LEN00B0004 Lighting Contactor 20 Amp 4 Pole, Pub # E87010-A0109-T007-A6-LEN0, Doc # A5E31166494A-001

SIEMENS
Product data sheet
E87010-A0109-T007-A6-LEN0
Lighting Contactor
Class LE
Electrically Held
20 Amp, 4 Pole
General technical data:
Finger-safe (main circuit / control circuit)
Degree of pollution
Altitude (m)
Ambient storage temperature (°C)
Ambient operating temperature (°C)
Humidity (% non-condensing)
Shock resistance at rectangular impulse (g/ms)
Shock resistance at sine pulse (g/ms)
Rated impulse voltage resistance (kV)
Rated insulation voltage (V)
Mechanical operating cycles as operating time:
of contactor
of contactor with additional aux contacts
Main circuit:
Number of NC / NO main contacts
Typical power loss per conductor (W)
Off-load operating frequency (cycles per hour)
Current ratings:
Tungsten (poles per phase)
Ballast (poles per phase)
General & resistive (poles per phase)
Coil ratings:
Inrush / sealed power (VA)
Coil voltage tolerance factor
Coil code 024
Coil code 120
Coil code 208
Coil code 240
Coil code 277
Coil code 347
Coil code 480
Coil code 600
Internal/standard auxiliary contact:
Number of NC / NO auxiliary contacts
Rating
©2012 Siemens Industry, Inc.
Subject to change without prior notice.
Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092
August 2012
yes / yes
3
2,000
-55 to 80
0 to 40
10 to 95
6.7 / 5, 4.2 / 10
10.5 / 5, 6.6 / 10
no data
no data
30,000,000
10,000,000
0NC / 4NO
0.7
10,000
20A @277V 1p 1ph
20A @480V 2p 1ph
20A @480V 3p 3ph
20A @347V 1p 1ph
20A @600V 2p 1ph
20A @600V 3p 3ph
20A @600V 1p 1ph
20A @600V 2p 1ph
20A @600V 3p 3ph
31.7 / 4.8
0.8 - 1.1
24VAC 60HZ
110VAC 50HZ / 120VAC 60HZ
198VAC 50HZ / 208VAC 60HZ
220VAC 50HZ / 240VAC 60HZ
277VAC 60HZ
347VAC 60HZ
480VAC 60HZ
600VAC 60HZ
(must use an external/optional auxiliary contact)
NA
A5E31166494A-001
Page 1 of 2
Installation/mounting/dimensions:
Mounting orientation
Type of mounting: screw / DIN rail
Height x Width x Depth (mm)
Minimum clearance to sides (mm)
Minimum clearance to earthed parts (mm)
Connection type / torque for main circuit terminals
Connection type / torque for control circuit terminals
Solid & stranded conductors for main contacts (AWG)
Solid & stranded conductors for control circuit (AWG)
Conductor type for main and control circuits
Short circuit current rating of main circuit:
Short circuit current rating
Max fuse / circuit breaker (Amp)
Certificates:
vertical
yes / yes
57.5 x 45 x 73
0
6
screw / 7-10 lb in
screw / 7-10 lb in
2x(20-16), 2x(18-14), 2x(12)
2x(20-16), 2x(18-14)
75°C CU
5kA @ 600V
30 / 25
cULus
Dimensions
Wiring Diagram
©2012 Siemens Industry, Inc.
Subject to change without prior notice.
Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092
A5E31166494A-001