LEN00H0003 Lighting Contactor 400 Amp 3 Pole, Pub # E87010-A0116-T007-A6-LEN0, Doc # A5E31166503A-001

SIEMENS
Product data sheet
E87010-A0116-T007-A6-LEN0
Lighting Contactor
Class LE
Electrically Held
400 Amp, 3 Pole
General technical data:
Finger-safe (main circuit / control circuit)
Degree of pollution
Altitude (m)
Ambient storage temperature (°C)
Ambient operating temperature (°C)
Humidity (% non-condensing)
Shock resistance at rectangular impulse (g/ms)
Shock resistance at sine pulse (g/ms)
Rated impulse voltage resistance (kV)
Rated insulation voltage (V)
Mechanical operating cycles as operating time:
of contactor
of contactor with additional aux contacts
Main circuit:
Number of NC / NO main contacts
Typical power loss per conductor (W)
Off-load operating frequency (cycles per hour)
Current ratings:
Tungsten (poles per phase)
Ballast (poles per phase)
General & resistive (poles per phase)
Coil ratings:
Inrush / sealed power (VA)
Coil voltage tolerance factor
Coil code 024
Coil code 120
Coil code 208
Coil code 240
Coil code 277
Coil code 347
Coil code 480
Coil code 600
Internal/standard auxiliary contact:
Number of NC / NO auxiliary contacts
Rating
©2012 Siemens Industry, Inc.
Subject to change without prior notice.
Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092
August, 2012
no / yes
3
2,000
-55 to 80
0 to 40
10 to 95
8.5 / 5, 4.2 / 10
13.4 / 5, 6.5 / 10
no data
no data
10,000,000
10,000,000
0NC / 3NO
35
2,000
400A @277V 1p 1ph
400A @480V 2p 1ph
400A @480V 3p 3ph
400A @600V 1p 1ph
400A @600V 2p 1ph
400A @600V 3p 3ph
400A @600V 1p 1ph
400A @600V 2p 1ph
400A @600V 3p 3ph
830 / 9.2
0.8 - 1.1
23-26V AC 40-60HZ, DC
110-127V AC 40-60HZ, DC
200-220V AC 40-60HZ, DC
220-240V AC 40-60HZ, DC
240-277V AC 40-60HZ, DC
NA
440-480V AC 40-60HZ, DC
575-600V AC 40-60HZ, DC
2 NC / 2 NO
A300 / Q300
A5E31166503A-001
Page 1 of 2
Installation/mounting/dimensions:
Mounting orientation
Type of mounting: screw / DIN rail
Height x Width x Depth (mm)
Minimum clearance to sides (mm)
Minimum clearance to earthed parts (mm)
Connection type / torque for main circuit terminals
Connection type / torque for control circuit terminals
Solid & stranded conductors for main contacts (AWG)
Solid & stranded conductors for control circuit (AWG)
Conductor type for main and control circuits
Short circuit current rating of main circuit:
Short circuit current rating
Max fuse / circuit breaker (Amp)
Certificates:
vertical
yes / no
214 x 160 x 225
10
10
screw / 180-195 lb in
screw / 7-10 lb in
2x(2/0-500MCM)
2x(18-14)
75°C CU
18kA @ 600V
800 / 500
cULus
Dimensions
Wiring Diagram
©2012 Siemens Industry, Inc.
Subject to change without prior notice.
Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092
A5E31166503A-001
Page 2 of 2