Smart Power Supply S8AS CSM_S8AS_DS_E_8_1 A New Type of Power Supply That Provides Safety and Maintainability • 240- and 480-W power supplies with and digital circuit protectors in a single package. • Each branch output tripping current value can be easily set at 0.1-A increments. • Startup and shutdown sequence control included. • Various monitor displays and alarms (output voltage, output current, maintenance forecast monitor, temperature). • Conforms to UL Class 2 • Mounts to DIN Rail. For the most recent information on models that have been certified for safety standards, refer to your OMRON website. Refer to Safety Precautions for All Power Supplies and Safety Precautions on page 23. Model Number Structure Model Number Legend S8AS-@@@@@@ 1 2 3 1. Capacity 240: 240 W 480: 480 W 3. Additional Functions Blank: Changeable parameter settings with no communications N: Unchangeable parameter settings with no communications R: Changeable parameter settings with communications (RS-485) 2. Number of Output Branches 06: 6 branch outputs 08: 8 branch outputs Ordering Information S8AS Capacity Input voltage Output voltage Maximum cutoff output current (per branch) 240 W 10 A 100 to 240 VAC 480 W Total output current 24 V Number Communications of output functions branches 6 branch outputs 3.8 A 20 A 8 branch outputs Parameter settings Model None Changeable S8AS-24006 None Not changeable S8AS-24006N RS-485 Changeable S8AS-24006R None Changeable S8AS-48008 None Not changeable S8AS-48008N RS-485 Changeable S8AS-48008R Be sure to read and fully understand the content of the S8AS User's Manual (Cat. No. Z269) before changing settings on the S8AS. 1 S8AS Specifications S8AS-24006@ Item 100 to 240 VAC (85 to 264 VAC) Frequency *1 50/60 Hz (47 to 63 Hz) Output conditions 100-V input 3.8 A max. 200-V input 2.0 A max. Power factor EN61000-3-2 100-V input 0.5 mA max. 200-V input 1.0 mA max. Inrush current 100-V input *2 200-V input 25 A max. (for a cold start at 25°C) Number of branches 6 Maximum cutoff output current (per branch) 3.8 A Total output current 10 A Allowable voltage range *3 ±10% (with V.ADJ) Ripple noise voltage 2.0% [P-P] max. (for rated input and output voltage) *4 Output leakage current 10 mA max. Input fluctuation 0.5% max. (Input: 85 to 264 VAC, 100% load) *5 Load fluctuation (rated input voltage) 4.0% max. (rated input, 0% to 100% load) *5 50 A max. (for a cold start at 25°C) Temperature fluctuation 0.05%/°C max. Startup time *2 3,000 ms max. (for rated input and output voltage) *4 Output hold time *2 20 ms max. (for rated input and output voltage) *4 Abnormal voltage tripping 28.8 V (Cannot be changed.) Abnormal current tripping *2 Setting range: 0.5 to 3.8 A (in 0.1-A increments) Abnormal total current tripping Branch outputs are cut off when the total output current is more than 17 A for 2 s, 15 A for 5 s, 13 A for 10 s, or 12 A for 20 s. Tripping alarm output Photoswitch output 30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max. Undervoltage detection functions Undervoltage detection Setting range: 18.0 to 26.4 V (in 0.1-V increments) Undervoltage detection output Photoswitch output 30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max. Maintenance forecast monitor function Maintenance forecast monitor Setting range: 0.0 to 5.0 yr (in 0.5-yr increments) Maintenance forecast monitor output Photoswitch output 30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max. Overtemperature detection function Over-temperature Setting range: 25 to 90°C (in 1°C increments) Over-temperature output Photoswitch output 30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max. Output voltage display Display range:17.0 to 30.0 V Display accuracy: 2% rdg ±1 digit max. Output current display Branch output display range: 0.0 to 4.0 A Peak output current display range: 0.0 to 20.0 A Total current display range: 0.0 to 40.0 A Display accuracy: 5% FS (4 A) ±1 digit max. Maintenance forecast monitor display Display range: FUL (Full)/HLF (Half)/0.0 to 5.0 yr Temperature display Display range: −20 to 100°C Display accuracy: 2°C ±1 digit max. Tripping functions Display functions Functions S8AS-24006R 0.95 min. Harmonic current Leakage current S8AS-24006N 80% min. Voltage range *1 Current Input conditions S8AS-24006 Model Efficiency (Typ.) 3.8 A (Cannot be changed.) 20.0 V (Cannot be changed.) 0.5 yr (Cannot be changed.) 90°C (Cannot be changed.) Setting range: 0.5 to 3.8 A (in 0.1-A increments) Setting range: 18.0 to 26.4 V (in 0.1-V increments) Setting range: 0.0 to 5.0 yr (in 0.5-yr increments) Setting range: 25 to 90°C (in 1°C increments) The input can be enabled or disabled for each branch output. 19.2 to 30.0 VDC, minimum signal width: 10 ms, tripping after input within 20 ms + the shutdown sequence set time All branch outputs: Enabled (Cannot be changed.) 19.2 to 30.0 VDC, minimum signal width: 10 ms, tripping after input within 20 ms + the shutdown sequence set time The input can be enabled or disabled for each branch output. 19.2 to 30.0 VDC, minimum signal width: 10 ms, tripping after input within 20 ms + the shutdown sequence set time Startup sequence Setting range: 0.0 to 99.9 s in 0.1-s increments Branch output 1: 0.0 s (Cannot be changed.) Branch output 2: 0.4 s (Cannot be changed.) Branch output 3: 0.8 s (Cannot be changed.) Branch output 4: 1.2 s (Cannot be changed.) Branch output 5: 1.6 s (Cannot be changed.) Branch output 6: 2.0 s (Cannot be changed.) Setting range: 0.0 to 99.9 s in 0.1-s increments Shutdown sequence Setting range: 0.0 to 99.9 s in 0.1-s increments All branch outputs: 0.0 s (Cannot be changed.) Setting range: 0.0 to 99.9 s in 0.1-s increments Communications Not supported Sampling period 1 ms Parallel connection Not supported Series connection Not supported External Tripping Input Supported (RS-485) Note: Refer to the next page for information on *1 to *5. 2 S8AS Item Others Model S8AS-24006 S8AS-24006N S8AS-24006R Ambient operating temperature Refer to the derating curve (no icing or condensation). *2 Storage temperature −25 to 65°C Ambient operating humidity 25% to 85% (storage: 25% to 90%) Withstand voltage 3.0 kVAC for 1 min between all input terminals collectively and all branch output, all I/O signal, and all communications terminals collectively (Detection current: 20 mA) 2.0 kVAC for 1 min between all inputs and protective earth (Detection current: 20 mA) 1.0 kVAC for 1 min between protective earth and all branch output, all I/O signal, and all communications terminals collectively (Detection current: 20 mA) 500 VAC for 1 min between all branch output and all I/O signal/communications terminals collectively (Detection current: 20 mA) 500 VAC for 1 min between all I/O signal terminals collectively and communications terminals collectively (Detection current: 20 mA) 500 VAC for 1 min between all I/O signal terminals collectively and all output signal terminals collectively (detection current: 20 mA) Insulation resistance 100 MΩ min. at 500 VDC between the protective earth terminal or all input terminals collectively and all branch output, all I/O signal, and all communications terminals collectively Vibration resistance No abnormality after 10 to 55 Hz at 0.375-mm single amplitude for 2 h each in 3 directions. Shock resistance No abnormality after 150 m/s2 3 times each in 6 directions. Output indicator Provided (Color: green) Conducted EMI Conforms to EN 61204-3 Class A and FCC Class A. Radiated EMI Conforms to EN 61204-3 Class A. Safety standards cULus: UL508 (Listing. Class2: Per UL1310), CSA C22.2 No.107.1 (Class2: Per CSA C22.2 No.223) cURus: UL60950-1, CSA C22.2 No.60950-1 EN: EN50178, EN60950-1 VDE: VDE0160, VDE0805 Teil1 SEMI standard SEMI F47-0706 (200 VAC input) Weight 1,600 g max. *1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. *2. Refer to Engineering Data on page 8 for details. *3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than 10% of the voltage adjustment range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. If the output voltage exceeds 28.8 V, all branch outputs will be cut off. *4. Rated input and output conditions: Rated input voltage, rated frequency, rated output voltage, rated total output current, and maximum cutoff output current. *5. 100% load conditions: Rated output voltage, rated total output current, and maximum cutoff output current. 