Temperature Controllers
E5CS
CSM_E5CS_DS_E_5_3
Simple Functions in DIN 48 × 48 mm-size
Plug-in Temperature Controllers
• Easy setting using DIP switch.
• Models with two alarms added to Series, ideal for applications
requiring alarms.
• Universal-input (thermocouple/platinum resistance
thermometer) models also available.
• Clearly visible digital display with character height of 13.5 mm.
• RoHS compliant.
Refer to Safety Precautions for All Temperature
Controllers.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Refer to E5CS/E5CSV Operation for
operating procedures.
Model Number Structure
■ Model Number Legend
Plug-in Models
E5CS-@@@@U-W
1 2 3 4 5
3
6
1. Control Outputs
R: Relay
Q: Voltage for driving SSR
2. Alarm Outputs
Blank: No alarm
1:
1 alarm
2:
2 alarms
3. Input
KJ: Thermocouple
P: Platinum resistance thermometer
G: Thermistor
T: Thermocouple/platinum resistance
thermometer (universal-input)
4. Power Supply Voltage
Blank: 100 to 240 VAC
D:
24 VAC/VDC
5. Terminal Shape
U:
Plug-in
6. Case Color
W:
Light gray
Note: A functional explanation is provided here for illustration, but models are not necessarily available for all possible combinations. Refer to
Ordering Information when ordering.
Examples
• Relay control output, without alarm, thermocouple input, plug-in construction, light gray case: E5CS-RKJU-W
• Relay control output, one alarm output, platinum resistance thermometer input, plug-in construction, light gray case: E5CS-R1PU-W
1
E5CS
Ordering Information
■ List of Models
Case Color: Light Gray, Thermocouple or Platinum Resistance Thermometer,
Power Supply Voltage: 100 to 240 VAC
Size
E5CS-U
48 × 48 mm
Type
Plug-in
Control
modes
ON/OFF or
PID
Alarms
0
1
Outputs
Model with
thermocouple
Model with platinum
resistance
thermometer
Relay
E5CS-RKJU-W
E5CS-RPU-W
Voltage (for driving SSR)
E5CS-QKJU-W
E5CS-QPU-W
Relay
E5CS-R1KJU-W
E5CS-R1PU-W
Voltage (for driving SSR)
E5CS-Q1KJU-W
E5CS-Q1PU-W
Case Color: Light Gray, Thermocouple or Platinum Resistance Thermometer,
Power Supply Voltage: 24 VAC/VDC
Size
E5CS-U
48 × 48 mm
Type
Plug-in
Control
modes
ON/OFF or
PID
Alarms
0
1
Outputs
Model with
thermocouple
Model with platinum
resistance
thermometer
Relay
E5CS-RKJDU-W
E5CS-RPDU-W
Voltage (for driving SSR)
E5CS-QKJDU-W
---
Relay
E5CS-R1KJDU-W
E5CS-R1PDU-W
Voltage (for driving SSR)
E5CS-Q1KJDU-W
---
Case Color: Light Gray, Thermistor or Universal-input, Power Supply Voltage: 100
to 240 VAC
Size
E5CS-U
48 × 48 mm
Type
Plug-in
Control
modes
ON/OFF or
PID
Alarms
0
1
2
(See note.)
Outputs
Model with thermistor
Model with universalinput (thermocouple
and platinum
resistance
thermometer)
Relay
E5CS-RGU-W
E5CS-RTU-W
Voltage (for driving SSR)
E5CS-QGU-W
E5CS-QTU-W
Relay
E5CS-R1GU-W
E5CS-R1TU-W
Voltage (for driving SSR)
E5CS-Q1GU-W
E5CS-Q1TU-W
Relay
---
E5CS-R2TU-W
Voltage (for driving SSR)
E5CS-Q2TU-W
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting,
change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller
User’s Manual” (Cat. No. H140-E1-01).
