• I/O Relay Terminals with 16 points to mount G2RV Slim I/O
Relays.
• Push-In Plus terminal blocks are used to save wiring work in
comparison with traditional screw terminals. (Wiring time is
reduced by 60%* in comparison with traditional screw
terminals.)
• Work is reduced ever further with one-step cable connection
to the PLC.
• Diode provided for coil surge absorption.
• Operation indicators for immediate recognition of I/O signal
status.
• Accepts G3RV Slim I/O SSRs.
• DIN Track or screw mounting.
For the most recent information on models that have been
certified for safety standards, refer to your OMRON website.
* According to OMRON actual measurement data from November 2015.
Refer to Safety Precautions on page 9.
Model Number Legend
G70V - @ @ @ 16 P - @
(1) (2) (3) (4) (5) (6)
(1) Mountable Relays
S: Relays
Z: Sockets
(2) Input/Output Classification
I: For input
O: For output
(3) I/O Specification
C: Contacts (Applicable when (2) is O
(for output) (relay output).)
D: DC (Applicable when (2) is I (for
input) (coil for input).)
M: AC/DC (Applicable when (1) is Z
(Sockets).)
(4) Number of I/O Points
16: 16 points
(5) Terminal Type
P: Push-In Plus terminal blocks
(6) Internal I/O Circuit Common
Blank: NPN
1: PNP
(For Input NPN)
PLC
(For Input PNP)
G70V
(+)
PLC
G70V
)+(
−
Common
)−(
(−)
(For Output NPN)
+ Common
(For Output PNP)
PLC
G70V
PLC
−
X
+
(−)
G70V
(+)
(+)
NPN
transistor
Common
X
Common
PNP
transistor
X
X
(−)
1
G70V
Ordering Information
I/O Relay Terminal
Terminals
Type
Internal I/O circuit
common
Points
Rated
voltage
Model
NPN (– common)
Input *1
Push-In Plus terminal blocks
PNP (+ common)
16
NPN (+ common)
Output *2
G70V-SID16P
G70V-SID16P-1
24 VDC
G70V-SOC16P
PNP (– common)
G70V-SOC16P-1
*1. Mountable Relays: G2RV-1-S-AP-G DC21V.
*2. Mountable Relays: G2RV-1-S-G DC21V.
Relay Terminal Sockets
Applicable I/O Relay Terminal
Type
G70V-SID16P
Common Processing in Connector
Input
G70V-SID16P-1
G70V-SOC16P
Output
G70V-SOC16P-1
Model
NPN (– common)
G70V-ZID16P
PNP (+ common)
G70V-ZID16P-1
NPN (+ common)
G70V-ZOM16P
PNP (– common)
G70V-ZOM16P-1
Note: Relays are not mounted to the G70V-ZID/ZOM16P(-1) Relay Terminal Sockets. Combine the Relay Terminal Sockets with Slim I/O Relays
or Slim I/O SSRs.
Accessories (Order Separately)
Mountable Relays
Applicable I/O Relay Terminal
G70V-SID16P(-1)
Type
Input
Classification
Slim I/O Relays
G70V-SOC16P(-1)
Model
Slim I/O Relays *1
Output
Slim I/O SSRs
G2RV-1-S-AP-G DC21
No Latching Lever *2
G2RV-1-S-G DC21
Latching Lever
G2RV-1-SI-G DC21
For AC
Zero cross function
G3RV-202S DC24
No zero cross function
G3RV-202SL DC24
For DC
G3RV-D03SL DC24
Note: To use Slim I/O SSRs, either remove the Slim I/O Relays to mount them or order a Relay Terminal Socket and I/O SSRs separately and
combine them.
*1. G2RV-1-S-AP-G Slim I/O Relays are mounted to G70V-SID16P(- 1) I/O Relay Terminals as a standard feature.
*2. G2RV-1-S-G Slim I/O Relays are mounted to G70V-SOC16P(- 1) I/O Relay Terminals as a standard feature.
When ordering, designate the rated voltage.
Connecting Cables XW2Z-R
• Cable with Loose Wire and Crimp Terminals:
• Cable with Loose Wires:
• Cable with Fujitsu connectors (1:1):
(1:2):
(1:3):
• Cable with MIL connectors (1:1):
(1:2):
Refer to Applicable Cables on page 11 for details.