3 S8AS S8AS-48008@ Item Model Efficiency (Typ.) Voltage range *1 100 to 240 VAC (85 to 264 VAC) Frequency *1 50/60 Hz (47 to 63 Hz) Current Input conditions 100-V input 7.4 A max. 200-V input 3.9 A max. Power factor S8AS-48008N S8AS-48008R 0.95 min. Harmonic current Leakage current Output conditions S8AS-48008 80% min. EN61000-3-2 100-V input 0.5 mA max. 200-V input 1.0 mA max. Inrush current 100-V input *2 200-V input 25 A max. (for a cold start at 25°C) Number of branches 8 Maximum cutoff output current (per branch) 3.8 A Total output current 20 A Allowable voltage range *3 ±10% (with V.ADJ) Ripple noise voltage 2.0%[P-P] max. (for rated input and output voltage) *4 Output leakage current 10 mA max. Input fluctuation 0.5% max. (Input: 85 to 264 VAC, 100% load) *5 Load fluctuation (rated input voltage) 4.0% max. (rated input, 0% to 100% load) *5 50 A max. (for a cold start at 25°C) Temperature fluctuation 0.05%/°C max. Startup time *2 3,000 ms max. (for rated input and output voltage) *4 Output hold time *2 20 ms min. (for rated input and output voltage) *4 Abnormal voltage tripping 28.8 V (Cannot be changed.) Abnormal current tripping *2 Setting range: 0.5 to 3.8 A (in 0.1-A increments) Abnormal total current tripping Branch outputs are cut off when the total output current is more than 27 A for 1 s, 25 A for 2 s, or 22.5 A for 5 s. Tripping alarm output Photoswitch output 30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max. Undervoltage detection functions Undervoltage detection Setting range: 18.0 to 26.4 V (in 0.1-V increments) Undervoltage detection output Photoswitch output 30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max. Maintenance forecast monitor function Maintenance forecast monitor Setting range: 0.0 to 5.0 yr (in 0.5-yr increments) Maintenance forecast monitor output Photoswitch output 30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max. Overtemperature detection function Over-temperature Setting range: 25 to 90°C (in 1°C increments) Over-temperature output Photoswitch output 30 VDC max. and 50 mA max., Leakage current: 0.1 mA max., Residual voltage: 2 V max. Output voltage display Display range:17.0 to 30.0 V Display accuracy: 2% rdg ±1 digit max. Output current display Branch output display range: 0.0 to 4.0 A Peak output current display range: 0.0 to 20.0 A Total current display range: 0.0 to 40.0 A Display accuracy: 5% FS (4 A) ±1 digit max. Tripping functions Display functions 3.8 A (Cannot be changed.) 20.0 V (Cannot be changed.) 0.5 yr (Cannot be changed.) 90°C (Cannot be changed.) Setting range: 0.5 to 3.8 A (in 0.1-A increments) Setting range: 18.0 to 26.4 V (in 0.1-V increments) Setting range: 0.0 to 5.0 yr (in 0.5-yr increments) Setting range: 25 to 90°C (in 1°C increments) Maintenance forecast monitor display Display range: FUL (Full)/HLF (Half)/0.0 to 5.0 yr Functions Temperature display Display range: −20 to 100°C Display accuracy: 2°C ±1 digit max. The input can be enabled or disabled for each branch output. 19.2 to 30 VDC, minimum signal width: 10 ms, tripping after input within 20 ms + the shutdown sequence set time All branch outputs: Enabled (Cannot be changed.) 19.2 to 30 VDC, minimum signal width: 10 ms, tripping after input within 20 ms + the shutdown sequence set time The input can be enabled or disabled for each branch output. 19.2 to 30 VDC, minimum signal width: 10 ms, tripping after input within 20 ms + the shutdown sequence set time Startup sequence Setting range: 0.0 to 99.9 s in 0.1-s increments Branch output 1: 0.0 s (Cannot be changed.) Branch output 2: 0.4 s (Cannot be changed.) Branch output 3: 0.8 s (Cannot be changed.) Branch output 4: 1.2 s (Cannot be changed.) Branch output 5: 1.6 s (Cannot be changed.) Branch output 6: 2.0 s (Cannot be changed.) Branch output 7: 2.4 s (Cannot be changed.) Branch output 8: 2.8 s (Cannot be changed.) Setting range: 0.0 to 99.9 s in 0.1-s increments Shutdown sequence Setting range: 0.0 to 99.9 s in 0.1-s increments All branch outputs: 0.0 s (Cannot be changed.) Setting range: 0.0 to 99.9 s in 0.1-s increments Communications Not supported Sampling period 1 ms Parallel connection Not supported Series connection Not supported External Tripping Input Supported (RS-485) Note: Refer to the next page for information on *1 to *5. 4 S8AS Item Others Model S8AS-48008 S8AS-48008N S8AS-48008R Ambient operating temperature Refer to the derating curve (no icing or condensation). *2 Storage temperature −25 to 65°C Ambient operating humidity 25% to 85% (storage: 25% to 90%) Withstand voltage 3.0 kVAC for 1 min between all input terminals collectively and all branch output, all I/O signal, and all communications terminals collectively (Detection current: 20 mA) 2.0 kVAC for 1 min between all inputs and protective earth (Detection current: 20 mA) 1.0 kVAC for 1 min between protective earth and all branch output, all I/O signal, and all communications terminals collectively (Detection current: 30 mA) 500 VAC for 1 min between all branch output and all I/O signal/communications terminals collectively (Detection current: 20 mA) 500 VAC for 1 min between all I/O signal terminals collectively and communications terminals collectively (Detection current: 20 mA) 500 VAC for 1 min between all I/O signal terminals collectively and all output signal terminals collectively (detection current: 20 mA) Insulation resistance 100 MΩ min. at 500 VDC between the protective earth terminal or all input terminals collectively and all branch output, all I/ O signal, and all communications terminals collectively Vibration resistance No abnormality after 10 to 55 Hz at 0.375-mm single amplitude for 2 h each in 3 directions. Shock resistance No abnormality after 150 m/s2 3 times each in 6 directions. Output indicator Provided (Color: green) Conducted EMI Conforms to EN 61204-3 Class A and FCC Class A. Radiated EMI Conforms to EN 61204-3 Class A. Safety standards (pending) cULus: UL508 (Listing. Class2: Per UL1310), CSA C22.2 No.107.1 (Class2: Per CSA C22.2 No.223) cURus: UL60950-1, CSA C22.2 No.60950-1 EN: EN50178, EN60950-1 VDE: VDE0160, VDE0805 Teil1 SEMI standard SEMI F47-0706 (200 VAC input) Weight 2,400 g max. *1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. *2. Refer to Engineering Data on page 8 for details. *3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than 10% of the voltage adjustment range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. If the output voltage exceeds 28.8 V, all branch outputs will be cut off. *4. Rated input and output conditions: Rated input voltage, rated frequency, rated output voltage, rated total output current, and maximum cutoff output current. *5. 100% load conditions: Rated output voltage, rated total output current, and maximum cutoff output current. 5 S8AS Connections Block Diagrams S8AS-24006@ (S8AS-24006R only) RS-485 A (−) B (+) Communications circuit TRP Voltage Temperature Switches detection detection LOW Display circuit LFE Processing circuit (main processing) TMP COM Communications between processing circuits (RS-232C) TRG+ TRG− Branch output 6 Branch output 5 Branch output 4 Rectification and smoothing Branch output 3 Branch output 2 Branch output 1 Current limiting circuit Current- Processing circuit (replacement time) SCREW (M3.5) AC (L) Fuse: 8A INPUT AC (N) Cutoff detection circuit resistor Thermal fuse Noise filter Rectifi- Inrush Harmonic current Smoothing cation current suppression circuit limit (Power factor improvement) Current fuse Cutoff circuit +V DC OUTPUT Currentdetection resistor −V −V Rectification and smoothing SCREW (M4) Drive control circuit Power supply detection Voltage-ON detection Photocoupler (S8AS-48008R only) S8AS-48008@ RS-485 Communications circuit A (−) B (+) TRP LOW Display Voltage Temperature detection detection Switches circuit LFE Processing circuit (main processing) TMP Communications between processing circuits (RS-232C) COM TRG+ TRG− Branch output 8 Branch output 7 Branch output 6 Branch output 5 Branch output 4 Branch output 3 Branch output 2 Branch output 1 SCREW (M3.5) INPUT AC (N) Current limiting circuit Cutoff circuit Current- Cutoff detection circuit resistor AC (L) Fuse: 12 A Noise filter Rectifi- Inrush Harmonic current Smoothcation current suppression circuit ing limit (Power factor improvement) Rectification and smoothing Thermal fuse Currentdetection resistor Current fuse +V DC OUTPUT −V −V SCREW (M4) Voltage-ON detection Control circuits Drive circuit Processing circuit Voltage detection Current detection Current-ON detection Auxiliary power Rectification supply circuit and smoothing 6 S8AS Constructions and Nomenclature Nomenclature S8AS-24006@ No. 1 9 2 AC Input Terminals (L and N) 2 Protective Earth (PE) Terminal ( 10 11 3 Positive Branch Output Terminals (+) Screwless terminals with 2-pole terminals for each branch output. 12 4 Negative Branch Output Terminals (−) Screwless terminals with 2-pole terminals for each branch output and screw terminal shared by the negative branch output terminals. S8AS-24006 A(-) N 1 +1 DC ON 5 2 3 4 5 6 +V -V -V +2 +3 +4 +5 3 +6 -1 -2 -3 -4 -5 -6 7 4 S8AS-48008@ 1 9 2 13 5 S8AS-48008 POWER SUPPLY L Tripping Alarm (A) Output (TRP) *3 Turns ON to indicate when an abnormal voltage or current was detected and the output was cut off. (The photoswitch output will turn OFF.) Undervoltage (B) Detection Output (LOW) Turns ON to indicate when the 24VDC output voltage of the S8AS falls below the threshold due to decrease in input voltage or other factors. (The photoswitch output will turn OFF.) Maintenance (C) Forecast Monitor Output (LFE) Turns OFF to indicate when the number of years to the set replacement time has been reached. (The photoswitch output will turn OFF.) V.ADJ TRP LOW LFE TMP COM + TRG - 6 V A Yrs °C s 1 2 3 4 5 6 INPUT 50/60Hz AC100-240V 3.8A ) Connects to the ground wire. *2 8 B(+) RS485 Class2 OUTPUT DC 24V 3.8A Functions Connects the input power supply (100 to 240 VAC, 50/60 Hz) (commercial power supply). *1 1 POWER SUPPLY L Name 13 A(-) N 8 B(+) RS485 INPUT 1 2 3 4 5 6 7 8 V A Yrs °C s 50/60Hz AC100-240V 7.4A 1 Class2 OUTPUT DC 24V 3.8A DC ON 2 3 4 5 6 7 8 10 11 (D) 12 +V +1 +2 +3 +4 +5 +6 -1 -2 -3 -4 -5 -6 +7 +8 Over-temperature Output (TMP) Negative Common (E) Terminal (COM) (no polarity) -V -V I/O Signal Terminals 3 Turns ON to indicate that the temperature exceeded the overtemperature output threshold. (The photoswitch output will turn OFF.) Negative common shared by the four alarm outputs ((A) to (D)) above. Positive External Tripping Input (TRG+) Can be used to send an input signal from an external device to Negative External cut off a branch output. *4 (G) Tripping Input (TRG−) V.ADJ (F) TRP LOW LFE TMP COM + TRG - 5 6 7 5. I/O Signal Terminal Internal Circuit Configuration Photoswitch -7 -8 4 Output Indicator (DC ON (Green)) Indicates whether there is output voltage supplied. 