New Product I/O Relay Terminal G70V I/O Relay Terminals with 16 Points and Push-In Plus terminal blocks to Downsize Control Panels and Save Labor • I/O Relay Terminals with 16 points to mount G2RV Slim I/O Relays. • Push-In Plus terminal blocks are used to save wiring work in comparison with traditional screw terminals. (Wiring time is reduced by 60%* in comparison with traditional screw terminals.) • Work is reduced ever further with one-step cable connection to the PLC. • Diode provided for coil surge absorption. • Operation indicators for immediate recognition of I/O signal status. • Accepts G3RV Slim I/O SSRs. • DIN Track or screw mounting. For the most recent information on models that have been certified for safety standards, refer to your OMRON website. * According to OMRON actual measurement data from November 2015. Refer to Safety Precautions on page 9. Model Number Legend G70V - @ @ @ 16 P - @ (1) (2) (3) (4) (5) (6) (1) Mountable Relays S: Relays Z: Sockets (2) Input/Output Classification I: For input O: For output (3) I/O Specification C: Contacts (Applicable when (2) is O (for output) (relay output).) D: DC (Applicable when (2) is I (for input) (coil for input).) M: AC/DC (Applicable when (1) is Z (Sockets).) (4) Number of I/O Points 16: 16 points (5) Terminal Type P: Push-In Plus terminal blocks (6) Internal I/O Circuit Common Blank: NPN 1: PNP (For Input NPN) PLC (For Input PNP) G70V (+) PLC G70V )+( − Common )−( (−) (For Output NPN) + Common (For Output PNP) PLC G70V PLC − X + (−) G70V (+) (+) NPN transistor Common X Common PNP transistor X X (−) 1 G70V Ordering Information I/O Relay Terminal Terminals Type Internal I/O circuit common Points Rated voltage Model NPN (– common) Input *1 Push-In Plus terminal blocks PNP (+ common) 16 NPN (+ common) Output *2 G70V-SID16P G70V-SID16P-1 24 VDC G70V-SOC16P PNP (– common) G70V-SOC16P-1 *1. Mountable Relays: G2RV-1-S-AP-G DC21V. *2. Mountable Relays: G2RV-1-S-G DC21V. Relay Terminal Sockets Applicable I/O Relay Terminal Type G70V-SID16P Common Processing in Connector Input G70V-SID16P-1 G70V-SOC16P Output G70V-SOC16P-1 Model NPN (– common) G70V-ZID16P PNP (+ common) G70V-ZID16P-1 NPN (+ common) G70V-ZOM16P PNP (– common) G70V-ZOM16P-1 Note: Relays are not mounted to the G70V-ZID/ZOM16P(-1) Relay Terminal Sockets. Combine the Relay Terminal Sockets with Slim I/O Relays or Slim I/O SSRs. Accessories (Order Separately) Mountable Relays Applicable I/O Relay Terminal G70V-SID16P(-1) Type Input Classification Slim I/O Relays G70V-SOC16P(-1) Model Slim I/O Relays *1 Output Slim I/O SSRs G2RV-1-S-AP-G DC21 No Latching Lever *2 G2RV-1-S-G DC21 Latching Lever G2RV-1-SI-G DC21 For AC Zero cross function G3RV-202S DC24 No zero cross function G3RV-202SL DC24 For DC G3RV-D03SL DC24 Note: To use Slim I/O SSRs, either remove the Slim I/O Relays to mount them or order a Relay Terminal Socket and I/O SSRs separately and combine them. *1. G2RV-1-S-AP-G Slim I/O Relays are mounted to G70V-SID16P(- 1) I/O Relay Terminals as a standard feature. *2. G2RV-1-S-G Slim I/O Relays are mounted to G70V-SOC16P(- 1) I/O Relay Terminals as a standard feature. When ordering, designate the rated voltage. Connecting Cables XW2Z-R • Cable with Loose Wire and Crimp Terminals: • Cable with Loose Wires: • Cable with Fujitsu connectors (1:1): (1:2): (1:3): • Cable with MIL connectors (1:1): (1:2): Refer to Applicable Cables on page 11 for details. Labels XW2Z-RY@C XW2Z-RA@C XW2Z-R@C XW2Z-RI@C-@ XW2Z-RO@C-@ XW2Z-R@C-@-@ XW2Z-RI@C XW2Z-RO@C XW2Z-RI@-@-D@ XW2Z-RM@-@-D@ XW2Z-RO@-@-D1 Minimum order (sheet) (quantity per sheet) Model 5 (1 sheet / 72 pieces) XW5Z-P2.5LB2 Parts for DIN Track Mounting Type DIN Tracks Model 1m PFP-100N 0.5 m PFP-50N End Plate PFP-M Spacer PFP-S Minimum order (quantity) --10 Refer to your OMRON website for details on the PFP-@. 