Transmag 2 with sensor 911/E Catalog Specifications Sheet

© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter TRANSMAG 2 with sensor 911/E
■ Overview
■ Mode of operation
The flow measuring principle is based on Faraday’s law of electromagnetic induction according to which the sensor converts
the flow into an electrical voltage proportional to the velocity of
the flow.
■ Function
The TRANSMAG 2 is a microprocessor-based transmitter with a
build-in alphanumeric display in several languages. The transmitters evaluate the signals from the associated electromagnetic
sensors and also fulfil the task of a power supply unit which provides the magnet coils with a constant current.
The magnetic flux density in the sensor is additionally monitored
by reference coils.
Further information on connection, mode of operation and installation can be found in the data sheets for the sensors.
Displays and keypad
SITRANS F M TRANSMAG 2 with the SITRANS F M 911/E sensor
is a pulsed alternating field magnetic flowmeter where the magnetic field strength is much higher than conventional DC pulsed
magnetic flowmeters.
Operation of the transmitter can be carried out using:
• Keypad and display unit
• HART communicator
• PC/laptop and SIMATIC PDM software via HART communication
• PC/laptop and SIMATIC PDM software using PROFIBUS PA
communication
■ Benefits
• Wide range of sizes DN 15 to DN 1000 (½" to 40")
• Broad range of liner and electrode materials for extreme process medias
• Fully welded construction provides a ruggedness that suits
the toughest applications and environments.
• Automatic reading of SmartPLUG for easy commissioning
• Simple menu operation with two-line display
• Comprehensiv self-diagnostic with selfmonitoring and internal
simulation
■ Application
The main applications of the SITRANS F M transmitter
TRANSMAG 2 can be found in the following sectors:
• Pulp and Paper industry
• Mining industry
The pulse alternating field technology is ideal for difficult applications like:
• High concentrated paper stock > 3 %
• Heavy mining slurries
• Mining slurries with magnetic particles.
• Low conductive medias 1 S/cm (0.1 S/cm depending on
medium)
min. 230 Ω
Operating and
display panel
PC/
laptop
HART
communicator
Coupling
module
RS 232
HART communication
PROFIBUS DP
Master
PROFIBUS PA
+
Coupler with
power supply
T
Bus
term.
.......
Transmitter with
PROFIBUS PA interface
PROFIBUS PA communication
■ Design
• Available for remote mounting
• PROFIBUS PA (profile 2.0) / HART communication
• Analog output and digital outputs for pulses, device status,
limits, flow direction, frequency output
Siemens FI 01 · 2016
3/105
3
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter TRANSMAG 2 with sensor 911/E
■ Technical specifications
Output configuration
Transmitter TRANSMAG 2
• Pulse
Mode of operation and design
Measuring principle
Magnetic field excitation
3
Electromagnetic with pulsed
alternating field (PAC)
Automatic power supply synchronization
- 50 Hz AC power supply
Bipolar (16.7 Hz)
Bipolar with prepulse (10 Hz)
Unipolar (8.33 Hz)
- 60 Hz AC power supply
Bipolar (20 Hz)
Bipolar with prepulse (12 Hz)
Unipolar (10 Hz)
- Pulse significance
 5000 pulses/s
- Pulse width
 0.1 ms
• Limit frequency
 10000 Hz
• Limits
Limits for flow and quantity, flow
direction, alarm
Digital output 2 (relay)
(only 7ME5034-0.…)
Relay
NC or NO function
Accuracy under reference
conditions
• Rating
Max. 5 W, max. 50 V AC/DC,
max. 200 mA
Measuring tolerance of pulse output
• Output configuration
Limits for flow and quantity, flow
direction, alarm
• With v > 0.25 m/s (0.82 ft/s)
  0.5 % of measured value
 1.2 mm/s (0.05 inch/s)
• With v < 0.25 m/s (0.82 ft/s)
 2.5 mm/s (0.1 inch/s)
Digital input (optional to digital
output 2)
(only 7ME5034-2.…)
Measuring tolerance of analog output
As pulse output plus  0.1 %
conversion error  20 µA
• Input function configurable as
high-active or low-active
Set measured value or counter to
zero
Repeatability
0.2 % of measured value
• Signal voltage
Max. 30 V DC, Ri = 3 k:
High level: +11 ... +30 V DC
Low level: -30 ... +5 V DC
Reference conditions
• Process temperature
25 °C 5 °C (77 °F 9 °F)
• Ambient temperature
25 °C 5 °C (77 °F 9 °F)
• Warm-up time
Min. 30 min
• Installation conditions
Inlet pipe section  10 x DN
Outlet pipe section  5 x DN
Installed centered in pipe
• Medium
Water without gaseous or solid
components
Calibration
Standard production calibration,
calibration report shipped with sensor
For PROFIBUS devices
PROFIBUS PA (for
PROFIBUS-devices 7ME5034-1….)
• Communication
Layer 1 and 2 according to
PROFIBUS PA
Transmission according to
IEC 1158-2
Layer 7 (protocol layer) according
to PROFIBUS PA and DP V1
(EN 50170)
Device class B, device profile 2.0
Max. 4 simultaneous C2 connections
• Bus voltage
9 ... 32 V DC permissible
• Current consumption from bus
10 mA; limited to  15 mA in event
of fault by electrical current limitation
Zero-point, 2 x 25 % and 2 x 90 %
Output
Electrical isolation
Outputs electrically isolated from
one another and from the power
supply, max. 60 V permissible
against PE/equipotential bonding
Current output
0/4 ... 20 mA
(7ME5034-0…. or 7ME5034-2….)
