Solid-state Timer H3CR Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Refer to Warranty and Application Considerations (page 52), and Safety Precautions (page 22, 44, 51). DIN 48 ✕ 48-mm Multifunctional Timer Series • Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low Voltage, and EMC Directives. • Approved by UL and CSA. • Lloyds/NK approvals. • Six-language instruction manual provided. ■ Broad Line-up of H3CR Series H3CR H3CR-A H3CR-F Multifunctional Timer Twin Timer H3CR-A H3CR-AS H3CR-AP H3CR-A8 H3CR-A8S H3CR-A8E H3CR-F H3CR-FN H3CR-F8 H3CR-F8N 11-pin model 8-pin model H3CR-G 11-pin model H3CR-H Star-delta Timer Power OFF-delay Timer H3CR-G8L 8-pin model H3CR-G8EL H3CR-HRL 11-pin model H3CR-H8L 8-pin model H3CR-H8RL 8-pin model 8-pin with instantaneous contact output model Note: H3CR-AS, H3CR-A8S: Transistor output models Contents Solid-state Timer H3CR-A .......................................................................................................................................... 2 H3CR-F........................................................................................................................................... 26 H3CR-G .......................................................................................................................................... 34 H3CR-H .......................................................................................................................................... 42 Common to ALL Timers Operation ........................................................................................................................................ 1 52 Accessories .................................................................................................................................... 54 Safety Precautions.......................................................................................................................... 58 Solid-state Multi-functional Timers H3CR-A Multiple Operating Modes and Multiple Time Ranges. DIN 48 x 48-mm Multifunctional Timer. • A wide AC/DC power supply range greatly reduces the number of timer models kept in stock. • A wide range of applications with multiple operating modes, eight modes for 11-pin models and five modes for 8-pin models. • Ecological design with reduced current consumption. • Easy sequence checking with instantaneous outputs for a zero set value. • Length of 75 mm or less when panel-mounted with a P3G-08 Socket (H3CR-A8E, 100 to 240 VAC, 100 to 125 VDC) • PNP input models available. • Standards: UL, CSA, NK, LR, CCC, EN 61812-1, and CE Marking. For the most recent information on models that have been certified for safety standards, refer to your OMRON website. Model Number Structure ■ Model Number Legend Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 3 for availability. H3CR-A@ @ @ - @ @ 1 2 3 4 5 1. Number of Pins None: 11-pin models 8: 8-pin models 2. Input Type for 11-pin Models None: No-voltage input (NPN type) P: Voltage input (PNP type) 3. Output None: Relay output (DPDT) S: Transistor output (NPN/PNP universal use) E: Relay output (SPDT) with instantaneous relay output (SPDT) 4. Suffix 301: Double time scale (range) models (0.1 s to 600 h) 5. Supply Voltage 100-240AC/100-125DC: 100 to 240 VAC/100 to 125 VDC 24-48AC/12-48DC: 24 to 48 VAC/12 to 48 VDC 24-48AC/DC: 24 to 48 VAC/VDC (Only for H3CR-A8E) 2 H3CR-A Ordering Information ■ List of Models Note: 1. Specify both the model number and supply voltage when ordering. Example: H3CR-A 100-240AC/100-125DC Supply voltage 2. The operating modes are as follows A: ON-delay D: Signal OFF-delay B: Flicker OFF start E: Interval B2: Flicker ON start G: Signal ON/OFF-delay C: Signal ON/OFF-delay J: One-shot 11-pin Models Output Supply voltage 100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC Contact Input type No-voltage input Time range 0.05 s to 300 h Operating mode (See note 2) Model (See note 1.) Eight multi-modes: A, B, H3CR-A B2, C, D, E, G, J 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC 100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC Voltage input Eight multi-modes: A, B, H3CR-AP B2, C, D, E, G, J 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC 100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC No-voltage input 0.1 s to 600 h H3CR-A-301 0.05 s to 300 h H3CR-AS 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC Transistor (Photocoupler) 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC 8-pin Models Output Contact Supply voltage 100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC Input type Time range No-input available 0.05 s to 300 h 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC 100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC Operating mode (See note 2) Model (See note 1.) Five multi-modes: A, B, H3CR-A8 B2, E, J (Power supply start) 0.1 s to 600 h H3CR-A8-301 0.05 s to 300 h H3CR-A8S 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC Transistor (Photocoupler) 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC Time-limit contact and 100 to 240 VAC (50/60 Hz)/ instantaneous contact 100 to 125 VDC 24 to 48 VAC/VDC (50/60 Hz) 3 H3CR-A8E H3CR-A ■ Accessories (Order Separately) Adapter, Protective Cover, Hold down Clip, Setting Ring and Panel Cover Name/specifications Models Y92F-30 Flush Mounting Adapter Y92F-73 *1 Y92F-74 *1 Y92A-48B *2 Protective Cover Hold-down Clip (Sold in sets of two) For PF085A Socket Y92H-8 For PL08 or PL11 Sockets Y92H-7 Setting Ring A Y92S-27 *3 Setting Ring B and C Y92S-28 *3 Panel Cover Light gray (5Y7/1) Y92P-48GL *4 Black (N1.5) Y92P-48GB *4 *1 The Y92A-48B Protective Cover and the Y92P-48G@ Panel Cover can not be used at the same time with the Y92F-73/-74 Flush Mounting Adapter. *2 The Y92A-48B Protective Cover is made from hard plastic. Remove the Protective Cover to change to set value. The Y92F-73/-74 Flush Mounting Adapter and the Y92P-48G@ Panel Cover cannot be used at the same time with Y92A-48B Protective Cover. *3 The Y92S-27/-28 Setting Ring cannot be used alone. It must be used together with the Y92P-48G@ Panel Cover. *4 The Y92A-48B Protective Cover and the Y92F-73/-74 Flush Mounting Adapter cannot be used at the same time with the Y92P-48G@ Panel Cover. Sockets Timer Round Sockets Pin Connection 11-pin Front Connecting Back Connecting 8-pin Front Connecting Back Connecting Terminal Models DIN track mounting P2CF-11 DIN track mounting (Finger-safe type) P2CF-11-E Screw terminal P3GA-11 Solder terminal PL11 Wrapping terminal PL11-Q PCB terminal PLE11-0 DIN track mounting P2CF-08 DIN track mounting (Finger-safe type) P2CF-08-E DIN track mounting PF085A Screw terminal P3G-08 Solder terminal PL08 Wrapping terminal PL08-Q PCB terminal PLE08-0 Note: 1. The P2CF-@@-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals. 2. The P3GA-11 and P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection. 3. For details, refer to your OMRON website. Terminal Cover Application For back connecting socket Model Y92A-48G Remarks For P3G-08 and P3GA-11 Note: For details, refer to your OMRON website. 4 H3CR-A Specifications ■ General Item Operating mode H3CR-A/-AS/-A-301 H3CR-AP A: ON-delay B: Flicker OFF start B2: Flicker ON start C: Signal ON/OFF-delay D: Signal OFF-delay E: Interval G: Signal ON/OFF-delay J: One-shot H3CR-A8/-A8S/-A8-301 H3CR-A8E A: ON-delay (power supply start) B: Flicker OFF start (power supply start) B2: Flicker ON start (power supply start) E: Interval (power supply start) J: One-shot (power supply start) Pin type 11-pin Input type No-voltage input 8-pin Time-limit output type H3CR-A/-A8/-AP/-A-301/-A8-301: Relay output (DPDT) H3CR-AS/-A8S: Transistor output (NPN/PNP universal)* Voltage input --Relay output (SPDT) Instantaneous output type --- Relay output (SPDT) Mounting method DIN track mounting, surface mounting, and flush mounting Approved standards UL508, CSA C22.2 No.14, NK, Lloyds, CCC Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2. Output category according to EN60947-5-1 for Timers with Contact Outputs. Output category according to EN60947-5-2 for Timers with Transistor Outputs. * The internal circuits are optically isolated from the output. This enables universal application as NPN or PNP transistor. For details, refer to your OMRON website. ■ Time Ranges Note: When the time setting knob is turned below “0” until the point where the time setting knob stops, the output will operate instantaneously at all time range settings. For details, refer to your OMRON website. Standard (0.05-s to 300-h) Models Time unit Full scale setting 1.2 s (sec) 0.05 to 1.2 10 s (10 sec) 1.2 to 12 min (min) 0.12 to 1.2 10 min (10 min) 1.2 to 12 h (hrs) 0.12 to 1.2 10 h (10 hrs) 1.2 to 12 3 0.3 to 3 3 to 30 0.3 to 3 3 to 30 0.3 to 3 3 to 30 12 1.2 to 12 12 to 120 1.2 to 12 12 to 120 1.2 to 12 12 to 120 30 3 to 30 30 to 300 3 to 30 30 to 300 3 to 30 30 to 300 Double (0.1-s to 600-h) Models Time unit Full scale setting 5 2.4 s (sec) 0.1 to 2.4 10 s (10 sec) 2.4 to 24 min (min) 0.24 to 2.4 10 min (10 min) 2.4 to 24 h (hrs) 0.24 to 2.4 10 h (10 hrs) 2.4 to 24 6 0.6 to 6 6 to 60 0.6 to 6 6 to 60 0.6 to 6 6 to 60 24 2.4 to 24 24 to 240 2.4 to 24 24 to 240 2.4 to 24 24 to 240 60 6 to 60 60 to 600 6 to 60 60 to 600 6 to 60 60 to 600 H3CR-A ■ Ratings Rated supply voltage (See notes 1, 2, and 5.) 100 to 240 VAC (50/60 Hz)/100 to 125 VDC, 24 to 48 VAC (50/60 Hz)/12 to 48 VDC (24 to 48 VAC/VDC for H3CR-A8E) (See note 3.) Operating voltage range 85% to 110% of rated supply voltage (90% to 110% at 12 VDC) Power reset Minimum power-opening time: 0.1 s Input (See note 6.) No-voltage Input ON impedance: 1 kΩ max. ON residual voltage: 1 V max. OFF impedance: 100 kΩ min. Voltage Input Max. permissible capacitance between inputs lines (terminals 6 and 7): 1,200 pF Load connectable in parallel with inputs (terminals 6 and 7). • 100 to 240 VAC/100 to 125 VDC High (logic) level: 85 to 264 VAC/85 to 137.5 VDC Low (logic) level: 0 to 10 VAC/0 to 10 VDC • 24 to 48 VAC/12 to 48 VDC High (logic) level: 20.4 to 52.8 VAC/10.8 to 52.8 VDC Low (logic) level: 0 to 2.4 VAC/0 to 1.2 VDC Power consumption H3CR-A/-A8 • 100 to 240 VAC/100 to 125 VDC (When at 240 VAC, 60 Hz) Relay ON: approx. 2.0 VA (1.6 W) • 24 to 48 VAC/12 to 48 VDC (When at 24 VDC) Relay ON: approx. 0.8 W H3CR-AP (See note 3) • 100 to 240 VAC/100 to 125 VDC (When at 240 VAC, 60 Hz) Relay ON: approx. 2.5 VA (2.2 W) (See note 4.) • 24 to 48 VAC/12 to 48 VDC (When at 24 VDC) Relay ON: approx. 0.9 W (See note 4.) H3CR-A8E • 100 to 240 VAC/100 to 125 VDC (When at 240 VAC, 60 Hz) Relay ON/OFF: approx. 2 VA (0.9 W) • 24 to 48 VAC/VDC (When at 24 VDC) Relay ON/OFF: approx. 0.9 W H3CR-AS/-A8S • 24 to 48 VAC/12 to 48 VDC (When at 24 VDC) Output ON: 0.3 W Output OFF: 0.2 W Control outputs Relay OFF: approx. 1.3 VA (1.1 W) Relay OFF: approx. 0.2 W Relay OFF: approx. 1.8 VA (1.7 W) (See note 4.) Relay OFF: approx. 0.3 W (See note 4.) • Models with Contact Outputs H3CR-A/-A8/-AP 5A at 250 VAC/30 VDC, 0.15A at 125 VDC, resistive load (cosφ = 1) Minimum applied load: 10mA at 5 VDC (failure level: P reference value) Contact materials: Ag-alloy H3CR-A8E 5A at 250 VAC/30 VDC, 0.15A at 125 VDC, resistive load (cosφ = 1) Minimum applied load: 10mA at 5 VDC (failure level: P reference value) Contact materials: AgSnIn • Transistor output: Open collector(NPN/PNP) H3CR-AS/-A8S 100 mA max at 30 VDC max., residual voltage: 2 VDC max. Note: 1. DC ripple rate: 20% max. (A single-phase, full-wave-rectification power supply can be used). 2. Do not use an inverter output as the power supply. Refer to your OMRON website for details. 