Labels
XW2Z-RY@C
XW2Z-RA@C
XW2Z-R@C
XW2Z-RI@C-@
XW2Z-RO@C-@
XW2Z-R@C-@-@
XW2Z-RI@C
XW2Z-RO@C
XW2Z-RI@-@-D@
XW2Z-RM@-@-D@
XW2Z-RO@-@-D1
Minimum order (sheet)
(quantity per sheet)
Model
5
(1 sheet / 72 pieces)
XW5Z-P2.5LB2
Parts for DIN Track Mounting
Type
DIN
Tracks
Model
1m
PFP-100N
0.5 m
PFP-50N
End Plate
PFP-M
Spacer
PFP-S
Minimum order (quantity)
--10
Refer to your OMRON website for details on the PFP-@.
2
G70V
Specifications
Coil Ratings (Common to Input/Output per Relay)
Item
Rated voltage (V)
Rated current
(mA)
Coil resistance
(Ω)
Must
operate of
rated voltage
13.3
1575
80% max.
24 VDC
Must
Maximum
release of rated voltage of rated
voltage
voltage
10% min.
110%
Power
consumption
(mW)
Approx. 280
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with a tolerance of ±15% for coil resistance.
2. The operating characteristics are measured at a coil temperature of 23°C.
3. The value for maximum voltage is the maximum value within the allowable voltage fluctuation range for the relay coil’s operating power
supply. Continuous operation at this voltage is not within product specifications.
4. The rated current includes the current for the indicators on the I/O Relay Terminal.
Contact Ratings (G2RV-1-S-G I/O Relay)
Classification
For input
For output
Resistive load (cosφ=1)
Item
Inductive load
(cosφ=0.4 L/R=7 ms)
Resistive load (cosφ=1)
Rated load
50 mA at 30 VAC
50 mA at 36 VDC
6 A at 250 VAC
6 A at 30 VDC
2.5 A at 250 VAC
2 A at 30 VDC
Rated carry current
50 mA
6A
Max. switching voltage
30 VAC, 36 VDC
250 VAC, 125 VDC
Max. switching current
50 mA
6A
Maximum switching capacity
---
1,500 VA
180 W
Error rate (reference value) *
1 mA at 100 mVDC
10 mA at 5 VDC
Electrical life expectancy
5,000,000 operations min.
NO contacts: 70,000 operations min.
NC contacts: 50,000 operations min.
Mechanical life expectancy
5,000,000 operations min.
5,000,000 operations min.
500 VA
60 W
* The above values are for a switching frequency of 120 operations/min.
Characteristics
G70V-SID16P(-1)
(Input, DC coil)
Model
Item
Contact form
G70V-SOC16P(-1)
(output, DC coil)
SPST-NO × 16
SPDT×16
Contact material
Ag alloy + Au plating
Ag alloy
Contact resistance *1
150 mΩ max.
Must Operate time *2
20 ms max.
Release time *2
40 ms max.
Max.
switching
frequency
Mechanical limit
18,000 operations/hour
At rated load
1,800 operations/hr (under rated load)
Insulation resistance
100 MΩ min.
Dielectric strength
Between coil and contacts: 2,500 VAC for 1 min
Vibration resistance
100 m/s2
Shock resistance
100 m/s2, 3 times each in 6 directions along 3 axes
Noise immunity
Noise level: 1.5 kV; pulse width: 100 ns to 1 μs
Ambient operating
temperature
−40 to 55°C (with no icing or condensation)
Ambient operating humidity
35% to 85% RH
LED color
Power supply
Green
I/O
Yellow
Weight
Approx. 350 g
Approx. 370 g
Note: The above values are initial values.
*1. Measurement condition: 1 A at 5 VDC.
*2. Ambient temperature: 23°C.
Applicable Standards
• UL 61010-2-201, CAN/CSA-C22.2 No.61010-2-201, TÜV (EN 61810-1)
3
G70V
Engineering Data (Reference Value)
Operations (× 103)
Endurance Curve (NO Contacts)
G70V-SOC16P(-1)
1000
30 VDC resistive load
250 VAC resistive load
100
30 VDC
inductive load
250 VAC inductive load
10
0
2
4
6
Switched current (A)
Note: These data are actual measured values that were sampled from the production line and prepared in graph format, and are for reference
purposes only. A relay is manufactured by mass production, and as a basic rule must be used with allowance made for a certain amount of
deviation.