7 Output Voltage Adjuster (V.ADJ) Adjusts the output voltage. 8 Seven-segment Display (Red) Displays measured values or set values. 9 Branch Output Indicators (Orange) Light or flash when there is a display related to branch output (outputs 1 to 6 and 8). *5 6 10 Unit Indicators (Orange) Light or flash when there is a unit (e.g., V, A, Yrs, °C, s) related to the value shown on the 7-segment display. 11 Status indicators (Red/Green) Indicate the status of the branch outputs: Cutoff: red, Connected: green. *6 TRP LOW LFE TMP COM + TRG - 12 Reset (RST) Key Used to clear the error status when a branch output was cut off by an error or there was an alarm output. Enter (ENT) Key Used to switch the display item, enter or execute settings, etc. Operation Keys Up (SEL) Key (A) (B) (C) (D) (E) (F) (G) Down (CH) Key 13 Communications Terminals (A (−), B (+)) (Only for Models That Support Communications) Used to change the display item forward or to increase a set value. Used to switch the branch output or to decrease a set value.The branch output number that is set remains the same in other modes. Used to connect to the RS-485 communications line. Note: The noise value depends on the wiring method and other factors. Insert a clamp filter (recommended: E04SR301334 manufactured by SEIWA) on the communications wiring as a countermeasure against noise. *1. The fuse is located on the (L) side. *2. This is the protective earth terminal specified in the safety standards. Always ground this terminal. *3. In Test Mode, the tripping alarm output (TRP) will operate even if one or more of the branch outputs is set to OFF. This error output, however, will not be held when operation moves to another operating mode. *4. Wire the polarity of the external tripping input correctly. After completing wiring, confirm that the input operates correctly. *5. The branch output indicators are OFF when current is not used. *6. 6.Information on procedures for detailed displays is given in Status Indicators on page 16. 7 S8AS Engineering Data Load rate (%) Total output current Derating Curve Extended Detection Time (ms) 120 Setting range 100 Tripping region Currentlimiting by internal circuits 1 1,000 80 60 60 40 20 3.8 0.5 20 11 16 19 Branch output (A) 0 −20 −10 0 10 20 30 40 50 60 70 80 Ambient temperature (°C) Note: 1. Internal parts may occasionally be deteriorated or damaged. Do not use the S8AS in areas outside the derating curve (i.e., in the area shown by shading A in the above graph). 2. Use forced cooling if necessary to satisfy the derating curve. 3. For 480-W models, reduce the load to 80% or less for longterm use at an input voltage of 95 VAC or less. Abnormal Current Tripping Standard Detection Tripping Performance The S8AS detects the current of branch outputs as digital values and numeric processing is performed to execute cutoff operations. Refer to Abnormal Current Tripping for the tripping performance. The following cutoff functions are also provided. Judgment Type Selection Standard, instantaneous, or extended can be set as the method for detecting the tripping current. With the S8AS-24006N/48008N, only the extended detection is supported. Refer to the S8AS User's Manual (Cat. No. Z269) for the setting method. Current Limit Time (ms) This function is provided to limit excessive short currents, such as those that can flow for equipment short faults. Setting range Currentlimiting by internal circuits Tripping region 100 Startup Delay This function is provided to disable cutoff operations for 40 ms after the branch outputs turn ON so that cutoff operations will not occur for large inrush currents. Safety Circuits 60 Temperature fuses and current fuses are provided for each branch output to ensure safety even in the unusual event of an internal failure. 20 0.5 3.8 11 16 19 Branch output (A) Mounting Instantaneous Detection Standard Mounting Face-up Mounting Time (ms) S8AS-24006 POWER SUPPLY A(-) L N 1 2 3 4 5 6 INPUT Currentlimiting by internal circuits DC ON 20 19 Branch output (A) 2 V A Yrs °C s 3 4 5 6 +V Class2 OUTPUT DC 24V 3.8A -V -V +1 +2 +3 +4 +5 +6 -1 -2 -3 -4 -5 -6 V.ADJ TRP LOW LFE TMP COM + TRG - 3.8 1 50/60Hz AC100-240V 3.8A Tripping region 0.5 B(+) RS485 Setting range Note: 1. The above illustration shows a 240-W model. 2. Poor heat dissipation resulting from improper installation conditions may occasionally deteriorate or damage internal parts and also cause the maintenance forecast monitor function to not operate properly. Do not use any mounting orientation other than a standard one. Inrush Current, Startup Time, Output Hold Time Input ON Input OFF AC input voltage Inrush current on input application AC input current 96.5% 90% Output voltage Startup time (3,000 ms max.) Hold time (20 ms min.) 8 S8AS Functions Functions Alarm Alarm output Output status Alarm display Abnormal voltage tripping TRP output: OFF (normally ON) All branch outputs cut off. A10 Abnormal current tripping TRP output: OFF (normally ON) Relevant branch output cut off. A11 Abnormal total current tripping (240-W models only) TRP output: OFF (normally ON) All branch outputs cut off. A12 Undervoltage detection LOW output: OFF (normally ON) ON A21 Maintenance forecast monitor LFE output: OFF (normally ON) ON A23 Overheating alarm LFE output: OFF (normally ON) ON A23/HOT Over-temperature TMP output: OFF (normally ON) ON A30 Tripping Functions Function Operation Abnormal voltage tripping Refer to Chart 1. *1, *2, *3 The output voltage is monitored and all branch outputs are cut off if the detection voltage is reached. Notification of the status is provided using the alarm display and the tripping alarm output (TRP). The alarm display will alternate between the voltage and the alarm code (A10). Detection voltage: 28.8 V (fixed) The output current is monitored and the branch output that is abnormal is cut off if the preset current is reached. Notification of the status is provided using the alarm display and the tripping alarm output (TRP). The alarm display will alternate between the current and the alarm code (A11). Setting range: 0.5 to 3.8 A (in 0.1-A increments). The S8AS-24006N and S8AS-48008N are set to 3.8 A. (Cannot be changed.) Abnormal One of the following three abnormal current tripping types can be set. With the S8AS-24006N/48008N, only the standard detection is supported. current tripping Refer to Chart 2. Standard Detection: Tripping within 100 ms. (Abnormal current will be detected and the output will be cut off within 20 ms if *1, *2 current continuously exceeds the set value for more than 80 ms.) Instantaneous Detection: Tripping within 20 ms. (Abnormal current will be detected and the output will be cut off within 10 ms if current continuously exceeds the set value for more than 10 ms.) Extended Detection: Tripping within 1,000 ms. (Abnormal current will be detected and the output will be cut off within 20 ms if current continuously exceeds the set value for more than 980 ms.) Abnormal total current tripping *1, *2 Using the abnormal total current tripping function, the S8AS monitors the total output current and when the total output current exceeds the set value, all branch outputs are cut off. Notification of the status is provided using the alarm display and the tripping alarm output (TRP). The error code A12 will be shown on the display. There are a number of conditions for the tripping current and time. If even one of these conditions is detected, the abnormal total current tripping function will be activated. 240 W: Branch outputs are cut off when the total output current is more than 17 A for 2 s, 15 A for 5 s, 13 A for 10 s, or 12 A for 20 s. 480 W: Branch outputs are cut off when the total output current is more than 27 A for 1 s, 25 A for 2 s, or 22.5 A for 5 s. The output can be cut off by inputting a voltage to the external tripping input (TRG terminal). If a shutdown sequence has been set, outputs will be cut off according to the shutdown sequence. Each branch output can be enabled or disabled individually. On the S8AS-24006N/S8AS-48008N, all branch outputs are enabled. (Cannot be changed.) External tripping External input signal width: 10 ms min. input Input signal levels *1 High level: 19.2 to 30 VDC Low level: 0 to 2.5 VDC Tripping can also be performed by using communications (S8AS-24006R/S8AS-48008R only). Refer to the S8AS User's Manual (Cat. No. Z269) for information on tripping using communications. Note: Three abnormal current tripping types with different tripping current characteristics are supported: standard detection, instantaneous detection, and extended detection. Select the required tripping type. *1. Outputs are cut off using semiconductor relays and electrical insulation is not provided. *2. With the default settings, the alarm display and alarm output can be cleared using one of the following methods. • Clear using the reset operation. • Clear by turning the supply power OFF and ON again. *3. The voltage detection is performed on the voltage after AC/DC conversion in the internal circuits. The displayed voltage will be somewhat different from the value at the output terminals of the power source due to internal voltage drop. To confirm correct output voltages, measure the voltages at the branch output terminals. 