2 G70V Specifications Coil Ratings (Common to Input/Output per Relay) Item Rated voltage (V) Rated current (mA) Coil resistance (Ω) Must operate of rated voltage 13.3 1575 80% max. 24 VDC Must Maximum release of rated voltage of rated voltage voltage 10% min. 110% Power consumption (mW) Approx. 280 Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with a tolerance of ±15% for coil resistance. 2. The operating characteristics are measured at a coil temperature of 23°C. 3. The value for maximum voltage is the maximum value within the allowable voltage fluctuation range for the relay coil’s operating power supply. Continuous operation at this voltage is not within product specifications. 4. The rated current includes the current for the indicators on the I/O Relay Terminal. Contact Ratings (G2RV-1-S-G I/O Relay) Classification For input For output Resistive load (cosφ=1) Item Inductive load (cosφ=0.4 L/R=7 ms) Resistive load (cosφ=1) Rated load 50 mA at 30 VAC 50 mA at 36 VDC 6 A at 250 VAC 6 A at 30 VDC 2.5 A at 250 VAC 2 A at 30 VDC Rated carry current 50 mA 6A Max. switching voltage 30 VAC, 36 VDC 250 VAC, 125 VDC Max. switching current 50 mA 6A Maximum switching capacity --- 1,500 VA 180 W Error rate (reference value) * 1 mA at 100 mVDC 10 mA at 5 VDC Electrical life expectancy 5,000,000 operations min. NO contacts: 70,000 operations min. NC contacts: 50,000 operations min. Mechanical life expectancy 5,000,000 operations min. 5,000,000 operations min. 500 VA 60 W * The above values are for a switching frequency of 120 operations/min. Characteristics G70V-SID16P(-1) (Input, DC coil) Model Item Contact form G70V-SOC16P(-1) (output, DC coil) SPST-NO × 16 SPDT×16 Contact material Ag alloy + Au plating Ag alloy Contact resistance *1 150 mΩ max. Must Operate time *2 20 ms max. Release time *2 40 ms max. Max. switching frequency Mechanical limit 18,000 operations/hour At rated load 1,800 operations/hr (under rated load) Insulation resistance 100 MΩ min. Dielectric strength Between coil and contacts: 2,500 VAC for 1 min Vibration resistance 100 m/s2 Shock resistance 100 m/s2, 3 times each in 6 directions along 3 axes Noise immunity Noise level: 1.5 kV; pulse width: 100 ns to 1 μs Ambient operating temperature −40 to 55°C (with no icing or condensation) Ambient operating humidity 35% to 85% RH LED color Power supply Green I/O Yellow Weight Approx. 350 g Approx. 370 g Note: The above values are initial values. *1. Measurement condition: 1 A at 5 VDC. *2. Ambient temperature: 23°C. Applicable Standards • UL 61010-2-201, CAN/CSA-C22.2 No.61010-2-201, TÜV (EN 61810-1) 3 G70V Engineering Data (Reference Value) Operations (× 103) Endurance Curve (NO Contacts) G70V-SOC16P(-1) 1000 30 VDC resistive load 250 VAC resistive load 100 30 VDC inductive load 250 VAC inductive load 10 0 2 4 6 Switched current (A) Note: These data are actual measured values that were sampled from the production line and prepared in graph format, and are for reference purposes only. A relay is manufactured by mass production, and as a basic rule must be used with allowance