3. Models with 24-to-48-VAC or 12-to-48-VDC power supply have inrush current. Caution is thus required when turning ON and OFF power to the Timer with a non-contact output from a device such as a sensor. (Models with an inrush current of approximately 50 mA and a 24VDC power supply are available (the H3CR-A-302 and H3CR-A8-302).) For details, consult your OMRON sales representative. 4. The values are for when the terminals 2 and 7 and terminals 10 and 6 are short-circuited, and include the consumption current of the input circuit. 5. Refer to your OMRON website when using the Timer together with a 2-wire AC proximity sensor. 6. For details, see Input Connections: No-voltage Input Signal Levels on page 11, and Input Connections: Voltage Input Signal Levels on page 12. 6 H3CR-A ■ Characteristics Accuracy of operating time Setting error Reset time ±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s or 3 s) ±5% FS ±50 ms (See note 1) Min. power-opening time: 0.1 s max. Min. pulse width: 0.05 s (H3CR-A/-AS) Reset voltage 10% max. of rated supply voltage Influence of voltage ±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s or 3 s) Influence of temperature ±1% FS max. (±1%±10 ms max. in a range of 1.2 s or 3 s) Insulation resistance 100 MΩ min. (at 500 VDC) Dielectric strength 2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between current-carrying metal parts and exposed noncurrent-carrying metal parts) 2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between control output terminals and operating circuit) 2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities) 1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other) 2,000 VAC, 50/60 Hz for 1 min (between input and control output terminals and operation circuit) for H3CR-AP Impulse withstand 5 kV (between power terminals) for 100 to 240 VAC/100 to 125 VDC, 1 kV for 24 to 48 VAC/12 to 48 VDC voltage 5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC/100 to 125 VDC, 1.5 kV for 24 to 48 VAC/12 to 48 VDC and 24 to 48 VAC/VDC Noise immunity ±1.5 kV (between power terminals) and ±600 V (between no-voltage input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) Static immunity Malfunction: 8 kV Destruction: 15 kV Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in 3 directions for 2 hours each Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in 3 directions for 10 minutes each Shock resistance Destruction: 1,000 m/s2 3 times each in 6 directions Malfunction: 100 m/s2 3 times each in 6 directions Ambient temperature Operating: −10°C to 55°C (with no icing) Storage: −25°C to 65°C (with no icing) Ambient humidity Operating: 35% to 85% Life expectancy Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note 2) EMC (EMI) EN61812-1 Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A (EMS) EN61812-1 Immunity ESD: IEC61000-4-2 Immunity RF-interference: IEC61000-4-3 Immunity Burst: IEC61000-4-4 Immunity Surge: IEC61000-4-5 Immunity Conducted Disturbance: IEC61000-4-6 Immunity Voltage Dip/Interruption: IEC61000-4-11 Case color Light gray (Munsell 5Y7/1) Degree of protection IP40 (panel surface) Weight Approx. 90 g Note: 1. The value is ±5% FS +100 ms to −0 ms max. when the C, D, or G mode signal of the H3CR-AP is OFF. 2. Refer to the Life-test Curve (Reference). 3. Contact output only. Switching operations (x 103) ■ Life-test Curve (Reference) 10,000 5,000 1,000 30 VDC L/R = 7 ms 500 250 VAC/30 VDC (cosφ = 1) 100 250 VAC (cosφ = 0.4) 0 1 2 3 4 Load current (A) 7 5 Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1) and a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P). H3CR-A Connections ■ Block Diagrams H3CR-A/-AS/-A-301 AC (DC) input Power supply circuit Zero setting detection circuit Time range/ unit selectors Operating mode selector Oscillation circuit Counting circuit Output circuit Input circuit Indicator circuit Reset input, start input, and gate input Power-ON Output-ON indicator indicator H3CR-AP AC (DC) input Power supply circuit Start Zero setting detection circuit Time range/ unit selectors Operating mode selector Oscillation circuit Counting circuit Output circuit Input circuit Indicator circuit Power-ON Output-ON indicator indicator 8 H3CR-A H3CR-A8/-A8S/A8-301 AC (DC) input Power supply circuit Zero setting detection circuit Time range/ unit selectors Operating mode selector Oscillation circuit Counting circuit Output circuit Indicator circuit Power-ON Output-ON indicator indicator H3CR-A8E AC (DC) input Power supply circuit Zero setting detection circuit Oscillation circuit Time range/ unit selectors Counting circuit Operating mode selector Output circuit Indicator circuit Power-ON Output-ON indicator indicator Instantaneous output circuit ■ I/O Functions Inputs (for -A/ Start -AS models) Reset Outputs Starts time-measurement. Interrupts time-measurement and resets time-measurement value. Timing operation is stopped and the control output turns OFF (it is reset). Gate The timing operation is interrupted while the gate input is active. Control output Outputs are turned ON according to designated output mode when preset value is reached. Note: H3CR-AP incorporates start input only. Models H3CR-A8/-A8E/-A8S/-A8-301 do not have an input function. 9 H3CR-A ■ Terminal Arrangement Note: 1. The delayed contact of conventional Timers was indicated as The contact symbol of the H3CR-A is indicated as because its operating mode is six multi-modes (four multi-modes for the H3CR-A8). 2. Do not use an empty terminal on the H3CR-AP/-AS/-A8S as a relay terminal or otherwise. 11-pin Models 8-pin Models H3CR-A8/-A8-301 (Contact Output) Gate input Start input Reset input H3CR-A/-A-301 (Contact Output) Power supply Power supply H3CR-A8S (Transistor Output) Gate input Start input Reset input H3CR-AS (Transistor Output) Power supply Note: Terminals 1, 3, 4, and 5 are empty. Terminals 2 and 7 are the same as for the H3CR-A8. Power supply H3CR-A8E (Contact Output) Note: Terminals 1, 3, 4, and 8 are empty. Terminals 2, 5, 6, 7, and 10 are the same as for the H3CR-A. Start input H3CR-AP (Contact Output) Power supply Power supply Note: 1. Terminal 5 is empty. 2. Separate power supplies can be used for the Timer and inputs. 10 H3CR-A ■ Input Connections H3CR-A/-AS/-A-301 The inputs of the H3CR-A/-AS/-A-301 are no-voltage (short-circuit or open) inputs. No-voltage Inputs No-contact Input (Connection to NPN open collector output sensor.) 12 to 24 VDC (sensor power supply) Sensor Contact Input 12 to 24 VDC (sensor power supply) + DC power − supply Timer Timer 5 Gate 6 Start 7 Reset 5 Gate 6 Start 7 Reset 2 Input (0 V) 2 Input (0 V) Operates with transistor ON Operates with relay ON No-voltage Input Signal Levels No-contact input 1. Short-circuit level Transistor ON Residual voltage: 1 V max. Impedance when ON: 1 kΩ max. 2. Open level Transistor OFF Impedance when OFF: 100 kΩ min. Contact input 11 No-contact Input (Connection to a voltage output sensor.) Use contacts which can adequately switch 0.1 mA at 5 V + DC power − supply Timer Sensor 5 Gate 6 Start 7 Reset 2 Input (0 V) Operates with transistor ON H3CR-A H3CR-AP The start input of the H3CR-AP is voltage input. (Voltage imposition or open) Voltage Inputs Sensor + DC power − supply Timer 10 Power supply (+) 6 Start 7 Input 0V 2 Power supply (−) Operates with PNP transistor ON 12 to 24 VDC (sensor power supply) Sensor Contact Input + DC power − supply Timer 10 Power supply (+) 6 Start 7 Input 0V DC power supply 12 to 24 VDC (sensor power supply) No-contact Input (Connection to NPN open collector output sensor) AC power supply No-contact Input (Connection to PNP open collector output sensor) 2 Power supply (−) Operates with NPN transistor ON Note: The input circuit is isolated from the power supply circuit. Thus, an NPN transistor can be connected. Timer Power 10 supply (+) 6 Start 7 Input 0V 2 Power supply (−) Operates with relay ON Note: Refer to the signal levels in the following table and be aware of the minimum applicable load of the relay. Note: Before making connections, refer to Safety Precautions (H3CR-@). Voltage Input Signal Levels No-contact input 1. Transistor ON Residual voltage: 1 V max. The voltage between terminals 6 and 7 must be 10.8 VDC min. 2. Transistor OFF Leakage current: 0.01 mA max. The voltage between terminals 6 and 7 must be 1.2 VDC max. Contact input Use contacts that can adequately switch 0.1 mA at each operating voltage. The voltage between terminals 6 and 7 with contacts ON or OFF must satisfy the specified value. Contacts ON 100-to-240-VAC and 100-to-125-VDC models: 85 to 264 VAC or 85 to 137.5 VDC 24-to-48-VAC and 12-to-48-VDC models: 20.4 to 52.8 VAC or 10.8 to 52.8 VDC Contacts OFF 100-to-240-VAC and 100-to-125-VDC models: 0 to 10 VAC or 0 to 10 VDC 24-to-48-VAC and 12-to-48-VDC models: 0 to 2.4 VAC or 0 to 1.2 VDC 12 H3CR-A Operation ■ Timing Chart (Refer to page 20 for application examples.) H3CR-A/-AS/-AP*/-A-301 Operating mode Timing chart A: ON-delay t Power Start Reset Output relay (NC) Output relay (NO) (Output indicator) Power indicator B: Flicker OFF start Power Start Reset Output relay (NC) Output relay (NO) (Output indicator) Power indicator B2: Flicker ON start t Basic operation Power Start (See note) t Output Note: Start input is invalid while the Timer is in operation. Basic operation Power Start (See note) t t t t Output Note: Start input is invalid while the Timer is in operation. Basic operation Power Start Reset Output relay (NC) Power Start (See note) t t t t Output Output relay (NO) (Output indicator) Power indicator C: Signal ON/ OFF-delay Basic operation Power Start Start (See note) Output relay (NC) Output Power indicator 13 Power Reset Output relay (NO) (Output indicator) Note: 1. 2. 3. 4. 5. 6. Note: Start input is invalid while the Timer is in operation. t t t t Note: Start input is valid and retriggerable while the Timer is in operation. Allow at least 0.1 s for the Timer reset time if the power supply is reset due to an interruption in the power supply. The minimum input pulse width (for start, reset) is 0.05 s. The letter "t" in the timing charts indicates the set time, and "t-a" means that the period is less than the set time. (t - a < 1) H3CR-AP model incorporates start input only. Model H3CR-AS only has operation equivalent to time-limit contact: NO. When the setting dial is turned all the way past 0 for instantaneous output, "t" (set time) in the above time chart is 0-sec operation. H3CR-A Operating mode Timing chart D: Signal OFFdelay Basic operation Power Start Power Reset Start (See note) Output relay (NC) t Output Output relay (NO) (Output indicator) Note: Start input is valid and retriggerable while the Timer is in operation. Power indicator E: Interval Basic operation Power Power Start Reset Start (See note) Output relay (NC) Output Output relay (NO) (Output indicator) Note: Start input is valid and retriggerable while the Timer is in operation. (Previous start input will be cancelled.) Power indicator G: Signal ON/ OFF-delay t Basic operation Power Power Start Start (See note) Reset Output relay (NC) t t t Output Output relay (NO) (Output indicator) Note: Start input is valid and retriggerable while the Timer is in operation. Power indicator J: One-shot output t Basic operation Power Start Power Reset Start (See note) Output relay (NC) 1±0.6 s (Fixed) Output relay (NO) (Output indicator) Power indicator 1±0.6 s (Fixed) Output t 1±0.6 s (Fixed) Note: Start input is valid and retriggerable while the Timer is in operation. (Previous start input will be cancelled.) Gate Signal Input (This timing chart indicates the gate input in operating mode A (ON-delay operation).) t1 Power ON OFF Start ON OFF Gate ON OFF Reset ON OFF Output ON relay OFF t2 Note: 1. Allow at least 0.1 s for the Timer reset time if the power supply is reset due to an interruption in the power supply. 