9 S8AS Chart 1: Operation Timing Chart 2: Operation Timing (Fixed) 28.8 V (Abnormal voltage tripping) 24 V (Rated) (Settable) 3.8 A (Abnormal current tripping) 3.0 A (Normal current) 20 V (undervoltage detection) (Settable) 0 100 ms 0 t A21 Alarm display t A10 Tripping alarm output * Undervoltage detection output * 20 ms Tripping alarm output * A11 Alarm display Within 20 ms for instantaneous detection and 100 ms for standard detection, or within 1000 ms for extended detection (depends on tripping type). * The tripping alarm output is a photoswitch output. The output is normally ON and turns OFF when an alarm is detected. Reset * The undervoltage detection output and tripping alarm output are both photoswitch outputs. The output is normally ON and turns OFF when an alarm is detected. Alarm Functions Function Operation Undervoltage detection output (Refer to Chart 1.) *1, *2 The voltage is monitored and notification is provided using the alarm display and output (LOW) if the preset voltage is exceeded for more than 80 ms. The alarm display will alternate between the voltage and the alarm code (A21). Undervoltage detection threshold setting range: 18.0 to 26.4 V in 0.1-V increments.The S8AS-24006N and S8AS-48008N are set to 20.0 V. (Cannot be changed.) Maintenance forecast monitor *1 The time that the power is ON is calculated as the S8AS run time and notification is provided using the alarm display and maintenance forecast monitor output (LFE) if the preset time is reached. The alarm display will alternate between the run time and the alarm code (A23). Display range: FUL (Full), HLF (Half), or 0.0 to 5.0 years. The internal temperature of the S8AS is monitored using a built-in temperature sensor and notification is provided using the alarm display and over-temperature output (TMP) if the preset temperature is exceeded for more than 1 s. The alarm display will alternate between the temperature and the alarm code (A30). The over-temperature output is convenient for control Over-temperature operations, such as operating a cooling fan to suppress temperature increased in the control panel. (Refer to Chart 3.) Note: The alarm display and over-temperature output are automatically cleared if the temperature falls below the set *1 temperature. Display range: −20 to 100°C in 1°C increments. Temperature setting range: 25 to 90°C in 1°C increments. Note: 1. Branch outputs are not cut off for the alarm functions 2. The voltage detection is performed on the voltage after AC/DC conversion in the interval circuits. The displayed voltage will be somewhat different from the value at the output terminals of the power source due to internal voltage drop. To confirm correct output voltages, measure the voltages at the branch output terminals. Chart 3: Operation Timing Temperature 50°C (Settable) 0 Alarm display t A30 A30 A30 Temperature * * The alarm display and over-temperature output are automatically cleared (with hysteresis). The over-temperature output is a photoswitch output. It is normally ON and turns OFF when an alarm is detected. 10 S8AS Maintenance Forecast Monitor Function Indication and Output Example: Display When the Time Remaining to the Maintenance Time Is Less Than 0.5 yr When the Product is purchased, “ful” will be displayed. As the electrolytic capacitors deteriorate, the display will change to “hlf” (Refer to Maintenance Forecast Monitor Function). “ful” will be displayed for the maintenance forecast display for approximately one month after the Power Supply is first turned ON. The accumulated value will then be displayed depending on the ambient conditions. (However, the “hlf” display may not appear, depending on the application environment and the set value for maintenance forecast.) If the maintenance forecast setting L (which can be set to 0.0 to 5.0 years in 0.5-year increments) is set to a value larger than two years, the display automatically changes to a value (L - 0.5) after the remaining time to maintenance is reduced to the set number of years, and an alarm (A23) and the remaining time will be displayed alternately. If the setting is less than 2.0 years, the display changes to a value (1.5) after the remaining time becomes less than two years, and after the remaining time becomes less than the set time, an alarm (A23) and the remaining time (L - 0.5) will be displayed alternately. If the alarm (A23) and a numeric value are displayed alternately, the transistor (maintenance forecast output terminal (Yrs)) will turn OFF to indicate the need for maintenance., i.e., there will be no continuity at the maintenance forecast output terminals. (The LEF output will turn OFF when the maintenance time has been reached.) 1 2 3 4 5 6 V A Yrs °C s 1 2 3 4 5 6 V A Yrs °C s Note: 1. The time remaining to maintenance is based on continuous operation, not including the time when the power supply is turned OFF. 2. “ful” will be displayed until approximately one month of time has passed to enable estimating the speed of deterioration. The output will remain ON (i.e., there will be continuity at the maintenance forecast output terminal (Yrs)). 3. For details on the display, refer to Relationship between Displayed Values and Output of Set Values. Maintenance Forecast Monitor Function The Power Supply is equipped with electrolytic capacitors. The electrolyte inside the electrolytic capacitors penetrates the sealing rubber and evaporates as time passes after it is manufactured. This causes deterioration of characteristics, such as decreasing the capacitance. Due to this deterioration of the characteristics of the electrolytic capacitor, the Power Supply decreases its performance as time passes. The maintenance forecast monitor function shows an approximate period left for maintenance of the Power Supply due to deterioration of electrolytic capacitors. When the period left for maintenance that the power supply forecasts reaches the set value, an alarm is indicated and an output signal is triggered. Use this function to know the approximate replacement timing of the Power Supply. Note: The maintenance forecast monitor function indicates an approximate period left for maintenance, based on deterioration of the electrolytic capacitors. It does not predict failures resulting from other causes. Relationship between Displayed Values and Output of Set Values L: Maintenance forecast set value 0.0 to 5.0, 0.5 steps When L is set to between 2.5 and 5 years. Initial capacity (L − 0.5) "1.0" is displayed on the main display for the duration that the maintenance forecast up to replacement satisfies the condition 1.0 ≤ T < 1.5. Capacity at replacement time Electrolytic capacitor capacity 5.0 Main display 2.5 2.0 1.5 1.0 0.5 0 T: Maintenance time until replacement L = 2.5 Maintenance forecast monitor output L = 0.5 1 2 3 4 5 6 V A Yrs °C s 1 2 3 4 5 6 V A Yrs °C s 1 2 3 4 5 6 V A Yrs °C s 1 2 3 4 5 6 V A Yrs °C s The numeric value decreases with time. 11 S8AS Principle of Operation Difference between Expected Life and Replacement Time The deterioration speed of the electrolytic capacitors varies considerably with the ambient temperature. (Generally the speed follows the Arrhenius Law, i.e., for every 10°C increase in the temperature, the rate of degradation doubles.) The S8AS monitors the temperature inside the Power Supply, and calculates the amount of deterioration according to the operating hours and internal temperature. OMRON calculates the expected life based on the following conditions. 1. Rated input voltage 2. Load rate: 50% 3. Ambient temperature: 40°C 4. Standard Mounting Based on this amount of deterioration, the Power Supply will provide an alarm indication and output when the period left for maintenance reaches the set value. Note: 1. Due to degradation of internal electronic parts, replace the Power Supply approximately 15 years after purchase even if the maintenance forecast monitor indication and output do not appear. 2. The maintenance forecast is accelerated or decelerated according to operating conditions. Periodically check the display. 3. Acceleration or deceleration of the maintenance forecast may cause the output to repeatedly go ON and OFF. 4. The accuracy of the maintenance forecast function may be adversely affected by applications in which the AC input is frequently turned ON and OFF. Note: The expected life is calculated by performing a temperature rise test using an aluminum electrolytic capacitor, and therefore is not a guaranteed value. The expected life span of the S8AS is 10 years. The maintenance forecast is the service life (the Power Supply's internal temperature is monitored at all times) of the internal electrolytic capacitors in actual operating conditions, and depends on the customer's operating conditions. The maximum period of the maintenance forecast is taken as 15 years. Other Functions Function Operation Startup sequence (Refer to Chart 5.) The connection timing for branch outputs 1 to 6 and 8 can be set individually to offset the connection timing to the load devices. Creating time delays between starting loads enables safer load operation. It also reduces total inrush current so that power supply capacity can be optimized. Setting range: 0.0 to 99.9 s in 0.1-s increments. For the S8AS-24006N and S8AS-48008N, the settings are 0.0 s for branch output 1, 0.4 s for branch output 2, 0.8 s for branch output 3, 1.2 s for branch output 4, 1.6 s for branch output 5, 2.0 for branch output 6, 2.4 s for branch output 7, and 2.8 s for branch output 8. (Cannot be changed.) * Shutdown sequence (Refer to Chart 6.) The cutoff timing for branch outputs 1 to 6 and 8 can be set individually to offset the cutoff timing of load devices for the external tipping input or to enable an emergency stop. Setting range: 0.0 to 99.0 s in 0.1-s increments. For the S8AS-24006N and S8AS-48008N, all branch outputs have a setting of 0.0 s. (Cannot be changed.) * Startup Delay A delay function is provided so that the abnormal current tripping function or overcurrent alarm function will not be triggered by large initial inrush currents, e.g., for capacitive loads or lamp loads. The abnormal current tripping function will function once the set time has elapsed. (Note: The delay is 40 ms and cannot be changed.) Current Alarm function disabled for large inrush currents at startup. 