made for a certain amount of deviation. Load Current vs. Ambient Temperature G3RV-202S DC24 G70V-SOC16P(-1) G3RV-D03 DC24 (A) Single Relay 6 16 points ON 5 (A) Load Current (A) Load Current (A) Load Current (A) G3RV-202SL DC24 3 4 (A) 3 Single Relay Single Relay 2 2 3 16 points ON 16 points ON 2 1 1 1 0.5 0.2 0 -40 -20 0 0 -40 20 25 40 55 60 Ambient Temperature -20 0 20 25 40 55 60 Ambient Temperature 0 -40 Inrush Current Resistance: Non-repetitive The following graphs show the maximum inrush currents that can be withstood for non-repetitive operation. For repetitive operation, the figures should be reduced by half. G3RV-D03 DC24 Inrush current (A. Peak) Inrush current (A. Peak) G3RV-202S DC24 G3RV-202SL DC24 40 35 30 25 35 30 25 20 20 15 15 10 10 5 5 0 10 30 50 100 300 500 1,000 3,000 5,000 Energized time (ms) 4 40 0 10 30 50 100 300 500 1,000 3,000 5,000 Energized time (ms) -20 0 20 40 55 60 Ambient Temperature G70V Terminal Arrangement/Internal Connection G70V-SID16P (NPN input/– common) Connector Pin Configuration Top View 10 20 Relay No. 1 2 3 4 5 6 7 8 + − 1 11 2 12 3 13 4 14 5 15 6 16 7 17 8 18 9 19 10 20 9 10 11 12 13 14 15 16 + − Connector pin No. 1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 9 19 X Input relays G2RV-1-S-AP-G X V V X V G G G Push-in power supply terminals X X X X X X X X X X X X X X V V V V V V V V V V V V V V V G G G G G G G G G G G G G G G Push-in I/O terminals mark Connector pin No. Note: Pin numbers are indicated for convenience. The ▲ mark can be used to determine orientation. Terminal name Description V (push-in power supply terminals) Unit power supply terminals (24 VDC) G (push-in power supply terminals) V (push-in I/O terminals) Relay-drive coil terminals (24 VDC) G (push-in I/O terminals) G70V-SID16P-1 (PNP input/+ common) Connector Pin Configuration Top View 10 20 Relay No. 1 2 3 4 5 6 7 8 − + 1 11 2 12 3 13 4 14 5 15 6 16 7 17 8 18 9 19 10 20 9 10 11 12 13 14 15 16 − + mark Connector pin No. Connector pin No. 1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 9 19 X Input relays G2RV-1-S-AP-G X V V X V G G G Push-in power supply terminals X X X X X X X X X X X X X X V V V V V V V V V V V V V V V G G G G G G G G G G G G G G G Push-in I/O terminals Note: Pin numbers are indicated for convenience. The ▲ mark can be used to determine orientation. Terminal name V (push-in power supply terminals) G (push-in power supply terminals) V (push-in I/O terminals) G (push-in I/O terminals) Description Unit power supply terminals (24 VDC) Relay-drive coil terminals (24 VDC) 5 G70V G70V-SOC16P (NPN output/+ common) Note: A controller with an NPN transistor, common output can be connected to the G70V-SOC16P. Connector Pin Configuration Top View X Output relays Relay No. G2RV-1-S-G 1 2 3 4 5 6 7 8 − + 1 11 2 12 3 13 4 14 5 15 6 16 7 17 8 18 9 19 10 20 9 10 11 12 13 14 15 16 − + Connector pin No. mark Connector pin No. 1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 10 20 9 19 12 22 32 42 52 62 72 82 12 22 32 42 52 62 72 82 V V 14 24 34 44 54 64 74 84 14 24 34 44 54 64 74 84 G G 11 21 31 41 51 61 71 81 11 21 31 41 51 61 71 81 Note: Pin numbers are indicated for convenience. The ▲ mark can be used to determine orientation. Terminal name Description V (push-in power supply terminals) Unit power supply terminals (24 VDC) G (push-in power supply terminals) 11 to 81 (push-in I/O terminal common terminals) 12 to 82 (push-in I/O terminal NC terminals) Relay contact