Solid-state Timer
H3CR
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions
or comments. Refer to Warranty and Application Considerations (page 52), and Safety Precautions (page 22, 44, 51).
DIN 48 ✕ 48-mm Multifunctional Timer Series
• Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low
Voltage, and EMC Directives.
• Approved by UL and CSA.
• Lloyds/NK approvals.
• Six-language instruction manual provided.
■ Broad Line-up of H3CR Series
H3CR
H3CR-A
H3CR-F
Multifunctional Timer
Twin Timer
H3CR-A
H3CR-AS
H3CR-AP
H3CR-A8
H3CR-A8S
H3CR-A8E
H3CR-F
H3CR-FN
H3CR-F8
H3CR-F8N
11-pin model
8-pin model
H3CR-G
11-pin model
H3CR-H
Star-delta Timer
Power OFF-delay Timer
H3CR-G8L
8-pin model
H3CR-G8EL
H3CR-HRL 11-pin model
H3CR-H8L
8-pin model
H3CR-H8RL
8-pin model
8-pin with
instantaneous
contact output
model
Note: H3CR-AS, H3CR-A8S: Transistor output models
Contents
Solid-state Timer
H3CR-A ..........................................................................................................................................
2
H3CR-F...........................................................................................................................................
26
H3CR-G ..........................................................................................................................................
34
H3CR-H ..........................................................................................................................................
42
Common to ALL Timers
Operation ........................................................................................................................................
1
52
Accessories ....................................................................................................................................
54
Safety Precautions..........................................................................................................................
58
Solid-state Multi-functional Timers
H3CR-A
Multiple Operating Modes and Multiple Time
Ranges. DIN 48 x 48-mm Multifunctional
Timer.
• A wide AC/DC power supply range greatly reduces the number
of timer models kept in stock.
• A wide range of applications with multiple operating modes,
eight modes for 11-pin models and five modes for 8-pin models.
• Ecological design with reduced current consumption.
• Easy sequence checking with instantaneous outputs for a zero
set value.
• Length of 75 mm or less when panel-mounted with a P3G-08
Socket (H3CR-A8E, 100 to 240 VAC, 100 to 125 VDC)
• PNP input models available.
• Standards: UL, CSA, NK, LR, CCC, EN 61812-1, and CE
Marking.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Model Number Structure
■ Model Number Legend
Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 3 for availability.
H3CR-A@ @ @ - @ @
1
2
3
4
5
1. Number of Pins
None: 11-pin models
8:
8-pin models
2. Input Type for 11-pin Models
None: No-voltage input (NPN type)
P:
Voltage input (PNP type)
3. Output
None: Relay output (DPDT)
S:
Transistor output (NPN/PNP universal use)
E:
Relay output (SPDT) with instantaneous relay output (SPDT)
4. Suffix
301: Double time scale (range) models (0.1 s to 600 h)
5. Supply Voltage
100-240AC/100-125DC: 100 to 240 VAC/100 to 125 VDC
24-48AC/12-48DC:
24 to 48 VAC/12 to 48 VDC
24-48AC/DC:
24 to 48 VAC/VDC (Only for H3CR-A8E)
2
H3CR-A
Ordering Information
■ List of Models
Note: 1. Specify both the model number and supply voltage when ordering.
Example: H3CR-A 100-240AC/100-125DC
Supply voltage
2. The operating modes are as follows
A:
ON-delay
D: Signal OFF-delay
B:
Flicker OFF start
E: Interval
B2: Flicker ON start
G: Signal ON/OFF-delay
C:
Signal ON/OFF-delay
J: One-shot
11-pin Models
Output
Supply voltage
100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
Contact
Input type
No-voltage input
Time range
0.05 s to 300 h
Operating mode
(See note 2)
Model
(See note 1.)
Eight multi-modes: A, B, H3CR-A
B2, C, D, E, G, J
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
Voltage input
Eight multi-modes: A, B, H3CR-AP
B2, C, D, E, G, J
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
No-voltage input
0.1 s to 600 h
H3CR-A-301
0.05 s to 300 h
H3CR-AS
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
Transistor
(Photocoupler)
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
8-pin Models
Output
Contact
Supply voltage
100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
Input type
Time range
No-input available 0.05 s to 300 h
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
Operating mode
(See note 2)
Model
(See note 1.)
Five multi-modes: A, B, H3CR-A8
B2, E, J
(Power supply start)
0.1 s to 600 h
H3CR-A8-301
0.05 s to 300 h
H3CR-A8S
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
Transistor
(Photocoupler)
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
Time-limit contact and 100 to 240 VAC (50/60 Hz)/
instantaneous contact 100 to 125 VDC
24 to 48 VAC/VDC (50/60 Hz)
3
H3CR-A8E
H3CR-A
■ Accessories (Order Separately)
Adapter, Protective Cover, Hold down Clip, Setting Ring and Panel Cover
Name/specifications
Models
Y92F-30
Flush Mounting Adapter
Y92F-73 *1
Y92F-74 *1
Y92A-48B *2
Protective Cover
Hold-down Clip (Sold in sets of
two)
For PF085A Socket
Y92H-8
For PL08 or PL11 Sockets
Y92H-7
Setting Ring A
Y92S-27 *3
Setting Ring B and C
Y92S-28 *3
Panel Cover
Light gray (5Y7/1)
Y92P-48GL *4
Black (N1.5)
Y92P-48GB *4
*1 The Y92A-48B Protective Cover and the Y92P-48G@ Panel Cover can not be used at the same time with the Y92F-73/-74 Flush Mounting Adapter.
*2 The Y92A-48B Protective Cover is made from hard plastic. Remove the Protective Cover to change to set value. The Y92F-73/-74 Flush
Mounting Adapter and the Y92P-48G@ Panel Cover cannot be used at the same time with Y92A-48B Protective Cover.
*3 The Y92S-27/-28 Setting Ring cannot be used alone. It must be used together with the Y92P-48G@ Panel Cover.
*4 The Y92A-48B Protective Cover and the Y92F-73/-74 Flush Mounting Adapter cannot be used at the same time with the Y92P-48G@ Panel Cover.
Sockets
Timer
Round Sockets
Pin
Connection
11-pin
Front Connecting
Back Connecting
8-pin
Front Connecting
Back Connecting
Terminal
Models
DIN track mounting
P2CF-11
DIN track mounting
(Finger-safe type)
P2CF-11-E
Screw terminal
P3GA-11
Solder terminal
PL11
Wrapping terminal
PL11-Q
PCB terminal
PLE11-0
DIN track mounting
P2CF-08
DIN track mounting
(Finger-safe type)
P2CF-08-E
DIN track mounting
PF085A
Screw terminal
P3G-08
Solder terminal
PL08
Wrapping terminal
PL08-Q
PCB terminal
PLE08-0
Note: 1. The P2CF-@@-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals.
2. The P3GA-11 and P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection.
3. For details, refer to your OMRON website.
Terminal Cover
Application
For back connecting socket
Model
Y92A-48G
Remarks
For P3G-08 and P3GA-11
Note: For details, refer to your OMRON website.
4
H3CR-A
Specifications
■ General
Item
Operating mode
H3CR-A/-AS/-A-301
H3CR-AP
A: ON-delay
B: Flicker OFF start
B2: Flicker ON start
C: Signal ON/OFF-delay
D: Signal OFF-delay
E: Interval
G: Signal ON/OFF-delay
J: One-shot
H3CR-A8/-A8S/-A8-301
H3CR-A8E
A: ON-delay (power supply start)
B: Flicker OFF start (power supply start)
B2: Flicker ON start (power supply start)
E: Interval (power supply start)
J: One-shot (power supply start)
Pin type
11-pin
Input type
No-voltage input
8-pin
Time-limit output type
H3CR-A/-A8/-AP/-A-301/-A8-301: Relay output (DPDT)
H3CR-AS/-A8S: Transistor output (NPN/PNP universal)*
Voltage input
--Relay output (SPDT)
Instantaneous output type ---
Relay output (SPDT)
Mounting method
DIN track mounting, surface mounting, and flush mounting
Approved standards
UL508, CSA C22.2 No.14, NK, Lloyds, CCC
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1 for Timers with Contact Outputs.
Output category according to EN60947-5-2 for Timers with Transistor Outputs.
* The internal circuits are optically isolated from the output. This enables universal application as NPN or PNP transistor.
For details, refer to your OMRON website.
■ Time Ranges
Note: When the time setting knob is turned below “0” until the point where the time setting knob stops, the output will operate instantaneously at
all time range settings.
For details, refer to your OMRON website.
Standard (0.05-s to 300-h) Models
Time unit
Full scale
setting
1.2
s (sec)
0.05 to 1.2
10 s (10 sec)
1.2 to 12
min (min)
0.12 to 1.2
10 min (10 min)
1.2 to 12
h (hrs)
0.12 to 1.2
10 h (10 hrs)
1.2 to 12
3
0.3 to 3
3 to 30
0.3 to 3
3 to 30
0.3 to 3
3 to 30
12
1.2 to 12
12 to 120
1.2 to 12
12 to 120
1.2 to 12
12 to 120
30
3 to 30
30 to 300
3 to 30
30 to 300
3 to 30
30 to 300
Double (0.1-s to 600-h) Models
Time unit
Full scale
setting
5
2.4
s (sec)
0.1 to 2.4
10 s (10 sec)
2.4 to 24
min (min)
0.24 to 2.4
10 min (10 min)
2.4 to 24
h (hrs)
0.24 to 2.4
10 h (10 hrs)
2.4 to 24
6
0.6 to 6
6 to 60
0.6 to 6
6 to 60
0.6 to 6
6 to 60
24
2.4 to 24
24 to 240
2.4 to 24
24 to 240
2.4 to 24
24 to 240
60
6 to 60
60 to 600
6 to 60
60 to 600
6 to 60
60 to 600
H3CR-A
■ Ratings
Rated supply voltage (See notes 1, 2, and 5.) 100 to 240 VAC (50/60 Hz)/100 to 125 VDC, 24 to 48 VAC (50/60 Hz)/12 to 48 VDC (24 to 48 VAC/VDC for H3CR-A8E)
(See note 3.)
Operating voltage range
85% to 110% of rated supply voltage (90% to 110% at 12 VDC)
Power reset
Minimum power-opening time: 0.1 s
Input (See note 6.)
No-voltage Input
ON impedance:
1 kΩ max.
ON residual voltage:
1 V max.
OFF impedance:
100 kΩ min.
Voltage Input
Max. permissible capacitance between inputs lines (terminals 6 and 7): 1,200 pF
Load connectable in parallel with inputs (terminals 6 and 7).
• 100 to 240 VAC/100 to 125 VDC
High (logic) level: 85 to 264 VAC/85 to 137.5 VDC
Low (logic) level:
0 to 10 VAC/0 to 10 VDC
• 24 to 48 VAC/12 to 48 VDC
High (logic) level: 20.4 to 52.8 VAC/10.8 to 52.8 VDC
Low (logic) level:
0 to 2.4 VAC/0 to 1.2 VDC
Power consumption
H3CR-A/-A8
• 100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON: approx. 2.0 VA (1.6 W)
• 24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Relay ON: approx. 0.8 W
H3CR-AP (See note 3)
• 100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON: approx. 2.5 VA (2.2 W) (See note 4.)
• 24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Relay ON: approx. 0.9 W (See note 4.)
H3CR-A8E
• 100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON/OFF: approx. 2 VA (0.9 W)
• 24 to 48 VAC/VDC
(When at 24 VDC)
Relay ON/OFF: approx. 0.9 W
H3CR-AS/-A8S
• 24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Output ON: 0.3 W Output OFF: 0.2 W
Control outputs
Relay OFF: approx. 1.3 VA (1.1 W)
Relay OFF: approx. 0.2 W
Relay OFF: approx. 1.8 VA (1.7 W) (See note 4.)
Relay OFF: approx. 0.3 W (See note 4.)
• Models with Contact Outputs
H3CR-A/-A8/-AP
5A at 250 VAC/30 VDC, 0.15A at 125 VDC, resistive load (cosφ = 1)
Minimum applied load: 10mA at 5 VDC (failure level: P reference value)
Contact materials: Ag-alloy
H3CR-A8E
5A at 250 VAC/30 VDC, 0.15A at 125 VDC, resistive load (cosφ = 1)
Minimum applied load: 10mA at 5 VDC (failure level: P reference value)
Contact materials: AgSnIn
• Transistor output: Open collector(NPN/PNP)
H3CR-AS/-A8S
100 mA max at 30 VDC max., residual voltage: 2 VDC max.