0 t 40 ms: Delay * The sequencing functions are designed for the six branch outputs of one S8AS. There is no synchronization processing between S8AS Power Supplies when more than one S8AS is used. Sequencing functions for branch outputs 7 and 8 are available only with the S8AS-48008N. 12 S8AS Chart 5: Operation Timing Chart 6: Operation Timing Power supply voltage External tripping input Branch output 1 voltage Branch output 1 voltage Startup sequence time Shutdown sequence time Branch output 2 voltage Branch output 2 voltage Startup sequence time Shutdown sequence time Branch output 3 voltage Branch output 3 voltage Startup sequence time Branch output 6 or branch output 8 voltage Shutdown sequence time Branch output 6 or branch output 8 voltage Startup sequence time Self-diagnostics (0.5 s min.) Note: For the S8AS-24006N and S8AS-48008N, the settings are 0.0 s for branch output 1, 0.4 s for branch output 2, 0.8 s for branch output 3, 1.2 s for branch output 4, 1.6 s for branch output 5, 2.0 for branch output 6, 2.4 s for branch output 7, and 2.8 s for branch output 8. (Cannot be changed.) (Branch outputs 7 and 8 are available only with the S8AS48008N.) Shutdown sequence time 20 ms max. Note: 1. Cut off simultaneously for tripping for abnormal voltages (28.8 V or higher). 2. For the S8AS-24006N and S8AS-48008N, all branch outputs have a setting of 0.0 s. (Cannot be changed.) 13 S8AS Key Operations and Displays in Each Mode Power ON • First startup after purchase. • When power was turned OFF in any mode except Test Mode. When power was turned OFF in Test Mode *3 Run Mode Setting Mode Test Mode *2 Output voltage display Current tripping threshold Value Setting Individual branch outputs *1, *2 No key operation for more than 3 s. Current tripping type Total Current Display *1 Output Current Display Undervoltage detection threshold Clearing selected peak output current. Peak Output Current Display Maintenance Forecast Monitor Output Display Value Setting Cut off all branch outputs (Shutdown Sequence) No key operation for more than 3 s. *1 Over-temperature output threshold Cut off Connected Selection of Standard, Instantaneous, or Extended Detection No key operation for more than 3 s. Execute Value Setting No key operation for more than 3 s. or no key operation for more than 3 s. Startup Sequence Time Setting *2 Time Setting Connect all branch outputs (Startup Sequence) No key operation for more than 3 s. Temperature Display Shutdown Sequence Time Setting *2 Execute Time Setting No key operation for more than 3 s. External Tripping Input Setting *2 Enable/Disable Setting No key operation for more than 3 s. Selection of Tripping Trigger Type: EGE/LVL External Tripping Trigger Type No key operation for more than 3 s. Communications Settings (Models with communications only) Settings No key operation for more than 3 s. Press for 3 s. Select reset method Selection of Method No key operation for more than 3 s. Mode Selection Menu Press for 3 s. Press for 3 s. *3 Select Run Mode Select Setting Mode *3 Select Test Mode Select Protection level Press for 3 s. Level Selection *3 Initialize Parameters Press for 3 s. Yes, initialize. *1. Branch outputs can be changed using the Down ( ) Key. The changes to the branch outputs will be retained in other displays as well. *2. Settings are displayed in order for branch outputs. Specific branch output settings have been omitted. *3. Not displayed for the S8AS-24006N/48008N. 14 S8AS Mode Descriptions The S8AS supports a Run Mode, Setting Mode, and Test Mode. Run Mode Used for normal operation. The measurements for the output voltage, output current, replacement time, and internal temperature can be read on the seven-segment display. Setting Mode * Used to set or change S8AS parameters. Mode Selection Menu (1) Run Mode (RUN) (1) In Run Mode, the current for each branch output, the total output current, the output voltage, the replacement time, the internal temperature, and other values can be displayed. Use this mode for operation once initial settings and system adjustments have been completed. (2) Setting Mode (SET) (2) Setting Mode is used to set parameters. Used to test operation for devices connected to Test Mode the S8AS. Note: Refer to the S8AS User's Manual (Cat. No. Z269) for details. * The S8AS-24006N and S8AS-48008N do not have a Setting Mode. (3) Test Mode (TST) (3) Test Mode enables forcing branch outputs ON and OFF. Connections and cutoffs can be manipulated for all outputs for each branch output. By default, all outputs will be ON (connected). Use this mode to set unused branch outputs to OFF (not connected). Initial Setting Procedure after Purchase The following diagram illustrates mode transitions for the S8AS. When the S8AS is turned ON for the first time, it will enter Setting Mode. After changing to Setting Mode, set the initial setting for each parameter, and then switch to Test Mode or Run Mode. • When newly purchased. Power ON • S8AS was not in Test Mode when power went OFF. S8AS was in Test Mode when power went OFF. *3 Mode Selection Menu Run Mode (4) Protection Level (PRT) (4) Protection Level can be used to set restrictions for setting parameters. Three levels, levels 0, 1, and 2, are available. The default is level 1. Refer to the User's Manual for the parameters that are protected in each level. (5) Initialize Parameters (INI) Select Run Mode run (RUN) (5) Parameters can be initialized to return all parameters to their default settings. The Initialize Parameters is not displayed in the default protection level (level 1). Press for 3 s. *1 Select Setting Mode set (SET) ((1) Switches to RUN Mode display.) Setting Mode Select Test Mode tst (TST) Test Mode Press for 3 s. *1 Select Protection Level prt (PRT) Press for 3 s. *1, *2 Initialize Parameters ini (INI) Go to Setting Mode to change any of the default parameter settings. Operation may be restricted by the protection level, preventing changes to some parameters. If necessary, change the protection level. Refer to the User's Manual for details on parameters and restrictions for the protection levels. *1. Not displayed for the S8AS-24006N/48008N. *2. Initialize Parameters is displayed only in protection level 0. *3. If the Mode Selection Menu is entered in Test Mode and then the power is turned OFF before entering another operating mode, the S8AS will start in Test Mode the next time it is started. 15 S8AS Run Mode Status Indicators Run Mode is used for normal operation. When the power is turned ON and the mode was Run Mode or Setting Mode the last time the input power was turned OFF, the S8AS will start in Run Mode and connecting the branch outputs will be started. Monitoring of voltages, currents, replacement time, and temperature can be confirmed using the Up Key and Down Key ( / ). The status indicators light according to the branch output status as described below. (1) Output Voltage 1 2 3 4 5 6 V A Yrs °C s (1) When Run Mode is entered, the parameter that was displayed the last time Run Mode was used will be displayed. The voltage output display is shown at the left as an example. Lit green Normal connection status Flashing green Connection standby status during the startup sequence Lit red Cutoff status for an abnormality Flashing red Cutoff status for an internal abnormality Not lit Forced cutoff or operation stopped S8AS-24006 POWER SUPPLY A(-) B(+) RS485 (2) Total Output Current 1 2 3 4 5 6 L (2) The total current for all outputs is displayed. N V A Yrs °C s (3) Present Output Current for Branch Output 1 *1 (Select the branch output with the V A Yrs °C s Down (CH) Key.)) (4) Peak Current for Branch Output 2 1 2 3 4 5 6 V A Yrs °C s Flashing (Select the branch output with the Down (CH) Key.)) (5) Replacement Time (3) The output current of the last branch output that was set will be displayed regardless of the operating mode. The current output of the branch output 1 is shown at the left. The current output of the branch output 2 is shown by pressing the Down (CH) Key. *The branch output number set with the Down (CH) Key is stored in memory even when the operating mode or parameters are changed. The branch output displayed when Test Mode is entered will not necessarily be branch output 1. (4) Press the Up (SEL) Key to display the peak current for the branch output displayed in step 2 (e.g., branch output 2). The “A” unit indicator will flash while the peak current is being displayed. The peak current can be cleared by performing the following procedure while the peak current is being displayed. 1. Press the ENT Key. 2. Change the “NO” display to the “YES” display using the Up (SEL) Key. 3. Press the ENT Key again. 2 V A Yrs °C s 3 4 5 6 -V -V +1 +2 +3 +4 +5 +6 -1 -2 -3 -4 -5 -6 Clearing the Peak Output Currents The peak output currents can be cleared. Select the peak output current to be cleared in Run Mode and then use the following operation. Peak Output Current Display 1 2 3 4 5 6 Waiting display, 1 s V A Yrs °C s Clearing completed. 