terminals 14 to 84 (push-in I/O terminal NO terminals) G70V-SOC16P-1 (PNP output/- common) Note: A controller with a PNP transistor, + common output can be connected to the G70V-SOC16P-1. Connector Pin Configuration Top View X Output relays G2RV-1-S-G Relay No. 1 2 3 4 5 6 7 8 − + 1 11 2 12 3 13 4 14 5 15 6 16 7 17 8 18 9 19 10 20 9 10 11 12 13 14 15 16 − + Connector pin No. mark Connector pin No. 1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 10 20 9 19 V V G G 12 14 11 22 24 21 32 34 31 42 44 41 52 54 51 62 64 61 72 74 71 82 84 81 12 14 11 22 24 21 Note: Pin numbers are indicated for convenience. The ▲ mark can be used to determine orientation. Terminal name V (push-in power supply terminals) G (push-in power supply terminals) Description Unit power supply terminals (24 VDC) 11 to 81 (push-in I/O terminal common terminals) 12 to 82 (push-in I/O terminal NC terminals) 14 to 84 (push-in I/O terminal NO terminals) 6 Relay contact terminals 32 34 31 42 44 41 52 54 51 62 64 61 72 74 71 82 84 81 G70V Dimensions (Unit: mm) I/O Relay Terminals and Relay Terminal Sockets For Inputs G70V-SID16P G70V-SID16P-1 G70V-ZID16P G70V-ZID16P-1 143 max. 4.35 4.2-dia. hole (M4 screw) 4.35 Relay 90 max. 35.2 7.5 4.35 10.26 4.1 5 4.35 4.2-dia. hole (M4 screw) 18.3 16.7 20.2 29.9 56 max. Note: 1. Relays are not mounted to the G70V-ZID16P(-1) Relay Terminal Sockets. The dimensions are for when Relays are not mounted. 2. Specified mounting torque: 0.59 to 0.98 N·m. For Outputs G70V-SOC16P G70V-SOC16P-1 G70V-ZOM16P G70V-ZOM16P-1 143 max. 4.35 4.2-dia. hole (M4 screw) 4.35 Relay 90 max. 35.2 7.8 7.8 4.35 10.26 4.1 4.35 4.2-dia. hole (M4 screw) 5 20.2 16.7 18.24 29.9 56 max. Note: 1. Relays are not mounted to the G70V-ZOM16P(-1) Relay Terminal Sockets. The dimensions are for when Relays are not mounted. 2. Specified mounting torque: 0.59 to 0.98 N·m. 7 G70V I/O Relay Terminal Details Input Relay Terminal G70V-SID16P G70V-SID16P-1 • Supply a power supply that meets the voltage specifications for both the Relays and I/O Relay Terminal to the V and G terminals. Make sure that the polarity is correct. The V terminals are positive and the G terminals are negative. • Supply the rated voltage (24 VDC) of the Controller’s input circuit to the power supply input terminals (V and G). Use a power supply with low noise. Power supply terminal block Communications connector Input Relays (G2RV-1-S-AP-G) Operation indicator (yellow) V V G G V DIN Track mounting hooks I/O Terminal Blocks V V V V V V V V G G G G G G G G V V V V V V V 24 VDC G G G G G G G G 24 VDC Output Relay Terminal G70V-SOC16P G70V-SOC16P-1 Power supply terminal block Operation indicator (yellow) Communications connector Output Relays (G2RV-1-S-G) • Supply a power supply that meets the voltage specifications for both the Relays and I/O Relay Terminal to the V and G terminals. Make sure that the polarity is correct. The V terminals are positive and the G terminals are negative. • The terminals (11 to 81, 12 to 82, and 14 to 84) are contact outputs. Supply a suitable power supply for the loads. • The power supply input terminals (V and G) supply power to both drive the Relays and to operate the Controller’s output transistors. Align the voltage specifications of the Controller and the I/O Relay Terminal. DIN Track mounting hooks I/O Terminal Blocks L0 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 L15 12 22 32 42 52 62 72 82 12 22 32 42 52 62 72 82 V 14 24 34 44 