Note: 1. DC ripple rate: 20% max. (A single-phase, full-wave-rectification power supply can be used).
2. Do not use an inverter output as the power supply. Refer to your OMRON website for details.
3. Models with 24-to-48-VAC or 12-to-48-VDC power supply have inrush current. Caution is thus required when turning ON and OFF power
to the Timer with a non-contact output from a device such as a sensor. (Models with an inrush current of approximately 50 mA and a 24VDC power supply are available (the H3CR-A-302 and H3CR-A8-302).)
For details, consult your OMRON sales representative.
4. The values are for when the terminals 2 and 7 and terminals 10 and 6 are short-circuited, and include the consumption current of the
input circuit.
5. Refer to your OMRON website when using the Timer together with a 2-wire AC proximity sensor.
6. For details, see Input Connections: No-voltage Input Signal Levels on page 11, and Input Connections: Voltage Input Signal Levels on
page 12.
6
H3CR-A
■ Characteristics
Accuracy of operating
time
Setting error
Reset time
±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s or 3 s)
±5% FS ±50 ms (See note 1)
Min. power-opening time: 0.1 s max.
Min. pulse width:
0.05 s (H3CR-A/-AS)
Reset voltage
10% max. of rated supply voltage
Influence of voltage
±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s or 3 s)
Influence of temperature ±1% FS max. (±1%±10 ms max. in a range of 1.2 s or 3 s)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between current-carrying metal parts and exposed noncurrent-carrying metal parts)
2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
2,000 VAC, 50/60 Hz for 1 min (between input and control output terminals and operation circuit) for H3CR-AP
Impulse withstand
5 kV (between power terminals) for 100 to 240 VAC/100 to 125 VDC, 1 kV for 24 to 48 VAC/12 to 48 VDC
voltage
5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC/100 to
125 VDC, 1.5 kV for 24 to 48 VAC/12 to 48 VDC and 24 to 48 VAC/VDC
Noise immunity
±1.5 kV (between power terminals) and ±600 V (between no-voltage input terminals), square-wave noise by noise
simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity
Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance
Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in 3 directions for 2 hours each
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in 3 directions for 10 minutes each
Shock resistance
Destruction: 1,000 m/s2 3 times each in 6 directions
Malfunction: 100 m/s2 3 times each in 6 directions
Ambient temperature
Operating: −10°C to 55°C (with no icing)
Storage:
−25°C to 65°C (with no icing)
Ambient humidity
Operating: 35% to 85%
Life expectancy
Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note 2)
EMC
(EMI)
EN61812-1
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
(EMS)
EN61812-1
Immunity ESD:
IEC61000-4-2
Immunity RF-interference:
IEC61000-4-3
Immunity Burst:
IEC61000-4-4
Immunity Surge:
IEC61000-4-5
Immunity Conducted Disturbance: IEC61000-4-6
Immunity Voltage Dip/Interruption: IEC61000-4-11
Case color
Light gray (Munsell 5Y7/1)
Degree of protection
IP40 (panel surface)
Weight
Approx. 90 g
Note: 1. The value is ±5% FS +100 ms to −0 ms max. when the C, D, or G mode signal of the H3CR-AP is OFF.
2. Refer to the Life-test Curve (Reference).
3. Contact output only.
Switching operations (x 103)
■ Life-test Curve (Reference)
10,000
5,000
1,000
30 VDC L/R = 7 ms
500
250 VAC/30
VDC (cosφ = 1)
100
250 VAC (cosφ = 0.4)
0
1
2
3
4
Load current (A)
7
5
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1) and
a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
H3CR-A
Connections
■ Block Diagrams
H3CR-A/-AS/-A-301
AC (DC) input
Power supply
circuit
Zero setting
detection
circuit
Time range/
unit selectors
Operating
mode selector
Oscillation
circuit
Counting
circuit
Output circuit
Input circuit
Indicator
circuit
Reset input, start input, and gate input
Power-ON Output-ON
indicator indicator
H3CR-AP
AC (DC) input
Power supply
circuit
Start
Zero setting
detection
circuit
Time range/
unit selectors
Operating
mode selector
Oscillation
circuit
Counting
circuit
Output circuit
Input circuit
Indicator
circuit
Power-ON Output-ON
indicator
indicator
8
H3CR-A
H3CR-A8/-A8S/A8-301
AC (DC) input
Power supply
circuit
Zero setting
detection
circuit
Time range/
unit selectors
Operating
mode selector
Oscillation
circuit
Counting
circuit
Output circuit
Indicator
circuit
Power-ON Output-ON
indicator indicator
H3CR-A8E
AC (DC) input
Power supply
circuit
Zero setting
detection
circuit
Oscillation
circuit
Time range/
unit selectors
Counting
circuit
Operating
mode selector
Output circuit
Indicator
circuit
Power-ON Output-ON
indicator
indicator
Instantaneous
output circuit
■ I/O Functions
Inputs (for -A/ Start
-AS models) Reset
Outputs
Starts time-measurement.
Interrupts time-measurement and resets time-measurement value. Timing operation is stopped and the
control output turns OFF (it is reset).
Gate
The timing operation is interrupted while the gate input is active.
Control output
Outputs are turned ON according to designated output mode when preset value is reached.
Note: H3CR-AP incorporates start input only.
Models H3CR-A8/-A8E/-A8S/-A8-301 do not have an input function.
9
H3CR-A
■ Terminal Arrangement
Note: 1. The delayed contact of conventional Timers was indicated as
The contact symbol of the H3CR-A is indicated as
because its operating mode is six multi-modes (four multi-modes for the H3CR-A8).
2. Do not use an empty terminal on the H3CR-AP/-AS/-A8S as a relay terminal or otherwise.
11-pin Models
8-pin Models
H3CR-A8/-A8-301 (Contact Output)
Gate input
Start input
Reset input
H3CR-A/-A-301 (Contact Output)
Power supply
Power supply
H3CR-A8S (Transistor Output)
Gate input
Start input
Reset input
H3CR-AS (Transistor Output)
Power supply
Note: Terminals 1, 3, 4, and 5 are empty. Terminals 2 and 7 are the
same as for the H3CR-A8.
Power supply
H3CR-A8E (Contact Output)
Note: Terminals 1, 3, 4, and 8 are empty. Terminals 2, 5, 6, 7, and 10
are the same as for the H3CR-A.
Start input
H3CR-AP (Contact Output)
Power supply
Power supply
Note: 1. Terminal 5 is empty.
2. Separate power supplies can be used for the Timer and inputs.
10
H3CR-A
■ Input Connections
H3CR-A/-AS/-A-301
The inputs of the H3CR-A/-AS/-A-301 are no-voltage (short-circuit or open) inputs.
No-voltage Inputs
No-contact Input
(Connection to NPN open
collector output sensor.)
12 to 24 VDC
(sensor power supply)
Sensor
Contact Input
12 to 24 VDC
(sensor power supply)
+ DC power
− supply
Timer
Timer
5 Gate
6 Start
7 Reset
5 Gate
6 Start
7 Reset
2 Input (0 V)
2 Input (0 V)
Operates with transistor ON
Operates with relay ON
No-voltage Input Signal Levels
No-contact
input
1. Short-circuit level
Transistor ON
Residual voltage: 1 V max.
Impedance when ON: 1 kΩ max.
2. Open level
Transistor OFF
Impedance when OFF: 100 kΩ min.
Contact
input
11
No-contact Input
(Connection to a voltage
output sensor.)
Use contacts which can
adequately switch 0.1 mA at 5 V
+ DC power
− supply
Timer
Sensor
5 Gate
6 Start
7 Reset
2 Input (0 V)
Operates with transistor ON
H3CR-A
H3CR-AP
The start input of the H3CR-AP is voltage input. (Voltage imposition or open)
Voltage Inputs
Sensor
+ DC power
− supply
Timer
10 Power
supply (+)
6 Start
7
Input 0V
2
Power
supply
(−)
Operates with PNP transistor ON
12 to 24 VDC
(sensor power supply)
Sensor
Contact Input
+ DC power
− supply
Timer
10 Power
supply (+)
6 Start
7 Input 0V
DC power supply
12 to 24 VDC
(sensor power supply)
No-contact Input
(Connection to NPN open
collector output sensor)
AC power supply
No-contact Input
(Connection to PNP open
collector output sensor)
2 Power
supply (−)
Operates with NPN transistor ON
Note: The input circuit is isolated from the
power supply circuit. Thus, an NPN
transistor can be connected.
Timer
Power
10 supply (+)
6
Start
7
Input 0V
2
Power
supply (−)
Operates with relay ON
Note: Refer to the signal levels in the
following table and be aware of the
minimum applicable load of the relay.
Note: Before making connections, refer to Safety Precautions (H3CR-@).
Voltage Input Signal Levels
No-contact
input
1. Transistor ON
Residual voltage: 1 V max.
The voltage between terminals 6 and 7 must be 10.8 VDC min.
2. Transistor OFF
Leakage current: 0.01 mA max.
The voltage between terminals 6 and 7 must be 1.2 VDC max.
Contact
input
Use contacts that can adequately switch 0.1 mA at each
operating voltage.
The voltage between terminals 6 and 7 with contacts ON or
OFF must satisfy the specified value.
Contacts ON
100-to-240-VAC and 100-to-125-VDC models: 85 to 264 VAC
or 85 to 137.5 VDC
24-to-48-VAC and 12-to-48-VDC models: 20.4 to 52.8 VAC or
10.8 to 52.8 VDC
Contacts OFF
100-to-240-VAC and 100-to-125-VDC models: 0 to 10 VAC or
0 to 10 VDC
24-to-48-VAC and 12-to-48-VDC models: 0 to 2.4 VAC or 0 to
1.2 VDC
12
H3CR-A
Operation
■ Timing Chart (Refer to page 20 for application examples.)
H3CR-A/-AS/-AP*/-A-301
Operating
mode
Timing chart
A: ON-delay
t
Power
Start
Reset
Output relay (NC)
Output relay (NO)
(Output indicator)
Power indicator
B:
Flicker OFF
start
Power
Start
Reset
Output relay (NC)
Output relay (NO)
(Output indicator)
Power indicator
B2:
Flicker ON
start
t
Basic operation
Power
Start
(See note)
t
Output
Note: Start input is invalid while the
Timer is in operation.
Basic operation
Power
Start
(See note)
t
t
t
t
Output
Note: Start input is invalid while
the Timer is in operation.
Basic operation
Power
Start
Reset
Output relay (NC)
Power
Start
(See note)
t
t
t
t
Output
Output relay (NO)
(Output indicator)
Power indicator
C:
Signal ON/
OFF-delay
Basic operation
Power
Start
Start
(See note)
Output relay (NC)
Output
Power indicator
13
Power
Reset
Output relay (NO)
(Output indicator)
Note: 1.
2.
3.
4.
5.
6.
Note: Start input is invalid while the
Timer is in operation.
t
t
t
t
Note: Start input is valid and
retriggerable while the Timer
is in operation.
Allow at least 0.1 s for the Timer reset time if the power supply is reset due to an interruption in the power supply.
The minimum input pulse width (for start, reset) is 0.05 s.
The letter "t" in the timing charts indicates the set time, and "t-a" means that the period is less than the set time. (t - a < 1)
H3CR-AP model incorporates start input only.
Model H3CR-AS only has operation equivalent to time-limit contact: NO.
When the setting dial is turned all the way past 0 for instantaneous output, "t" (set time) in the above time chart is 0-sec operation.
H3CR-A
Operating
mode
Timing chart
D:
Signal OFFdelay
Basic operation
Power
Start
Power
Reset
Start
(See note)
Output relay (NC)
t
Output
Output relay (NO)
(Output indicator)
Note: Start input is valid and
retriggerable while the
Timer is in operation.
Power indicator
E:
Interval
Basic operation
Power
Power
Start
Reset
Start
(See note)
Output relay (NC)
Output
Output relay (NO)
(Output indicator)
Note: Start input is valid and
retriggerable while the
Timer is in operation.
(Previous start input
will be cancelled.)
Power indicator
G:
Signal ON/
OFF-delay
t
Basic operation
Power
Power
Start
Start
(See note)
Reset
Output relay (NC)
t
t
t
Output
Output relay (NO)
(Output indicator)
Note: Start input is valid and
retriggerable while the Timer
is in operation.
Power indicator
J:
One-shot
output
t
Basic operation
Power
Start
Power
Reset
Start
(See note)
Output relay (NC)
1±0.6 s
(Fixed)
Output relay (NO)
(Output indicator)
Power indicator
1±0.6 s
(Fixed)
Output
t
1±0.6 s
(Fixed)
Note: Start input is valid and
retriggerable while the
Timer is in operation.