2. The minimum input pulse width (for start, reset) is 0.05 s. 3. The letter "t" in the timing charts indicates the set time, and "t-a" means that the period is less than the set time. (t - a < 1) 4. In J Mode, there will be only one output even if the start input is longer than the set time. 5. H3CR-AP model incorporates start input only. 6. Model H3CR-AS only has operation equivalent to time-limit contact: NO. 7. When the setting dial is turned all the way past 0 for intantaneous output, "t" (set time) in the above time chart is 0-sec operation. Note: The set time is the sum of t1 and t2. Start and reset are also both enabled when the gate signal is ON. 14 H3CR-A H3CR-A8/-A8S/-A8-301 Operating mode A: ON-delay Timing chart Power Basic operation Output relay (NC) Power t Output relay (NO) (output indicator) Power indicator B: Flicker OFF start Output t t t−a Rt t t t t−a Power Basic operation Output relay (NC) Power Output relay (NO) (output indicator) Power indicator B 2: Flicker ON start t Power t Power t Output Power indicator 15 t Basic operation Output relay (NO) (output indicator) Note: 1. 2. 3. 4. 5. t v Output relay (NC) Power Output relay (NO) (output indicator) Power indicator t Output Power Output relay (NC) t Power Output relay (NO) (output indicator) Power indicator J: One-shot output t Basic operation Output relay (NC) E: Interval t Output Basic operation 1±0.6 s (Fixed) 1±0.6 s (Fixed) Power t Output 1±0.6 s (Fixed) Allow a timer reset time (Rt) of 0.1 s or longer. The letter "t" in the timing charts indicates the set time, and "t-a" means that the period is less than the set time. (t - a < 1) Model H3CR-A8S only has operation equivalent to time-limit contact: NO. When the setting dial is turned all the way past 0 for intantaneous output, "t" (set time) in the above time chart is 0-sec operation. You can use J Mode to use the power supply as the start input. H3CR-A H3CR-A8E Operating mode Timing chart A: ON-delay Power Output relay (NC) Basic operation Output relay (NO) (output indicator) Instantaneous output relay (NC) Power Instantaneous output relay (NO) Output t Power indicator B: Flicker OFF start t t t−a Rt t t t t−a Power Output relay (NC) Basic operation Output relay (NO) (output indicator) Instantaneous output relay (NC) Power Instantaneous output relay (NO) Output t t t t Power indicator B 2: Flicker ON start Power Output relay (NC) Basic operation Output relay (NO) (output indicator) Power Instantaneous output relay (NC) t t t t Output Instantaneous output relay (NO) Power indicator E: Interval Power Output relay (NC) Output relay (NO) (output indicator) Basic operation Instantaneous output relay (NC) Power Instantaneous output relay (NO) t Output Power indicator J: One-shot output Power Output relay (NC) Output relay (NO) (output indicator) Instantaneous output relay (NC) Instantaneous output relay (NO) (Fixed) (Fixed) Basic operation Power t Output 1±0.6 s (Fixed) Power indicator Note: Refer to page 14. 16 H3CR-A Nomenclature Power indicator (green) (Flashes when Timer operates; lit when Timer stops operating) Operating mode display window Operating mode selector Select a mode from: A, B, B2, C, D, E, G, and J (H3CR-A, -AP, and -AS) A, B, B2, E and J (H3CR-A8, -A8S, and -A8E) Output indicator (orange) (Lit when output) Scale range display windows Time unit display window Time range selector (select one from 1.2, 3, 12, and 30 at full scale; with the H3CR-A@-301, select from 2.4, 6, 24, or 60 at full scale.) Time setting knob (set time) Scale range display windows changes as below by turning the Time range selector clockwise.* 0 0.2 0.4 0.6 0.8 1.0 1.2 0 0.5 1 1.5 2 2.5 3 0 2 4 6 8 10 12 0 5 10 15 20 25 30 * On the H3CR-A@-301 type, the time is twice as long. 17 Time unit selector (select one from sec, 10s, min, 10m, hrs, and 10h) H3CR-A Dimensions Note: All units are in millimeters unless otherwise indicated. H3CR-A H3CR-AP H3CR-AS H3CR-A-301 15 66.6 52.3 0.7 6 48 39 dia. 48 44.8 × 44.8 11 pins H3CR-A8 H3CR-A8S H3CR-A8E H3CR-A8-301 15 66.6 52.3 0.7 6 48 39 dia. 48 44.8 × 44.8 8 pins Dimensions with Set Ring Y92S-27/-28 (Order Separately) 16.5 50 42 dia. 50 Panel cover Time Setting Ring Dimensions with Front Connecting Socket P2CF-08-@/P2CF-11-@ Dimensions with Back Connecting Socket P3G-08/P3GA-11 15 100.8* H3CR-A H3CR-A-301 H3CR-AS H3CR-AP 98.5 89.9* H3CR-A8@ H3CR-A8-301 H3CR-A8E H3CR-A8S 87.6 81.5 80 H3CR-A H3CR-A-301 H3CR-AS H3CR-AP + Adapter Y92F-30 P2CF-11 P2CF-11-E 2.3* P2CF-08 P2CF-08-E 2.3* 15 P3GA-11 (When Y92A-48G mounted) 81.5 75 H3CR-A8@ H3CR-A8-301 H3CR-A8E H3CR-A8S + Adapter Y92F-30 P3G-08 (When Y92A-48G mounted) Note: There are no restrictions to the mounting direction. * These dimensions vary with the kind of DIN track (reference value). 18 H3CR-A ■ Accessories (Order Separately) Protective Cover Y92A-48B Hold-down Clip Y92H-8 To use the Protective Cover with a flush mounting, use the Y92F-30 flush mounting adaptor. The Y92H-8 Hold-down Clip is attached to the PF085A socket. This Protective Cover cannot be used together with the Y92F-73/-74 flush mounting adaptor or the panel cover. Y92H-7 Y92H-7 Hold-down Clip is attached with screws together with the PL08 socket or the PL11 socket. 19 H3CR-A Application Examples (H3CR-A) A Mode: ON-delay ON-delay operation (A mode) is a basic mode. 1. Power-ON Start/Power-OFF Reset The Power-ON start/Power-OFF reset operation is a standard operating method. t 3. Control of Integrated Time with Gate Signal Gate signal processing (during input or a temporary timing stop) is possible with both power start and signal start. Power (2 and 10) t1 t2 t1 + t2: set time Power (2 and 10) Start (2 and 6) Reset (2 and 7) Start (2 and 6) Control output: NC (8 and 11) NC (1 and 4) Gate (2 and 5) Control output: NO (9 and 11) NO (1 and 3) Control output: NC (8 and 11) NC (1 and 4) Power indicator Flashing Control output: NO (9 and 11) NO (1 and 3) Lit Power indicator Externally short-circuited Flashing Lit Gate signal (The operation is interrupted with the gate signal if the Timer detects an abnormal signal.) Externally short-circuited Power supply 2. Signal Start/Signal Reset The Signal start/Signal reset operation is useful for remote control of the Timer. Power supply B/B2 Mode: Flicker The flicker operation in the B and B2 modes can be effectively applied to lamp or buzzer (ON and OFF) alarms or the monitoring of an intermittent operation with a display. Power (2 and 10) Start (2 and 6) 1. Power-ON Start/Power-OFF Reset (in B Mode) Reset (2 and 7) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3) Power (2 and 10) Power indicator Lit Flashing Lit Start signal (remote control possible) Reset signal (remote control possible) Start (2 and 6) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3) Power indicator Flashing Externally short-circuited Power supply (Power continuously supplied) Power supply 20 H3CR-A 2. Signal Start/Signal Reset (in B Mode) If there is an abnormal signal, flashing starts. When the abnormal condition is restored, a reset signal stops the display flashing. t 2. Signal-ON-OFF Start/Instantaneous Operation/Time-limit Reset Power (2 and 10) t Power (2 and 10) Start (2 and 6) Start (2 and 6) Control output: NC (8 and 11) NC (1 and 4) Reset (2 and 7) Control output: NO (9 and 11) NO (1 and 3) Control output: NC (8 and 11) NC (1 and 4) Lit Flashing Lit Flashing Lit Start signal (The operation starts with the signal ON or OFF) Start signal Reset signal Power supply Power supply (Power continuously supplied) (Power continuously supplied) D Mode: Signal OFF-delay C Mode: Signal ON/OFF-delay The Signal ON-/OFF-delay operation (C mode) is useful for the control of distribution of products on a production line into boxes by the specified number or time. Signal OFF-delay operation (D mode) can be effectively used to keep a load operating for a certain period. For example, this function enables the cooling fan for a lamp or heater to operate for a certain period after the lamp or heater is switched OFF. 1. Power-ON Start/Instantaneous Operation/ Time-limit Reset 1. Power-ON Start/Instantaneous Operation/ Time-limit Reset A set of these functions is useful for the operation of a machine for a specified period when power is ON. t Power (2 and 10) Start (2 and 6) t Power (2 and 10) Control output: NC (8 and 11) NC (1 and 4) Start (2 and 6) Control output: NO (9 and 11) NO (1 and 3) Control output: NC (8 and 11) NC (1 and 4) Power indicator Lit Control output: NO (9 and 11) NO (1 and 3) Power indicator Flashing Start signal (NC to NO) Flashing Lit Flashing Lit Externally short-circuited Power supply Power supply 21 Lit Flashing Lit Lit Power indicator Flashing Power indicator Control output: NO (9 and 11) NO (1 and 3) Lit H3CR-A 2. Signal Start/Instantaneous Operation/ Time-limit Reset 2. Signal Start/Instantaneous Operation/ Time-limit Reset This function is useful for the repetitive control such as the filling of liquid for a specified period after each Signal start input. Power (2 and 10) Start (2 and 6) t t Power (2 and 10) Control output: NC (8 and 11) NC (1 and 4) Start (2 and 6) Control output: NO (9 and 11) NO (1 and 3) Control output: NC (8 and 11) NC (1 and 4) Power indicator Lit Flashing Lit Control output: NO (9 and 11) NO (1 and 3) Power indicator Start signal (NO to NC to NO) Start signal Flashing Lit Flashing Lit Power supply Power supply (Power continuously supplied) (Power continuously supplied) E Mode: Interval 1. Power-ON Start/Instantaneous Operation/ Time-limit Reset This function is useful for the operation of a machine for a specified period after power is ON. t t Power (2 and 10) Start (2 and 6) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3) Power indicator Flashing Externally short-circuited Lit Flashing Lit Power supply 22 H3CR-A Safety Precautions (H3CR-A) Refer to Safety Precautions for All Timers. Note: The following precautions apply to all H3CR-A models. ■ Power Supplies ■ Input/Output For the power supply of an input device of the H3CR-A use an isolating transformer with the primary and secondary windings mutually isolated and the secondary winding not grounded. Correct H3CR-A G, S, R 5, 6, 7 10 Input terminal 2 Power supply 2 Relationship between Input and Power Supply Circuits (except for H3CR-A8E) The H3CR-A (except for H3CR-A8E) uses transformerless power supply. When connecting a relay or transistor as an external signal input device, pay attention to the following points to prevent shortcircuiting due to a sneak current to the transformerless power supply. If a relay or transistor is connected to two or more Timers, the input terminals of those Timers must be wired properly so that they will not differ in phase, otherwise the terminals will be short-circuited to one another. Incorrect Contact or transistor for external input signal Input terminal Isolation transformer is required. Input device H3CR-A Short-circuit current Power supply Incorrect G, S, R 5, 6, 7 2 H3CR-A Input terminal 10 Input terminal Power supply 2 Correct Contact or transistor for external input signal Input device H3CR-A Input terminal Isolation transformer Power supply The H3CR-A’s power supply terminal 2 is a common terminal for input signals to the Timer. Do not disconnect the wires on terminal 2, otherwise the internal circuitry of the Timer will be damaged. Input terminal 5, 6, 7 