1 2 3 4 5 6 V A Yrs °C s 1 2 3 4 5 6 V A Yrs °C s or 3 s with no key operations (5) Displays the estimated number of years until the replacement time. V A Yrs °C s V A Yrs °C s After flashing for 3 s Set value saved (flashes for 3 s) (6) Displays the internal temperature. (6) Internal Temperature 1 2 3 4 5 6 Status Indicators +V V.ADJ TRP LOW LFE TMP COM + TRG - 1 2 3 4 5 6 1 2 3 4 5 6 1 Class2 OUTPUT DC 24V 3.8A DC ON 1 2 3 4 5 6 1 2 3 4 5 6 INPUT 50/60Hz AC100-240V 3.8A 1 2 3 4 5 6 V A Yrs °C s ((1) Switches to output voltage display.) Press the Up (SEL) Key again to return to the output voltage display and start the display cycle again. V A Yrs °C s Indicator Status Notation Lit Flashing Note: 1. The S8AS will start in Run Mode when power is turned ON for the first time after shipping from the factory. 2. Settings cannot be changed in Run Mode. Use Setting Mode to change settings. (The setting for the S8AS-24006N and S8AS-48008N can not be changed.) 3. If a startup sequence has been set, connections will be started according to the set delays. 4. When moving to Run Mode, the branch output ON/OFF status from before entering Run Mode will be maintained. After testing branch output operation in Test Mode, always turn ON the required branch outputs before moving to Run Mode. 5. The voltage detection function monitors the voltage at the power input terminals. Measure the voltage at the branch output terminals to confirm that the output voltage is correct. 16 S8AS Setting Mode Setting Mode is used to set S8AS parameters. Settings can be read or changed while operation continues. The various parameters can be selected as shown below. Abnormal Current Tripping Value C-V The current at which a branch output is cut off Setting range: 0.5 to 3.8 A. The branch output will be cut off if the value set here is exceeded. Communications Settings (*1, *5) Unit No. Unit number setting (0 to 31) Branch output selection UNO Abnormal Current Tripping Type (*1) Detection settings for currents to cut off branch outputs Standard detection/instantaneous detection (*2) C-T Baud Rate Baud rate setting 48: 4,800 bps, 96: 9,600 bps Branch output selection BPS Undervoltage alarm The undervoltage alarm will be output if the voltage drops below this threshold value. Setting range: 18.0 to 26.4 V An alarm will be output if the value set here is exceeded. V-U Bit Length Bit length setting (7 or 8) LEN Maintenance forecast monitor The replacement time for the S8AS is calculated from the operating time and internal temperature. The maintenance forecast monitor output will operate when the replacement time falls below the value set here. Setting range: 0.0 to 5.0 years LFE Stop Bits Stop bit setting (1 or 2) BIT Over-temperature Output The temperature at which an signal is output. Setting range: 25 to 90°C An over-temperature signal will be output if the value set here is exceeded. TMP Parity Parity setting non: None, evn: Even, odd: Odd PTY Startup Sequence (*1) Enable/disable the startup sequence and set the time for each branch output. Time setting range: 0.0 to 99.9 s (*3) UPS Send Wait Time Send wait time setting 0 to 999 ms SWT Branch output selection Shutdown Sequence (*1) Enable/disable the shutdown sequence and set the time for each branch output. Time setting range: 0.0 to 99.9 s (*4) DWS Reset method *1 RST Branch output selection Reset method setting KEY: Clear errors using the Reset Key (RST) ALL: Clear errors using the Reset Key (RST) or by turning the power OFF and ON again. External tripping (*1) Enables (ON) or disables (OFF) the external tripping input function. TRG Branch output selection Tripping trigger type selection (*1) External tripping Tripping trigger type setting: EGE/LVL TGS Setting Parameters Parameters are set as shown below. Example for Setting the Abnormal Current Tripping Value Use 1 2 3 4 5 6 V A Yrs °C s After no key operations 1 2 3 4 5 6 for 3 s to change the set value. V A Yrs °C s When finished, press to save the set value. Set value saved (flashes for 3 s). After flashing for 3 s Indicator Status Notation Lit Flashing and Note: 1. Parameters cannot be changed in protection level 2, or when using the S8AS-24006N or S8AS-48008N. 2. The S8AS will start in Run Mode when power is turned ON for the first time after shipping from the factory. 3. Refer to the S8AS User's Manual (Cat. No. Z269), when having further settings. *1. Not displayed in protection level 1 or 2. *2. The S8AS-24006N and S8AS-48008N use Extended Detection. (Cannot be changed.) *3. The S8AS-24006N and S8AS-48008N use a startup sequence using an offset of 0.4 s starting with the first branch output. (Cannot be changed.) *4. The shutdown sequence shutdown delay on the S8AS24006N and S8AS-48008N is set at 0.0 s. (Cannot be changed.) *5. Communications settings will not be displayed on models that do not have communications functions. 1 2 3 4 5 6 V A Yrs °C s 17 S8AS Test Mode Protection Level Setting Device startup operation can be tested by turning ON/OFF branch outputs either individually or together. The branch outputs that are to be used are set to be connected in Test Mode. The operation to turn all branch outputs ON/OFF together can be used to check startup and shutdown sequences. A protection level can be set to prevent operating errors during normal operation. Reading or changing parameter settings and other operations can be restricted in three levels. Protection Level Test Mode (TST) Selected Press for 3 s. (1) (5) (3) 1 2 3 4 5 6 1 2 3 V A Yrs °C s 4 5 1 2 3 4 5 6 6 1 2 3 V A Yrs °C s 4 5 Intended for Possible operations 0 Facility designers and manufacturers All settings can be read and changed. 1 Facility maintenance personnel Some settings can be read and changed. 2 On-site operators Settings can be read but not changed. Select PRT (protection level) from the Mode Selection Menu and then perform the following procedure. (The following example shows changing to protection level 0.) 6 Setting Protection Level (2) (4) 1 2 3 4 5 6 1 2 3 V A Yrs °C s 4 5 6 After no key operations for 3 s 1 2 3 4 5 6 1 2 3 V A Yrs °C s 4 5 Mode Selection Menu (Protection Level) 6 After no key operations for 3 s Select TST (Test Mode) from the Mode Selection Menu and press the ENT Key. Test Mode will be entered. (1) When Test Mode is entered, the branch output number 1 indicator (see note) will flash and “OFF” or “ON” will flash on the 7-segment display. OFF flashing: Press the ENT Key to turn OFF branch output 1. ON flashing: Press the ENT Key to turn ON branch output 1. (2) The branch output can be selected at display (1) by using the Down (CH) Key. Press the ENT Key to turn the output ON and OFF. (3) If the Up (SEL) Key is pressed at display (1), all branch output number indicators will flash and “OFF” will flash on the 7-segment display. All branch outputs can be turned OFF in this condition. Press the ENT Key to turn all branch outputs OFF. (4) If the Up (SEL) Key is pressed at display (3), all branch output number indicators will flash and “ON” will flash on the 7-segment display. All branch outputs can be turned ON in this condition. Press the ENT Key to turn all branch outputs ON. (5) After completing ON/OFF testing and setting the branch outputs, press the Up (SEL) and Down (CH) Keys simultaneously for 3 s to go to the Mode Select Menu, and then enter Run Mode. Parameter Initialization All S8AS parameters can be restored to their default settings. Set protection level 0 and then go to the Mode Selection Menu. INI (parameter initialization) will be added to the menu. Select INI and then perform the following procedure. Mode Selection Menu (Parameter Initialization) After no key operations for 3 s * The branch output number set with the Down (CH) Key will not change even when the operating mode or parameters are changed. The branch output displayed when Test Mode is entered will not necessarily be branch output 1. Note: 1. In Test Mode, the branch output number indicators and 7segment display will continue to flash. 2. In Test Mode, the abnormal tripping output (TRP) will operate if one or more of the branch outputs are not connected. The TRP output will not operate if the operating mode is changed. 3. If power is turned OFF in Test Mode, Test Mode will be entered the next time power is turned ON. Indicator Status Notation Lit Flashing Parameter Initialization Run Mode Setting Confirmation (Flashes for 3 s.) Note: 1. The Mode Selection Menu is not displayed in protection level 1 or 2. The default setting is for protection level 1. 2. Default Settings • The operating mode will change to Run Mode. • The parameters will change to their default settings. • All branch outputs will be changed so they are connected. • The protection level will change to level 1. 