Load Current vs. Ambient Temperature
G3RV-202S DC24
G70V-SOC16P(-1)
G3RV-D03 DC24
(A)
Single Relay
6
16 points ON
5
(A)
Load Current (A)
Load Current (A)
Load Current (A)
G3RV-202SL DC24
3
4
(A)
3
Single Relay
Single Relay
2
2
3
16 points ON
16 points ON
2
1
1
1
0.5
0.2
0
-40
-20
0
0
-40
20 25
40
55 60
Ambient Temperature
-20
0
20 25
40 55 60
Ambient Temperature
0
-40
Inrush Current Resistance: Non-repetitive
The following graphs show the maximum inrush currents that can be withstood for non-repetitive operation.
For repetitive operation, the figures should be reduced by half.
G3RV-D03 DC24
Inrush current (A. Peak)
Inrush current (A. Peak)
G3RV-202S DC24
G3RV-202SL DC24
40
35
30
25
35
30
25
20
20
15
15
10
10
5
5
0
10
30 50
100
300 500 1,000
3,000 5,000
Energized time (ms)
4
40
0
10
30 50
100
300 500 1,000
3,000 5,000
Energized time (ms)
-20
0
20
40 55 60
Ambient Temperature
G70V
Terminal Arrangement/Internal Connection
G70V-SID16P
(NPN input/– common)
Connector Pin Configuration
Top View
10
20
Relay No.
1
2
3
4
5
6
7
8
+
−
1
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
9
10
11
12
13
14
15
16
+
−
Connector
pin No.
1
2
3
4
5
6
7
8
11
12
13
14
15
16
17
18
9
19
X Input relays
G2RV-1-S-AP-G
X
V
V
X
V
G G
G
Push-in power supply terminals
X
X
X
X
X
X
X
X
X
X
X
X
X
X
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
Push-in I/O terminals
mark
Connector pin No.
Note: Pin numbers are indicated for convenience. The ▲ mark can be used to determine orientation.
Terminal name
Description
V (push-in power supply terminals)
Unit power supply terminals (24 VDC)
G (push-in power supply terminals)
V (push-in I/O terminals)
Relay-drive coil terminals (24 VDC)
G (push-in I/O terminals)
G70V-SID16P-1
(PNP input/+ common)
Connector Pin Configuration
Top View
10
20
Relay No.
1
2
3
4
5
6
7
8
−
+
1
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
9
10
11
12
13
14
15
16
−
+
mark
Connector pin No.
Connector
pin No.
1
2
3
4
5
6
7
8
11
12
13
14
15
16
17
18
9
19
X Input relays
G2RV-1-S-AP-G
X
V
V
X
V
G G
G
Push-in power supply terminals
X
X
X
X
X
X
X
X
X
X
X
X
X
X
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
Push-in I/O terminals
Note: Pin numbers are indicated for convenience. The ▲ mark can be used to determine orientation.
Terminal name
V (push-in power supply terminals)
G (push-in power supply terminals)
V (push-in I/O terminals)
G (push-in I/O terminals)
Description
Unit power supply terminals (24 VDC)
Relay-drive coil terminals (24 VDC)
5
G70V
G70V-SOC16P
(NPN output/+ common)
Note: A controller with an NPN transistor, common output can be connected to the G70V-SOC16P.
Connector Pin Configuration
Top View
X Output relays
Relay No.
G2RV-1-S-G
1
2
3
4
5
6
7
8
−
+
1
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
9
10
11
12
13
14
15
16
−
+
Connector
pin No.
mark
Connector pin No.
1
2
3
4
5
6
7
8
11
12
13
14
15
16
17
18
10
20
9
19
12
22
32
42
52
62
72
82
12
22
32
42
52
62
72
82
V
V
14
24
34
44
54
64
74
84
14
24
34
44
54
64
74
84
G
G
11
21
31
41
51
61
71
81
11
21
31
41
51
61
71
81
Note: Pin numbers are indicated for convenience. The ▲ mark can be used to determine orientation.