54 64 74 84 14 24 34 44 54 64 74 84 G G 11 21 31 41 51 61 71 81 11 21 31 41 51 61 71 81 AC (DC power supply is also possible.) V 24 VDC 8 G70V Safety Precautions Be sure to read the Common Precautions for I/O Relay Terminal in the website at the following URL: http://www.ia.omron.com/. Warning Indications Precautions for Safe Use Supplementary comments on what to do or avoid doing, to use the product safely. Precautions for Correct Use Supplementary comments on what to do or avoid doing, to prevent failure to operate, malfunction, or undesirable effects on product performance. Precautions for Safe Use Transportation • Do not transport the I/O Relay Terminal under the following locations. Doing so may occasionally result in damage, malfunction, or deterioration of performance characteristics. • Locations subject to water or oil • Locations subject to high temperature or high humidity • Locations subject to condensation due to rapid changes in temperature Operating and Storage Environments • Do not use or store the I/O Relay Terminal in the following locations. Doing so may result in damage, malfunction, or deterioration of performance characteristics. • Locations subject to rainwater or water splashes • Locations subject to exposure to water, oil, or chemicals • Locations subject to high temperature or high humidity • Locations subject to ambient storage temperatures outside the range −40 to 65°C • Locations subject to ambient operating temperatures outside the range −40 to 55°C • Locations subject to relative humidity outside the range 35% to 85% or locations in which condensation may occur due to rapid changes in temperature • Locations subject to corrosive gases or inflammable gases • Locations subject to dust, salts, or iron, or locations where there is salt damage • Locations subject to direct sunlight • Locations subject to shock or vibration Push-In Plus Terminal Blocks • Do not wire anything to the release holes. • Do not tilt or twist a flat-blade screwdriver while it is inserted into a release hole on the terminal block. The terminal block may be damaged. • Insert a flat-blade screwdriver into the release holes at an angle. The terminal block may be damaged if you insert the screwdriver straight in. • Do not allow the flat-blade screwdriver to fall out while it is inserted into a release hole. • Do not bend a wire past its natural bending radius or pull on it with excessive force. Doing so may cause the wire disconnection. • Do not insert more than one wire into each terminal insertion hole. • To prevent wiring materials from smoking or ignition, use the wiring materials given in the following table. Stripping length Recommended wire gauge 0.25 to 1.5mm2/AWG24 to 16 Ferrules used 10 mm Ferrules not used 8 mm Note: Please use Ferrules with UL certification (R/C). Application • Select a load within the rated values. Not doing so may result in malfunction, failure, or burning. • The I/O Relay Terminal may occasionally rupture if short-circuit current flows. As protection against accidents due to shortcircuiting, be sure to install protective devices, such as fuses and no-fuse breakers, on the power supply side. • Use a power supply within the rated frequencies. Otherwise, malfunction, failure, or burning may occasionally occur. • Minor electric shock may occasionally occur. Always turn OFF the power supply before performing wiring. Installation and Mounting • Mount the I/O Relay Terminal in