SH
Output to 125A, 690 Vac
High Industrial Performance (HIPpak) Solid-State Relays
FEATURES/BENEFITS
• Random and zero-cross models available for all applications
• Low zero-cross turn-on voltage
• Input and output protection and control LED standard
• IP20 touch-proof flaps
• Connectors for power wiring and heat sinks available
• Designed in conformity with EN60947-4-3 (IEC947-4-3) and
EN60950/VDE0805 (Reinforced Insulation)
IP20 touch-proof flaps
Part No.
Load
Voltage
Load
Current
Control
Voltage
Switch
Type
SH24D25
12-275 Vac
25A
3-32 Vdc
Zero Cross
SH24A25
12-275 Vac
25A
20-265 Vac/dc
Zero Cross
SH24D35
12-275 Vac
35A
3-32 Vdc
Zero Cross
SH24A35
12-275 Vac
35A
20-265 Vac/dc
Zero Cross
SH24D50
12-275 Vac
50A
3-32 Vdc
Zero Cross
SH24R50
12-275 Vac
50A
3-32 Vdc
Random
SH24R75
12-275 Vac
75A
3-32 Vdc
Random
SH24D75
12-275 Vac
75A
3-32 Vdc
Zero Cross
SH24D95
12-275 Vac
95A
3-32 Vdc
Zero Cross
SH24D125
12-275 Vac
125A
3-32 Vdc
Zero Cross
SH48R35
24-510 Vac
35A
3.5-32 Vdc
Random
SH48D35
24-510 Vac
35A
3.5-32 Vdc
Zero Cross
SH48A35
24-510 Vac
35A
20-265 Vac/dc
Zero Cross
SH48R50
24-510 Vac
50A
3.5-32 Vdc
Random
SH48D50
24-510 Vac
50A
3.5-32 Vdc
Zero Cross
SH48A50
24-510 Vac
50A
20-265 Vac/dc
Zero Cross
SH48R75
24-510 Vac
75A
3.5-32 Vdc
Random
SH48D75
24-510 Vac
75A
3.5-32 Vdc
Zero Cross
SH48A75
24-510 Vac
75A
20-265 Vac/dc
Zero Cross
SH48R95
24-510 Vac
95A
3.5-32 Vdc
Random
SH48D95
24-510 Vac
95A
3.5-32 Vdc
Zero Cross
SH48A95
24-510 Vac
95A
20-265 Vac/dc
Zero Cross
SH48R125
24-510 Vac
125A
3.5-32 Vdc
Random
SH48D125
24-510 Vac
125A
3.5-32 Vdc
Zero Cross
SH48A125
24-510 Vac
125A
20-265 Vac/dc
Zero Cross
SH60D50
24-690 Vac
50A
3.5-32 Vdc
Zero Cross
SH60D75
24-690 Vac
75A
3.5-32 Vdc
Zero Cross
SH60D95
24-690 Vac
95A
3.5-32 Vdc
Zero Cross
SH60D125
24-690 Vac
125A
3.5-32 Vdc
Zero Cross
TYPICAL APPLICATION
,INE
6OLTAGE
,INE0ROTECTION
,
!
#ONTROL
!
4
,%$
,AND4CANBESWAPPED
332MUSTBEMOUNTEDONAHEATSINK
,/!$
Figure 1a — SHXXDXX relays
,INE
6OLTAGE
,INE0ROTECTION
,
!
,%$
#ONTROL
4
!
,AND4CANBESWAPPED
332MUSTBEMOUNTEDONAHEATSINK
,/!$
Figure 1b — SHXXAXX relays
,INE
6OLTAGE
,INE0ROTECTION
,
!
#ONTROL
!
,%$
4
,AND4CANBESWAPPED
332MUSTBEMOUNTEDONAHEATSINK
,/!$
Figure 1c — SHXXRXX relays
© 2008 TELEDYNE RELAYS
(800) 284-7007 • www.teledynerelays.com
SH Page 1
SH\102008\Q4
NEW Series SH
Output to 125A, 690 Vac
High Industrial Performance (HIPpak) Solid-State Relays
ELECTRICAL SPECIFICATIONS
(+25°C ambient temperature unless otherwise specified)
CONTROL CHARACTERISTICS
INPUT (CONTROL) SPECIFICATIONS
Max
Units
Input Current Range
SHXXR/D (except SH60)
10
13
mA
SHXXA
5
10
mA
12
mA
SH60
)NPUT#URRENTM!