Terminal name
Description
V (push-in power supply terminals)
Unit power supply terminals (24 VDC)
G (push-in power supply terminals)
11 to 81 (push-in I/O terminal common terminals)
12 to 82 (push-in I/O terminal NC terminals)
Relay contact terminals
14 to 84 (push-in I/O terminal NO terminals)
G70V-SOC16P-1
(PNP output/- common)
Note: A controller with a PNP transistor, + common output can be connected to the G70V-SOC16P-1.
Connector Pin Configuration
Top View
X Output relays
G2RV-1-S-G
Relay No.
1
2
3
4
5
6
7
8
−
+
1
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
9
10
11
12
13
14
15
16
−
+
Connector
pin No.
mark
Connector pin No.
1
2
3
4
5
6
7
8
11
12
13
14
15
16
17
18
10
20
9
19
V
V
G
G
12
14
11
22
24
21
32
34
31
42
44
41
52
54
51
62
64
61
72
74
71
82
84
81
12
14
11
22
24
21
Note: Pin numbers are indicated for convenience. The ▲ mark can be used to determine orientation.
Terminal name
V (push-in power supply terminals)
G (push-in power supply terminals)
Description
Unit power supply terminals (24 VDC)
11 to 81 (push-in I/O terminal common terminals)
12 to 82 (push-in I/O terminal NC terminals)
14 to 84 (push-in I/O terminal NO terminals)
6
Relay contact terminals
32
34
31
42
44
41
52
54
51
62
64
61
72
74
71
82
84
81
G70V
Dimensions
(Unit: mm)
I/O Relay Terminals and Relay Terminal Sockets
For Inputs
G70V-SID16P
G70V-SID16P-1
G70V-ZID16P
G70V-ZID16P-1
143 max.
4.35
4.2-dia. hole (M4 screw)
4.35
Relay
90 max.
35.2
7.5
4.35
10.26
4.1
5
4.35
4.2-dia. hole
(M4 screw)
18.3
16.7
20.2
29.9
56 max.
Note: 1. Relays are not mounted to the G70V-ZID16P(-1) Relay Terminal Sockets.
The dimensions are for when Relays are not mounted.
2. Specified mounting torque: 0.59 to 0.98 N·m.
For Outputs
G70V-SOC16P
G70V-SOC16P-1
G70V-ZOM16P
G70V-ZOM16P-1
143 max.
4.35
4.2-dia. hole (M4 screw)
4.35
Relay
90 max.
35.2
7.8
7.8
4.35
10.26
4.1
4.35
4.2-dia. hole
(M4 screw)
5
20.2
16.7
18.24
29.9
56 max.
Note: 1. Relays are not mounted to the G70V-ZOM16P(-1) Relay Terminal Sockets.
The dimensions are for when Relays are not mounted.
2. Specified mounting torque: 0.59 to 0.98 N·m.
7
G70V
I/O Relay Terminal Details
Input Relay Terminal
G70V-SID16P
G70V-SID16P-1
• Supply a power supply that meets the voltage specifications
for both the Relays and I/O Relay Terminal to the V and G
terminals.
Make sure that the polarity is correct.
The V terminals are positive and the G terminals are
negative.
• Supply the rated voltage (24 VDC) of the Controller’s input
circuit to the power supply input terminals (V and G). Use a
power supply with low noise.
Power supply terminal block
Communications
connector
Input Relays
(G2RV-1-S-AP-G)
Operation indicator
(yellow)
V
V
G G
V
DIN Track mounting hooks
I/O Terminal
Blocks
V
V
V
V
V
V
V
V
G G G G G G G G
V
V
V
V
V
V
V
24 VDC
G G G G G G G G
24 VDC
Output Relay Terminal
G70V-SOC16P
G70V-SOC16P-1
Power supply terminal block
Operation
indicator (yellow)
Communications
connector
Output Relays
(G2RV-1-S-G)
• Supply a power supply that meets the voltage specifications
for both the Relays and I/O Relay Terminal to the V and G
terminals.
Make sure that the polarity is correct.
The V terminals are positive and the G terminals are
negative.
• The terminals (11 to 81, 12 to 82, and 14 to 84) are contact
outputs. Supply a suitable power supply for the loads.
• The power supply input terminals (V and G) supply power to
both drive the Relays and to operate the Controller’s output
transistors.
Align the voltage specifications of the Controller and the I/O
Relay Terminal.