the specified direction. Otherwise excessive heat generated by the I/O Relay Terminal may occasionally cause burning. • Mount the I/O Relay Terminal firmly to a DIN Track. Otherwise, the I/O Relay Terminal may fall off. • Do not handle the I/O Relay Terminal with oily or dusty (especially iron dust) hands. • Make sure that there is no excessive ambient temperature rise due to the heat generation of the I/O Relay Terminal. If the I/O Relay Terminal is mounted inside a panel, install a fan so that the interior of the panel is fully ventilated. Installation and Wiring • Use wires that are suited to the load current and voltage. Otherwise, excessive heat generated by the wires may cause burning or may cause the wire covering to melt, possibly leading to electric shock. • Do not use wires with a damaged outer covering. Otherwise, it may result in electric shock or ground leakage. • Do not wire any wiring in the same duct or conduit as power or high-tension lines. Otherwise, inductive noise may damage the I/O Relay Terminal or cause it to malfunction. • Do not apply a voltage or current that exceeds the rating to any terminal. Doing so may result in failure or burning. 9 G70V 2. Removing Wires from the Push-In Plus Terminal Block Precautions for Correct Use • Do not drop the I/O Relay Terminal or subject it to abnormal vibration or shock during transportation or mounting. Doing so may result in deterioration of performance, malfunction, or failure. • Do not transport an I/O Relay Terminal when it is not packaged. Damage or failure may occur. • Use a power supply with low noise. Use the following procedure to remove wires from the terminal block. The same method is used to remove stranded wires, solid wires, and ferrules. 1. Hold a flat-blade screwdriver at an angle and insert it into the release hole. 2. With the flat-blade screwdriver still inserted into the release hole, remove the wire from the terminal insertion hole. 3. Remove the flat-blade screwdriver from the release hole. Push-In Plus Terminal Blocks Flat-blade screwdriver 3 1 1. Connecting Wires to the Push-In Plus Terminal Block Part Names of the Terminal Block 3 1 10 to 15° 2 2 Release hole Wire Terminal (Insertion) hole 3. Recommended Ferrules and Crimp Tools Recommended ferrules Applicable wire Connecting Wires with Ferrules and Solid Wires Insert the solid wire or ferrule straight into the terminal block until the end strikes the terminal block. Release hole Terminal (Insertion) hole Ferrules and solid wires • If a wire is difficult to connect because it is too thin, use a flat-blade screwdriver in the same way as when connecting stranded wire. Connecting Stranded Wires Use the following procedure to connect the wires to the terminal block. 1. Hold a flat-blade screwdriver at an angle and insert it into the release hole. The angle should be between 10° and 15°. If the flat-blade screwdriver is inserted correctly, you will feel the spring in the release hole. 2. With the flat-blade screwdriver still inserted into the release hole, insert the wire into the terminal hole until it strikes the terminal block. 3. Remove the flat-blade screwdriver from the release hole. 1 Flat-blade screwdriver 3 3 1 10 to 15° 2 2 Stranded Wires Checking Connections • After the insertion, pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal block. • To prevent short circuits, insert the stripped part of a stranded or solid wire or the conductor part of a ferrule until it is hidden inside the terminal insertion hole. (See the following diagram.) 