18 S8AS List of Alarms Alarm display A10 Name Abnormal voltage tripping A11 Abnormal current tripping A12 Abnormal total current tripping Alarm outputs Power outputs Recovery/reset method TRP output: OFF Total current (normally ON) tripping Remove the cause of the abnormality and then press the Reset Key( ) on the front panel or use communications reset function (S8AS-24006R and S8AS48008R only). * Power supply will be restarted after recovery. Note: Once an error has been reset, another reset operation cannot be performed for at least 15 seconds. TRP output: OFF Cut off (normally ON) Remove the cause of the abnormality and then press the Reset Key( ) on the front panel or use communications reset function (S8AS-24006R and S8AS48008R only). * Power supply will be restarted after recovery. Note: Once an error has been reset, another reset operation cannot be performed for at least 15 seconds. TRP output: OFF Total current (normally ON) tripping Remove the cause of the abnormality and then press the Reset Key( ) on the front panel or use communications reset function (S8AS-24006R and S8AS48008R only). * Note: Once an error has been reset, another reset operation cannot be performed for at least 15 seconds. ALM output: OFF ON (normally ON) Remove the cause of the abnormality and then press the Reset Key( ) on the front panel or use communications reset function (S8AS-24006R and S8AS48008R only). * Note: 1. Once an error has been reset, another reset operation cannot be performed for at least 15 seconds. 2. The alarm status will be reset if the cause of the alarm has been removed when the power supply is reset. A21 Undervoltage alarm A23 Maintenance LEF output: OFF forecast (normally ON) monitor output ON The replacement time specified for the S8AS has become less than the value set for the maintenance forecast monitor function. Either replace the S8AS or change the set value. A23/HOT Overheating alarm ON Take steps to reduce the internal temperature of the S8AS. The error will automatically be cleared when the temperature becomes stable. However, if the overheating alarm stays ON for more than 3 hours, it can no longer be cleared. Be sure to clear the error within 3 hours. LFE output: OFF (normally ON) OverTMP output: OFF The alarm display and over-temperature output will automatically be reset if the temperature ON (normally ON) temperature remains below the set value minus 3°C for at least 5 s. output Note: Alarms will be displayed in order of priority if more than one alarm occurs at the same time. Order of priority: A10, A12, A11, A23/HOT, A21, A23, A30. * Enabling or disabling the functionality to reset errors by turning the power supply OFF and then ON can be set using the Reset Method Setting (RST) parameter. However, the settings for the S8AS-24006N and S8AS-48008N cannot be changed. (Initial setting: Errors can be reset by turning the power supply OFF and ON again.) A30 19 S8AS Alarm Display Communications (S8AS-24006R/48008R) The S8AS displays alarms according to the parameters set in Setting Mode. The alarm number and detected value are alternated on the display for each alarm. The built-in RS-485 port can be used to connect special Support Tool to set parameters, monitor, perform tripping operations for branch outputs, and perform other remote monitoring and control operations from a network. Example: Abnormal Current Tripping Alarm at Branch Output 4 0.5 s 1 2 3 4 5 6 V A Yrs °C s 0.5 s 1 2 3 4 5 6 V A Yrs °C s 0.5 s 0.5 s Current when alarm occurred Note: Indicator Status Notation Lit Flashing 1 2 3 4 5 6 V A Yrs °C s Note: Alarms will be displayed in order of priority if more than one alarm occurs at the same time. Order of priority: A10, A12, A11, A23/HOT, A21, A23, A30. Resetting Alarms When an alarm is displayed, remove the cause of the alarm and then press the Reset Key ( ) for at least 3 s. The following display will appear and the alarm will be reset. For information on resetting alarms, refer to List of Alarms on the previous page. Type RS-485 Communications method Half-duplex Sync method Start-stop Baud rate 4,800 or 9,600 bps Transmitted code ASCII Data bit length 7 or 8 bits Stop bit length 1 or 2 bits Error detection Vertical parity and BCC Parity check None, even, or odd Protocol CompoWay/F Support Tool (S8AS-24006R/48008R) The Support Tool is used to set and monitor models that support communications. Parameters can be set, operation can be monitored, and parameter files can be managed. Support Tool Functions • Reading and writing parameter settings • Monitoring present values • Monitoring status (cutoff status, normal/error status) Applicable OS: Windows 2000 or XP Visit OMRON's website for downloading the Support Tool. 20 S8AS Dimensions (Unit: mm) S8AS Smart Power Supplies 124.7 122 S8AS-24006 S8AS-24006N 160 Three, M4 square washers 10 S8AS-24006 POWER SUPPLY L N 1 2 3 4 5 6 INPUT 1 50/60Hz AC100-240V 3.8A 34.9 6 115 +1 +2 +3 +4 +5 +6 -1 -2 -3 -4 -5 -6 M4 square washers 4.5 (sliding: 15 max.) 160 Three, M4 square washers 10 122 5 -V -V 5.08 131.8 142.4 124.7 4 V.ADJ TRP LOW LFE TMP COM + TRG - S8AS-24006R V A Yrs °C s 3 +V Class2 OUTPUT DC 24V 3.8A DC ON 2 S8AS-24006 POWER SUPPLY A(-) B(+) RS485 L N 1 2 3 4 5 6 INPUT 1 50/60Hz AC100-240V 3.8A 34.9 5 6 115 -V -V +1 +2 +3 +4 +5 +6 -1 -2 -3 -4 -5 -6 M4 square washers 4.5 (sliding: 15 max.) 5.08 131.8 124.7 122 4 V.ADJ TRP LOW LFE TMP COM + TRG - S8AS-48008 S8AS-48008N V A Yrs °C s 3 +V Class2 OUTPUT DC 24V 3.8A DC ON 2 230 10 Three, M4 square washers S8AS-48008 POWER SUPPLY L N INPUT 1 2 3 4 5 6 7 8 V A Yrs °C s 50/60Hz AC100-240V 7.4A 1 34.9 Class2 OUTPUT DC 24V 3.8A DC ON 3 4 5 6 7 8 +V 115 -V -V +1 +2 +3 +4 +5 +6 -1 -2 -3 -4 -5 -6 +7 +8 V.ADJ TRP LOW LFE TMP COM + TRG - -7 -8 M4 square washers (sliding: 15 max.) 5.08 131.8 S8AS-48008R 2 4.5 142.4 124.7 122 10 230 Three, M4 square washers S8AS-48008 POWER SUPPLY L A(-) N B(+) RS485 INPUT 1 2 3 4 5 6 7 8 V A Yrs °C s 50/60Hz AC100-240V 7.4A 1 Class2 OUTPUT DC 24V 3.8A 34.9 DC ON 3 4 5 6 7 8 115 +V -V -V +1 +2 +3 +4 +5 +6 -1 -2 -3 -4 -5 -6 +7 +8 V.ADJ TRP LOW LFE TMP COM + TRG - 5.08 131.9 2 -7 -8 M4 square washers (sliding: 15 max.) 4.5 Mounting Rail (Material: Aluminum) PFP-100N PFP-50N 7.3±0.15 4.5 Model 35±0.3 15 25 10 25 25 1,000 (500) * 10 25 15(5) * 27±0.15 1 PFP-100N PFP-50N *Values in parentheses are for the PFP-50N. Mounting Rail (Material: Aluminum) 21 S8AS Mounting Rail (Material: Aluminum) PFP-100N PFP-50N 7.3±0.15 4.5 Model 35±0.3 15 25 10 25 25 10 25 27±0.15 PFP-50N 1 15(5) * 1,000 (500) * PFP-100N *Values in parentheses are for the PFP-50N. Mounting Rail (Material: Aluminum) 16 PFP-100N2 4.5 35±0.3 27 15 25 10 25 25 1,000 10 25 15 Model 24 29.2 1 PFP-100N2 1.5 Mounting Rail (Order Separately) 10 End Plate PFP-M 6.2 1.8 Model M4 × 8 pan-head screw 50 PFP-M 1 1.8 35.5 35.5 11.5 1.3 10 M4 spring washer 4.8 22 S8AS Safety Precautions Refer to Safety Precautions for All Power Supplies. Attachment to the DIN Rail !CAUTION To mount the block on a DIN Rail, until it makes a clicking sound, pull down the Rail stopper hook portion (A) of the Block onto the Rail, and press the Block in direction (B) to lock it in place. Minor electric shock, fire, or Product failure may occasionally occur. Do not disassemble, modify, or repair the Product or touch interior of the Product. Minor burns may occasionally occur. Do not touch the Product during power is being supplied or immediately after power is turned OFF. A B To dismount the Block, pull down portion (C) with a flat-blade screwdriver and pull out the Block. Minor injury may occasionally occur due to electrical shock. Do not touch the terminals while power is being supplied. Also, be sure to close the terminal cover after wiring the terminals. Fire may occasionally occur. Tighten terminal screws to the specified torque. 30 mm min. C Rail stopper Wiring Precautions for Safe Use Mounting • The long-term reliability of the S8AS can be increased by installing it properly and providing sufficient heat dissipation. Use the S8AS within the derating curve. The S8AS is designed to radiate heat by means of natural air circulation. Provide appropriate space as shown below to allow air flow around the Power Supplies. • Poor heat dissipation resulting from improper installation conditions may occasionally deteriorate or damage internal parts and also cause the maintenance forecast monitor function to not operate properly. Do not use any mounting orientation other than a standard one. • Poor heat dissipation may deteriorate or damage internal parts. Do not loosen the screws on the side of the Product. • Do not allow any pieces of metal or conductors, or any clippings or cuttings resulting from installation work to enter the Product. S8AS-24006 S8AS-24006 POWER SUPPLY POWER SUPPLY N 1 2 3 4 5 6 INPUT 1 50/60Hz AC100-240V 3.8A DC ON 3 4 5 6 N INPUT -V -V +2 +3 +4 -2 -3 -4 1 50/60Hz AC100-240V 3.8A +5 +6 DC ON -1 1 2 3 4 5 6 -5 -6 2 V A Yrs °C s 3 4 5 Screw terminals 6 -V -V +1 +2 +3 +4 +5 +6 -1 -2 -3 -4 -5 -6 V.ADJ TRP LOW LFE TMP COM + TRG - 20 mm min. Terminals Name Recommended wire diameter Wire type Torque Wire stripping length AC input terminals and protective earth (PE) terminal AWG14 to 16 (cross-sectional Solid or 9.6 in.lb. 8 to area of 0.823 to stranded (1.08 N·m) 10 mm 2 2.081 mm ) Branch output terminals (−), UL Standard AWG12 to 14 8 to (cross-sectional Solid or 12 in.lb. area of 2.081 to stranded (1.36 N·m) 10 mm 2 3.309 mm ) +V Class2 OUTPUT DC 24V 3.8A V.ADJ TRP LOW LFE TMP COM + TRG - L +V Class2 OUTPUT DC 24V 3.8A +1 2 V A Yrs °C s Recommended Wire Diameter 75 mm min. Air flow L • Connect the ground completely. The ground is a protective earth (PE) terminal specified in safety standards. If the ground is not connected completely, electric shock or malfunction may occur. • Minor fire may possibly occur. Ensure that input and output terminals are wired correctly. • Heat generated by wiring materials may cause the temperature of internal parts to increase, which may result in deterioration of or damage to the internal parts. Select the wiring materials according to the current that is being used. Using the wiring materials, torque, and wire stripping lengths in the following table is recommended to prevent smoke or fire of the wire material due to an abnormal load. 75 mm min. Screwless terminals AWG12 to 20 Branch output (cross-sectional Solid or 8.8 in.lb. terminals (−), area of 0.517 to stranded (1.0 N·m) CSA Standard 3.309 mm2) 8 to 10 mm Branch output positive terminals, branch output negative terminals, I/O signal terminals, and communications terminals 10 mm AWG12 to 24 (cross-sectional Solid or --area of 0.2 to stranded 2.5 mm2) • Do not push more than 100 N of force to the terminal block when tightening screws. • The lock screws on both sides of the screwless connectors are not tightened at the factory. • Be sure to tighten the lock screws on the sides of the screwless connector after connecting it to the S8AS. When removing a screwless connector, be sure the lock screws are completely loose before pulling on the connector. • Be sure to remove the sheet covering the Product during installation before turning ON the power. 