DIN Track mounting hooks I/O Terminal Blocks
L0 L1 L2 L3 L4 L5 L6 L7
L8 L9 L10 L11 L12 L13 L14 L15
12 22 32 42 52 62 72 82
12 22 32 42 52 62 72 82
V
14 24 34 44 54 64 74 84
14 24 34 44 54 64 74 84
G G
11 21 31 41 51 61 71 81
11 21 31 41 51 61 71 81
AC (DC power supply is also possible.)
V
24 VDC
8
G70V
Safety Precautions
Be sure to read the Common Precautions for I/O Relay Terminal in the website at the following URL:
http://www.ia.omron.com/.
Warning Indications
Precautions for
Safe Use
Supplementary comments on what to do
or avoid doing, to use the product safely.
Precautions for
Correct Use
Supplementary comments on what to do
or avoid doing, to prevent failure to
operate, malfunction, or undesirable
effects on product performance.
Precautions for Safe Use
Transportation
• Do not transport the I/O Relay Terminal under the following
locations. Doing so may occasionally result in damage,
malfunction, or deterioration of performance characteristics.
• Locations subject to water or oil
• Locations subject to high temperature or high humidity
• Locations subject to condensation due to rapid changes in
temperature
Operating and Storage Environments
• Do not use or store the I/O Relay Terminal in the following
locations. Doing so may result in damage, malfunction, or
deterioration of performance characteristics.
• Locations subject to rainwater or water splashes
• Locations subject to exposure to water, oil, or chemicals
• Locations subject to high temperature or high humidity
• Locations subject to ambient storage temperatures outside the
range −40 to 65°C
• Locations subject to ambient operating temperatures outside the
range −40 to 55°C
• Locations subject to relative humidity outside the range 35% to
85% or locations in which condensation may occur due to rapid
changes in temperature
• Locations subject to corrosive gases or inflammable gases
• Locations subject to dust, salts, or iron, or locations where there
is salt damage
• Locations subject to direct sunlight
• Locations subject to shock or vibration
Push-In Plus Terminal Blocks
• Do not wire anything to the release holes.
• Do not tilt or twist a flat-blade screwdriver while it is inserted into a
release hole on the terminal block. The terminal block may be
damaged.
• Insert a flat-blade screwdriver into the release holes at an angle.
The terminal block may be damaged if you insert the screwdriver
straight in.
• Do not allow the flat-blade screwdriver to fall out while it is inserted
into a release hole.
• Do not bend a wire past its natural bending radius or pull on it with
excessive force. Doing so may cause the wire disconnection.
• Do not insert more than one wire into each terminal insertion hole.
• To prevent wiring materials from smoking or ignition, use the wiring
materials given in the following table.
Stripping length
Recommended wire gauge
0.25 to 1.5mm2/AWG24 to 16
Ferrules used
10 mm
Ferrules not
used
8 mm
Note: Please use Ferrules with UL certification (R/C).
Application
• Select a load within the rated values. Not doing so may result in
malfunction, failure, or burning.
• The I/O Relay Terminal may occasionally rupture if short-circuit
current flows. As protection against accidents due to shortcircuiting, be sure to install protective devices, such as fuses and
no-fuse breakers, on the power supply side.
• Use a power supply within the rated frequencies. Otherwise,
malfunction, failure, or burning may occasionally occur.
• Minor electric shock may occasionally occur. Always turn OFF the
power supply before performing wiring.
Installation and Mounting
• Mount the I/O Relay Terminal in the specified direction. Otherwise
excessive heat generated by the I/O Relay Terminal may
occasionally cause burning.
• Mount the I/O Relay Terminal firmly to a DIN Track. Otherwise, the
I/O Relay Terminal may fall off.
• Do not handle the I/O Relay Terminal with oily or dusty (especially
iron dust) hands.
• Make sure that there is no excessive ambient temperature rise due
to the heat generation of the I/O Relay Terminal. If the I/O Relay
Terminal is mounted inside a panel, install a fan so that the interior
of the panel is fully ventilated.
Installation and Wiring
• Use wires that are suited to the load current and voltage.
Otherwise, excessive heat generated by the wires may cause
burning or may cause the wire covering to melt, possibly leading to
electric shock.
• Do not use wires with a damaged outer covering. Otherwise, it may
result in electric shock or ground leakage.
• Do not wire any wiring in the same duct or conduit as power or
high-tension lines. Otherwise, inductive noise may damage the I/O
Relay Terminal or cause it to malfunction.