10 (mm2) (AWG) Recommended ferrules Ferrule Conduct or length (mm) Phoenix Contact product 0.25 24 8 AI0.25-8 0.34 22 0.5 20 0.75 18 Weidmuller product Wago product H0.25/12 FE-0.25-8N-YE 8 AI0.34-8 H0.34/12 FE-0.34-8N-TQ 8 AI0.5-8 H0.5/14 FE-0.5-8N-WH 8 AI0.75-8 H0.75/14 FE-0.75-8N-GY 1 18 8 AI1-8 H1.0/14 FE-1.0-8N-RD 1.5 16 8 AI1.5-8 H1.5/14 FE-1.5-8N-BK PZ6 roto Variocrimp4 Recommended crimp tool CRIMPFOX6 *1. Make sure that the outer diameter of the wire coating is smaller than the inner diameter of the insulation sleeve of the recommended ferrule. *2. Make sure that the ferrule processing dimensions conform to the following figures. 8 mm 2.7 mm max. 2.1 mm max. Recommended Flat-blade Screwdriver Use a flat-blade screwdriver to connect and remove wires. Use the following flat-blade screwdriver. The following table shows manufacturers and models as of 2015/Dec. Side Front 2.5 mm dia. 0.4 mm 2.5 mm Model Manufacturer XW4Z-00B Omron ESD0.40✕2.5 Wera SZF 0.4✕2.5 Phoenix Contact 0.4✕2.5✕75 302 Wiha AEF.2.5✕75 Facom 210-719 Wago SDI 0.4✕2.5✕75 Weidmuller G70V Applicable Cables Name Cables with Loose Wires and Crimp Terminals XW2Z-RY@C Appearance End B End A Device end I/O Relay Terminal 16 I/O points L 300 Cables with Loose Wires XW2Z-RA@C Connecting Cables 1,000 XW2Z-RY100C 1,500 XW2Z-RY150C 2,000 XW2Z-RY200C 3,000 XW2Z-RY300C 5,000 XW2Z-RY500C 2,000 XW2Z-RA200C 5,000 XW2Z-RA500C 1,000 XW2Z-R100C 1,500 XW2Z-R150C 2,000 XW2Z-R200C 3,000 XW2Z-R300C 16 I/O points 16 I/O points L (A) 32 input points Cables with Connectors (1:2) XW2Z-RI@C-@, XW2Z-RO@C-@ (120) 32 output points Applicable Connectors Various devices Various devices L 300 Cables with Connectors (1:1) XW2Z-R@C Cable length L (mm) (B) Straight length (without bends) 5,000 PLC I/O Units with Fujitsu connectors (1:1) XW2Z-R500C (A) 1,000 (B) 750 XW2Z-RI100C-75 (A) 1,500 (B) 1,250 XW2Z-RI150C-125 (A) 2,000 (B) 1,750 XW2Z-RI200C-175 (A) 3,000 (B) 2,750 XW2Z-RI300C-275 (A) 5,000 (B) 4,750 XW2Z-RI500C-475 (A) 1,000 (B) 750 XW2Z-RO100C-75 (A) 1,500 (B) 1,250 XW2Z-RO150C-125 (A) 2,000 (B) 1,750 XW2Z-RO200C-175 (A) 3,000 (B) 2,750 XW2Z-RO300C-275 (A) 5,000 (B) 4,750 XW2Z-RO500C-475 PLC I/O Units with Fujitsu connectors (1:2) (A) Cables with Connectors (1:3) XW2Z-R@C-@-@ 48 I/O points (B) (A) 1,500 (B) 1,250 (C) 1,000 XW2Z-R150C-125-100 (120) (A) 2,000 (B) 1,750 (C) 1,500 XW2Z-R200C-175-150 (A) 3,000 (B) 2,750 (C) 2,500 XW2Z-R300C-275-250 (270) (C) PLC I/O Units with Fujitsu connectors (1:3) Straight length (without bends) Cables with Connectors (1:1) XW2Z-RI@C, XW2Z-RO@C 16 input points 16 output points L 32 input points (A) Cables with Connectors (1:2) XW2Z-RI@-@-D1, XW2Z-RO@-@-D1, XW2Z-RM@-@-D1, XW2Z-RI@-@-D2, XW2Z-RM@-@-D2 32 output points 16 input points/ 16 output points 32 input points (120) (B) Straight length (without bends) 16 input points/ 16 output points 250 XW2Z-RI25C 500 XW2Z-RI50C 250 XW2Z-RO25C 500 PLC I/O Units with MIL connectors (1:1) XW2Z-RO50C (A) 500 (B) 250 XW2Z-RI50-25-D1 (A) 750 (B) 500 XW2Z-RI75-50-D1 (A) 500 (B) 250 XW2Z-RO50-25-D1 (A) 750 (B) 500 XW2Z-RO75-50-D1 (A) 500 (B) 250 XW2Z-RM50-25-D1 (A) 750 (B) 500 XW2Z-RM75-50-D1 (A) 500 (B) 250 XW2Z-RI50-25-D2 (A) 750 (B) 500 XW2Z-RI75-50-D2 (A) 500 (B) 250 XW2Z-RM50-25-D2 (A) 750 (B) 500 XW2Z-RM75-50-D2 PLC I/O Units with MIL connectors (NPN) (1:2) PLC I/O Units with MIL connectors (PNP) (1:2) 