(Previous start input will
be cancelled.)
Gate Signal Input (This timing chart indicates the gate input in operating mode A (ON-delay operation).)
t1
Power ON
OFF
Start ON
OFF
Gate ON
OFF
Reset ON
OFF
Output ON
relay OFF
t2
Note: 1. Allow at least 0.1 s for the Timer reset time if the power
supply is reset due to an interruption in the power supply.
2. The minimum input pulse width (for start, reset) is 0.05 s.
3. The letter "t" in the timing charts indicates the set time, and
"t-a" means that the period is less than the set time.
(t - a < 1)
4. In J Mode, there will be only one output even if the start input is
longer than the set time.
5. H3CR-AP model incorporates start input only.
6. Model H3CR-AS only has operation equivalent to time-limit
contact: NO.
7. When the setting dial is turned all the way past 0 for
intantaneous output, "t" (set time) in the above time chart is
0-sec operation.
Note: The set time is the sum of t1 and t2.
Start and reset are also both enabled when the gate signal is ON.
14
H3CR-A
H3CR-A8/-A8S/-A8-301
Operating
mode
A:
ON-delay
Timing chart
Power
Basic operation
Output relay
(NC)
Power
t
Output relay
(NO) (output
indicator)
Power
indicator
B:
Flicker OFF
start
Output
t
t
t−a
Rt
t
t
t
t−a
Power
Basic operation
Output relay
(NC)
Power
Output relay
(NO) (output
indicator)
Power
indicator
B 2:
Flicker ON
start
t
Power
t
Power
t
Output
Power
indicator
15
t
Basic operation
Output relay
(NO) (output
indicator)
Note: 1.
2.
3.
4.
5.
t
v
Output relay
(NC)
Power
Output relay
(NO) (output
indicator)
Power
indicator
t
Output
Power
Output relay
(NC)
t
Power
Output relay
(NO) (output
indicator)
Power
indicator
J:
One-shot
output
t
Basic operation
Output relay
(NC)
E:
Interval
t
Output
Basic operation
1±0.6 s
(Fixed)
1±0.6 s
(Fixed)
Power
t
Output
1±0.6 s
(Fixed)
Allow a timer reset time (Rt) of 0.1 s or longer.
The letter "t" in the timing charts indicates the set time, and "t-a" means that the period is less than the set time. (t - a < 1)
Model H3CR-A8S only has operation equivalent to time-limit contact: NO.
When the setting dial is turned all the way past 0 for intantaneous output, "t" (set time) in the above time chart is 0-sec operation.
You can use J Mode to use the power supply as the start input.
H3CR-A
H3CR-A8E
Operating
mode
Timing chart
A:
ON-delay
Power
Output relay (NC)
Basic operation
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Power
Instantaneous
output relay (NO)
Output
t
Power indicator
B:
Flicker OFF
start
t
t
t−a
Rt
t
t
t
t−a
Power
Output relay (NC)
Basic operation
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Power
Instantaneous
output relay (NO)
Output
t
t
t
t
Power indicator
B 2:
Flicker ON
start
Power
Output relay (NC)
Basic operation
Output relay (NO)
(output indicator)
Power
Instantaneous
output relay (NC)
t
t
t
t
Output
Instantaneous
output relay (NO)
Power indicator
E:
Interval
Power
Output relay (NC)
Output relay (NO)
(output indicator)
Basic operation
Instantaneous
output relay (NC)
Power
Instantaneous
output relay (NO)
t
Output
Power indicator
J:
One-shot
output
Power
Output relay (NC)
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Instantaneous
output relay (NO)
(Fixed)
(Fixed)
Basic operation
Power
t
Output
1±0.6 s
(Fixed)
Power indicator
Note: Refer to page 14.
16
H3CR-A
Nomenclature
Power indicator (green) (Flashes when Timer
operates; lit when Timer stops operating)
Operating mode display window
Operating mode selector
Select a mode from:
A, B, B2, C, D, E, G, and J (H3CR-A, -AP, and -AS)
A, B, B2, E and J (H3CR-A8, -A8S, and -A8E)
Output indicator (orange)
(Lit when output)
Scale range display windows
Time unit display window
Time range selector (select one
from 1.2, 3, 12, and 30 at full
scale; with the H3CR-A@-301,
select from 2.4, 6, 24, or 60 at
full scale.)
Time setting
knob (set time)
Scale range display windows changes as below by
turning
the Time range selector clockwise.*
0
0.2
0.4
0.6
0.8
1.0
1.2
0
0.5
1
1.5
2
2.5
3
0
2
4
6
8
10
12
0
5
10
15
20
25
30
* On the H3CR-A@-301 type, the time is twice as long.
17
Time unit selector (select one from
sec, 10s, min, 10m, hrs, and 10h)
H3CR-A
Dimensions
Note: All units are in millimeters unless otherwise indicated.
H3CR-A
H3CR-AP
H3CR-AS
H3CR-A-301
15
66.6
52.3
0.7
6
48
39 dia.
48
44.8 × 44.8
11 pins
H3CR-A8
H3CR-A8S
H3CR-A8E
H3CR-A8-301
15
66.6
52.3
0.7
6
48
39 dia.
48
44.8 × 44.8
8 pins
Dimensions with Set Ring
Y92S-27/-28 (Order Separately)
16.5
50
42 dia.
50
Panel cover
Time Setting
Ring
Dimensions with Front Connecting Socket
P2CF-08-@/P2CF-11-@
Dimensions with Back Connecting Socket
P3G-08/P3GA-11
15
100.8*
H3CR-A
H3CR-A-301
H3CR-AS
H3CR-AP
98.5
89.9*
H3CR-A8@
H3CR-A8-301
H3CR-A8E
H3CR-A8S
87.6
81.5
80
H3CR-A
H3CR-A-301
H3CR-AS
H3CR-AP
+
Adapter
Y92F-30
P2CF-11
P2CF-11-E
2.3*
P2CF-08
P2CF-08-E
2.3*
15
P3GA-11
(When
Y92A-48G
mounted)
81.5
75
H3CR-A8@
H3CR-A8-301
H3CR-A8E
H3CR-A8S
+
Adapter
Y92F-30
P3G-08
(When
Y92A-48G
mounted)
Note: There are no restrictions to the mounting direction.
* These dimensions vary with the kind of DIN track (reference value).
18
H3CR-A
■ Accessories (Order Separately)
Protective Cover
Y92A-48B
Hold-down Clip
Y92H-8
To use the Protective Cover with a flush mounting, use the Y92F-30
flush mounting adaptor.
The Y92H-8 Hold-down Clip is attached to the PF085A socket.
This Protective Cover cannot be used together with the Y92F-73/-74
flush mounting adaptor or the panel cover.
Y92H-7
Y92H-7 Hold-down Clip is attached with screws together with the
PL08 socket or the PL11 socket.
19
H3CR-A
Application Examples (H3CR-A)
A Mode: ON-delay
ON-delay operation (A mode) is a basic mode.
1. Power-ON Start/Power-OFF Reset
The Power-ON start/Power-OFF reset operation is a standard
operating method.
t
3. Control of Integrated Time with Gate
Signal
Gate signal processing (during input or a temporary timing stop) is
possible with both power start and signal start.
Power (2 and 10)
t1
t2
t1 + t2: set time
Power (2 and 10)
Start (2 and 6)
Reset (2 and 7)
Start (2 and 6)
Control output: NC (8 and 11)
NC (1 and 4)
Gate (2 and 5)
Control output: NO (9 and 11)
NO (1 and 3)
Control output: NC (8 and 11)
NC (1 and 4)
Power indicator
Flashing
Control output: NO (9 and 11)
NO (1 and 3)
Lit
Power indicator
Externally short-circuited
Flashing
Lit
Gate signal (The operation is interrupted with the
gate signal if the Timer detects an abnormal signal.)
Externally
short-circuited
Power
supply
2. Signal Start/Signal Reset
The Signal start/Signal reset operation is useful for remote control of
the Timer.
Power
supply
B/B2 Mode: Flicker
The flicker operation in the B and B2 modes can be effectively
applied to lamp or buzzer (ON and OFF) alarms or the monitoring of
an intermittent operation with a display.
Power (2 and 10)
Start (2 and 6)
1. Power-ON Start/Power-OFF Reset (in B
Mode)
Reset (2 and 7)
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power (2 and 10)
Power indicator
Lit
Flashing
Lit
Start signal (remote control possible)
Reset signal
(remote control possible)
Start (2 and 6)
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power indicator
Flashing
Externally short-circuited
Power
supply
(Power continuously supplied)
Power
supply
20
H3CR-A
2. Signal Start/Signal Reset (in B Mode)
If there is an abnormal signal, flashing starts. When the abnormal
condition is restored, a reset signal stops the display flashing.
t
2. Signal-ON-OFF Start/Instantaneous
Operation/Time-limit Reset
Power (2 and 10)
t
Power (2 and 10)
Start (2 and 6)
Start (2 and 6)
Control output: NC (8 and 11)
NC (1 and 4)
Reset (2 and 7)
Control output: NO (9 and 11)
NO (1 and 3)
Control output: NC (8 and 11)
NC (1 and 4)
Lit
Flashing
Lit
Flashing
Lit
Start signal
(The operation starts with the signal ON or OFF)
Start signal
Reset signal
Power
supply
Power
supply
(Power continuously supplied)
(Power continuously supplied)
D Mode: Signal OFF-delay
C Mode: Signal ON/OFF-delay
The Signal ON-/OFF-delay operation (C mode) is useful for the
control of distribution of products on a production line into boxes by
the specified number or time.
Signal OFF-delay operation (D mode) can be effectively used to keep
a load operating for a certain period. For example, this function
enables the cooling fan for a lamp or heater to operate for a certain
period after the lamp or heater is switched OFF.
1. Power-ON Start/Instantaneous Operation/
Time-limit Reset
1. Power-ON Start/Instantaneous Operation/
Time-limit Reset
A set of these functions is useful for the operation of a machine for a
specified period when power is ON.
t
Power (2 and 10)
Start (2 and 6)
t
Power (2 and 10)
Control output: NC (8 and 11)
NC (1 and 4)
Start (2 and 6)
Control output: NO (9 and 11)
NO (1 and 3)
Control output: NC (8 and 11)
NC (1 and 4)
Power indicator
Lit
Control output: NO (9 and 11)
NO (1 and 3)
Power indicator
Flashing
Start signal (NC to NO)
Flashing
Lit
Flashing
Lit
Externally short-circuited
Power
supply
Power
supply
21
Lit
Flashing
Lit
Lit
Power indicator
Flashing
Power indicator
Control output: NO (9 and 11)
NO (1 and 3)
Lit
H3CR-A
2. Signal Start/Instantaneous Operation/
Time-limit Reset
2. Signal Start/Instantaneous Operation/
Time-limit Reset
This function is useful for the repetitive control such as the filling of
liquid for a specified period after each Signal start input.
Power (2 and 10)
Start (2 and 6)
t
t
Power (2 and 10)
Control output: NC (8 and 11)
NC (1 and 4)
Start (2 and 6)
Control output: NO (9 and 11)
NO (1 and 3)
Control output: NC (8 and 11)
NC (1 and 4)
Power indicator
Lit
Flashing
Lit
Control output: NO (9 and 11)
NO (1 and 3)
Power indicator
Start signal (NO to NC to NO)
Start signal
Flashing
Lit
Flashing
Lit
Power
supply
Power
supply
(Power continuously supplied)
(Power continuously supplied)
E Mode: Interval
1. Power-ON Start/Instantaneous Operation/
Time-limit Reset
This function is useful for the operation of a machine for a specified
period after power is ON.
t
t
Power (2 and 10)
Start (2 and 6)
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power indicator
Flashing
Externally short-circuited
Lit
Flashing
Lit
Power
supply
22
H3CR-A
Safety Precautions (H3CR-A)
Refer to Safety Precautions for All Timers.
Note: The following precautions apply to all H3CR-A models.
■ Power Supplies
■ Input/Output
For the power supply of an input device of the H3CR-A use an
isolating transformer with the primary and secondary windings
mutually isolated and the secondary winding not grounded.
Correct
H3CR-A
G, S, R
5, 6, 7
10
Input
terminal
2
Power supply
2
Relationship between Input and Power
Supply Circuits (except for H3CR-A8E)
The H3CR-A (except for H3CR-A8E) uses transformerless power
supply. When connecting a relay or transistor as an external signal
input device, pay attention to the following points to prevent shortcircuiting due to a sneak current to the transformerless power supply.