Case Color: Light Gray, Thermistor, Power Supply Voltage: 24 VAC/VDC
Size
E5CS-U
48 × 48 mm
Type
Plug-in
Control
modes
ON/OFF or
PID
Alarms
0
Outputs
Relay
1
Model with thermistor
E5CS-RGDU-W
E5CS-R1GDU-W
■ Accessories (Order Separately)
Socket without Alarm (8 Pins)
Type
Socket with Alarm (11 Pins)
Model
Type
Model
Front Connecting Socket
P2CF-08
Front Connecting Socket
P2CF-11
Back Connecting Socket (flush mounting)
P3G-08
Back Connecting Socket (flush mounting)
P3GA-11
Front Connecting Socket (with finger protection)
P2CF-08-E
Front Connecting Socket (with finger protection)
P2CF-11-E
Finger Safe Terminal Cover for P3G
Y92A-48G
Finger Safe Terminal Cover for P3G
Y92A-48G
Protective Cover
Type
Hard Protective Cover
Model
Y92A-48B
2
E5CS
Specifications
■ Ratings
Supply voltage
100 to 240 VAC, 50/60 Hz
24 VAC, 50/60 Hz; 24 VDC
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
100 to 240 VAC: 5 VA
24 VAC: 3 VA, 24 VDC: 2 W
Sensor input
Thermocouple:
K, J, L
Platinum resistance thermometer:
Pt100, JPt100
Thermistor:
E52-THE@@
Universal-input (thermocouple/platinum resistance thermometer): K, J, L, T, U, N, R, Pt100, JPt100
Control Relay output
SPDT, 250 VAC, 3 A (resistive load)
output Voltage output
12 VDC, 21 mA (with short-circuit protection circuit)
(for driving the SSR)
Control method
ON/OFF or 2-PID (with automatic PID parameter setting function)
Alarm output
SPST-NO, 250 VAC, 1A (resistive load)
Setting method
Digital setting using front panel keys
Indication method
7-segment digital display (character height: 13.5 mm) and deviation indicators
Other functions
•
•
•
•
•
•
Ambient operating
temperature
−10 to 55°C (with no condensation or icing); with 3-year guarantee: −10 to 50°C
Ambient operating humidity
25% to 85%
Storage temperature
−25 to 65°C (with no condensation or icing)
Setting change prohibit (key protection)
Input shift
Temperature unit change (°C/°F)
Direct/reverse operation
Temperature range, Sensor switching (K/J/L, Pt100/JPt100)
Switching is performed between a thermocouple and platinum resistance thermometer for universal-input
models.
• Control period switching
• 8-mode alarm output
• Sensor error detection (excluding thermistor models)
Note: Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)
3
E5CS
■ Characteristics
Setting accuracy
Indication accuracy
(ambient temperature of 23°C)
Influence of temperature
Influence of voltage
Influence of EMS.
(at EN 61326-1)
Thermocouple (See note 1.):
(±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Thermistor (See note 3.):
(1% FS of indication value) ±1 digit max.
R thermocouple inputs:
(±2% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple inputs:
(±2% of PV or ±4°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Thermistor:
(±2% FS) ±1 digit max.
Hysteresis (for ON/OFF control)
0.2% FS (0.1% FS for universal-input (thermocouple/platinum resistance thermometer) models)
Proportional band (P)
1 to 999°C (automatic adjustment using auto-tuning/self-tuning)
Integral time (I)
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Derivative time (D)
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Alarm output range
Absolute-value alarm: Same as the control range
Other:
0 to input setting range full scale (°C or °F)
Alarm hysteresis:
0.2°C or °F (fixed)
Control period
2/20 s
Sampling period
500 ms
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
Vibration
resistance
Shock resistance
2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Malfunction 100 m/s2 min., 3 times each in six directions
Destruction 300 m/s2 min., 3 times each in six directions
Life expectancy
Electrical
100,000 operations min. (relay output models)
Weight
Approx. 110 g (Controller only)
Degree of protection
Front panel: Equivalent to IP50, Enclosure Category 2 (IEC 60529), Rear case: IP20; Terminals: IP00
Memory protection
EEPROM (non-volatile memory) (number of writes: 1,000,000)
EMC
EMI Radiated:
EMI Conducted:
Radiated Electromagnetic Field Immunity:
EN 55011 Group 1 Class A
EN 55011 Group 1 Class A
EN 61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
RF-interference Immunity:
EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
10 V/m (900 MHz pulse modulated)
Conducted Disturbance Immunity:
EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
Noise Immunity (First Transient Burst Noise): EN 61000-4-4
Burst Immunity:
2 kV power-line (level 3), 1 kV I/O signal-line (level 3)
Surge Immunity:
EN 61000-4-5: Power line:
Normal mode 1 kV; Common mode 2 kV
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
Voltage Dip/Interrupting Immunity:
EN 61000-4-11 0.5 cycle, 100% (rated voltage)
Approved standards
UL 61010-1 (listing)
CSA C22.2 No.1010-1
Conformed standards
EN 61326-1 (See note 4.), EN 61010-1, IEC 61010-1
Note: 1. The following exceptions apply to thermocouples.
• U, L: ±2°C ±1 digit max.
• R: ±3°C ±1 digit max. at 200°C or less
2. The following exception applies to platinum resistance thermometers.
• Input set values 1 for E5CS-U: 1% FS ±1 digit max.
3. The following exceptions apply to thermistors.
• When the unit setting is °C, temperature indication ranges exceeding the set temperature range ±10% FS may not be accurate.
• When the unit setting is °F, the temperature range for the input setting numbers 4 and 9 (609 to 630°F) and temperature indication
ranges exceeding the set temperature range −5% FS to +10% FS may not be accurate.
4. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
4
E5CS
■ Temperature Range
Thermocouple Input Models
Input
2 3
7 8
9 0 1
Temperature
range
(selected
using switch)
4 5 6
(Default setting: 2)
1,000
900
800
700
600
500
400
300
200
100
0
Setting number
K
J/L
999
600
500
500
400
400
300
300
200
200
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
Minimum setting unit
1°C
1°C
The shaded value indicates the default
setting status.
Platinum Resistance Thermometer Input Models
2 3
7 8
9 0 1
Temperature
range
(selected
using switch)
4 5 6
(Default setting: 3)
Input
500
400
300
200
100
0
−100
Setting number
Minimum setting unit
JPt100/Pt100
400
300
400
300
200
50
50.0
0.0
80
199.9
99.9
0.0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
1°C
0.1°C
1°C
0.1°C
−50
−20
1°C
0.0
9
0.1°C
The shaded value indicates the default
setting status.
Thermistor Input Models (For details on Sensors, refer to E52.)
Input
2 3
7 8
9 0 1
Temperature
range
(selected
using switch)
4 5 6
(Default setting: 1)
500
400
300
200
100
0
−100
Setting number
G
6 kΩ
(0°C)
6 kΩ
(0°C)
50
100
30 kΩ 550 Ω
4 kΩ
(0°C) (200°C) (200°C)
6 kΩ
(0°C)
6 kΩ
(0°C)
50
100
30 kΩ 550 Ω
4 kΩ
(0°C) (200°C) (200°C)
300
150
150
100
−50
0
0
50
1
2
300
200
150
−50
3
4
Minimum setting unit
5
0
50
6
7
200
100
150
8
9
1°C
The shaded value indicates the default
setting status.
Universal-input (Thermocouple/Platinum Resistance Thermometer) Models
• Using Thermocouple Sensors, Control Mode Switch 5: OFF
Input
2 3
7 8
9 0 1
Temperature
range
(selected
using switch)
4 5 6
(Default setting: 0)
1,700
1,600
1,500
1,400
1,300
1,200
1,100
1,000
900
800
700
600
500
400
300
200
100
0
−100
Setting number
Minimum setting unit
K
J
L
T
U
N
R
1,700
1,300
1,300
850
850
400
199.9
−99
0.0
199.9
−99
0.0
−99
0
1
2
3
1°C
0.1°C
1°C
0.1°C
400
199.9
−99
4
5
1°C
0.0
6
−99
7
0.1°C
−99
8
0
9
1°C
The shaded value indicates the default
setting status.
• Using Platinum Resistance Thermometers, Control Mode Switch 5: ON
Input
2 3
7 8
9 0 1
Temperature
range
(selected
using switch)
4 5 6
(Default setting: 0)
1,000
900
800
700
600
500
400
300
200
100
0
−100
Setting number
Minimum setting unit
Pt100
JPt100
850
500
400
199.9
400
200
199.9
99
−99
0.0
0
1
1°C
0.1°C
−99
2
200
99
0
0
3
4
1°C
−99
5
0.0
6
0.1°C
−99
7
0
0
8
9
1°C
The shaded value indicates the default
setting status.
5
E5CS
External Connection Diagram
Sensor
Plug-in
models
Thermocouple (See note 3.)
Without Voltage output models (See note 1.)
alarms
Platinum resistance thermometer
(See note 3.)
Voltage output models (See note 1.)
Voltage
output
5
Relay output models
Voltage output models (See note 1.)
12 VDC,
21 mA
12 VDC,
21 mA
4
Thermistor
12 VDC,
21 mA
Voltage
output
5
4
Relay output models
Voltage
output
5
4
Relay output models
A
(K, J)
3
3
6
7
2
1
5
4
5
4
B
2
B
1
8
Voltage output models
(See note 1.)
12 VDC, 21 mA
OUT
Two alarm
points
8
9
5
4
Voltage output models
(See note 1.)
Alarm output 1
2
4
Two alarm
points
7
8
8
9
Alarm output 2
B
B
5
4
Relay output models
5 6 7
4
8
3
9
2
10
1 11
A
Voltage output models
(See note 1.)
Alarm output 1
Alarm output
5 6 7
4
8
3
9
2
10
1 11
100 to 240 VAC
24 VAC/VDC
(See note 2.)
12 VDC, 21 mA
OUT
Relay output models
Alarm output
100 to 240 VAC
24 VAC/VDC
(See note 2.)
6
1
7
5
Alarm output 2
Relay output models
7
5
100 to 240 VAC
24 VAC/VDC
(See note 2.)
12 VDC, 21 mA
OUT
7
3
8
100 to 240 VAC
24 VAC/VDC
(See note 2.)