11 G70V Name Appearance End B End A Device end I/O Relay Terminal 32 input points Mitsubishi Electric PLC Connecting Cables XW2Z-RI@C-@-MN, XW2Z-RO@C-@-MN (A) (120) 32 output points (B) Straight length (without bends) (A) 32 input points (120) 32 output points (B) Straight length (without bends) Schneider Electric PLC Connecting Cables XW2Z-R@C-SCH-@ 16 input points L 16 output points (A) 32 input points (120) 32 output points (B) Straight length (without bends) Siemens PLC Connecting Cables XW2Z-R@C-SIM-@ 16 input points L (A) 32 input points (120) 32 output points (B) Straight length (without bends) 12 Cable length L (mm) Connecting Cables (A) 1,000 (B) 750 XW2Z-RI100C-75-MN (A) 1,500 (B) 1,250 XW2Z-RI150C-125-MN (A) 2,000 (B) 1,750 XW2Z-RI200C-175-MN (A) 3,000 (B) 2,750 XW2Z-RI300C-275-MN (A) 1,000 (B) 750 XW2Z-RO100C-75-MN (A) 1,500 (B) 1,250 XW2Z-RO150C-125-MN (A) 2,000 (B) 1,750 XW2Z-RO200C-175-MN (A) 3,000 (B) 2,750 XW2Z-RO300C-275-MN 500 XW2Z-R050C-SCH-A 1,000 XW2Z-R100C-SCH-A 2,000 XW2Z-R200C-SCH-A 3,000 XW2Z-R300C-SCH-A 5,000 XW2Z-R500C-SCH-A 500 XW2Z-R050C-SCH-B 1,000 XW2Z-R100C-SCH-B 2,000 XW2Z-R200C-SCH-B 3,000 XW2Z-R300C-SCH-B 5,000 XW2Z-R500C-SCH-B 500 XW2Z-R050C-SCH-C 1,000 XW2Z-R100C-SCH-C 2,000 XW2Z-R200C-SCH-C 3,000 XW2Z-R300C-SCH-C 5,000 XW2Z-R500C-SCH-C 500 XW2Z-R050C-SCH-D 1,000 XW2Z-R100C-SCH-D 2,000 XW2Z-R200C-SCH-D 3,000 XW2Z-R300C-SCH-D 5,000 XW2Z-R500C-SCH-D 500 XW2Z-R050C-SIM-A 1,000 XW2Z-R100C-SIM-A 2,000 XW2Z-R200C-SIM-A 3,000 XW2Z-R300C-SIM-A 5,000 XW2Z-R500C-SIM-A 500 XW2Z-R050C-SIM-B 1,000 XW2Z-R100C-SIM-B 2,000 XW2Z-R200C-SIM-B 3,000 XW2Z-R300C-SIM-B 5,000 XW2Z-R500C-SIM-B 500 XW2Z-R050C-SIM-C 1,000 XW2Z-R100C-SIM-C 2,000 XW2Z-R200C-SIM-C 3,000 XW2Z-R300C-SIM-C 5,000 XW2Z-R500C-SIM-C 500 XW2Z-R050C-SIM-D 1,000 XW2Z-R100C-SIM-D 2,000 XW2Z-R200C-SIM-D 3,000 XW2Z-R300C-SIM-D 5,000 XW2Z-R500C-SIM-D 500 XW2Z-R050C-SIM-E 1,000 XW2Z-R100C-SIM-E 2,000 XW2Z-R200C-SIM-E 3,000 XW2Z-R300C-SIM-E 5,000 XW2Z-R500C-SIM-E Applicable Connectors Mitsubishi Electric PLCs with 32-point connectors (1:2) For inputs: AX42, A1SX41, A1SX42 For outputs: AY42, A1SY41, A1SY42 Schneider Electric PLCs with 32-point connectors (1:2) For inputs: 140 DDI 353 00 For outputs: 140 DDO 353 00 Schneider Electric PLCs with 16-point connectors (1:1) For inputs: BMX DDI 1602 For outputs: BMX DDO 1602 Siemens PLCs with 32-point connectors (1:2) For inputs: 6ES7 321-1BL00-0AA0 For outputs: 6ES7 322-1BL00-0AA0 Siemens PLCs with 16-point connectors (1:1) For inputs: 6ES7 321-1BH02-0AA0 Siemens PLCs with 32-point connectors (1:2) For inputs: 6ES7 421-1BL-0AA0 For outputs: 6ES7 422-1BL-0AA0 Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. OMRON Corporation Industrial Automation Company Authorized Distributor: Kyoto, JAPAN Contact: www.ia.omron.com Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69, 2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC 2895 Greenspoint Parkway, Suite 200 Hoffman Estates, IL 60169 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 OMRON ASIA PACIFIC PTE. LTD. No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711 OMRON (CHINA) CO., LTD. Room 2211, Bank of China Tower, 200 Yin Cheng Zhong Road, PuDong New Area, Shanghai, 200120, China Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 © OMRON Corporation 2016 All Rights Reserved. In the interest of product improvement, specifications are subject to change without notice. CSM_1_2_0516 Cat. No. J215-E1-01 0316(0316)