G, S, R AC or DC Power Supply Input terminal 10 H3CR-A 2 It is impossible to provide two independent power switches as shown below regardless of whether or not the Timers are different in phase. Contact or transistor for external input signal H3CR-A Input terminal Input terminal 23 Power supply H3CR-A Relationship between Input and Power Supply Circuits (H3CR-A@/-A@S) An appropriate input is applied to the input signal terminals of the H3CR-A@/-A@S when one of the input terminals is short-circuited with the common terminal (terminal 2) for the input signals. Never use terminal 10 as the common terminal for this purpose, otherwise the internal circuit of the Timer will be damaged. If a relay or transistor is connected to two or more Timers, the input terminals of those Timers must be wired properly so that they will not be different in phase or the terminals will be short-circuited to one another (refer to the figures below). Incorrect Contact or transistor for external input signal 10 6 Correct H3CR-AP 7 10 5, 6, 7 G, S, R Input terminal AC or DC power supply Power supply 2 H3CR-A/-AS 10 6 2 H3CR-AP 7 Incorrect Short-circuit current 2 10 AC or DC power supply 5, 6, 7 G, S, R Correct Contact or transistor for external input signal H3CR-A/-AS 10 6 Input terminal 2 *1 7 Power supply H3CR-AP 2 *2 10 Ry AC or DC power supply 5, 6, 7 G, S, R H3CR-A/-AS Input terminal Input contact Short-circuit current 6 7 10 H3CR-AP 2 2 *1 Power terminal 2 is a common terminal that is also used for the input signal. Do not use terminal 10 as a common terminal as this will damage the internal circuitry. *2 If a relay or other load is connected here, high voltage will be applied to the input terminal and damage the internal circuitry. • The transistor output of the H3CR-A@S is isolated from the internal circuitry by a photocoupler, and can therefore be used either as an NPN output type or a PNP (equivalent) output type. Relationship between Input and Power Supply Circuits (H3CR-AP) When using the timer in an environment where considerable noise occurs, keep the input signal source device, timer unit, and wiring as far away as possible from the source of the noise. It is also recommended that shielded wire be used for the input signal wiring as a countermeasure for noise. Common to All H3CR-A Models With the H3CR-AP, input wires must be as short as possible. If the floating capacity of wires exceeds 1,200 pF (approx. 10 m for cables with 120 pF/m), the operation will be affected. Pay particular attention when using shielded cables. The H3CR-A@S transistor output is isolated from the internal circuitry by a photocoupler. Therefore, either NPN or PNP output is possible. H3CR-AP AC/DC power supply Input circuit Power supply circuit Since the input circuit and the power supply circuit are configured independently, the input circuit can be turned ON or OFF irrespective of the ON/OFF state of the power supply. It must be noted that a voltage equivalent to the power supply voltage is applied to the input circuit. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. 24 MEMO 25 Solid-state Twin Timers H3CR-F DIN 48 × 48-mm Twin Timers • Wide power supply ranges of High Voltage 100 to 240 VAC/100 to 125 VDC and Low Voltage 24 to 48 VAC/12 to 48 VDC. • ON- and OFF-times can be set independently and so combinations of long ON- or OFF-time and short OFF- or ONtime settings are possible. • Twenty-four time ranges from 0.05 s to 300 h depending on the model to be used. • Models with a flicker ON start or flicker OFF start are available. • Easy sequence checks through instantaneous outputs for a zero set value at any time range. • Length, when panel-mounted with a Socket, of 80 mm or less. • 11-pin and 8-pin models are available. For the most recent information on models that have been certified for safety standards, refer to your OMRON website. Model Number Structure ■ Model Number Legend H3CR - F @ @ - @ @ 1 2 3 1. Classification F: Twin timers 2. Configuration None: 11-pin socket 8: 8-pin socket 4 5 3. Twin Timer Mode None: Flicker OFF start N: Flicker ON start 4. Time Range None: 0.05 s to 300 h models 5. Supply Voltage 100-240AC/100-125DC: 100 to 240 VAC/100 to 125 VDC 24-48AC/12-48DC: 24 to 48 VAC/12 to 48 VDC Note: When your order, specify the power supply voltage. Ordering Information ■ List of Models Operating modes Supply voltage 0.05 s to 300 h models 11-pin models Flicker OFF start Flicker ON start 8-pin models 100 to 240 VAC/100 to 125 VDC H3CR-F 100-240AC/100-125DC H3CR-F8 100-240AC/100-125DC 24 to 48 VAC/12 to 48 VDC H3CR-F 24-48AC/12-48DC H3CR-F8 24-48AC/12-48DC 100 to 240 VAC/100 to 125 VDC H3CR-FN 100-240AC/100-125DC H3CR-F8N 100-240AC/100-125DC 24 to 48 VAC/12 to 48 VDC H3CR-FN 24-48AC/12-48DC H3CR-F8N 24-48AC/12-48DC Note: Specify both the model number and supply voltage when ordering. Example: H3CR-F 100-240AC/100-125DC Supply voltage 26 H3CR-F ■ Accessories (Order Separately) Adapter, Protective Cover and Hold-down Clip Name/specifications Models Flush Mounting Adapter Y92F-30 Y92F-73 *1 Y92F-74 *1 Y92A-48B *2 Protective Cover Hold-down Clip (Sold in sets of two) For PF085A Socket Y92H-8 For PL08 or PL11 Sockets Y92H-7 Note: Refer to Operation (Common) datasheet for details. *1 The Y92A-48B Protective Cover and the Y92F-73/-74 Flush Mounting Adapter cannot be used at the same time. *2 The Y92A-48B Protective Cover is made from hard plastic. Remove the Protective Cover to change the set value. The Y92A-48B Protective Cover and the Y92F-73/-74 Flush Mounting Adapter also cannot be used at the same time. Sockets Timer Round Sockets Pin Connection 11-pin Front Connecting Back Connecting 8-pin Front Connecting Back Connecting Terminal Models DIN track mounting P2CF-11 DIN track mounting (Finger-safe type) P2CF-11-E Screw terminal P3GA-11 Solder terminal PL11 Wrapping terminal PL11-Q PCB terminal PLE11-0 DIN track mounting P2CF-08 DIN track mounting (Finger-safe type) P2CF-08-E DIN track mounting PF085A Screw terminal P3G-08 Solder terminal PL08 Wrapping terminal PL08-Q PCB terminal PLE08-0 Note: 1. The P2CF-@@-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals. 2. The P3GA-11 and P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection. 3. For details, refer to your OMRON website. Terminal Cover Application For back connecting socket Note: For details, refer to your OMRON website. 27 Model Y92A-48G Remarks For P3G-08 and P3GA-11 H3CR-F Specifications ■ General Item H3CR-F H3CR-F8 H3CR-FN Operating mode Flicker OFF start Pin type 11-pin Operating/Reset method Time-limit operation/Time-limit reset or self-reset Output type Relay output (DPDT) Mounting method DIN track mounting, surface mounting, and flush mounting Approved standards UL508, CSA C22.2 No.14, NK, Lloyds, CCC Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2. Output category according to EN60947-5-1. H3CR-F8N Flicker ON start 8-pin 11-pin 8-pin Note: For details, refer to your OMRON website. ■ Time Ranges Time unit Fullscale setting 1.2 s (sec) 0.05 to 1.2 ×10 s (10 sec) 1.2 to 12 min (min) 0.12 to 1.2 ×10 min (10 min) 1.2 to 12 h (hrs) 0.12 to 1.2 ×10 h (10 hrs) 1.2 to 12 3 0.3 to 3 3 to 30 0.3 to 3 3 to 30 0.3 to 3 3 to 30 12 1.2 to 12 12 to 120 1.2 to 12 12 to 120 1.2 to 12 12 to 120 30 3 to 30 30 to 300 3 to 30 30 to 300 3 to 30 30 to 300 Note: The times that can be set are given. When the time setting knob is turned below “0” until the point where the time setting knob stops, the output will operate instantaneously at all time range settings. For details, refer to your OMRON website. ■ Ratings Rated supply voltage (See notes 1, 2, and 3.) • 100 to 240 VAC 50/60 Hz/100 to 125 VDC • 24 to 48 VAC 50/60 Hz/12 to 48 VDC Operating voltage range 85% to 110% of rated supply voltage; 90% to 110% with 12-VDC models Power reset Minimum power-opening time: 0.1 s Power consumption 100 to 240 VAC: approx. 10 VA (2.1 W) at 240 VAC 24 VAC/VDC: approx. 2 VA (1.7 W) at 24 VAC approx. 1 W at 24 VDC Control outputs Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1) The minimum applicable load is 10mA at 5VDC (P reference value). Contact materials : Ag-alloy Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model. 2. Do not use an inverter output as the power supply. Refer to your OMRON website for details. 3. Refer to your OMRON website when using the Timer together with a 2-wire AC proximity sensor. 28 H3CR-F ■ Characteristics Accuracy of operating time ±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 1.2 and 3 s) Setting error ±5% FS ±50 ms max. Reset time 0.1 s max. Reset voltage 10% max. of rated voltage Influence of voltage ±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 1.2 and 3 s) Influence of temperature ±1% FS max. (±1% FS ±10 ms max. in ranges of 1.2 and 3s) Insulation resistance 100 MΩ min. (at 500 VDC) Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts) 2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit) 2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities) 1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other) Impulse withstand voltage 5kV (between power terminals), however, 1kV for 24 to 48VAC, 12 to 48 VDC 5kV (between current-carrying terminal and exposed non-current-carrying metal parts), however 1.5 kV for 24 to 48 VAC, 12 to 48 VDC Noise immunity ±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) Static immunity Malfunction: 8 kV Destruction: 15 kV Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions Shock resistance Destruction: 980 m/s2 three times each in six directions Malfunction: 98 m/s2 three times each in six directions Ambient temperature Operating: Storage: −10°C to 55°C (with no icing) −25°C to 65°C (with no icing) Ambient humidity Operating: 35% to 85% Life expectancy Mechanical: 20 million operations min. (under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note) EMC (EMI) Emission Enclosure: Emission AC Mains: (EMS) Immunity ESD: Immunity RF-interference: Immunity Burst: Immunity Surge: Immunity Conducted Disturbance: Immunity Voltage Dip/Interruption: Case color Light Gray (Munsell 5Y7/1) Degree of protection IP40 (panel surface) Weight Approx. 100 g EN61812-1 EN55011 Group 1 class A EN55011 Group 1 class A EN61812-1 IEC61000-4-2 IEC61000-4-3 IEC61000-4-4 IEC61000-4-5 IEC61000-4-6 IEC61000-4-11 Note: Refer to the Life-test Curve (Reference). ■ Life-test Curve (Reference) Switching operations (x 103) 10,000 5,000 1,000 500 30 VDC L/R = 7 ms 250 VAC/30 VDC (cosφ = 1) 100 250 VAC (cosφ = 0.4) Load current (A) 29 Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1) and a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P). H3CR-F Connections ■ Block Diagrams H3CR-F/-F8/-FN/F8N ON indicator Indicator circuit AC (DC) input Power supply circuit Zero setting detection circuit OFF indicator ROM RAM Clock Output circuit Time range/unit selectors One-chip microcomputer ■ I/O Functions --- Inputs Outputs Control output Outputs are turned ON/OFF according to the time set by the ON- and OFF-time setting knob. ■ Terminal Arrangement H3CR-F8/-F8N H3CR-F/-FN (+)(~) Power supply Power supply Note: Leave terminals 5, 6, and 7 open. Do not use them as relay terminals. 30 H3CR-F Operation ■ Timing Chart tON: ON set time tOFF: OFF set time Operating mode Timing chart Rt Flicker OFF start ON OFF Power ONindicator Lit Not lit OFF indicator Lit Not lit Output NO Output NC tOFF tON tOFF tON tOFF tOFF ON OFF ON OFF Flicker ON start Rt Power ON OFF ONindicator tON tOFF tON tOFF tON tOFF Lit Not lit OFF indicator Lit Not lit Output NO ON OFF Output NC ON OFF Note: 1. Allow a timer reset time (Rt) of 0.1 s or longer 2. When the setting dial is turned all the way past 0 for intantaneous output, "t" (set time) in the above time chart is 0-sec operation. Nomenclature Scale range display windows changes as below by turning the Time range selector clockwise. 