If a relay or transistor is connected to two or more Timers, the input
terminals of those Timers must be wired properly so that they will not
differ in phase, otherwise the terminals will be short-circuited to one
another.
Incorrect
Contact or transistor for
external input signal
Input
terminal
Isolation transformer is required.
Input device
H3CR-A
Short-circuit current
Power supply
Incorrect
G, S, R
5, 6, 7
2
H3CR-A
Input
terminal
10
Input
terminal
Power
supply
2
Correct
Contact or transistor for
external input signal
Input device
H3CR-A
Input
terminal
Isolation
transformer
Power supply
The H3CR-A’s power supply terminal 2 is a common terminal for
input signals to the Timer. Do not disconnect the wires on terminal 2,
otherwise the internal circuitry of the Timer will be damaged.
Input
terminal
5, 6, 7
G, S, R
AC or DC
Power Supply
Input terminal
10
H3CR-A
2
It is impossible to provide two independent power switches as shown
below regardless of whether or not the Timers are different in phase.
Contact or transistor for
external input signal
H3CR-A
Input
terminal
Input
terminal
23
Power supply
H3CR-A
Relationship between Input and Power
Supply Circuits (H3CR-A@/-A@S)
An appropriate input is applied to the input signal terminals of the
H3CR-A@/-A@S when one of the input terminals is short-circuited
with the common terminal (terminal 2) for the input signals. Never
use terminal 10 as the common terminal for this purpose, otherwise
the internal circuit of the Timer will be damaged.
If a relay or transistor is connected to two or more Timers, the input
terminals of those Timers must be wired properly so that they will not
be different in phase or the terminals will be short-circuited to one
another (refer to the figures below).
Incorrect
Contact or transistor for
external input signal
10
6
Correct
H3CR-AP
7
10
5, 6, 7
G, S, R
Input terminal
AC or DC
power supply
Power supply
2
H3CR-A/-AS
10
6
2
H3CR-AP
7
Incorrect
Short-circuit current
2
10
AC or DC
power supply
5, 6, 7
G, S, R
Correct
Contact or transistor for
external input signal
H3CR-A/-AS
10
6
Input terminal
2 *1
7
Power supply
H3CR-AP
2
*2
10
Ry
AC or DC
power supply
5, 6, 7
G, S, R
H3CR-A/-AS
Input terminal
Input
contact
Short-circuit current
6
7
10
H3CR-AP
2
2
*1 Power terminal 2 is a common terminal that is also used for the
input signal. Do not use terminal 10 as a common terminal as
this will damage the internal circuitry.
*2 If a relay or other load is connected here, high voltage will be
applied to the input terminal and damage the internal circuitry.
• The transistor output of the H3CR-A@S is isolated from the internal
circuitry by a photocoupler, and can therefore be used either as an
NPN output type or a PNP (equivalent) output type.
Relationship between Input and Power
Supply Circuits (H3CR-AP)
When using the timer in an environment where considerable noise
occurs, keep the input signal source device, timer unit, and wiring as
far away as possible from the source of the noise. It is also
recommended that shielded wire be used for the input signal wiring
as a countermeasure for noise.
Common to All H3CR-A Models
With the H3CR-AP, input wires must be as short as possible. If the
floating capacity of wires exceeds 1,200 pF (approx. 10 m for cables
with 120 pF/m), the operation will be affected. Pay particular
attention when using shielded cables.
The H3CR-A@S transistor output is isolated from the internal
circuitry by a photocoupler. Therefore, either NPN or PNP output is
possible.
H3CR-AP
AC/DC
power
supply
Input circuit
Power supply
circuit
Since the input circuit and the power supply circuit are configured
independently, the input circuit can be turned ON or OFF irrespective
of the ON/OFF state of the power supply.
It must be noted that a voltage equivalent to the power supply voltage
is applied to the input circuit.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
24
MEMO
25
Solid-state Twin Timers
H3CR-F
DIN 48 × 48-mm Twin Timers
• Wide power supply ranges of High Voltage 100 to 240 VAC/100
to 125 VDC and Low Voltage 24 to 48 VAC/12 to 48 VDC.
• ON- and OFF-times can be set independently and so
combinations of long ON- or OFF-time and short OFF- or ONtime settings are possible.
• Twenty-four time ranges from 0.05 s to 300 h depending on the
model to be used.
• Models with a flicker ON start or flicker OFF start are available.
• Easy sequence checks through instantaneous outputs for a
zero set value at any time range.
• Length, when panel-mounted with a Socket, of 80 mm or less.
• 11-pin and 8-pin models are available.
For the most recent information on models that have been
certified for safety standards, refer to your OMRON website.
Model Number Structure
■ Model Number Legend
H3CR - F @ @ - @ @
1 2
3
1. Classification
F:
Twin timers
2. Configuration
None: 11-pin socket
8:
8-pin socket
4
5
3. Twin Timer Mode
None: Flicker OFF start
N:
Flicker ON start
4. Time Range
None: 0.05 s to 300 h models
5. Supply Voltage
100-240AC/100-125DC: 100 to 240 VAC/100 to 125 VDC
24-48AC/12-48DC:
24 to 48 VAC/12 to 48 VDC
Note: When your order, specify the power supply voltage.
Ordering Information
■ List of Models
Operating modes
Supply voltage
0.05 s to 300 h models
11-pin models
Flicker OFF start
Flicker ON start
8-pin models
100 to 240 VAC/100 to 125 VDC
H3CR-F 100-240AC/100-125DC
H3CR-F8 100-240AC/100-125DC
24 to 48 VAC/12 to 48 VDC
H3CR-F 24-48AC/12-48DC
H3CR-F8 24-48AC/12-48DC
100 to 240 VAC/100 to 125 VDC
H3CR-FN 100-240AC/100-125DC
H3CR-F8N 100-240AC/100-125DC
24 to 48 VAC/12 to 48 VDC
H3CR-FN 24-48AC/12-48DC
H3CR-F8N 24-48AC/12-48DC
Note: Specify both the model number and supply voltage when ordering.
Example: H3CR-F 100-240AC/100-125DC
Supply voltage
26
H3CR-F
■ Accessories (Order Separately)
Adapter, Protective Cover and Hold-down Clip
Name/specifications
Models
Flush Mounting Adapter
Y92F-30
Y92F-73 *1
Y92F-74 *1
Y92A-48B *2
Protective Cover
Hold-down Clip
(Sold in sets of two)
For PF085A Socket
Y92H-8
For PL08 or PL11 Sockets
Y92H-7
Note: Refer to Operation (Common) datasheet for details.
*1 The Y92A-48B Protective Cover and the Y92F-73/-74 Flush Mounting Adapter cannot be used at the same time.
*2 The Y92A-48B Protective Cover is made from hard plastic.
Remove the Protective Cover to change the set value.
The Y92A-48B Protective Cover and the Y92F-73/-74 Flush Mounting Adapter also cannot be used at the same time.
Sockets
Timer
Round Sockets
Pin
Connection
11-pin
Front Connecting
Back Connecting
8-pin
Front Connecting
Back Connecting
Terminal
Models
DIN track mounting
P2CF-11
DIN track mounting
(Finger-safe type)
P2CF-11-E
Screw terminal
P3GA-11
Solder terminal
PL11
Wrapping terminal
PL11-Q
PCB terminal
PLE11-0
DIN track mounting
P2CF-08
DIN track mounting
(Finger-safe type)
P2CF-08-E
DIN track mounting
PF085A
Screw terminal
P3G-08
Solder terminal
PL08
Wrapping terminal
PL08-Q
PCB terminal
PLE08-0
Note: 1. The P2CF-@@-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals.
2. The P3GA-11 and P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection.
3. For details, refer to your OMRON website.
Terminal Cover
Application
For back connecting socket
Note: For details, refer to your OMRON website.
27
Model
Y92A-48G
Remarks
For P3G-08 and P3GA-11
H3CR-F
Specifications
■ General
Item
H3CR-F
H3CR-F8
H3CR-FN
Operating mode
Flicker OFF start
Pin type
11-pin
Operating/Reset method
Time-limit operation/Time-limit reset or self-reset
Output type
Relay output (DPDT)
Mounting method
DIN track mounting, surface mounting, and flush mounting
Approved standards
UL508, CSA C22.2 No.14, NK, Lloyds, CCC
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1.
H3CR-F8N
Flicker ON start
8-pin
11-pin
8-pin
Note: For details, refer to your OMRON website.
■ Time Ranges
Time unit
Fullscale
setting
1.2
s (sec)
0.05 to 1.2
×10 s (10 sec)
1.2 to 12
min (min)
0.12 to 1.2
×10 min (10 min)
1.2 to 12
h (hrs)
0.12 to 1.2
×10 h (10 hrs)
1.2 to 12
3
0.3 to 3
3 to 30
0.3 to 3
3 to 30
0.3 to 3
3 to 30
12
1.2 to 12
12 to 120
1.2 to 12
12 to 120
1.2 to 12
12 to 120
30
3 to 30
30 to 300
3 to 30
30 to 300
3 to 30
30 to 300
Note: The times that can be set are given. When the time setting knob is turned below “0” until the point where the time setting knob stops, the
output will operate instantaneously at all time range settings.
For details, refer to your OMRON website.
■ Ratings
Rated supply voltage (See notes 1, 2, and 3.) • 100 to 240 VAC 50/60 Hz/100 to 125 VDC
• 24 to 48 VAC 50/60 Hz/12 to 48 VDC
Operating voltage range
85% to 110% of rated supply voltage; 90% to 110% with 12-VDC models
Power reset
Minimum power-opening time: 0.1 s
Power consumption
100 to 240 VAC: approx. 10 VA (2.1 W) at 240 VAC
24 VAC/VDC:
approx. 2 VA (1.7 W) at 24 VAC
approx. 1 W at 24 VDC
Control outputs
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
The minimum applicable load is 10mA at 5VDC (P reference value).
Contact materials : Ag-alloy
Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
2. Do not use an inverter output as the power supply. Refer to your OMRON website for details.
3. Refer to your OMRON website when using the Timer together with a 2-wire AC proximity sensor.
28
H3CR-F
■ Characteristics
Accuracy of operating
time
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 1.2 and 3 s)
Setting error
±5% FS ±50 ms max.
Reset time
0.1 s max.
Reset voltage
10% max. of rated voltage
Influence of voltage
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 1.2 and 3 s)
Influence of temperature ±1% FS max. (±1% FS ±10 ms max. in ranges of 1.2 and 3s)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand
voltage
5kV (between power terminals), however, 1kV for 24 to 48VAC, 12 to 48 VDC
5kV (between current-carrying terminal and exposed non-current-carrying metal parts), however 1.5 kV for 24 to 48 VAC,
12 to 48 VDC
Noise immunity
±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity
Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance
Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Shock resistance
Destruction: 980 m/s2 three times each in six directions
Malfunction: 98 m/s2 three times each in six directions
Ambient temperature
Operating:
Storage:
−10°C to 55°C (with no icing)
−25°C to 65°C (with no icing)
Ambient humidity
Operating:
35% to 85%
Life expectancy
Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
Electrical:
100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)
EMC
(EMI)
Emission Enclosure:
Emission AC Mains:
(EMS)
Immunity ESD:
Immunity RF-interference:
Immunity Burst:
Immunity Surge:
Immunity Conducted Disturbance:
Immunity Voltage Dip/Interruption:
Case color
Light Gray (Munsell 5Y7/1)
Degree of protection
IP40 (panel surface)
Weight
Approx. 100 g
EN61812-1
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61812-1
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
IEC61000-4-6
IEC61000-4-11
Note: Refer to the Life-test Curve (Reference).
■ Life-test Curve (Reference)
Switching operations (x 103)
10,000
5,000
1,000
500
30 VDC L/R = 7 ms
250 VAC/30 VDC
(cosφ = 1)
100
250 VAC (cosφ = 0.4)
Load current (A)
29
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1) and
a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
H3CR-F
Connections
■ Block Diagrams
H3CR-F/-F8/-FN/F8N
ON indicator
Indicator
circuit
AC (DC) input
Power supply
circuit
Zero setting
detection
circuit
OFF indicator
ROM
RAM
Clock
Output
circuit
Time range/unit
selectors
One-chip microcomputer
■ I/O Functions
---
Inputs
Outputs
Control output
Outputs are turned ON/OFF according to the time set by the ON- and OFF-time setting knob.
■ Terminal Arrangement
H3CR-F8/-F8N
H3CR-F/-FN
(+)(~)
Power supply
Power supply
Note: Leave terminals 5, 6, and 7 open.