• Do not apply a voltage or current that exceeds the rating to any
terminal. Doing so may result in failure or burning.
9
G70V
2. Removing Wires from the Push-In Plus Terminal Block
Precautions for Correct Use
• Do not drop the I/O Relay Terminal or subject it to abnormal
vibration or shock during transportation or mounting. Doing so may
result in deterioration of performance, malfunction, or failure.
• Do not transport an I/O Relay Terminal when it is not packaged.
Damage or failure may occur.
• Use a power supply with low noise.
Use the following procedure to remove wires from the terminal block.
The same method is used to remove stranded wires, solid wires, and
ferrules.
1. Hold a flat-blade screwdriver at an angle and insert it into the
release hole.
2. With the flat-blade screwdriver still inserted into the release hole,
remove the wire from the terminal insertion hole.
3. Remove the flat-blade screwdriver from the release hole.
Push-In Plus Terminal Blocks
Flat-blade screwdriver
3
1
1. Connecting Wires to the Push-In Plus Terminal Block
Part Names of the Terminal Block
3
1
10 to 15°
2
2
Release hole
Wire
Terminal (Insertion) hole
3. Recommended Ferrules and Crimp Tools
Recommended ferrules
Applicable wire
Connecting Wires with Ferrules and Solid Wires
Insert the solid wire or ferrule straight into the terminal block until the
end strikes the terminal block.
Release hole
Terminal (Insertion) hole
Ferrules
and solid wires
• If a wire is difficult to connect because it is too thin, use a flat-blade
screwdriver in the same way as when connecting stranded wire.
Connecting Stranded Wires
Use the following procedure to connect the wires to the terminal block.
1. Hold a flat-blade screwdriver at an angle and insert it into the
release hole.
The angle should be between 10° and 15°. If the flat-blade
screwdriver is inserted correctly, you will feel the spring in the
release hole.
2. With the flat-blade screwdriver still inserted into the release hole,
insert the wire into the terminal hole until it strikes the terminal
block.
3. Remove the flat-blade screwdriver from the release hole.
1
Flat-blade screwdriver
3
3
1
10 to 15°
2
2
Stranded Wires
Checking Connections
• After the insertion, pull gently on the wire to make sure that it will
not come off and the wire is securely fastened to the terminal block.
• To prevent short circuits, insert the stripped part of a stranded or
solid wire or the conductor part of a ferrule until it is hidden inside
the terminal insertion hole. (See the following diagram.)
10
(mm2)
(AWG)
Recommended ferrules
Ferrule
Conduct
or length
(mm)
Phoenix
Contact
product
0.25
24
8 AI0.25-8
0.34
22
0.5
20
0.75
18
Weidmuller
product
Wago product
H0.25/12
FE-0.25-8N-YE
8 AI0.34-8
H0.34/12
FE-0.34-8N-TQ
8 AI0.5-8
H0.5/14
FE-0.5-8N-WH
8 AI0.75-8
H0.75/14
FE-0.75-8N-GY
1
18
8 AI1-8
H1.0/14
FE-1.0-8N-RD
1.5
16
8 AI1.5-8
H1.5/14
FE-1.5-8N-BK
PZ6 roto
Variocrimp4
Recommended crimp tool
CRIMPFOX6
*1. Make sure that the outer diameter of the wire coating is smaller
than the inner diameter of the insulation sleeve of the
recommended ferrule.
*2. Make sure that the ferrule processing dimensions conform to the
following figures.
8 mm
2.7 mm max.
2.1 mm max.
Recommended Flat-blade Screwdriver
Use a flat-blade screwdriver to connect and remove wires.
Use the following flat-blade screwdriver.
The following table shows manufacturers and models as of 2015/Dec.
Side
Front
2.5 mm dia.