0 0.2 0.4 0.6 0.8 1.0 0 0.5 1 1.5 2 2.5 0 2 4 6 8 10 12 0 5 10 15 20 25 30 OFF indicator (green) Lit when the output is OFF. ON indicator (orange) Lit when the output is ON. Scale range display windows 1.2 3 OFF-time unit display window OFF-time unit selector (select one from sec. 10 s, min., 10 min, hrs, and 10 h) ON-time setting knob (with orange pointer) For ON-time setting OFF-time setting knob (with green pointer) For OFF-time setting Time range selector (select one from 1.2, 3, 12, and 30 at full scale) For both ON-time and OFF-time. 31 ON-time unit display window ON-time unit selector (select one from sec, 10 s, min, 10 min, hrs, and 10 h) H3CR-F Dimensions Note: All units are in millimeters unless otherwise indicated. 17.4 H3CR-F H3CR-FN 5.7 66.6 52.3 0.7 6 48 37 din. 48 44.8 × 44.8 14 din. 11 pins 17.4 5.7 H3CR-F8 H3CR-F8N 66.6 52.3 0.7 6 48 37 din. 48 44.8 × 44.8 14 din. 8 pins Dimensions with Flush Mounting Adapter Y92F-30 Flush Mounting Adapter (Order Separately) Panel P3G Back Connecting Socket (Order separately) Mounting Hole Dimensions (Conform to DIN 43700.) 0.5 R max. 58 45+0.6 -0 (N) 52 45+0.6 -0 42 48 Note: 1. The orientation of the Adapters for two or more Timers is different for a horizontal or vertical layout. Make sure the orientation is correct. Consecutive Mounting of n Timers Without Front Covers: N = (48n - 2.5) + 1 - 0 With Front Covers: N = (51n - 5.5) + 1 - 0 With Panel Covers: N = (50n - 4.5) + 1 - 0 2. The applicable thickness of the mounting panel must be 1 to 5 mm. Y92F-73 Flush Mounting Adapter (Order Separately) Panel Adapter mounting holes: Two, 4.5 d P3G Back Connecting Socket 52 to 53 0.5 R max. 65 to 66 88 45±0.15 76±0.2 Insert the Timer in this direction.* 45±0.15 58 Note: A Front Cover and Flush Mounting Adapter cannot be used at the same time. 52.3 Note: The applicable thickness of the mounting panel must be 1 to 3.2 mm. * Insert the Timer from the back of the Adapter. 32 H3CR-F Y92F-74 Flush Mounting Adapter (Order Separately) Panel 56 P3G Back Connecting Socket 58 45±0.2 0.5 R max. 45+0.5 -0 55+0.5 -0 68 43±0.2 50+0.2 0 52.3 Note: A Front Cover and Flush Mounting Adapter cannot be used at the same time. Dimensions with Front Connecting Socket P2CF-08-@/P2CF-11-@ Dimensions with Back Connecting Socket P3G-08/P3GA-11 17.4 H3CR-F H3CR-FN 103.2* H3CR-F8 H3CR-F8N 100.9 92.3* Note: The applicable thickness of the mounting panel must be 1 to 3.2 mm. 90.0 81.5 80 H3CR-F H3CR-FN + Adapter 81.5 75 H3CR-F8 H3CR-F8N + Adapter P3G-08 (When Y92A-48G mounted) Note: There are no restrictions to the mounting direction. Y92F-30 2.3* 2.3* P2CF-11 P2CF-08 P2CF-11-E P2CF-08-E * These dimensions vary with the kind of DIN track (reference value). P3GA-11 (When Y92A-48G mounted) 17.4 Y92F-30 ■ Accessories (Order Separately) Protective Cover Y92A-48B Hold-down Clip Y92H-8 To use the Protective Cover with a flush mounting, use the Y92F-30 flush mounting adaptor. The Y92H-8 Hold-down Clip is attached to the PF085A socket. This Protective Cover cannot be used together with the Y92F-73/-74 flush mounting adaptor or the panel cover. Hold-down Clip Y92H-7 Y92H-7 Hold-down Clip is attached with screws together with the PL08 socket or the PL11 socket. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. 33 Solid-state Star-delta Timers H3CR-G DIN 48 × 48-mm Star-delta Timer • A wide star-time range (up to 120 seconds) and star-delta transfer time range (up to 1 seconds). For the most recent information on models that have been certified for safety standards, refer to your OMRON website. Model Number Structure ■ Model Number Legend H3CR - G 8 @ L @ 1 2 3 4 5 1. Classification G: Star-delta timer 2. Configuration 8: 8-pin socket 3. Outputs None: Star-delta operation contact E: Star-delta operation contact and instantaneous contact 4. Dimensions L: Long-body model Note: When your order, specify the power supply voltage. 5. Supply Voltage 100-120AC: 100 to 120 VAC 200-240AC: 200 to 240 VAC Ordering Information ■ List of Models Outputs Supply voltage Time-limit contact Time-limit contact and instantaneous contact 8-pin models 100 to 120 VAC H3CR-G8L 100-120AC 200 to 240 VAC H3CR-G8L 200-240AC 100 to 120 VAC H3CR-G8EL 100-120AC 200 to 240 VAC H3CR-G8EL 200-240AC Note: Specify both the model number and supply voltage when ordering. Example: H3CR-G8L 100-120AC Supply voltage 34 H3CR-G Accessories (Order Separately) ■ Accessories (Order Separately) Adapter, Protective Cover, Setting Ring and Panel Cover Name/specifications Models Y92F-30 Flush Mounting Adapter Y92F-70 *1 Y92F-71 *1 Y92A-48B *2 Protective Cover Hold-down Clip For PF085A Socket Y92H-2 For PL08 Sockets Y92H-1 Setting Ring A Y92S-27 *3 Setting Ring B and C Y92S-28 *3 Panel Cover Light gray (5Y7/1) Y92P-48GL *4 Black (N1.5) Y92P-48GB *4 Note: Refer to Operation (Common) datasheet for detail. *1 The Y92A-48B Protective Cover and the Y92P-48G@ Panel Cover can not be used at the same time with the Y92F-70/-71 Flush Mounting Adapter. *2 The Y92A-48B Protective Cover is made from hard plastic. Remove the Protective Cover to change to set value. The Y92F-70/-71 Flush Mounting Adapter and the Y92P-48G@ Panel Cover cannot be used at the same time with Y92A-48B Protective Cover. *3 The Y92S-27/-28 Setting Ring cannot be used alone. It must be used together with the Y92P-48G@ Panel Cover. *4 The Y92A-48B Protective Cover and the Y92F-70/-71 Flush Mounting Adapter cannot be used at the same time with the Y92P-48G@ Panel Cover. Sockets Timer Round Sockets Pin Connection 8-pin Front Connecting Back Connecting Terminal Models DIN track mounting P2CF-08 DIN track mounting (Finger-safe type) P2CF-08-E DIN track mounting PF085A Screw terminal P3G-08 Solder terminal PL08 Wrapping terminal PL08-Q PCB terminal PLE08-0 Note: 1. The P2CF-08-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals. 2. The P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection. 3. For details, refer to your OMRON website. Terminal Cover Application For back connecting socket Note: For details, refer to your OMRON website. 35 Model Y92A-48G Remarks For P3G-08 and P3GA-11 H3CR-G Specifications ■ General Item H3CR-G8L H3CR-G8EL Functions Star-delta timer Star-delta timer with instantaneous output Pin type 8-pin Operating/Reset method Time-limit operation/Self-reset Output type Time-limit: SPST-NO (star operation circuit) SPST-NO (delta operation circuit) Mounting method DIN track mounting, surface mounting, and flush mounting Approved standards UL508, CSA C22.2 No.14, NK, Lloyds, CCC Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2. Output category according to EN60947-5-1. Time-limit: SPST-NO (star operation circuit) SPST-NO (delta operation circuit) Instantaneous: SPST-NO Note: For details, refer to your OMRON website. ■ Time Ranges Time unit Star operation time ranges Scale number (max.) 6 Set time range 0.5 to 6 s 12 1 to 12 s 60 5 to 60 s 120 10 to 120 s Star-delta transfer time Programmable at 0.05 s, 0.1 s, 0.25 s, 0.5 s, 0.75 s, or 1.0 s ■ Ratings Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz) Operating voltage range 85% to 110% of rated supply voltage Power reset Minimum power-opening time: 0.5 s Power consumption 100 to 120 VAC: approx. 6 VA (2.6 W) at 120 VAC 200 to 240 VAC: approx. 12 VA (3.0 W) at 240 VAC Control outputs Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1) The minimum applicable load is 10mA at 5VDC (P reference value). Contact materials : Ag-alloy Note: 1. Do not use an inverter output as the power supply. Refer to your OMRON website for details. 2. Refer to your OMRON website when using the Timer together with a 2-wire AC proximity sensor. 36 H3CR-G ■ Characteristics Accuracy of operating time ±0.2% FS max. Setting error ±5% FS ±50 ms max. Accuracy of Star-delta transfer time ±25% FS + 5 ms max. Reset voltage 10% max. of rated voltage Influence of voltage ±0.2% FS max. Influence of temperature ±1% FS max. Insulation resistance 100 MΩ min. (at 500 VDC) Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts) 2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit) 2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities) 1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other) Impulse withstand voltage 5 kV (between power terminals) 5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) Noise immunity ±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) Static immunity Malfunction: 8 kV Destruction: 15 kV Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions Shock resistance Destruction: 980 m/s2 three times each in six directions Malfunction: 294 m/s2 three times each in six directions Ambient temperature Operating: Storage: −10°C to 55°C (with no icing) −25°C to 65°C (with no icing) Ambient humidity Operating: 35% to 85% Life expectancy Mechanical: 20 million operations min. (under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note) EMC (EMI) Emission Enclosure: Emission AC Mains: (EMS) Immunity ESD: Immunity RF-interference: Immunity Burst: Immunity Surge: Immunity Conducted Disturbance: Immunity Voltage Dip/Interruption: Case color Light Gray (Munsell 5Y7/1) Degree of protection IP40 (panel surface) Weight H3CR-G8L: approx. 110 g; H3CR-G8EL: approx. 130 g Note: Refer to the Life-test Curve (Reference). 37 EN61812-1 EN55011 Group 1 class A EN55011 Group 1 class A EN61812-1 IEC61000-4-2 IEC61000-4-3 IEC61000-4-4 IEC61000-4-5 IEC61000-4-6 IEC61000-4-11 H3CR-G ■ Life-test Curve (Reference) Switching operations (× 103) 10,000 5,000 1,000 500 30 VDC L/R = 7 ms 250 VAC/30 VDC (cosφ = 1) Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1) and a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P). 100 250 VAC (cosφ = 0.4) Load current (A) Connections ■ Block Diagrams H3CR-G8L AC input Power supply circuit Star operation time oscillation circuit Star operation time range selector Star-delta transfer time selector Star operation time counting circuit Star-delta transfer time oscillation circuit Star-delta transfer time counting circuit Output circuit Star operation Delta operation Indicator circuit Star operation indicator Delta operation indicator H3CR-G8EL AC input Power supply circuit Star operation time oscillation circuit Star operation time range selector Star-delta transfer time selector Star operation time counting circuit Star-delta transfer time oscillation circuit Star-delta transfer time counting circuit Star operation Output circuit Delta operation Indicator circuit Star operation indicator Delta operation indicator Instantaneous output circuit 38 H3CR-G ■ I/O Functions --- Inputs Outputs Control output If the time reaches the value set with the time setting knob, the star operation output will be turned OFF and there will be delta operation output after the set star-delta transfer time has elapsed. ■ Terminal Arrangement H3CR-G8L H3CR-G8EL Delta operation contact Star operation contact Delta operation contact Instantaneous contact Note: Leave terminals 1, 3, and 4 open. Do not use them as relay terminals. Star operation contact Note: Leave terminal 4 open. Do not use them as relay terminals. Operation ■ Timing Chart t1: t2: Star operation time setting Star-delta transfer time Model Timing chart 0.5 s min. H3CR-G8L/-G8EL Power (2 − 7) ON OFF Instantaneous output (1 − 3) (-E models) ON OFF Star operation output (8 − 5) ON OFF Delta operation output (8 − 6) ON OFF Star operation indicator Lit Not lit Delta operation indicator Lit Not lit t1 t2 Nomenclature Scale range display windows changes as below by turning the Time range selector clockwise. 