Do not use them as relay terminals.
30
H3CR-F
Operation
■ Timing Chart
tON: ON set time
tOFF: OFF set time
Operating mode
Timing chart
Rt
Flicker OFF start
ON
OFF
Power
ONindicator
Lit
Not lit
OFF indicator
Lit
Not lit
Output NO
Output NC
tOFF
tON
tOFF
tON
tOFF
tOFF
ON
OFF
ON
OFF
Flicker ON start
Rt
Power
ON
OFF
ONindicator
tON
tOFF
tON
tOFF
tON
tOFF
Lit
Not lit
OFF indicator
Lit
Not lit
Output NO
ON
OFF
Output NC
ON
OFF
Note: 1. Allow a timer reset time (Rt) of 0.1 s or longer
2. When the setting dial is turned all the way past 0 for intantaneous output, "t" (set time) in the above time chart is 0-sec operation.
Nomenclature
Scale range display windows
changes as below by turning
the Time range selector clockwise.
0
0.2
0.4
0.6
0.8
1.0
0
0.5
1
1.5
2
2.5
0
2
4
6
8
10
12
0
5
10
15
20
25
30
OFF indicator (green)
Lit when the output is OFF.
ON indicator (orange)
Lit when the output is ON.
Scale range display
windows
1.2
3
OFF-time unit display window
OFF-time unit selector (select one from sec.
10 s, min., 10 min, hrs, and 10 h)
ON-time setting knob (with orange pointer)
For ON-time setting
OFF-time setting knob (with green pointer)
For OFF-time setting
Time range selector (select one
from 1.2, 3, 12, and 30 at full
scale)
For both ON-time and OFF-time.
31
ON-time unit display window
ON-time unit selector (select one
from sec, 10 s, min, 10 min, hrs, and
10 h)
H3CR-F
Dimensions
Note: All units are in millimeters unless otherwise indicated.
17.4
H3CR-F
H3CR-FN
5.7
66.6
52.3
0.7
6
48
37 din.
48
44.8 × 44.8
14 din.
11 pins
17.4
5.7
H3CR-F8
H3CR-F8N
66.6
52.3
0.7
6
48
37 din.
48
44.8 × 44.8
14 din.
8 pins
Dimensions with Flush Mounting Adapter
Y92F-30 Flush Mounting Adapter (Order Separately)
Panel
P3G
Back Connecting Socket
(Order separately)
Mounting Hole Dimensions
(Conform to DIN 43700.)
0.5 R max.
58
45+0.6
-0
(N)
52
45+0.6
-0
42
48
Note: 1. The orientation of the Adapters for two or more Timers is
different for a horizontal or vertical layout. Make sure the
orientation is correct.
Consecutive Mounting of n Timers
Without Front Covers: N = (48n - 2.5) + 1 - 0
With Front Covers: N = (51n - 5.5) + 1 - 0
With Panel Covers: N = (50n - 4.5) + 1 - 0
2. The applicable thickness of the mounting panel must be 1 to 5 mm.
Y92F-73 Flush Mounting Adapter (Order Separately)
Panel
Adapter mounting holes: Two, 4.5 d
P3G
Back Connecting Socket
52 to 53
0.5 R max.
65 to 66
88 45±0.15
76±0.2
Insert the Timer
in this direction.*
45±0.15
58
Note: A Front Cover and Flush Mounting Adapter cannot be used at the
same time.
52.3
Note: The applicable thickness of the mounting panel must be 1 to
3.2 mm.
* Insert the Timer from the back of the Adapter.
32
H3CR-F
Y92F-74 Flush Mounting Adapter (Order Separately)
Panel
56
P3G
Back Connecting Socket
58 45±0.2
0.5 R max.
45+0.5
-0
55+0.5
-0
68
43±0.2
50+0.2
0
52.3
Note: A Front Cover and Flush Mounting Adapter cannot be used at the
same time.
Dimensions with Front Connecting Socket
P2CF-08-@/P2CF-11-@
Dimensions with Back Connecting Socket
P3G-08/P3GA-11
17.4
H3CR-F
H3CR-FN
103.2*
H3CR-F8
H3CR-F8N
100.9
92.3*
Note: The applicable thickness of the mounting panel must be
1 to 3.2 mm.
90.0
81.5
80
H3CR-F
H3CR-FN
+
Adapter
81.5
75
H3CR-F8
H3CR-F8N
+
Adapter
P3G-08
(When
Y92A-48G
mounted)
Note: There are no restrictions to the mounting direction.
Y92F-30
2.3*
2.3*
P2CF-11
P2CF-08
P2CF-11-E
P2CF-08-E
* These dimensions vary with the kind of DIN track (reference value).
P3GA-11
(When
Y92A-48G
mounted)
17.4
Y92F-30
■ Accessories (Order Separately)
Protective Cover
Y92A-48B
Hold-down Clip
Y92H-8
To use the Protective Cover with a flush mounting, use the Y92F-30
flush mounting adaptor.
The Y92H-8 Hold-down Clip is attached to the PF085A socket.
This Protective Cover cannot be used together with the Y92F-73/-74
flush mounting adaptor or the panel cover.
Hold-down Clip
Y92H-7
Y92H-7 Hold-down Clip is attached with screws together with the
PL08 socket or the PL11 socket.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
33
Solid-state Star-delta Timers
H3CR-G
DIN 48 × 48-mm Star-delta Timer
• A wide star-time range (up to 120 seconds) and star-delta
transfer time range (up to 1 seconds).
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Model Number Structure
■ Model Number Legend
H3CR - G 8 @ L @
1 2 3 4 5
1. Classification
G: Star-delta timer
2. Configuration
8: 8-pin socket
3. Outputs
None: Star-delta operation contact
E:
Star-delta operation contact
and instantaneous contact
4. Dimensions
L:
Long-body model
Note: When your order, specify the power supply voltage.
5. Supply Voltage
100-120AC: 100 to 120 VAC
200-240AC: 200 to 240 VAC
Ordering Information
■ List of Models
Outputs
Supply voltage
Time-limit contact
Time-limit contact and instantaneous contact
8-pin models
100 to 120 VAC
H3CR-G8L 100-120AC
200 to 240 VAC
H3CR-G8L 200-240AC
100 to 120 VAC
H3CR-G8EL 100-120AC
200 to 240 VAC
H3CR-G8EL 200-240AC
Note: Specify both the model number and supply voltage when ordering.
Example: H3CR-G8L 100-120AC
Supply voltage
34
H3CR-G
Accessories (Order Separately)
■ Accessories (Order Separately)
Adapter, Protective Cover, Setting Ring and Panel Cover
Name/specifications
Models
Y92F-30
Flush Mounting Adapter
Y92F-70 *1
Y92F-71 *1
Y92A-48B *2
Protective Cover
Hold-down Clip
For PF085A Socket
Y92H-2
For PL08 Sockets
Y92H-1
Setting Ring A
Y92S-27 *3
Setting Ring B and C
Y92S-28 *3
Panel Cover
Light gray (5Y7/1)
Y92P-48GL *4
Black (N1.5)
Y92P-48GB *4
Note: Refer to Operation (Common) datasheet for detail.
*1 The Y92A-48B Protective Cover and the Y92P-48G@ Panel Cover can not be used at the same time with the Y92F-70/-71 Flush Mounting Adapter.
*2 The Y92A-48B Protective Cover is made from hard plastic. Remove the Protective Cover to change to set value. The Y92F-70/-71 Flush
Mounting Adapter and the Y92P-48G@ Panel Cover cannot be used at the same time with Y92A-48B Protective Cover.
*3 The Y92S-27/-28 Setting Ring cannot be used alone. It must be used together with the Y92P-48G@ Panel Cover.
*4 The Y92A-48B Protective Cover and the Y92F-70/-71 Flush Mounting Adapter cannot be used at the same time with the Y92P-48G@ Panel Cover.
Sockets
Timer
Round Sockets
Pin
Connection
8-pin
Front Connecting
Back Connecting
Terminal
Models
DIN track mounting
P2CF-08
DIN track mounting
(Finger-safe type)
P2CF-08-E
DIN track mounting
PF085A
Screw terminal
P3G-08
Solder terminal
PL08
Wrapping terminal
PL08-Q
PCB terminal
PLE08-0
Note: 1. The P2CF-08-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals.
2. The P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection.
3. For details, refer to your OMRON website.
Terminal Cover
Application
For back connecting socket
Note: For details, refer to your OMRON website.
35
Model
Y92A-48G
Remarks
For P3G-08 and P3GA-11
H3CR-G
Specifications
■ General
Item
H3CR-G8L
H3CR-G8EL
Functions
Star-delta timer
Star-delta timer with instantaneous output
Pin type
8-pin
Operating/Reset method
Time-limit operation/Self-reset
Output type
Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Mounting method
DIN track mounting, surface mounting, and flush mounting
Approved standards
UL508, CSA C22.2 No.14, NK, Lloyds, CCC
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1.
Time-limit:
SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Instantaneous: SPST-NO
Note: For details, refer to your OMRON website.
■ Time Ranges
Time unit
Star operation time ranges
Scale number (max.)
6
Set time range
0.5 to 6 s
12
1 to 12 s
60
5 to 60 s
120
10 to 120 s
Star-delta transfer time
Programmable at 0.05 s, 0.1 s, 0.25 s, 0.5 s, 0.75 s, or 1.0 s
■ Ratings
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz)
Operating voltage range
85% to 110% of rated supply voltage
Power reset
Minimum power-opening time: 0.5 s
Power consumption
100 to 120 VAC: approx. 6 VA (2.6 W) at 120 VAC
200 to 240 VAC: approx. 12 VA (3.0 W) at 240 VAC
Control outputs
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
The minimum applicable load is 10mA at 5VDC (P reference value).
Contact materials : Ag-alloy
Note: 1. Do not use an inverter output as the power supply. Refer to your OMRON website for details.
2. Refer to your OMRON website when using the Timer together with a 2-wire AC proximity sensor.
36
H3CR-G
■ Characteristics
Accuracy of operating
time
±0.2% FS max.
Setting error
±5% FS ±50 ms max.
Accuracy of Star-delta
transfer time
±25% FS + 5 ms max.
Reset voltage
10% max. of rated voltage
Influence of voltage
±0.2% FS max.
Influence of temperature ±1% FS max.
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand
voltage
5 kV (between power terminals)
5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
Noise immunity
±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity
Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance
Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Shock resistance
Destruction: 980 m/s2 three times each in six directions
Malfunction: 294 m/s2 three times each in six directions
Ambient temperature
Operating:
Storage:
−10°C to 55°C (with no icing)
−25°C to 65°C (with no icing)
Ambient humidity
Operating:
35% to 85%
Life expectancy
Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
Electrical:
100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)
EMC
(EMI)
Emission Enclosure:
Emission AC Mains:
(EMS)
Immunity ESD:
Immunity RF-interference:
Immunity Burst:
Immunity Surge:
Immunity Conducted Disturbance:
Immunity Voltage Dip/Interruption:
Case color
Light Gray (Munsell 5Y7/1)
Degree of protection
IP40 (panel surface)
Weight
H3CR-G8L: approx. 110 g; H3CR-G8EL: approx. 130 g
Note: Refer to the Life-test Curve (Reference).
37
EN61812-1
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61812-1
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
IEC61000-4-6
IEC61000-4-11
H3CR-G
■ Life-test Curve (Reference)
Switching operations (× 103)
10,000
5,000
1,000
500
30 VDC L/R = 7 ms
250 VAC/30 VDC
(cosφ = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1) and
a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
100
250 VAC (cosφ = 0.4)
Load current (A)
Connections
■ Block Diagrams
H3CR-G8L
AC input
Power
supply
circuit
Star operation
time
oscillation
circuit
Star
operation
time range
selector
Star-delta
transfer time
selector
Star
operation
time counting
circuit
Star-delta
transfer time
oscillation
circuit
Star-delta
transfer time
counting
circuit
Output
circuit
Star operation
Delta operation
Indicator
circuit
Star
operation
indicator
Delta
operation
indicator
H3CR-G8EL
AC input
Power
supply
circuit
Star operation
time
oscillation
circuit
Star
operation
time range
selector
Star-delta
transfer time
selector
Star
operation
time counting
circuit
Star-delta
transfer time
oscillation
circuit
Star-delta
transfer time
counting
circuit
Star operation
Output
circuit
Delta operation
Indicator
circuit
Star
operation
indicator
Delta
operation
indicator
Instantaneous
output circuit
38
H3CR-G
■ I/O Functions
---
Inputs
Outputs
Control output
If the time reaches the value set with the time setting knob, the star operation output will be turned OFF
and there will be delta operation output after the set star-delta transfer time has elapsed.