Min
Must Turn-Off Voltage
SHXXR/D
2.0
Vdc
SHXXA
5.0
Vdc
Reverse Voltage Protection (R/D)
32
V
Clamping Voltage (R/D)
36
V
Input Immunity (EN61000-4-4)
2
kV
Input Immunity (EN61000-4-5)
2
kV
#ONTROL6OLTAGE6
)NPUT#URRENTM!
Figure 3a — SH24R/D, SH48R/D relays
MECHANICAL SPECIFICATION
MAX
Œ 0.185 ()
Figure 3b — SH24A, SH48A relays
-
#ONTROL6OLTAGE6
1.18
MAX
!
$IMENSIONSININCHESMM
7EIGHTOZG
Figure 2
SH Page 2
-
)NPUT#URRENTM!
!
4
,
MAX
#ONTROL6OLTAGE6
Figure 3c — SH60D relays
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
© 2008 TELEDYNE RELAYS
SH\102008\Q4
NEW Series SH
Output to 125A, 690 Vac
High Industrial Performance (HIPpak) Solid-State Relays
ELECTRICAL SPECIFICATIONS
(+25°C ambient temperature unless otherwise specified)
OUTPUT (LOAD) SPECIFICATIONS
Min
Max
Units
SH24
(450)
600
Vpeak
SH48
(950)
1200
Vpeak
1600
Vpeak
Turn-On Time (60 Hz)
SHXXR
0.04
ms
SHXXD
8.3
ms
SHXXA
24.9
ms
SHXXR/D
8.3
ms
SHXXA
24.9
ms
Off-State dv/dt
500
V/μs
Maximum di/dt (Non-Repetitive)
50
A/μs
Peak Voltage (VDR Clamping)
SH60
Load Currrent Range (Resistive)
25 output current
.005
25
Arms
35 output current
.005
40
Arms
50 output current
.005
60
Arms
75 output current
.005
90
Arms
95 output current
.005
110
Arms
125 output current
.005
150
Arms
Turn-Off Time (60 Hz)
Operating Frequency
SHXXR
0.1
400
Hz
SHXXD/A
0.1
800
Hz
25 output current
600
A2s
35 output current
1250
A2s
50 output current
2500
A2s
75 output current
7200
A2s
95 output current
14400
A2s
125 output current
24000
A2s
25 output current
1.7
°C/W
35 output current
0.6
°C/W
50 output current
0.45
°C/W
75 output current
0.4
°C/W
95 output current
0.3
°C/W
125 output current
0.25
°C/W
I2t for fuse matching (<10ms)
Maximum Surge Current Rating (Non-Repetitive)
25 output current
350
A
35 output current
500
A
50 output current
720
A
75 output current
1200
A
95 output current
1700
A
125 output current
2200
A
0.9
V
Junction-Case Thermal Resistance
On-State Voltage Drop
Output Power Dissipation (Max)
25 output current
0.9x0.9xI + 0.016xI2W
35 output current
0.9x0.9xI + 0.015xI2W
50 output current
0.9x0.9xI + 0.012xI2W
75 output current
0.9x0.9xI + 0.0045xI2
W
95 output current
0.9x0.9xI + 0.0035xI2
W
125 output current
0.9x0.9xI + 0.002xI2W
IEC/EN61000-4-4 (bursts)
Zero-Cross Window (Typical)
SHXXR
NA
SHXXD/A
±12
Vac
Off-State Leakage Current
SHXXR
3
mA
SHXXD/A
1
mA
© 2008 TELEDYNE RELAYS
Conducted Immunity Level
SH24
2kV criterion A
SH48/SH60
4kV criterion A
IEC/EN61000-4-5 (surge)
SH24
2kV criterion A
SH48
4kV criterion A
SH60
4kV criterion A (with external VDR)
(800) 284-7007 • www.teledynerelays.com
SH Page 3
SH\102008\Q4
NEW Series SH
Output to 125A, 690 Vac
High Industrial Performance (HIPpak) Solid-State Relays
SURGE CURRENT
!PEAK
GENERAL SPECIFICATIONS
(+25°C ambient temperature unless otherwise specified)
ENVIRONMENTAL SPECIFICATIONS
Min
Max
Units
Up to 35 output current
–55
+80
°C
Above 35 output current
–40
+80
°C
Up to 35 output current
–55
+125
°C
Above 35 output current
–40
+125
°C
.ON2EPETITIVE
Operating Temperature
2EPETITIVEWITHINITIAL4J #
TS
Figure 4a — 25A output current
Storage Temperature
!PEAK
.ON2EPETITIVE
2EPETITIVEWITHINITIAL4J #
Ambient Humidity
TS