0 1 2 3 4 5 6 0 2 4 6 8 10 12 0 10 20 30 40 50 60 0 20 40 60 80 100 120 Star operation indicator (green) Delta operation indicator (orange) Scale range display windows Time unit display (sec is fixed) Star operation time range selector (select one from 6, 12, 60, and 120 at full scale) Star-delta transfer time selector (select one from 0.05 s, 0.1 s, 0.25 s, 0.5 s, 0.75 s, and 1.0 s) Time setting knob (for setting star operation time) Star-delta transfer time display window 39 H3CR-G Dimensions Note: All units are in millimeters unless otherwise indicated. Dimension of Timer main unit 15 (78) 6 63.7 0.7 48 13.6 44.8 ✕ 44.8 39 dia. 48 79.4 Dimensions with Set Ring and Panel Cover Y92S-27/-28 (Order Separately) 16.5 50 42 dia. 50 Time setting ring Dimensions with Front Connecting Socket P2CF-08-@ 15 101.3* H3CR-G8@L Panel cover Dimensions with Back Connecting Socket P3G-08 99 92.9 86.4 H3CR-G8@L + Adapter Y92F-30 P2CF-08 P2CF-08-E 2.3* P3G-08 (When Y92A-48G mounted) Note: There are no restrictions to the mounting direction. * These dimensions vary with the kind of DIN track (reference value). 40 H3CR-G ■ Accessories (Order Separately) Protective Cover Y92A-48B Hold-down Clip Y92H-2 To use the Protective cover with a flush mounting, use the Y92F-30 flush mounting adaptor. The Y92H-2 Hold-down Clip is attached to the PF085A socket. This Protective cover cannot be used together with the Y92F-70/-71 flush mounting adaptor or the panel cover. Y92H-1 Y92H-1 Hold-down Clip is attached with screws together with the PL08 socket. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. 41 Solid-state Power OFF-delay Timers H3CR-H DIN 48 48-mm Power OFF-delay Timer • Long power OFF-delay times; S-series: up to 12 seconds, M-series: up to 12 minutes. • Models with forced-reset input are available. • 11-pin and 8-pin models are available. For the most recent information on models that have been certified for safety standards, refer to your OMRON website. Model Number Structure ■ Model Number Legend Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 42 for availability. H3CR - H @ @ L @ @ 1 2 3 4 5 Note: Specify the model number, supply voltage, and time range (S or M) when ordering. 6 1. Classification H: Power OFF-delay timer 2. Configuration None: 11-pin socket 8: 8-pin socket 3. Input None: Without reset input R: With reset input 4. Dimensions L: Long-body model 6. Time Range S: 0.05 to 12 s M: 0.05 to 12 min 5. Supply Voltage 100-120AC: 100 to 120 VAC 200-240AC: 200 to 240 VAC 24AC/DC: 24VAC/DC 48DC: 48 VDC 100-125DC: 100 to 125 VDC ■ List of Models Input Output Supply voltage S-series 11-pin models Without DPDT reset input With reset input M-series 8-pin models --- 8-pin models 100 to 120 VAC --- H3CR-H8L 100-120AC S 200 to 240 VAC H3CR-H8L 200-240AC S 24 VAC/DC H3CR-H8L 24AC/DC S H3CR-H8L 24AC/DC M 48 VDC H3CR-H8L 48DC S H3CR-H8L 48DC M 100 to 125 VDC H3CR-H8L 100-125DC S 100 to 120 VAC H3CR-HRL 100-120AC S --- H3CR-H8L 100-120AC M H3CR-H8L 200-240AC M H3CR-H8L 100-125DC M H3CR-HRL 100-120AC M --- 200 to 240 VAC H3CR-HRL 200-240AC S H3CR-HRL 200-240AC M 24 VAC/DC H3CR-HRL 24AC/DC S H3CR-HRL 24AC/DC M 48 VDC H3CR-HRL 48DC S H3CR-HRL 48DC M 100 to 125 VDC H3CR-HRL 100-125DC S SPDT 11-pin models H3CR-HRL 100-125DC M 100 to 120 VAC --- H3CR-H8RL 100-120AC S --- H3CR-H8RL 100-120AC M 200 to 240 VAC H3CR-H8RL 200-240AC S H3CR-H8RL 200-240AC M 24 VAC/DC H3CR-H8RL 24AC/DC S H3CR-H8RL 24AC/DC M 48 VDC H3CR-H8RL 48DC S H3CR-H8RL 48DC M 100 to 125 VDC H3CR-H8RL 100-125DC S H3CR-H8RL 100-125DC M Note: Specify the model number, supply voltage, and time range (S or M) when ordering. Example: H3CR-H8L 100-120AC S Time range Supply voltage 42 H3CR-H ■ Accessories (Order Separately) Adapter, Protective Cover and Hold-down Clip Name/specifications Flush Mounting Adapters Protective Cover Hold-down Clips For PF085A Socket For PL08 or PL11 Sockets Models Y92F-30 Y92F-70 *1 Y92F-71 *1 Y92A-48B *2 Y92H-2 Y92H-1 Note: Refer to Operation (Common) datasheet for details. *1.The Y92A-48B Protective Cover and the Y92F-70/-71 Flush Mounting Adapter cannot be used at the same time. *2.The Y92F-48B Protective Cover is made from hard plastic. Remove the Protective Cover to change the set value. Sockets Timer Pin Round Sockets Terminal DIN track mounting DIN track mounting (Finger-safe type) Screw terminal Solder terminal Wrapping terminal PCB terminal DIN track mounting DIN track mounting (Finger-safe type) DIN track mounting Screw terminal Solder terminal Wrapping terminal PCB terminal Connection Front Connecting 11-pin Back Connecting 8-pin Front Connecting Back Connecting Models P2CF-11 P2CF-11-E P3GA-11 PL11 PL11-Q PLE11-0 P2CF-08 P2CF-08-E PF085A P3G-08 PL08 PL08-Q PLE08-0 Note: 1. The P2CF-@@-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals. 2. The P3GA-11 and P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection. 3. For details, refer to your OMRON website. Terminal Cover Application For back connecting socket Model Remarks For P3G-08 and P3GA-11 Y92A-48G Note: For details, refer to your OMRON website. Specifications ■ General Item Operating/Reset method Pin type Input type Output type Mounting method Approved standards H3CR-H8L H3CR-H8RL H3CR-HRL Instantaneous operation/Time-limit reset Instantaneous operation/Time-limit reset/Forced reset 8-pin 11-pin --No-voltage input Relay output (DPDT) Relay output (SPDT) Relay output (DPDT) DIN track mounting, surface mounting, and flush mounting UL508, CSA C22.2 No.14, NK, Lloyds, CCC Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2. Output category according to EN60947-5-1. Note: For details, refer to your OMRON website. ■ Time Ranges Time unit Scale number (max.) 0.6 Set time range 1.2 6 12 Min. power ON time Time-up operation repeat period Forced-reset repeat period S-series s (sec) 0.05 to 0.6 0.12 to 1.2 0.6 to 6 1.2 to 12 0.1 s min. 3 s min. 3 s min. M-series min (min) 2 s min. Note: 1. If the above minimum power ON time is not secured, the H3CR may not operate. Be sure to secure the above minimum power ON time. 2. Do not use the Timer with a repeat period of less than 3 s. Doing so may result in abnormal heating or burning. Refer to Safety Precautions (H3CR-H) on page 50 for details. 43 H3CR-H ■ Ratings Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz), 24 VAC/VDC (50/60 Hz), 48 VDC, 100 to 125 VDC Operating voltage range 85% to 110% of rated supply voltage No-voltage input (See note 3.) ON-impedance: 1 kΩ max. ON residual voltage: 1 V max. OFF impedance: 500 kΩ min. Power consumption 100 to 120 VAC: approx. 0.23 VA (0.22 W) at 120 VAC 200 to 240 VAC: approx. 0.35 VA (0.3 W) at 240 VAC 24 VAC/DC: approx. 0.17 VA (0.15 W) at 24 VAC approx. 1.0 W at 24 VDC 48 VDC: approx. 0.18 W at 48 VDC 100 to 125 VDC: approx. 0.5 W at 125 VDC Control outputs Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1) The minimum applicable load is 10mA at 5VDC (P reference value). Contact materials : Ag-alloy Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model. 2. Do not use an inverter output as the power supply. Refer to your OMRON website for details. 3. For contact input, use contacts which can adequately switch 1 mA at 5 V. ■ Characteristics Accuracy of operating time ±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 0.6 and 1.2 s) Setting error ±5% FS ±50 ms max. Operation start voltage 30% max. of rated voltage Influence of voltage ±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 0.6 and 1.2 s) Influence of temperature ±1% FS max. (±1% FS ±10 ms max. in ranges of 0.6 and 1.2 s) Insulation resistance 100 MΩ min. (at 500 VDC) Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts) 2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit) 2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities) 1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other) Impulse withstand voltage 5 kV (between power terminals) for 100 to 120 VAC, 200 to 240 VAC, 100 to 125 VDC; 1 kV for 24 VAC/DC, 48 VDC 5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 120 VAC, 200 to 240 VAC, 100 to 125 VDC; 1.5 kV for 24 VAC/DC, 48 VDC Noise immunity ±1.5 kV (between power terminals) and ±600 V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise); ±1 kV (between power terminals) for 48 VDC Static immunity Malfunction: 8 kV, Destruction:15 kV Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions Shock resistance Destruction: 980 m/s2 three times each in six directions Malfunction: 98 m/s2 three times each in six directions Ambient temperature Operating: Storage: −10°C to 55°C (with no icing), −25°C to 65°C (with no icing) Ambient humidity Operating: 35% to 85% Life expectancy Mechanical: 10 million operations min. (under no load at 1,200 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h) (See note) EMC (EMI) Emission Enclosure: Emission AC Mains: (EMS) Immunity ESD: Immunity RF-interferenc: Immunity Burst: Immunity Surge: Immunity Conducted Disturbance: Immunity Voltage Dip/Interruption: Case color Light Gray (Munsell 5Y7/1) Degree of protection IP40 (panel surface) Weight Approx. 120 g EN61812-1 EN55011 Group 1 class A EN55011 Group 1 class A EN61812-1 IEC61000-4-2 IEC61000-4-3 IEC61000-4-4 IEC61000-4-5 IEC61000-4-6 IEC61000-4-11 Note: Refer to the Life-test Curve(Reference). 44 H3CR-H ■ Life-test Curve(Reference) Switching operations (× 103) 10,000 5,000 1,000 500 30 VDC L/R = 7 ms 250 VAC/30 VDC (cosφ = 1) 100 250 VAC (cosφ = 0.4) Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1) and a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC for H3CR-H8L/-HRL and 100 mA at 5 VDC for H3CR-H8RL (failure level: P). Load current (A) Connections ■ Block Diagrams Without Reset Input (H3CR-H8L) Time range/ unit selector Power supply circuit Oscillation circuit Counting circuit Power failure detection circuit Output circuit Indicator circuit LCD AC (DC) input Output indicator With Reset Input (H3CR-H8RL/-HRL) Time range/ unit selector Power supply circuit Oscillation circuit Counting circuit Indicator circuit Power failure detection circuit Reset input Output circuit LCD AC (DC) input Output indicator Input circuit ■ I/O Functions 45 Inputs Reset Turns off the control output and resets the elapsed time. Outputs Control output Operates instantaneously when the power is turned on and time-limit resets when the set time is up after the power is turned off. H3CR-H ■ Terminal Arrangement Note: DC models, including 24 VAC/DC models, have polarity. 8-pin Models Without Reset Input (H3CR-H8L) With Reset Input (H3CR-H8RL) Reset input Power supply Power supply Note: Leave terminal 3 open. Do not use them as relay terminals. 11-pin Model With Reset Input (H3CR-HRL) Reset input Power supply Note: Leave terminal 6 open. Do not use them as relay terminals. 46 H3CR-H Operation ■ Timing Chart t: Set time Rt: Minimum power ON time (S-series: 0.1 s min.; M-series: 2 s min.) If the power ON time is less than this value, the Timer may not operate (i.e., output may not turn ON). Model Timing chart Rt H3CR-H8L Power (See note) ON Rt t t OFF Output (1 − 3) Output (1 − 4) Output (8 − 6) Output (8 − 5) Output indicator Lit Not lit H3CR-H8RL Rt ON Power (See note) OFF t Rt t 0.05 s min. 0.05 s min. ON (Short-circuited) Reset input OFF (Open) Output (8 − 6) Output (8 − 5) Lit Not lit Output indicator H3CR-HRL Power (See note) ON Rt OFF 0.05 s min. Reset input Output (1 − 3) Output (1 − 4) Output (11 − 9) Output (11 − 8) Output indicator Lit Not lit Note: If the power is turned ON until the set time is up, the timer will be retriggered. 