■ Terminal Arrangement
H3CR-G8L
H3CR-G8EL
Delta
operation
contact
Star
operation
contact
Delta
operation
contact
Instantaneous contact
Note: Leave terminals 1, 3, and 4 open.
Do not use them as relay terminals.
Star
operation
contact
Note: Leave terminal 4 open. Do not use
them as relay terminals.
Operation
■ Timing Chart
t1:
t2:
Star operation time setting
Star-delta transfer time
Model
Timing chart
0.5 s min.
H3CR-G8L/-G8EL
Power (2 − 7)
ON
OFF
Instantaneous output
(1 − 3) (-E models)
ON
OFF
Star operation
output (8 − 5)
ON
OFF
Delta operation
output (8 − 6)
ON
OFF
Star operation indicator
Lit
Not lit
Delta operation indicator
Lit
Not lit
t1
t2
Nomenclature
Scale range display windows
changes as below by turning
the Time range selector clockwise.
0
1
2
3
4
5
6
0
2
4
6
8
10
12
0
10
20
30
40
50
60
0
20
40
60
80
100
120
Star operation
indicator (green)
Delta operation
indicator (orange)
Scale range display
windows
Time unit display
(sec is fixed)
Star operation time range selector
(select one from 6, 12, 60, and 120
at full scale)
Star-delta transfer time selector
(select one from 0.05 s, 0.1 s,
0.25 s, 0.5 s, 0.75 s, and 1.0 s)
Time setting knob (for setting
star operation time)
Star-delta transfer time display window
39
H3CR-G
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Dimension of Timer main unit
15
(78)
6
63.7
0.7
48
13.6
44.8 ✕ 44.8
39 dia.
48
79.4
Dimensions with Set Ring and Panel Cover
Y92S-27/-28 (Order Separately)
16.5
50
42 dia.
50
Time setting ring
Dimensions with Front Connecting Socket
P2CF-08-@
15
101.3*
H3CR-G8@L
Panel cover
Dimensions with Back Connecting Socket
P3G-08
99
92.9
86.4
H3CR-G8@L
+
Adapter
Y92F-30
P2CF-08
P2CF-08-E
2.3*
P3G-08
(When
Y92A-48G
mounted)
Note: There are no restrictions to the mounting direction.
* These dimensions vary with the kind of DIN track (reference value).
40
H3CR-G
■ Accessories (Order Separately)
Protective Cover
Y92A-48B
Hold-down Clip
Y92H-2
To use the Protective cover with a flush mounting, use the Y92F-30
flush mounting adaptor.
The Y92H-2 Hold-down Clip is attached to the PF085A socket.
This Protective cover cannot be used together with the Y92F-70/-71
flush mounting adaptor or the panel cover.
Y92H-1
Y92H-1 Hold-down Clip is attached with screws together with the
PL08 socket.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
41
Solid-state Power OFF-delay Timers
H3CR-H
DIN 48  48-mm Power OFF-delay Timer
• Long power OFF-delay times;
S-series: up to 12 seconds,
M-series: up to 12 minutes.
• Models with forced-reset input are available.
• 11-pin and 8-pin models are available.
For the most recent information on models that have been
certified for safety standards, refer to your OMRON website.
Model Number Structure
■ Model Number Legend
Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 42 for
availability.
H3CR - H @ @ L @ @
1 2
3 4 5
Note: Specify the model number, supply voltage, and time range (S or M) when ordering.
6
1. Classification
H:
Power OFF-delay timer
2. Configuration
None: 11-pin socket
8:
8-pin socket
3. Input
None: Without reset input
R:
With reset input
4. Dimensions
L:
Long-body model
6. Time Range
S:
0.05 to 12 s
M:
0.05 to 12 min
5. Supply Voltage
100-120AC: 100 to 120 VAC
200-240AC: 200 to 240 VAC
24AC/DC: 24VAC/DC
48DC:
48 VDC
100-125DC: 100 to 125 VDC
■ List of Models
Input Output Supply voltage
S-series
11-pin models
Without DPDT
reset
input
With
reset
input
M-series
8-pin models
---
8-pin models
100 to 120 VAC ---
H3CR-H8L 100-120AC S
200 to 240 VAC
H3CR-H8L 200-240AC S
24 VAC/DC
H3CR-H8L 24AC/DC S
H3CR-H8L 24AC/DC M
48 VDC
H3CR-H8L 48DC S
H3CR-H8L 48DC M
100 to 125 VDC
H3CR-H8L 100-125DC S
100 to 120 VAC H3CR-HRL 100-120AC S ---
H3CR-H8L 100-120AC M
H3CR-H8L 200-240AC M
H3CR-H8L 100-125DC M
H3CR-HRL 100-120AC M ---
200 to 240 VAC H3CR-HRL 200-240AC S
H3CR-HRL 200-240AC M
24 VAC/DC
H3CR-HRL 24AC/DC S
H3CR-HRL 24AC/DC M
48 VDC
H3CR-HRL 48DC S
H3CR-HRL 48DC M
100 to 125 VDC H3CR-HRL 100-125DC S
SPDT
11-pin models
H3CR-HRL 100-125DC M
100 to 120 VAC ---
H3CR-H8RL 100-120AC S ---
H3CR-H8RL 100-120AC M
200 to 240 VAC
H3CR-H8RL 200-240AC S
H3CR-H8RL 200-240AC M
24 VAC/DC
H3CR-H8RL 24AC/DC S
H3CR-H8RL 24AC/DC M
48 VDC
H3CR-H8RL 48DC S
H3CR-H8RL 48DC M
100 to 125 VDC
H3CR-H8RL 100-125DC S
H3CR-H8RL 100-125DC M
Note: Specify the model number, supply voltage, and time range (S or M) when ordering.
Example: H3CR-H8L 100-120AC S
Time range
Supply voltage
42
H3CR-H
■ Accessories (Order Separately)
Adapter, Protective Cover and Hold-down Clip
Name/specifications
Flush Mounting Adapters
Protective Cover
Hold-down Clips
For PF085A Socket
For PL08 or PL11 Sockets
Models
Y92F-30
Y92F-70 *1
Y92F-71 *1
Y92A-48B *2
Y92H-2
Y92H-1
Note: Refer to Operation
(Common) datasheet for
details.
*1.The Y92A-48B Protective
Cover and the Y92F-70/-71
Flush Mounting Adapter cannot
be used at the same time.
*2.The Y92F-48B Protective
Cover is made from hard
plastic.
Remove the Protective Cover
to change the set value.
Sockets
Timer
Pin
Round Sockets
Terminal
DIN track mounting
DIN track mounting
(Finger-safe type)
Screw terminal
Solder terminal
Wrapping terminal
PCB terminal
DIN track mounting
DIN track mounting
(Finger-safe type)
DIN track mounting
Screw terminal
Solder terminal
Wrapping terminal
PCB terminal
Connection
Front Connecting
11-pin
Back Connecting
8-pin
Front Connecting
Back Connecting
Models
P2CF-11
P2CF-11-E
P3GA-11
PL11
PL11-Q
PLE11-0
P2CF-08
P2CF-08-E
PF085A
P3G-08
PL08
PL08-Q
PLE08-0
Note: 1. The P2CF-@@-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals.
2. The P3GA-11 and P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection.
3. For details, refer to your OMRON website.
Terminal Cover
Application
For back connecting socket
Model
Remarks
For P3G-08 and P3GA-11
Y92A-48G
Note: For details, refer to your OMRON website.
Specifications
■ General
Item
Operating/Reset method
Pin type
Input type
Output type
Mounting method
Approved standards
H3CR-H8L
H3CR-H8RL
H3CR-HRL
Instantaneous operation/Time-limit reset Instantaneous operation/Time-limit reset/Forced reset
8-pin
11-pin
--No-voltage input
Relay output (DPDT)
Relay output (SPDT)
Relay output (DPDT)
DIN track mounting, surface mounting, and flush mounting
UL508, CSA C22.2 No.14, NK, Lloyds, CCC
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1.
Note: For details, refer to your OMRON website.
■ Time Ranges
Time unit
Scale number (max.)
0.6
Set time range
1.2
6
12
Min. power ON time
Time-up operation repeat period
Forced-reset repeat period
S-series
s (sec)
0.05 to 0.6
0.12 to 1.2
0.6 to 6
1.2 to 12
0.1 s min.
3 s min.
3 s min.
M-series
min (min)
2 s min.
Note: 1. If the above minimum power ON time is not secured, the H3CR may not operate. Be sure to secure the above minimum power ON time.
2. Do not use the Timer with a repeat period of less than 3 s. Doing so may result in abnormal heating or burning. Refer to Safety Precautions
(H3CR-H) on page 50 for details.
43
H3CR-H
■ Ratings
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz), 24 VAC/VDC (50/60 Hz), 48 VDC,
100 to 125 VDC
Operating voltage range
85% to 110% of rated supply voltage
No-voltage input (See note 3.)
ON-impedance:
1 kΩ max.
ON residual voltage: 1 V max.
OFF impedance:
500 kΩ min.
Power consumption
100 to 120 VAC: approx. 0.23 VA (0.22 W) at 120 VAC
200 to 240 VAC: approx. 0.35 VA (0.3 W) at 240 VAC
24 VAC/DC:
approx. 0.17 VA (0.15 W) at 24 VAC
approx. 1.0 W at 24 VDC
48 VDC:
approx. 0.18 W at 48 VDC
100 to 125 VDC: approx. 0.5 W at 125 VDC
Control outputs
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
The minimum applicable load is 10mA at 5VDC (P reference value).
Contact materials : Ag-alloy
Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
2. Do not use an inverter output as the power supply. Refer to your OMRON website for details.
3. For contact input, use contacts which can adequately switch 1 mA at 5 V.
■ Characteristics
Accuracy of operating
time
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 0.6 and 1.2 s)
Setting error
±5% FS ±50 ms max.
Operation start voltage
30% max. of rated voltage
Influence of voltage
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 0.6 and 1.2 s)
Influence of temperature ±1% FS max. (±1% FS ±10 ms max. in ranges of 0.6 and 1.2 s)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand
voltage
5 kV (between power terminals) for 100 to 120 VAC, 200 to 240 VAC, 100 to 125 VDC;
1 kV for 24 VAC/DC, 48 VDC
5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 120 VAC, 200 to
240 VAC, 100 to 125 VDC;
1.5 kV for 24 VAC/DC, 48 VDC
Noise immunity
±1.5 kV (between power terminals) and ±600 V (between input terminals), square-wave noise by noise simulator
(pulse width: 100 ns/1 μs, 1-ns rise); ±1 kV (between power terminals) for 48 VDC
Static immunity
Malfunction: 8 kV, Destruction:15 kV
Vibration resistance
Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Shock resistance
Destruction: 980 m/s2 three times each in six directions
Malfunction: 98 m/s2 three times each in six directions
Ambient temperature
Operating:
Storage:
−10°C to 55°C (with no icing),
−25°C to 65°C (with no icing)
Ambient humidity
Operating:
35% to 85%
Life expectancy
Mechanical: 10 million operations min. (under no load at 1,200 operations/h)
Electrical:
100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h) (See note)
EMC
(EMI)
Emission Enclosure:
Emission AC Mains:
(EMS)
Immunity ESD:
Immunity RF-interferenc:
Immunity Burst:
Immunity Surge:
Immunity Conducted Disturbance:
Immunity Voltage Dip/Interruption:
Case color
Light Gray (Munsell 5Y7/1)
Degree of protection
IP40 (panel surface)
Weight
Approx. 120 g
EN61812-1
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61812-1
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
IEC61000-4-6
IEC61000-4-11
Note: Refer to the Life-test Curve(Reference).
44
H3CR-H
■ Life-test Curve(Reference)
Switching operations (× 103)
10,000
5,000
1,000
500
30 VDC L/R = 7 ms
250 VAC/30 VDC
(cosφ = 1)
100
250 VAC (cosφ = 0.4)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1) and
a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC for H3CR-H8L/-HRL and 100 mA at 5
VDC for H3CR-H8RL (failure level: P).