0.4 mm
2.5 mm
Model
Manufacturer
XW4Z-00B
Omron
ESD0.40✕2.5
Wera
SZF 0.4✕2.5
Phoenix Contact
0.4✕2.5✕75 302
Wiha
AEF.2.5✕75
Facom
210-719
Wago
SDI 0.4✕2.5✕75
Weidmuller
G70V
Applicable Cables
Name
Cables with Loose
Wires and Crimp
Terminals
XW2Z-RY@C
Appearance
End B
End A
Device end
I/O Relay Terminal
16 I/O points
L
300
Cables with Loose
Wires
XW2Z-RA@C
Connecting Cables
1,000
XW2Z-RY100C
1,500
XW2Z-RY150C
2,000
XW2Z-RY200C
3,000
XW2Z-RY300C
5,000
XW2Z-RY500C
2,000
XW2Z-RA200C
5,000
XW2Z-RA500C
1,000
XW2Z-R100C
1,500
XW2Z-R150C
2,000
XW2Z-R200C
3,000
XW2Z-R300C
16 I/O points
16 I/O points
L
(A)
32 input points
Cables with
Connectors (1:2)
XW2Z-RI@C-@,
XW2Z-RO@C-@
(120)
32 output points
Applicable Connectors
Various devices
Various devices
L
300
Cables with
Connectors (1:1)
XW2Z-R@C
Cable length L (mm)
(B)
Straight length (without bends)
5,000
PLC I/O Units with Fujitsu
connectors (1:1)
XW2Z-R500C
(A) 1,000
(B) 750
XW2Z-RI100C-75
(A) 1,500
(B) 1,250
XW2Z-RI150C-125
(A) 2,000
(B) 1,750
XW2Z-RI200C-175
(A) 3,000
(B) 2,750
XW2Z-RI300C-275
(A) 5,000
(B) 4,750
XW2Z-RI500C-475
(A) 1,000
(B) 750
XW2Z-RO100C-75
(A) 1,500
(B) 1,250
XW2Z-RO150C-125
(A) 2,000
(B) 1,750
XW2Z-RO200C-175
(A) 3,000
(B) 2,750
XW2Z-RO300C-275
(A) 5,000
(B) 4,750
XW2Z-RO500C-475
PLC I/O Units with Fujitsu
connectors (1:2)
(A)
Cables with
Connectors (1:3)
XW2Z-R@C-@-@
48 I/O points
(B)
(A) 1,500
(B) 1,250
(C) 1,000
XW2Z-R150C-125-100
(120)
(A) 2,000
(B) 1,750
(C) 1,500
XW2Z-R200C-175-150
(A) 3,000
(B) 2,750
(C) 2,500
XW2Z-R300C-275-250
(270)
(C)
PLC I/O Units with Fujitsu
connectors (1:3)
Straight length (without bends)
Cables with
Connectors (1:1)
XW2Z-RI@C,
XW2Z-RO@C
16 input points
16 output points
L
32 input points
(A)
Cables with
Connectors (1:2)
XW2Z-RI@-@-D1,
XW2Z-RO@-@-D1,
XW2Z-RM@-@-D1,
XW2Z-RI@-@-D2,
XW2Z-RM@-@-D2
32 output points
16 input points/
16 output points
32 input points
(120)
(B)
Straight length (without bends)
16 input points/
16 output points
250
XW2Z-RI25C
500
XW2Z-RI50C
250
XW2Z-RO25C
500
PLC I/O Units with
MIL connectors (1:1)
XW2Z-RO50C
(A) 500
(B) 250
XW2Z-RI50-25-D1
(A) 750
(B) 500
XW2Z-RI75-50-D1
(A) 500
(B) 250
XW2Z-RO50-25-D1
(A) 750
(B) 500
XW2Z-RO75-50-D1
(A) 500
(B) 250
XW2Z-RM50-25-D1
(A) 750
(B) 500
XW2Z-RM75-50-D1
(A) 500
(B) 250
XW2Z-RI50-25-D2
(A) 750
(B) 500
XW2Z-RI75-50-D2
(A) 500
(B) 250
XW2Z-RM50-25-D2
(A) 750
(B) 500
XW2Z-RM75-50-D2
PLC I/O Units with
MIL connectors (NPN) (1:2)
PLC I/O Units with
MIL connectors (PNP) (1:2)
11
G70V
Name
Appearance
End B
End A
Device end
I/O Relay Terminal
32 input points
Mitsubishi Electric PLC
Connecting Cables
XW2Z-RI@C-@-MN,
XW2Z-RO@C-@-MN
(A)
(120)
32 output points