With
alarms
4
6
100 to 240 VAC
24 VAC/VDC
(See note 2.)
Alarm output
5 6 7
4
8
3
9
2
10
1 11
100 to 240 VAC
24 VAC/VDC
(See note 2.)
Note: 1. The voltage output (12 VDC, 21 mA) is not electrically isolated from the internal circuits. When using a grounding thermocouple, do not
connect output terminals 4 or 5 to ground. Otherwise, unwanted current paths will cause measurement errors.
2. Models with 100 to 240 VAC and 24 VAC/VDC are separate. Models using 24 VDC have no polarity.
3. Be sure to check the sensor type before using multi-output (thermocouple/platinum resistance thermometer) models.
Nomenclature
E5CS-U Plug-in Models
Temperature display
Output indicator
Deviation indicators
Alarm indicators
Mode indicators
Mode Key
Up Key
Down key
6
E5CS
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■ Controller
E5CS-U
Terminal Arrangement
(Bottom View)
94.45
(7.75)
6.25
48 × 48
4
5 6 7
4
8
9
3
2
10
1 11
5
3
6
72.5
2
7
1
8
Models without
alarms
44.8 × 44.8
Models with
alarms
Panel Cutout Dimensions
45 +0.6
0
Note: The external dimensions are the same for both models
with and without alarms.
45
+0.6
0
60 min.
L
45+0.6
0
+1
L = (48 × N − 2.5) 0
Mounting side-by-side
(group mounting of N Controllers)
E5CS-U + Adapter for Flush Mounting (Enclosed) + Back Connecting Socket (Order Separately)
(Without Alarms)
Panel
Adapter for
flush mounting
Y92F-30 Adapter for flush mounting
P3G-08
Back Connecting Socket
58
Tightening screws
48
7
95
E5CS-U + Adapter for Flush Mounting (Enclosed) + Back Connecting Socket (Order Separately)
(With Alarms)
Panel
Adapter for
flush mounting
Y92F-30 Adapter for flush mounting
P3GA-11
Back Connecting Socket
58
Tightening screws
48
7
100
Note: Use the P2CF-08 and P3G-08 Sockets for models without alarms, and use the P2CF-11 and P3GA-11 Sockets for models with alarms.
7
E5CS
■ Accessories (Order Separately)
8-pin Sockets without Alarms
P2CF-08 Front Connecting Socket
Eight, M3.5 × 7.5
sems screws
Terminal Arrangement/
Internal Connections
(Top View)
3
7.8
Mounting Hole Dimensions
4.5
6 5 4 3
Two, 4.5-dia. hole or two, M4
Two,
4.5-dia.
holes
40±0.2
70 max.
35.4
Note: DIN Track mounting is also
possible.
7 8 1 2
4
P3G-08 Back Connecting Socket
Note: The P2CF-08-E Socket with finger protection is also available.
50 max.
20.3 max.
27 dia.
Terminal Arrangement
(Bottom View)
7
9
3 4 5 6
45
2 1 8 7
17
45
M3.5
4.9
8
Note: The Y92A-48G Finger Safe Terminal Cover is also available.
11-pin Sockets with Alarms
P2CF-11 Front Connecting Socket
Eleven, M3.5 × 7.5
sems screws
7.8
3
4.5
Terminal Arrangement/
Internal Connections
(Top View)
Mounting Hole Dimensions
8 7 6 5
Two,
4.5-dia.
holes
4
Two, 4.5-dia. mounting holes
70 max.
35.4
40±0.2
9
3
Note: DIN Track mounting is also
possible.
10 11 1 2
50 max.
4
P3GA-11 Back Connecting Socket
31.2 max.
Note: The P2CF-11-E Socket with finger protection is also available.
27 dia.
4
7
Terminal Arrangement
(Bottom View)
3
5 6 7 8
4
25.6
45
3
45
4.5
16.3
9
2 1 11 10
6
6.2
8.7
Note: The Y92A-48G Finger Safe Terminal Cover is also available.
Note: Do not use any other types of Sockets. Doing so will adversely affect the accuracy.
Applicable Thermistors
Hard Protective Cover
Use Element Interchangeable Thermistors (E52-THE5A, E52THE6D, and E52-THE6F) to connect to the E5CS-@GU. For details
on Sensors, refer to E52.
The Y92A-48B Hard Protective Cover is available for the following
applications.
• To protect the set from dust and dirt.
• To prevent the panel from being
accidentally touched causing displacement
of set values.
• To provide effective protection against
water droplets.
92A -48
B
8
E5CS
Safety Precautions
Refer to Safety Precautions for All Temperature Controllers. Refer to E5CS/E5CSV Operation for operating procedures.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
9
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2015.8
In the interest of product improvement, specifications are subject to change without notice.