Figure 4b — 35A output current
!PEAK
.ON2EPETITIVE
2EPETITIVEWITHINITIAL4J #
TS
Output-Case Isolation
4000
Vrms
Insulation Resistance
@500Vdc
1000
MΩ
Rated Impulse Voltage
4000
Protection Level (CEI529)
IP20
Shock (according to CD168)
Baseplate
!PEAK
Vrms
Housing Material
Figure 4c — 50A output current
%
4000
Vibration (10–55 Hz according to CE168)
40 to 85
Input-Output Isolation
V
1.5
mm
30/50
g
PA6 UL94VO
Aluminum, nickel-plated
.ON2EPETITIVE
2EPETITIVEWITHINITIAL4J #
TS
Figure 4d — 75A output current
!PEAK
.ON2EPETITIVE
2EPETITIVEWITHINITIAL4J #
TS
Figure 4e — 95A output current
!PEAK
.ON2EPETITIVE
2EPETITIVEWITHINITIAL4J #
TS
Figure 4f — 125A output current
SH Page 4
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
© 2008 TELEDYNE RELAYS
SH\102008\Q4
NEW Series SH
Output to 125A, 690 Vac
High Industrial Performance (HIPpak) Solid-State Relays
THERMAL CURVES
#7 #7
#7
0OWER$ISSIPATION7
&ULLON3TATE
#7
#7
#7
#7
ON3TATE
0OWER$ISSIPATION7
#7
&ULLON3TATE
#7
#7
#7
#7
#7
#7
#7
#7
#7
#7
ON3TATE
#7
,OAD#URRENT!RMS
!MBIENT4EMPERATURE #
Figure 5e — 95A output power
#7
#7
#7
#7
ON3TATE
#7
!MBIENT4EMPERATURE #
Figure 5d — 75A output power
&ULLON3TATE
!MBIENT4EMPERATURE #
,OAD#URRENT!RMS
0OWER$ISSIPATION7
0OWER$ISSIPATION7
#7
#7
#7
Figure 5c — 50A output power
&ULLON3TATE
!MBIENT4EMPERATURE #
,OAD#URRENT!RMS
#7
#7
ON3TATE
Figure 5b — 35A output power
#7
,OAD#URRENT!RMS
0OWER$ISSIPATION7
#7
#7
Figure 5a — 25A output power
#7
!MBIENT4EMPERATURE #
#7
#7
,OAD#URRENT!RMS
#7
&ULLON3TATE
ON3TATE
0OWER$ISSIPATION7
#7
#7
&ULLON3TATE
#7
#7
#7
#7
#7
ON3TATE
#7
,OAD#URRENT!RMS
!MBIENT4EMPERATURE #
Figure 5f — 125A output power
12°C/W corresponds to a relay without heat sink
6°C/W corresponds to a relay mounted on a DIN-rail adaptor (Teledyne P/N DL12)
© 2008 TELEDYNE RELAYS
(800) 284-7007 • www.teledynerelays.com
SH Page 5
SH\102008\Q4
NEW Series SH
Output to 125A, 690 Vac
High Industrial Performance (HIPpak) Solid-State Relays
OPTIONAL CONNECTIONS
Directly with wires,
with or without ferrules
With tips
(ring terminals)
With special adaptation for
high-voltage relays
CONTROL WIRING
Number of Wires
1
Solid
(no ferrule)
Screwdriver
Type
2
Fine Stranded
(with ferrule)
Solid
(no ferrule)
Recommended
Torque
Fine Stranded
(with ferrule)
N.m
AWG18…AWG14
AWG18…AWG14
AWG18…AWG14
AWG18…AWG14
Pozidriv 2
0.8
Screwdriver
Type
Recommended
Torque
POWER WIRING
Number of Wires
1
Solid
(no ferrule)
2
Fine Stranded
(with ferrule)
Solid
(no ferrule)
Fine Stranded
(with ferrule)
N.m
AWG16…AWG8
AWG16…AWG10
AWG16…AWG8
AWG16…AWG10
Power with tips
Pozidriv 2
1.2
Options
Fastons: Call us
AWG6
16mm2
AWG4
16mm2
W max = 13mm
AWG0
50mm2
for high current
SH Page 6
Special kit for high current
AWG2 / 35mm2
AWG0 / 50mm2
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
© 2008 TELEDYNE RELAYS
SH\102008\Q4
NEW Series SH
Output to 125A, 690 Vac
High Industrial Performance (HIPpak) Solid-State Relays
2–2.5°C/W
Teledyne P/N FW151
1.1°C/W
Teledyne P/N FW108
0.3°C/W
Teledyne P/N FW031
Mounting
HIPpak SSRs must be mounted on heat
sinks. A large range of heat sinks is
available. For heat-sink mounting, use
thermal grease or a thermal pad with high
conductibility specified by Teledyne.