Load current (A)
Connections
■ Block Diagrams
Without Reset Input (H3CR-H8L)
Time range/
unit selector
Power supply
circuit
Oscillation
circuit
Counting
circuit
Power failure
detection circuit
Output
circuit
Indicator
circuit
LCD
AC (DC) input
Output
indicator
With Reset Input (H3CR-H8RL/-HRL)
Time range/
unit selector
Power supply
circuit
Oscillation
circuit
Counting
circuit
Indicator
circuit
Power failure
detection circuit
Reset input
Output
circuit
LCD
AC (DC) input
Output
indicator
Input circuit
■ I/O Functions
45
Inputs
Reset
Turns off the control output and resets the elapsed time.
Outputs
Control output
Operates instantaneously when the power is turned on and time-limit resets when the set time is up
after the power is turned off.
H3CR-H
■ Terminal Arrangement
Note: DC models, including 24 VAC/DC models, have polarity.
8-pin Models
Without Reset Input (H3CR-H8L)
With Reset Input (H3CR-H8RL)
Reset
input
Power supply
Power supply
Note: Leave terminal 3 open. Do not use
them as relay terminals.
11-pin Model
With Reset Input (H3CR-HRL)
Reset input
Power supply
Note: Leave terminal 6 open. Do not use
them as relay terminals.
46
H3CR-H
Operation
■ Timing Chart
t:
Set time
Rt: Minimum power ON time (S-series: 0.1 s min.; M-series: 2 s min.)
If the power ON time is less than this value, the Timer may not operate (i.e., output may not turn ON).
Model
Timing chart
Rt
H3CR-H8L
Power
(See note)
ON
Rt
t
t
OFF
Output (1 − 3)
Output (1 − 4)
Output (8 − 6)
Output (8 − 5)
Output
indicator
Lit
Not lit
H3CR-H8RL
Rt
ON
Power
(See note)
OFF
t
Rt
t
0.05 s min.
0.05 s min.
ON (Short-circuited)
Reset input
OFF (Open)
Output (8 − 6)
Output (8 − 5)
Lit
Not lit
Output
indicator
H3CR-HRL
Power
(See note)
ON
Rt
OFF
0.05 s
min.
Reset input
Output (1 − 3)
Output (1 − 4)
Output (11 − 9)
Output (11 − 8)
Output
indicator
Lit
Not lit
Note: If the power is turned ON until the set time is up, the timer will be retriggered.
47
Rt
t
t
0.05 s min.
H3CR-H
Nomenclature
Scale range display windows
changes as below by turning
the Time range selector clockwise.
Output indicator (red)
Scale range display windows
0
0.1
0.2
0.3
0.4
0.5
0
0.2
0.4
0.6
0.8
1.0
0.6
1.2
0
1
2
3
4
5
6
0
2
4
6
8
10
12
Time setting knob (for setting
power OFF-delay time)
Time range selector (select
one from 0.6, 1.2, 6, and 12 at
full scale)
Time unit display
S-series: sec
M-series: min
Dimensions
Note: All units are in millimeters unless otherwise indicated.
H3CR-H8L
H3CR-H8RL
15
(78)
6
63.7
0.7
48
48
44.8 × 44.8
39 dia.
11 pins
79.4
15
H3CR-HRL
(78)
6
63.7
0.7
48
48
Dimensions with Front Connecting Socket
P2CF-08-@/P2CF-11-@
44.8 × 44.8
92.9
86.4
15
92.9
91.4
H3CR-HRL
99
112.2*
109.9
H3CR-H8@L
+
Adapter
Y92F-30
P2CF-08
P2CF-08-E
8 pins
Dimensions with Back Connecting Socket
P3G-08/P3GA-11
15
H3CR-H8@L
13.6
39 dia.
79.4
101.3*
13.6
2.3*
P2CF-11
P2CF-11-E
2.3*
P3G-08
(When
Y92A-48G
mounted)
H3CR-HRL
+
Adapter
Y92F-30
P3GA-11
(When
Y92A-48G
mounted)
Note: There are no restrictions to the mounting direction.
* These dimensions vary with the kind of DIN track (reference value).
48
H3CR-H
■ Accessories (Order Separately)
Protective Cover
Y92A-48B
Hold-down Clip
Y92H-2
To use the Protective Cover with a flush mounting, use the Y92F-30
flush mounting adaptor.
The Y92H-2 Hold-down Clip is attached to the PF085A socket.
This Protective Cover cannot be used together with the Y92F-70/-71
flush mounting adaptor or the panel cover.
Y92H-1
Y92H-1 Hold-down Clip is attached with screws together with the
PL08.
49
H3CR-H
Safety Precautions (H3CR-H)
Note: The undermentioned is common for all H3CR-H models.
■ Power Supplies
■ Wiring
The H3CR-H has a large inrush current; provide sufficient power
supply capacity. If the power supply capacity is too small, there may
be delays in turning ON the output.
With the H3CR-H@RL, for the power supply of an input device, use an
isolating transformer, of which the primary and secondary windings are
mutually isolated and the secondary winding is not grounded.
The H3CR-H has a high impedance circuit. Therefore, the H3CR-H
may not be reset if the H3CR-H is influenced by inductive voltage. In
order to eliminate any influence of inductive voltage, the wires
connected to the H3CR-H must be as short as possible and should
not be installed alongside power lines. If the H3CR-H is influenced by
inductive voltage that is 30% or more of the rated voltage, connect a
CR filter with a capacitance of approximately 0.1 F and a resistance
of approximately 120  or a bleeder resistor between the power
supply terminals. If there is any residual voltage due to current
leakage, connect a bleeder resistor between the power supply
terminals.
Correct
H3CR-H@RL
(4) <7>
5, 6, 7
(7) <10>
10
Input
terminal
(1) <5>
2
(2) <2>
2
Power supply
■ Operation
( ): H3CR-H8RL
< >: H3CR-HRL
An interval of 3 s minimum is required to turn on the H3CR-H after
the H3CR-H is turned off. If the H3CR-H is turned on and off
repeatedly with an interval of shorter than 3 s, abnormal heating or
burning may occur in internal elements.
3 s min.
Isolation transformer is required.
Input device
Incorrect
(4) <7>
5, 6, 7
H3CR-H@RL
(1) <5>
2
Input
terminal
(7) <10>
10
(2) <2>
2
Output
state 1
Power supply
Output
state 2
( ): H3CR-H8RL
< >: H3CR-HRL
Input device
Isolation
transformer
An appropriate input is applied to the input signal terminal of the Timer
when the input terminal for the input signal is short-circuited. Do not
attempt to connect any input terminal to any terminal other than the input
terminal or to apply voltage across other than the specified input
terminals or the internal circuits of the Timer may be damaged.
The H3CR-H@RL uses transformerless power supply. When
connecting a relay or transistor as an external signal input device,
pay attention to the following points to prevent short-circuiting due to
a sneak current to the transformerless power supply.
If input is made simultaneously from one input contact or a transistor
to the H3CR-H and a Timer whose common input terminals are used
as power terminals, such as the H3CR-A, a short-circuit current will
be generated. Either input through isolated contacts, or isolate the
power supply for one of the Timers.
H3CR-H@RL
10, 7*
1*, 5
2, 2*
After the forced reset function of the H3CR-H is activated, an interval
of 3 s minimum is required to activate the forced reset function again.
If the forced reset function is activated repeatedly with an interval of
shorter than 3 s, the internal parts of the H3CR-H may deteriorate
and the H3CR-H may malfunction.
Power
■ Input/Output (H3CR-H@RL)
4*, 7
Power
3 s min.
3 s min.
Reset
input
Output
If it is required that the output be turned on repeatedly with an
interval of shorter than 3 s, consider use of the H3CR-A in mode D
(signal OFF-delay).
On the H3CR-F@, do not set both the ON set dial and OFF set dial to
the lowest settings. Doing so may damage the contacts.
■ Others
If the H3CR-H is dropped or experiences some other kind of shock,
because a latching relay is used for output, contacts may be reversed
or go into a neutral state. If the H3CR-H is dropped, reconfirm correct
operation.
Short-circuit current
G. S. R.
5 6 7
10
H3CR-A
2
*: H3CR-H8RL
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
50
MEMO
51
Operation (Common)
Note: The undermentioned is common for all H3CR models.
■ Basic Setting
• H3CR-F Twin Timers
The display window at the bottom right inside the Time setting knob
shows 1.2, 3, 12, or 30 to indicate the scale number selected with the
selector switch on the front at bottom left.
Setting of Selectors
The selectors can be turned clockwise and counterclockwise to
select the desired time unit, time range, or operating mode.
Each selector has a snap mechanism that secures the selector at a
given position. Set the selector at a position at which it is secured. Do
not set it midway between two securing positions or a malfunction
could result from improper setting.
Selection of Operating Mode
Time range
selector
• H3CR-A Multifunctional Timer
The operation mode A to E, G, and J of the H3CR-A can be selected.
Use a Phillips head or flathead screwdriver to turn the selector
switch. The operation mode can be set to one of eight modes. The
window on the top shows E, G, J, A, B, B2, C, or D to indicate the
selected mode. On the H3CR-A8, the window on the top shows E, J,
B, A, or B2.
Operating mode
selector
Use a Phillips head or flathead screwdriver to turn the selector switch.
For ON-time, the desired time unit (sec, 10 s, min, 10 min, hrs, and 10 h)
is indicated in the ON-time unit display window at the lower right corner
of the front panel and can be changed by turning the ON-time unit
selector located below the ON-time unit display window.
Operating mode
display window
Groove for
screwdriver
Usable screwdrivers
Phillips head: No. 0-1
Flat head: Width 2.3 to 3.0 mm
(i.e., H3CR-A)
Scale range display
windows
Time range selector
Selection of Time Unit and Time Range
OFF-time setting knob
(with green pointer)
For OFF-time setting
OFF-time unit
display window
OFF-time unit
selector
ON-time unit
display window
ON-time unit
selector
• H3CR-A Multifunctional Timer
The desired time unit (sec, ✕10 s, min, ✕10 m, hrs, or ✕10 h) is
displayed in the window below the time setting knob by turning the
time unit selector located at the lower right corner of the front panel.
A time range (1.2, 3, 12, or 30 for H3CR-A@/2.4, 6, 24, or 60 for
H3CR-A@-301) is selected with the time range selector at the lower
left corner of the front panel, and the selected time range appears (in
the window at the lower right part) within the plastic frame of the time
setting knob.
Time setting
knob
Time range
selector
For OFF-time, the desired time unit (sec, 10 s, min, 10 min, hrs and
10 h) is indicated in the OFF-time unit display window at the upper
right corner of the front panel and can be changed by turning the
OFF-time unit selector located below the OFF-time unit display
window.
OFF-time unit
selector
Scale range
display window
Time unit selector
Time unit display window
52
H3CR
• H3CR-G Star-delta Timers
• H3CR-H Power OFF-delay Timers
The display window at the bottom right inside the Time setting knob
shows 6, 12, 60, or 120 to indicate the scale number Star operation
time selected with the selector switch on the front at bottom left.
Use a Phillips head screwdriver or flathead screwdriver to turn the
selector switch. The display window at the bottom right inside the
Time setting knob shows 0.6, 1.2, 6, or 12 to indicate the scale
number selected with the selector switch on the front at bottom left.
Scale range
display window
Time setting
knob
Star operation time
range selector
Time range
selector
Usable screwdrivers
Phillips head: No. 0-1
Flat head: Width 2.3 to 3.0 mm
Use a Phillips head screwdriver or flathead screwdriver to turn the
selector switch. The display window at the bottom center of the Time
setting knob shows 0.05, 0.1, 0.25, 0.5, 0.75, or 1.0 to show the star
-delta transfer time selected with the selector switch on the front at
bottom right.
Scale range
display window
Setting of Time
Use the time setting knob to set the desired time.
Time setting
knob
Star-delta
switching time
selector switch
Star operation
time range
selector
Star-delta
switching time
display window
Usable screwdrivers
Phillips head: No. 0-1
Flat head: Width 2.3 to 3.0 mm
■ Using the Time Setting Ring for H3CR-A/-G
Locking the Set Time
Limiting the Setting Range
Mount the Panel Cover on the Timer, set the desired time with the
time setting knob, and place Time Setting Ring A onto the time
setting knob so that the time setting notch of Time Setting Ring A is
in the center of the reset lock position of the Panel Cover.
Example: To set a range of 10 and 20 s.
Mount the Panel Cover on the Timer, set the time setting knob to 10 s
(the lower limit of the setting range), and place Time Setting Ring C
onto the time setting knob so that the stopper of Time Setting Ring C
is on the right edge of the reset lock position of the Panel cover. Next,
set the time setting knob to 20 s (the upper limit of the setting range),
place Time Setting Ring B onto the time setting knob so that the
stopper of Time Setting Ring B is on the left edge of the reset lock
position of the Panel Cover.