47 Rt t t 0.05 s min. H3CR-H Nomenclature Scale range display windows changes as below by turning the Time range selector clockwise. Output indicator (red) Scale range display windows 0 0.1 0.2 0.3 0.4 0.5 0 0.2 0.4 0.6 0.8 1.0 0.6 1.2 0 1 2 3 4 5 6 0 2 4 6 8 10 12 Time setting knob (for setting power OFF-delay time) Time range selector (select one from 0.6, 1.2, 6, and 12 at full scale) Time unit display S-series: sec M-series: min Dimensions Note: All units are in millimeters unless otherwise indicated. H3CR-H8L H3CR-H8RL 15 (78) 6 63.7 0.7 48 48 44.8 × 44.8 39 dia. 11 pins 79.4 15 H3CR-HRL (78) 6 63.7 0.7 48 48 Dimensions with Front Connecting Socket P2CF-08-@/P2CF-11-@ 44.8 × 44.8 92.9 86.4 15 92.9 91.4 H3CR-HRL 99 112.2* 109.9 H3CR-H8@L + Adapter Y92F-30 P2CF-08 P2CF-08-E 8 pins Dimensions with Back Connecting Socket P3G-08/P3GA-11 15 H3CR-H8@L 13.6 39 dia. 79.4 101.3* 13.6 2.3* P2CF-11 P2CF-11-E 2.3* P3G-08 (When Y92A-48G mounted) H3CR-HRL + Adapter Y92F-30 P3GA-11 (When Y92A-48G mounted) Note: There are no restrictions to the mounting direction. * These dimensions vary with the kind of DIN track (reference value). 48 H3CR-H ■ Accessories (Order Separately) Protective Cover Y92A-48B Hold-down Clip Y92H-2 To use the Protective Cover with a flush mounting, use the Y92F-30 flush mounting adaptor. The Y92H-2 Hold-down Clip is attached to the PF085A socket. This Protective Cover cannot be used together with the Y92F-70/-71 flush mounting adaptor or the panel cover. Y92H-1 Y92H-1 Hold-down Clip is attached with screws together with the PL08. 49 H3CR-H Safety Precautions (H3CR-H) Note: The undermentioned is common for all H3CR-H models. ■ Power Supplies ■ Wiring The H3CR-H has a large inrush current; provide sufficient power supply capacity. If the power supply capacity is too small, there may be delays in turning ON the output. With the H3CR-H@RL, for the power supply of an input device, use an isolating transformer, of which the primary and secondary windings are mutually isolated and the secondary winding is not grounded. The H3CR-H has a high impedance circuit. Therefore, the H3CR-H may not be reset if the H3CR-H is influenced by inductive voltage. In order to eliminate any influence of inductive voltage, the wires connected to the H3CR-H must be as short as possible and should not be installed alongside power lines. If the H3CR-H is influenced by inductive voltage that is 30% or more of the rated voltage, connect a CR filter with a capacitance of approximately 0.1 F and a resistance of approximately 120 or a bleeder resistor between the power supply terminals. If there is any residual voltage due to current leakage, connect a bleeder resistor between the power supply terminals. Correct H3CR-H@RL (4) <7> 5, 6, 7 (7) <10> 10 Input terminal (1) <5> 2 (2) <2> 2 Power supply ■ Operation ( ): H3CR-H8RL < >: H3CR-HRL An interval of 3 s minimum is required to turn on the H3CR-H after the H3CR-H is turned off. If the H3CR-H is turned on and off repeatedly with an interval of shorter than 3 s, abnormal heating or burning may occur in internal elements. 3 s min. Isolation transformer is required. Input device Incorrect (4) <7> 5, 6, 7 H3CR-H@RL (1) <5> 2 Input terminal (7) <10> 10 (2) <2> 2 Output state 1 Power supply Output state 2 ( ): H3CR-H8RL < >: H3CR-HRL Input device Isolation transformer An appropriate input is applied to the input signal terminal of the Timer when the input terminal for the input signal is short-circuited. Do not attempt to connect any input terminal to any terminal other than the input terminal or to apply voltage across other than the specified input terminals or the internal circuits of the Timer may be damaged. The H3CR-H@RL uses transformerless power supply. When connecting a relay or transistor as an external signal input device, pay attention to the following points to prevent short-circuiting due to a sneak current to the transformerless power supply. If input is made simultaneously from one input contact or a transistor to the H3CR-H and a Timer whose common input terminals are used as power terminals, such as the H3CR-A, a short-circuit current will be generated. Either input through isolated contacts, or isolate the power supply for one of the Timers. H3CR-H@RL 10, 7* 1*, 5 2, 2* After the forced reset function of the H3CR-H is activated, an interval of 3 s minimum is required to activate the forced reset function again. If the forced reset function is activated repeatedly with an interval of shorter than 3 s, the internal parts of the H3CR-H may deteriorate and the H3CR-H may malfunction. Power ■ Input/Output (H3CR-H@RL) 4*, 7 Power 3 s min. 3 s min. Reset input Output If it is required that the output be turned on repeatedly with an interval of shorter than 3 s, consider use of the H3CR-A in mode D (signal OFF-delay). On the H3CR-F@, do not set both the ON set dial and OFF set dial to the lowest settings. Doing so may damage the contacts. ■ Others If the H3CR-H is dropped or experiences some other kind of shock, because a latching relay is used for output, contacts may be reversed or go into a neutral state. If the H3CR-H is dropped, reconfirm correct operation. Short-circuit current G. S. R. 5 6 7 10 H3CR-A 2 *: H3CR-H8RL ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. 50 MEMO 51 Operation (Common) Note: The undermentioned is common for all H3CR models. ■ Basic Setting • H3CR-F Twin Timers The display window at the bottom right inside the Time setting knob shows 1.2, 3, 12, or 30 to indicate the scale number selected with the selector switch on the front at bottom left. Setting of Selectors The selectors can be turned clockwise and counterclockwise to select the desired time unit, time range, or operating mode. Each selector has a snap mechanism that secures the selector at a given position. Set the selector at a position at which it is secured. Do not set it midway between two securing positions or a malfunction could result from improper setting. Selection of Operating Mode Time range selector • H3CR-A Multifunctional Timer The operation mode A to E, G, and J of the H3CR-A can be selected. Use a Phillips head or flathead screwdriver to turn the selector switch. The operation mode can be set to one of eight modes. The window on the top shows E, G, J, A, B, B2, C, or D to indicate the selected mode. On the H3CR-A8, the window on the top shows E, J, B, A, or B2. Operating mode selector Use a Phillips head or flathead screwdriver to turn the selector switch. For ON-time, the desired time unit (sec, 10 s, min, 10 min, hrs, and 10 h) is indicated in the ON-time unit display window at the lower right corner of the front panel and can be changed by turning the ON-time unit selector located below the ON-time unit display window. Operating mode display window Groove for screwdriver Usable screwdrivers Phillips head: No. 0-1 Flat head: Width 2.3 to 3.0 mm (i.e., H3CR-A) Scale range display windows Time range selector Selection of Time Unit and Time Range OFF-time setting knob (with green pointer) For OFF-time setting OFF-time unit display window OFF-time unit selector ON-time unit display window ON-time unit selector • H3CR-A Multifunctional Timer The desired time unit (sec, ✕10 s, min, ✕10 m, hrs, or ✕10 h) is displayed in the window below the time setting knob by turning the time unit selector located at the lower right corner of the front panel. A time range (1.2, 3, 12, or 30 for H3CR-A@/2.4, 6, 24, or 60 for H3CR-A@-301) is selected with the time range selector at the lower left corner of the front panel, and the selected time range appears (in the window at the lower right part) within the plastic frame of the time setting knob. Time setting knob Time range selector For OFF-time, the desired time unit (sec, 10 s, min, 10 min, hrs and 10 h) is indicated in the OFF-time unit display window at the upper right corner of the front panel and can be changed by turning the OFF-time unit selector located below the OFF-time unit display window. OFF-time unit selector Scale range display window Time unit selector Time unit display window 52 H3CR • H3CR-G Star-delta Timers • H3CR-H Power OFF-delay Timers The display window at the bottom right inside the Time setting knob shows 6, 12, 60, or 120 to indicate the scale number Star operation time selected with the selector switch on the front at bottom left. Use a Phillips head screwdriver or flathead screwdriver to turn the selector switch. The display window at the bottom right inside the Time setting knob shows 0.6, 1.2, 6, or 12 to indicate the scale number selected with the selector switch on the front at bottom left. Scale range display window Time setting knob Star operation time range selector Time range selector Usable screwdrivers Phillips head: No. 0-1 Flat head: Width 2.3 to 3.0 mm Use a Phillips head screwdriver or flathead screwdriver to turn the selector switch. The display window at the bottom center of the Time setting knob shows 0.05, 0.1, 0.25, 0.5, 0.75, or 1.0 to show the star -delta transfer time selected with the selector switch on the front at bottom right. Scale range display window Setting of Time Use the time setting knob to set the desired time. Time setting knob Star-delta switching time selector switch Star operation time range selector Star-delta switching time display window Usable screwdrivers Phillips head: No. 0-1 Flat head: Width 2.3 to 3.0 mm ■ Using the Time Setting Ring for H3CR-A/-G Locking the Set Time Limiting the Setting Range Mount the Panel Cover on the Timer, set the desired time with the time setting knob, and place Time Setting Ring A onto the time setting knob so that the time setting notch of Time Setting Ring A is in the center of the reset lock position of the Panel Cover. Example: To set a range of 10 and 20 s. Mount the Panel Cover on the Timer, set the time setting knob to 10 s (the lower limit of the setting range), and place Time Setting Ring C onto the time setting knob so that the stopper of Time Setting Ring C is on the right edge of the reset lock position of the Panel cover. Next, set the time setting knob to 20 s (the upper limit of the setting range), place Time Setting Ring B onto the time setting knob so that the stopper of Time Setting Ring B is on the left edge of the reset lock position of the Panel Cover. Time setting notch Reset lock position Stopper Reset lock position Time Setting Ring A Panel cover Time setting notch Setting position Time Setting Ring B Example: To set the time to 10 s. 53 Time Setting Ring C Panel cover Range H3CR Accessories (Order Separately) (Common) Note: The undermentioned is common for all H3CR models. Note: All units are in millimeters unless otherwise indicated. Flush Mounting Adaptor Panel P3G Back Connecting Socket Y92F-30 58 52 42 48 Panel Cutout (Conforms ro DIN 43700) Note1: The adapters for two or more timers mounted in a vertical line are different in orientation from those mounted in a horizontal line. 0.5 R max. N can be obtained as follows (n: the number of H3CR models arranged side by side) Without a Cover: N = (48n - 2.5)+1/-0 With the Protective Cover: N = (51n - 5.5)+1/-0 With the Panel Cover: N = (50n - 4.5)+1/-0 45+0.6 −0 (N) 45+0.6 −0 Note2: The applicable thickness of the mounting panel must be 1 to 5 mm. Y92F-70/-73 Panel Cutout Panel P3G Back Connecting Socket Adapter mounting hole Two, 4.5 dia. R0.5 max. 52 to 53 88 45±0.15 65 to 66 76±0.2 Unit insertion direction* 45±0.15 52.3 (63.7) 58 (See note.) Note: The value shown in parentheses is for the Y92F-70. Y92F-71/-74 Panel 56 58 Note: The applicable thickness of the mounting panel must be 1 to 3.2 mm. * Insert timer unit from back side of adapter. P3G Back Connecting Socket Unit insertion direction* 43±0.2 50 +0.2 -0 45+0.5 −0 55+0.5 −0 68 45±0.2 R0.5 max. 52.3 (63.7) (See note.) Note: The value shown in parentheses is for the Y92F-71. Note: The applicable thickness of the mounting panel must be 1 to 3.2 mm. * Insert timer unit from back side of adapter. 