DIN Rail Adapter
Teledyne P/N DL12
Thermal Pad
Teledyne P/N –12
Typical Loads (Random)
SH relays with random turn-on are designed for high inductive loads or phase angle control applications.
Our data sheet lists nominal current of power thyristors corresponding to a resistive load (AC-51).
Depending on the loads, check the inrush current at turn ON and possible overvoltages at turn OFF.
Main applications:
• AC-55b — Incandescent or infrared lamps. Inrush current is generally 10 times In during few 10ms. Random relays often use inphase angle controllers or soft-starters with the right control.
• AC-53 — Three-phase motors. 2 or 3 random turn-on relays can drive such motors.
• AC-56a — Transformer loads. Very high inrush current up to 100 times In. Use a random turn-on SSR like the SH.
The table below lists recommended current values for proper lifetime expectancy.
SSR Model
AC-53 Current
(motor)
AC-55b Current
(lamp)
AC-55b Current
(transformer)
AC-55b Current
(capacitor)
12A
2.5A
2.5A
0.4A
XXX
25A
5A
5A
1A
XXX
35A
9A
9A
2A
XXX
50A
12A
12A
3A
13A
75A
16A
16A
6A
24A
95A
24A
24A
9A
36A
125A
32A
32A
12A
48A
Typical Loads (Zero-Cross)
SH relays with zero-cross turn-on are designed for most types of loads.
Our data sheet lists the AC-51 current value corresponding to resistive loads.
For other loads, check the inrush current at turn ON and possible overvoltages at turn OFF:
• AC-55b — Incandescent lamps. Inrush current is generally 10 times In during few 10ms.
• AC-55a — Electric discharge lamp. These loads often have overcurrent at turn ON and overvoltage at turn OFF, so use 400VAC
SSR on 230VAC mains.
• AC-58 — One-pole motors. These loads often have overcurrent at turn ON and overvoltage at turn OFF, so use 400VAC SSR on
230VAC mains and adapt the SSR current to the starting current of the motor.
• AC-53 — Three-phase motors. 2 or 3 SH zero-cross relays can drive these motors, but generally use E3P/E3PT or other threephase relays or SH random range.
• AC-56a — Transformer loads. Very high inrush current up to 100 times In. Use SH random relay or peak control SSR.
• AC-56b — Capacitor loads with very high current at turn ON and overvoltage at turn OFF. Our high-voltage relays are well adapted
for high inrush current.
© 2008 TELEDYNE RELAYS
(800) 284-7007 • www.teledynerelays.com
SH Page 7
SH\102008\Q4
NEW Series SH
Output to 125A, 690 Vac
High Industrial Performance (HIPpak) Solid-State Relays
Protection
• To protect the SSR against a short-circuit of the load, use a fuse with a I2t value = 1/2 I2t value specified.
EMC
Immunity:
• Our data sheets list the immunity level of our SSRs according to the main standards for these of products: IEC/EN61000-4-4 and
IEC/EN61000-4-5. You can compare the high immunity level with other products on the market.
Emission:
• Teledyne SSRs are designed in compliance with standards for class A equipment (Industry).
• Use of this product in domestic environments may cause radio interference. In this case the user may be required to employ
additional devices to reduce noise. SSRs are complex devices that must be interconnected with other equipment (loads, cables,
etc.) to form a system. Because the other equipment or interconnections may not be under Teledyne’s control, it shall be the
responsibility of the system integrator to ensure that systems containing SSRs comply with the requirement of any rules and
regulations applicable at the system level.
• In phase angle applications, a filter adapted to the load must be necessary.
• The very low zero-cross voltage of SH relays (<12V) improves the conducted emission level in comparison with most other SSRs
on the market with zero-cross voltages often higher than 50V.
SH Page 8
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
© 2008 TELEDYNE RELAYS
SH\102008\Q4