Time setting
notch
Reset lock position
Stopper
Reset lock position
Time Setting Ring A Panel cover
Time setting notch
Setting position
Time Setting
Ring B
Example: To set the time to 10 s.
53
Time Setting
Ring C
Panel cover
Range
H3CR
Accessories (Order Separately) (Common)
Note: The undermentioned is common for all H3CR models.
Note: All units are in millimeters unless otherwise indicated.
Flush Mounting Adaptor
Panel
P3G
Back Connecting Socket
Y92F-30
58
52
42
48
Panel Cutout
(Conforms ro DIN 43700)
Note1: The adapters for two or more timers mounted in a vertical line are different in
orientation from those mounted in a horizontal line.
0.5 R max.
N can be obtained as follows (n: the number of H3CR models arranged side by side)
Without a Cover: N = (48n - 2.5)+1/-0
With the Protective Cover: N = (51n - 5.5)+1/-0
With the Panel Cover: N = (50n - 4.5)+1/-0
45+0.6
−0
(N)
45+0.6
−0
Note2: The applicable thickness of the mounting panel must be 1 to 5 mm.
Y92F-70/-73
Panel Cutout
Panel
P3G
Back Connecting Socket
Adapter mounting hole Two, 4.5 dia.
R0.5 max.
52 to 53
88 45±0.15
65 to 66
76±0.2
Unit insertion
direction*
45±0.15
52.3 (63.7)
58
(See note.)
Note: The value shown in
parentheses is for
the Y92F-70.
Y92F-71/-74
Panel
56
58
Note: The applicable thickness of the
mounting panel must be 1 to 3.2 mm.
* Insert timer unit from back side
of adapter.
P3G
Back Connecting Socket
Unit insertion
direction*
43±0.2
50 +0.2
-0
45+0.5
−0
55+0.5
−0
68
45±0.2
R0.5 max.
52.3 (63.7)
(See note.)
Note: The value shown in
parentheses is for
the Y92F-71.
Note: The applicable thickness of the
mounting panel must be 1 to 3.2 mm.
* Insert timer unit from back side
of adapter.
54
H3CR
Track Mounting/Front Connecting Socket
P2CF-08
Eight,
M3.5 × 7.5 sems
7.8
3
4.5
70 max.
35.4
Two, 4.5 dia.
holes
Terminal Arrangement/
Internal Connections
(Top View)
Surface Mounting Holes
4
50 max.
Two, 4.5 dia. or two, M4
20.3 max.
P2CF-08-E (Finger Safe Terminal Type)
Conforming to VDE0106/P100
Eight,
M3.5 × 7.5 sems
40±0.2
5
7.8
4.5
3
1.3
70 max.
35.4
Two, 4.5 dia.
holes
4
40±0.2
19
20.3
50 max.
21.5 max.
Track Mounting/Front Connecting Socket
P2CF-11
Eleven,
M3.5 × 7.5 sems
7.8
3
4.5
70 max.
35.4
50 max.
31.2 max.
40±0.2
P2CF-11-E (Finger Safe Terminal Type)
Conforming to VDE0106/P100
Eleven,
M3.5 × 7.5 sems
7.8
5
4.5
3
1.2
70 max.
35.4
Two, 4.5 dia.
holes
55
Surface Mounting Holes
Two, 4.5 dia. or two, M4
4
4
Terminal Arrangement/
Internal Connections
(Top View)
40±0.2
50 max.
30
31.2 max.
H3CR
Back Connecting Socket
Terminal Arrangement/
Internal Connections
(Bottom View)
27 dia.
P3G-08
45
45
P3GA-11
4.9
17
Terminal Arrangement/
Internal Connections
(Bottom View)
27 dia.
45
25.6
45
4.5
6.2
16.3
Finger Safe Terminal Cover
Conforming to VDE0106/P100
Y92A-48G
(Attachment for P3G-08/P3GA-11
Socket)
Twelve, 6.4 dia. holes
34
48 × 48
47.7 × 47.7
16.5
24.6 27.6
47.4
Mounting Track
PFP-100N2
PFP-100N, PFP-50N
16
7.3±0.15
4.5
4.5
15
25
10
25
25
1,000 (500)
(See note)
10
25
35±0.3 27
27±0.15
35±0.3
15
1
15 (5)
(See note)
25
10
25
25
1,000
10
25 15
24
29.2
1
1.5
Note: The values shown in parentheses are for
the PFP-50N.
End Plate
Spacer
10
6.2
PFP-M
1
50
1.8
11.5
10 M4 x 8
pan head
screw
1.3
4.8
1.8
PFP-S
35.5 35.3
16
12
5
34.8
44.3
16.5
56
H3CR
Time Setting Ring/Panel Cover for H3CR-A/-G
There are two types of Panel Covers (Y92P-48GL, and Y92P-48GB),
all of which are available in two colors. Use the most suitable type of
Panel Cover with the design of the scaling plate according to the
application.
To lock the set time, you can lock the setting dial by using a Y92S-27
Setting Ring and a Y92P-48GL/-48GB Panel Cover. This will help to
prevent the set time from being changed accidentally.
To restrict the set time range, you can restrict the rotating range of
the setting dial by using a Y92S-28 Setting Ring and a 92P-48GL/48GB Panel Cover. Use them to restrict the upper and lower limits of
the setting range.
Refer to Using the Time Setting Ring for H3CR-A/-G on page 53 for
the procedure to attach the Setting Ring.
The Flush Mounting Adapter Y92F-70/Y92F-71 for H3CR-G, Y92F73/Y92F-74 for H3CR-A or the Protective Cover cannot be used.
Note: The Time Setting Ring/Panel Cover cannot be used for H3CRF model or H3CR-H model.
The Time Setting Ring and Panel Cover should be used as a pair.
Locking the Set
Time
Time Setting Ring A (Y92S-27) and Panel
Cover (Y92P-48GL, or -48GB)
Limiting the setting Time Setting Ring B or C (Y92S-28), and
range
Panel Cover (Y92P-48GL, or -48GB)
Y92S-27
Time Setting A
57
Y92S-28
Time Setting B
Y92S-28
Time Setting C
Y92P-48GL
Light Gray
Y92P-48GB
Black
H3CR
Safety Precautions for All H3CR Models
Note: The undermentioned is common for all H3CR models.
Warning Indications
CAUTION
Indicates a potentially hazardous situation
which, if not avoided, may result in minor
or moderate injury or in property damage.
Precautions for
Safe Use
Supplementary comments on what to do
or avoid doing, to use the product safely.
Precautions for
Correct Use
Supplementary comments on what to do
or avoid doing, to prevent failure to
operate, malfunction or undesirable effect
on product performance.
In rare circumstances there is a risk of slight electrical
shock, fire, or device damage. Do not disassemble,
modify, repair, or otherwise touch the inside.
In rare circumstances there is a risk of fire if the
screws become loose. Tighten the terminal screws to
the specified torque (1.08N·m).
Meaning of Product Safety Symbols
Used to warn of the risk of electric shock under
specific conditions.
Used for general prohibitions for which there is no
specific symbol.
Use to indicate prohibitions when there is a risk of
minor injury from electrical shock or other source if
the product is disassembled.
Precautions for Safe Use
Do not use the Timer in the following locations.
•
•
•
•
•
Locations with radical temperature changes.
Locations with high humidity that may result in condensation.
Locations with excessive vibration or shock.
Locations with corrosive gas or dust.
Locations where the Timer is exposed to sprayed water, oil, or
chemicals.
Pay the utmost attention not to make mistakes in polarity when wiring
the Timer.
Do not connect anything to terminals that are not used.
Risk of internal element damage if a voltage that exceeds the rating
is applied.
Using a surge absorber is recommended if surge voltages occur.
Used for general mandatory action precautions for
which there is no specified symbol.
CAUTION
Risk of fire and explosion due to arcing and relay heat
generation that accompanies switching. Do not use in an
environment where flammable or explosive gas is present.
The H3CR series uses a transformer-less power
supply. Exercise full caution as there is a risk of
electrical shock if input terminal is touched when
power voltage is applied.
The H3CR Series uses a transformerless power supply. Do not touch
the input terminals while the supply voltage is applied, otherwise an
electric shock may be received.
Verify that the power and output LEDs (LCD) are operating normally.
In some usage environments, the LEDs/LCD/ resin components may
deteriorate faster than normal, resulting in display failure. Inspect and
replace regularly.
When disposing of this product, follow the procedures for disposal of
industrial waste that apply in your region.
Verify that the product is the desired product before use.
Exercise caution as the outer casing of the timer may be immersed in
organic solvents (thinner, benzene, etc.), strong alkali, or strong
acids.
Precautions for Correct Use
The service life of the output relay varies widely
depending on switching capacity and switching
conditions. Use only within the rated load and
electrical life count, based on actual conditions of use.
Risk of contact sticking and burning if used past the
service life. Always use a load current that does not
exceed the rating, and if a heater is used, use a thermal switch in the
load circuit.
Do not remove the outer casing.
Changing the Setting
Do not change the time unit, time range, or operation mode while the
Timer is in operation, otherwise the Timer may malfunction.
The time unit and time range can be set with the respective selectors
turned clockwise or counterclockwise.
The selectors are of notched so that they will snap when they are
properly set. Do not set the selectors midway between notches,
otherwise the Timer may break or malfunction.
Do not use H3CR-A models (except for H3CR-A@S) in flicker mode
at the lowest selector setting, or H3CR-F models at the lowest
selector setting. Doing so may result in damage to contacts.
58
H3CR
Power Supplies
Others
A DC power supply can be connected if its ripple factor is 20% or
less and the mean voltage is within the rated operating voltage range
of the Timer.
If the Timer is mounted to a control board, dismount the Timer from
the control board or short-circuit the control board circuitry before
carrying out a voltage withstand test between the electric circuitry
and non-charged metal part of the Timer. This protects the internal
circuitry of the Timer from damage.
An AC power supply can be connected to the power input terminals
without regard to polarity. A DC power supply must be connected to
the power input terminals as designated according to the polarity of
the terminals.
Make sure that the voltage is applied within the specified range,
otherwise the internal elements of the Timer may be damaged.
Connect the power supply voltage through a relay or switch in such a
way that the voltage reaches a fixed value at once, otherwise the
Timer may not be reset or a timer error may result.
Be aware that the operating voltage will rise by 5% if the rated
voltage is applied to the Timer continuously while the ambient
temperature is close to the maximum permissible ambient
temperature.
The power supply circuit of any H3CR-A model (except for H3CRA@S), H3CR-F 100-to-240-VAC model, and H3CR-G model is a
switching circuit. If the power line connected to the power supply
circuit has a transformer with high inductance, a counterelectromotive voltage will be induced by the inductance. To suppress
the voltage, apply a CR filter to the power supply line.
Apply the power voltage at once through the switch and relay
contacts. If not applied at once, power reset may not take place or
time-up may occur.
When the power is turned on, a rush current (refer to your OMRON
website) may flow briefly and the timer may not start if there is
insufficient power capacity. Use a power supply with sufficient
capacity.
If the timer is left for an extended time at high temperature in the
time-up state (internal relay ON), the internal components
(electrolytic capacitors, etc.) may deteriorate faster than normal. For
this reason, use in combination with a relay, and avoid leaving in the
time-up state for an extended time (for example, one month or
longer).
Reference example
Use as shown below.
X2/b
T
T/a
X1
X1/a
X1/a
X2
X
MY relay, etc.
Cleaning
Do not use solvents such as thinner. Use commercially available
alcohol.
Mounting Direction
There are no restrictions to the mounting direction.
Precautions for EN61812-1
Conformance
The H3CR Series as a built-in timer conforms to EN61812-1
provided that the following conditions are satisfied.
Make sure that no voltage is applied to any terminals before
dismounting the Timer from the Socket.
The output section of the H3CR is provided only with basic isolation.
The H3CR itself is designed under the following conditions:
• Overvoltage category III
• Pollution degree 2
• Isolation
Operation parts: Reinforced isolation
With clearance of 5.5 mm and creepage distance of 5.5 mm at
230 VAC
Output: Basic isolation (See note)
With clearance of 3 mm and creepage distance of 3 mm at
230 VAC
Note: The 11-pin model ensures basic isolation by itself and also
ensures basic isolation with the 11-pin model mounted to the
OMRON P2CF-11-@ or P3GA-11 Socket.
Connect the two output contacts different in polarity to the loads so
that they will be the same in potential.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
59
: Auxiliary relay,
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
© OMRON Corporation 2013 All Rights Reserved.
OMRON (CHINA) CO., LTD.