54 H3CR Track Mounting/Front Connecting Socket P2CF-08 Eight, M3.5 × 7.5 sems 7.8 3 4.5 70 max. 35.4 Two, 4.5 dia. holes Terminal Arrangement/ Internal Connections (Top View) Surface Mounting Holes 4 50 max. Two, 4.5 dia. or two, M4 20.3 max. P2CF-08-E (Finger Safe Terminal Type) Conforming to VDE0106/P100 Eight, M3.5 × 7.5 sems 40±0.2 5 7.8 4.5 3 1.3 70 max. 35.4 Two, 4.5 dia. holes 4 40±0.2 19 20.3 50 max. 21.5 max. Track Mounting/Front Connecting Socket P2CF-11 Eleven, M3.5 × 7.5 sems 7.8 3 4.5 70 max. 35.4 50 max. 31.2 max. 40±0.2 P2CF-11-E (Finger Safe Terminal Type) Conforming to VDE0106/P100 Eleven, M3.5 × 7.5 sems 7.8 5 4.5 3 1.2 70 max. 35.4 Two, 4.5 dia. holes 55 Surface Mounting Holes Two, 4.5 dia. or two, M4 4 4 Terminal Arrangement/ Internal Connections (Top View) 40±0.2 50 max. 30 31.2 max. H3CR Back Connecting Socket Terminal Arrangement/ Internal Connections (Bottom View) 27 dia. P3G-08 45 45 P3GA-11 4.9 17 Terminal Arrangement/ Internal Connections (Bottom View) 27 dia. 45 25.6 45 4.5 6.2 16.3 Finger Safe Terminal Cover Conforming to VDE0106/P100 Y92A-48G (Attachment for P3G-08/P3GA-11 Socket) Twelve, 6.4 dia. holes 34 48 × 48 47.7 × 47.7 16.5 24.6 27.6 47.4 Mounting Track PFP-100N2 PFP-100N, PFP-50N 16 7.3±0.15 4.5 4.5 15 25 10 25 25 1,000 (500) (See note) 10 25 35±0.3 27 27±0.15 35±0.3 15 1 15 (5) (See note) 25 10 25 25 1,000 10 25 15 24 29.2 1 1.5 Note: The values shown in parentheses are for the PFP-50N. End Plate Spacer 10 6.2 PFP-M 1 50 1.8 11.5 10 M4 x 8 pan head screw 1.3 4.8 1.8 PFP-S 35.5 35.3 16 12 5 34.8 44.3 16.5 56 H3CR Time Setting Ring/Panel Cover for H3CR-A/-G There are two types of Panel Covers (Y92P-48GL, and Y92P-48GB), all of which are available in two colors. Use the most suitable type of Panel Cover with the design of the scaling plate according to the application. To lock the set time, you can lock the setting dial by using a Y92S-27 Setting Ring and a Y92P-48GL/-48GB Panel Cover. This will help to prevent the set time from being changed accidentally. To restrict the set time range, you can restrict the rotating range of the setting dial by using a Y92S-28 Setting Ring and a 92P-48GL/48GB Panel Cover. Use them to restrict the upper and lower limits of the setting range. Refer to Using the Time Setting Ring for H3CR-A/-G on page 53 for the procedure to attach the Setting Ring. The Flush Mounting Adapter Y92F-70/Y92F-71 for H3CR-G, Y92F73/Y92F-74 for H3CR-A or the Protective Cover cannot be used. Note: The Time Setting Ring/Panel Cover cannot be used for H3CRF model or H3CR-H model. The Time Setting Ring and Panel Cover should be used as a pair. Locking the Set Time Time Setting Ring A (Y92S-27) and Panel Cover (Y92P-48GL, or -48GB) Limiting the setting Time Setting Ring B or C (Y92S-28), and range Panel Cover (Y92P-48GL, or -48GB) Y92S-27 Time Setting A 57 Y92S-28 Time Setting B Y92S-28 Time Setting C Y92P-48GL Light Gray Y92P-48GB Black H3CR Safety Precautions for All H3CR Models Note: The undermentioned is common for all H3CR models. Warning Indications CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or in property damage. Precautions for Safe Use Supplementary comments on what to do or avoid doing, to use the product safely. Precautions for Correct Use Supplementary comments on what to do or avoid doing, to prevent failure to operate, malfunction or undesirable effect on product performance. In rare circumstances there is a risk of slight electrical shock, fire, or device damage. Do not disassemble, modify, repair, or otherwise touch the inside. In rare circumstances there is a risk of fire if the screws become loose. Tighten the terminal screws to the specified torque (1.08N·m). Meaning of Product Safety Symbols Used to warn of the risk of electric shock under specific conditions. Used for general prohibitions for which there is no specific symbol. Use to indicate prohibitions when there is a risk of minor injury from electrical shock or other source if the product is disassembled. Precautions for Safe Use Do not use the Timer in the following locations. • • • • • Locations with radical temperature changes. Locations with high humidity that may result in condensation. Locations with excessive vibration or shock. Locations with corrosive gas or dust. Locations where the Timer is exposed to sprayed water, oil, or chemicals. Pay the utmost attention not to make mistakes in polarity when wiring the Timer. Do not connect anything to terminals that are not used. Risk of internal element damage if a voltage that exceeds the rating is applied. Using a surge absorber is recommended if surge voltages occur. Used for general mandatory action precautions for which there is no specified symbol. CAUTION Risk of fire and explosion due to arcing and relay heat generation that accompanies switching. Do not use in an environment where flammable or explosive gas is present. The H3CR series uses a transformer-less power supply. Exercise full caution as there is a risk of electrical shock if input terminal is touched when power voltage is applied. The H3CR Series uses a transformerless power supply. Do not touch the input terminals while the supply voltage is applied, otherwise an electric shock may be received. Verify that the power and output LEDs (LCD) are operating normally. In some usage environments, the LEDs/LCD/ resin components may deteriorate faster than normal, resulting in display failure. Inspect and replace regularly. When disposing of this product, follow the procedures for disposal of industrial waste that apply in your region. Verify that the product is the desired product before use. Exercise caution as the outer casing of the timer may be immersed in organic solvents (thinner, benzene, etc.), strong alkali, or strong acids. Precautions for Correct Use The service life of the output relay varies widely depending on switching capacity and switching conditions. Use only within the rated load and electrical life count, based on actual conditions of use. Risk of contact sticking and burning if used past the service life. Always use a load current that does not exceed the rating, and if a heater is used, use a thermal switch in the load circuit. Do not remove the outer casing. Changing the Setting Do not change the time unit, time range, or operation mode while the Timer is in operation, otherwise the Timer may malfunction. The time unit and time range can be set with the respective selectors turned clockwise or counterclockwise. The selectors are of notched so that they will snap when they are properly set. Do not set the selectors midway between notches, otherwise the Timer may break or malfunction. Do not use H3CR-A models (except for H3CR-A@S) in flicker mode at the lowest selector setting, or H3CR-F models at the lowest selector setting. Doing so may result in damage to contacts. 58 H3CR Power Supplies Others A DC power supply can be connected if its ripple factor is 20% or less and the mean voltage is within the rated operating voltage range of the Timer. If the Timer is mounted to a control board, dismount the Timer from the control board or short-circuit the control board circuitry before carrying out a voltage withstand test between the electric circuitry and non-charged metal part of the Timer. This protects the internal circuitry of the Timer from damage. An AC power supply can be connected to the power input terminals without regard to polarity. A DC power supply must be connected to the power input terminals as designated according to the polarity of the terminals. Make sure that the voltage is applied within the specified range, otherwise the internal elements of the Timer may be damaged. Connect the power supply voltage through a relay or switch in such a way that the voltage reaches a fixed value at once, otherwise the Timer may not be reset or a timer error may result. Be aware that the operating voltage will rise by 5% if the rated voltage is applied to the Timer continuously while the ambient temperature is close to the maximum permissible ambient temperature. The power supply circuit of any H3CR-A model (except for H3CRA@S), H3CR-F 100-to-240-VAC model, and H3CR-G model is a switching circuit. If the power line connected to the power supply circuit has a transformer with high inductance, a counterelectromotive voltage will be induced by the inductance. To suppress the voltage, apply a CR filter to the power supply line. Apply the power voltage at once through the switch and relay contacts. If not applied at once, power reset may not take place or time-up may occur. When the power is turned on, a rush current (refer to your OMRON website) may flow briefly and the timer may not start if there is insufficient power capacity. Use a power supply with sufficient capacity. If the timer is left for an extended time at high temperature in the time-up state (internal relay ON), the internal components (electrolytic capacitors, etc.) may deteriorate faster than normal. For this reason, use in combination with a relay, and avoid leaving in the time-up state for an extended time (for example, one month or longer). Reference example Use as shown below. X2/b T T/a X1 X1/a X1/a X2 X MY relay, etc. Cleaning Do not use solvents such as thinner. Use commercially available alcohol. Mounting Direction There are no restrictions to the mounting direction. Precautions for EN61812-1 Conformance The H3CR Series as a built-in timer conforms to EN61812-1 provided that the following conditions are satisfied. Make sure that no voltage is applied to any terminals before dismounting the Timer from the Socket. The output section of the H3CR is provided only with basic isolation. The H3CR itself is designed under the following conditions: • Overvoltage category III • Pollution degree 2 • Isolation Operation parts: Reinforced isolation With clearance of 5.5 mm and creepage distance of 5.5 mm at 230 VAC Output: Basic isolation (See note) With clearance of 3 mm and creepage distance of 3 mm at 230 VAC Note: The 11-pin model ensures basic isolation by itself and also ensures basic isolation with the 11-pin model mounted to the OMRON P2CF-11-@ or P3GA-11 Socket. Connect the two output contacts different in polarity to the loads so that they will be the same in potential. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. 59 : Auxiliary relay, Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. OMRON Corporation Industrial Automation Company Authorized Distributor: Tokyo, JAPAN Contact: www.ia.omron.com Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69-2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC One Commerce Drive Schaumburg, IL 60173-5302 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 OMRON ASIA PACIFIC PTE. LTD. No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711 © OMRON Corporation 2013 All Rights Reserved. OMRON (CHINA) CO., LTD. In the interest of product improvement, Room 2211, Bank of China Tower, specifications are subject to change without notice. 200 Yin Cheng Zhong Road, Printed in Japan PuDong New Area, Shanghai, 200120, China CSM_2_2_0715 Cat. No. L084-E1-07 Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 0613 (0696)