(B)
Straight length (without bends)
(A)
32 input points
(120)
32 output points
(B)
Straight length (without bends)
Schneider Electric PLC
Connecting Cables
XW2Z-R@C-SCH-@
16 input points
L
16 output points
(A)
32 input points
(120)
32 output points
(B)
Straight length (without bends)
Siemens PLC
Connecting Cables
XW2Z-R@C-SIM-@
16 input points
L
(A)
32 input points
(120)
32 output points
(B)
Straight length (without bends)
12
Cable length L (mm)
Connecting Cables
(A) 1,000
(B) 750
XW2Z-RI100C-75-MN
(A) 1,500
(B) 1,250
XW2Z-RI150C-125-MN
(A) 2,000
(B) 1,750
XW2Z-RI200C-175-MN
(A) 3,000
(B) 2,750
XW2Z-RI300C-275-MN
(A) 1,000
(B) 750
XW2Z-RO100C-75-MN
(A) 1,500
(B) 1,250
XW2Z-RO150C-125-MN
(A) 2,000
(B) 1,750
XW2Z-RO200C-175-MN
(A) 3,000
(B) 2,750
XW2Z-RO300C-275-MN
500
XW2Z-R050C-SCH-A
1,000
XW2Z-R100C-SCH-A
2,000
XW2Z-R200C-SCH-A
3,000
XW2Z-R300C-SCH-A
5,000
XW2Z-R500C-SCH-A
500
XW2Z-R050C-SCH-B
1,000
XW2Z-R100C-SCH-B
2,000
XW2Z-R200C-SCH-B
3,000
XW2Z-R300C-SCH-B
5,000
XW2Z-R500C-SCH-B
500
XW2Z-R050C-SCH-C
1,000
XW2Z-R100C-SCH-C
2,000
XW2Z-R200C-SCH-C
3,000
XW2Z-R300C-SCH-C
5,000
XW2Z-R500C-SCH-C
500
XW2Z-R050C-SCH-D
1,000
XW2Z-R100C-SCH-D
2,000
XW2Z-R200C-SCH-D
3,000
XW2Z-R300C-SCH-D
5,000
XW2Z-R500C-SCH-D
500
XW2Z-R050C-SIM-A
1,000
XW2Z-R100C-SIM-A
2,000
XW2Z-R200C-SIM-A
3,000
XW2Z-R300C-SIM-A
5,000
XW2Z-R500C-SIM-A
500
XW2Z-R050C-SIM-B
1,000
XW2Z-R100C-SIM-B
2,000
XW2Z-R200C-SIM-B
3,000
XW2Z-R300C-SIM-B
5,000
XW2Z-R500C-SIM-B
500
XW2Z-R050C-SIM-C
1,000
XW2Z-R100C-SIM-C
2,000
XW2Z-R200C-SIM-C
3,000
XW2Z-R300C-SIM-C
5,000
XW2Z-R500C-SIM-C
500
XW2Z-R050C-SIM-D
1,000
XW2Z-R100C-SIM-D
2,000
XW2Z-R200C-SIM-D
3,000
XW2Z-R300C-SIM-D
5,000
XW2Z-R500C-SIM-D
500
XW2Z-R050C-SIM-E
1,000
XW2Z-R100C-SIM-E
2,000
XW2Z-R200C-SIM-E
3,000
XW2Z-R300C-SIM-E
5,000
XW2Z-R500C-SIM-E
Applicable Connectors
Mitsubishi Electric PLCs
with 32-point connectors
(1:2)
For inputs:
AX42, A1SX41, A1SX42
For outputs:
AY42, A1SY41, A1SY42
Schneider Electric PLCs
with 32-point connectors
(1:2)
For inputs:
140 DDI 353 00
For outputs:
140 DDO 353 00
Schneider Electric PLCs
with 16-point connectors
(1:1)
For inputs:
BMX DDI 1602
For outputs:
BMX DDO 1602
Siemens PLCs with
32-point connectors (1:2)
For inputs:
6ES7 321-1BL00-0AA0
For outputs:
6ES7 322-1BL00-0AA0
Siemens PLCs with
16-point connectors (1:1)
For inputs:
6ES7 321-1BH02-0AA0
Siemens PLCs with
32-point connectors (1:2)
For inputs:
6ES7 421-1BL-0AA0
For outputs:
6ES7 422-1BL-0AA0
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Kyoto, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2016 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
CSM_1_2_0516
Cat. No. J215-E1-01
0316(0316)