23 S8AS Installation Environment • Do not use the Product where it would be subjected to shock or vibration. A device such as a contact breaker may be a vibration source. Set the Product as far as possible from possible sources of shock or vibration. Additionally, install a PFP-M End Plate on each end of the Product after mounting it to a DIN Rail. • If the Product is used in an area with excessive electronic noise, be sure to separate the Product as far as possible from the noise sources. Ambient Operating and Storage Environment • Store the Product at an ambient temperature of −25 to 65°C and relative humidity of 25% to 90%. • Internal parts may occasionally be deteriorated or damaged. Do not use the Product in conditions exceeding the derating curve (in portion (1) of the Derating Curve on page 8). • Use the Product where the relative humidity is 25% to 85%. • Do not use the Product where it would be subjected to direct sunlight. • Do not use the Product where it would be subjected to the possibility of penetration of liquid, foreign substance, or corrosive gas. • To maintain performance of the maintenance forecast monitor, make sure the following conditions are satisfied for long-term storage. For storage exceeding three months, keep the Product at a temperature of −20°C to 30°C and a humidity of 25% to 70%. Output Voltage Adjustment • The output voltage adjuster (V.ADJ.) may possibly become damaged. Do not apply more than the required force. • Do not exceed the rated output capacity and rated total output current after adjusting the output voltage. Periodic Inspections Under normal operating conditions, the Product will require several years or even more than ten years until the maintenance forecast monitor function operates. When using the Product for an extended period of time, perform the following procedure periodically to confirm that the output for the maintenance forecast monitor function (LFE) is operating correctly. a) Change to Run Mode. b) Confirm that the (LFE) output is ON (i.e., that there is electrical continuity between (LEF) and (COM)). Precautions for Correct Use Tripping Performance • When the tripping alarm output operates, always remove the cause of the output first and then reset the alarm. • When using a load with a fixed-power operation, the S8AS may cause a cutoff when the power supply is turned OFF. • Outputs may be cut off by the abnormal voltage protection with loads that generate reverse peak electromotive force. • Tripping performance is depends on the ambient operating temperature. Use the Product within the derating range. Refer to the Derating Curve on page 8. • It is conceivable that internal parts may be deteriorated or damaged. Do not repeatedly perform cutoff or recovery operations more than necessary. Maintenance Forecast Monitor Function The accuracy of the maintenance forecast monitor function will be reduced in applications where the AC input turns ON and OFF frequently. Total Peak Output Current The S8AS is designed to provide a temporary peak current to provide the overcurrent required to start load devices. The total peak output current for all branch outputs combined is given below. However, if even one of the following conditions is not satisfied by the total current, all branch outputs will be cut off to ensure safety based on the amount of peak current and the usage time. • 240-W Models Input voltage range: 200 to 240 VAC Total peak current/Peak current pulse width: 17 A max./2 s max. 15 A max./5 s max. 13 A max./10 s max. 12 A max./20 s max. • 480-W Models Input voltage range: 200 to 240 VAC Total peak current/Peak current pulse width: 27 A max./1 s max. 25 A max./2 s max. 22.5 A max./5 s max. Note: 1. If the input voltage range is outside of the range given above, or if the total output current exceeds the maximum peak current, the S8AS may be cut off due to unstable internal operation. 2. After the load device has been started, ensure that the total current in steady state remains within the rated values. 3. When the peak current has exceeded the rated current, do not allow the peak current to flow again for the next 60 seconds. Startup Sequence and Shutdown Sequence The sequencing functions are designed for the branch outputs of one S8AS. There is no synchronizing processing between S8AS when more than one S8AS is used. Startup Delay The startup delay will not operate when a relay or other device is used for ON/OFF control on the output side of the S8AS, so a cutoff operation may occasionally occur. Dielectric Strength Test • The S8AS is designed to withstand 3,000 VAC for 1 minute between the AC input terminals collectively and the branch output, I/O signal, or communications terminals collectively. When testing, set the cutoff current for the withstand voltage test device to 20 mA. • The S8AS may possibly be damaged from the impulse voltage if a testing device switch is used to abruptly apply or cut off 3000 VAC. Increase the applied voltage gradually using the voltage adjustment on the testing device. • When testing terminals together, always short the specified terminals so that the voltage is applied to all of the terminals at the same time. 24 S8AS Insulation Resistance Test • When testing the insulation resistance, use a DC resistance meter at 500 VDC. • To prevent damage, always short branch output terminals (+/−), all I/O terminals, and communications terminals before testing. Prohibition of Parallel Connection Do not connect branch outputs from the S8AS in parallel. Also, do not connect the branch outputs in parallel with branch outputs of other S8AS Power Supplies. S8AS Output Voltage Adjustment • If the output voltage is set to less than 20 V (default setting), the undervoltage alarm may be activated. • Do not exceed the rated output capacity and rated total output current after adjusting the output voltage. • The output voltage may increase beyond the allowable voltage range rated voltage +10% when the V.ADJ adjuster is used. When adjusting the output voltage, check the output voltage of the power supply to make sure that the load is not damaged. Displaying the Output Voltage S8AS S8AS Connections cannot be made in parallel with other branch output circuits. The voltage detection is performed on the voltage after AC/DC conversion in the interval circuits. The displayed voltage will be somewhat different from the value at the output terminals of the power source due to internal voltage drop. To confirm correct output voltages, measure the voltages at the branch output terminals. Connecting Backup Devices No Output Voltage A harmonic current suppression circuit is built into the Power Supply. This circuit can create noise when the input is turned ON, but it will last only until the internal circuits stabilize and does not indicate any problem in the Product. The internal circuit's overcurrent protection or overvoltage protection may operate. Alternatively, the latch protection circuit may operate if there is a lightning inrush or other large voltage applied to the input. Contact your OMRON representative if there is still no output voltage after checking the following two points: • Checking Overcurrent Protection Check whether the load is in an overcurrent or short-circuited state. Remove the wires to the load before checking. • Checking Overvoltage Protection and Latching Protection Turn the power supply OFF and leave it OFF for at least 3 minutes, then turn it ON again. Do not connect a battery or other backup power supply to the output of the Product. Harmonic Current Suppression Circuit Startup Time At startup, the S8AS will check hardware and software before starting the operation of branch outputs. A time of approximately 3 seconds is required for these self-diagnostic functions. Take this time into account when designing the system. External Tripping Input • Wire the polarity of the external tripping input correctly. • After completing wiring, confirm that operation is correct. Tripping Alarm Output, Undervoltage Detection Output, Maintenance Forecast Monitor Output, and Over-temperature Output Photoswitch outputs: 30 VDC max., 50 mA max., residual voltage when ON: 2 V max., leakage current when OFF: 0.1 mA max. • Wire all output signal circuits correctly. • Internal current control circuits are not provided internally for output signals. Do not allow the output current to exceed 50 mA. • After completing wiring, confirm that the circuits operate correctly. 25 Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. 2014.2 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2014 All Right Reserved.