Rated operating conditions
Installation conditions
See also sensor
Ambient temperature
• Signal
- Upper limit
0/4 … 20 mA, selectable
• Operation
-20 ... +60 °C (-4 ... +140 °F)
- Failure
20 … 22.5 mA,
optional 3.6; 20 or 24 mA
• Display module
0 ... 50 °C (32 ... 122 °F)
Storage
-25 ... +80 °C (-13 ... +176 °F)
Degree of protection
IP67/NEMA 4X
• Load
- Output
max. 600 , max. load voltage
15 V DC
- For HART communication
 250 
Communication
• Protocol
Via analog output with PC coupling module or HART communicator
HART, version 5.1
Digital output
Signal
• Output
Configurable as active or passive
signals
- Active signal
24 V DC,  24 mA, Ri = 170 
- Passive signal
Open collector, max. 30 V DC,
200 mA
3/106
Siemens FI 01 · 2016
Electromagnetic compatibility
(EMC)
• Emitted interference
To IEC/EN 61326 for use in
industrial areas
• Noise immunity
To IEC/EN 61326 for use in
industrial areas
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter TRANSMAG 2 with sensor 911/E
Medium conditions
• Process temperature
-20 ... +150 °C (-4 ... 302 °F)
depending on the liner
Minimum conductivity of medium
• With SITRANS F M 911/E sensors
 1 µS/cm (0.1 µS/cm depending
on medium)
Design
Weight of transmitter
4.4 kg (9.7 lb)
Remote version
Transmitter must be connected to
sensor using shielded cable
Maximum cable length
100 m (328 ft)
Housing
Die-cast aluminum, painted
Displays and keypad
General display
LCD, backlid, two lines with
16 characters each
Multi-display for
Flow, totalizer, flow velocity
Keypad
4 keys for entering parameters
Power supply
corresponding to rating plate
Selection and Ordering data
Article No.
SITRANS F M electromagnetic
transmitter TRANSMAG 2
for alternating field, remote version,
110 ... 230 V AC
7 ME 5 0 3 4 - 7AA7 1 - 7AA 0
Click on the Article No. for the
online configuration in the PIA Life
Cycle Portal.
Output/communication
4 ... 20 mA with HART protocol
PROFIBUS PA connection
4 ... 20 mA with HART protocol,
digital input
0
1
2
Operator display and keypad
Without
With
0
1
Cable glands
M20/M16 x 1.5
½“ NPT
1
2
Order code
Selection and Ordering data
• AC supply
100 ... 250 V AC  15 %,
47 ... 63 Hz
• Power consumption
Approx. 120 ... 630 VA, depending on sensor
Line fuse
100 ... 230 V AC: T1.6A
Magnet current fuse
F5A/250 V
Sensor cables between sensor and transmitter
The signal voltage proportional to the flow and present at the
electrodes of the EMF is only a few µV to mV. Superimposed on
this are electrochemical interferences resulting from the contact
between the electrodes and liquid, and which can be up to several Volt. Also frequently superimposed are line frequency interferences, interferences resulting from vibrations on the pipelines
or signal cables, as well as strong magnetic fields in the vicinity.
Sufficient shielding must therefore be provided, as well as fixed
routing of the signal cables (electrode and magnet current cable) in the case of remote versions. This also applies to devices
with integral preamplifier (smartPLUG). The cable length between the sensor and transmitter must not exceed 100 m
(328 ft).
Attention must also be paid to the cable routing. Signal cables
must be routed free of vibration, and protected against strong
magnetic and stray fields. In case of doubt, the sensor cables
must be routed in grounded steel conduit.
3
Additional information
Please add “-Z“ to Article No. and specify Order
code(s) and plain text.
Strengthened mounting bracket for wall and pipeline
installation
A02
Measuring range, specify in plain text:
Y01: 0 to ... m3/h
Y01
Pulse significance, specify in plain text:
Y02: 0 to ... pulses/l
Setting of digital outputs, specify in plain text:
Y03: Setting of digital outputs: ...
Y02
Measuring-point number (max. 8 characters), specify in
plain text: Y15: ..........
Y15
Measuring-point description (max. 16 characters),
specify in plain text: Y16: ..........
Y16
Stainless steel tag plate
Y17
Other post-production requirements (add plain text)
Y99
Y03
Operating instructions for SITRANS F M TRANSMAG 2
Description
Article No.
• English
A5E00102775
• German
A5E00192774
This device is shipped with a Quick Start guide and a CD containing further SITRANS F literature.
All literature is available to download for free, in a range of languages, at
www.siemens.com/processinstrumentation/documentation
Siemens FI 01 · 2016
3/107
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter TRANSMAG 2 with sensor 911/E
Accessories
3
Spare parts
Description
Article No.
Description
Article No.
Standard wall mounting
bracket. Steel AISI 316L/
EN10088-2-1.4404
7ME5933-0AC04
Operating/Display module
7ME5933-0AC00
Special wall-/pipe mounting bracket kit. BI 2.5
DIN 59382 X6Cr17
7ME5933-0AC05
Potting kit for terminal box  FDK:085U0220
of flow sensors for
IP68/NEMA 6P
 We can offer shorter delivery times for configurations designated with
the Quick Ship Symbol . For details see page 9/5 in the appendix.
Electronics cover with glass 7ME5933-0AC01
plate (non Ex). Die cast aluminum, with corrosion-resistant Basic Polyester powder
coating (min. 60 m)
Cover for sensor cable and
gasket. Die cast aluminum,
with corrosion-resistant
Basic Polyester powder
coating (min. 60 m)
7ME5933-0AC02
Cover for mains
supply/communication. Die
cast aluminum, with corrosion-resistant Basic Polyester powder coating
(min. 60 m)
7ME5933-0AC03
Safety clamp for electronic
cover with glass plate
(7ME5933-0AC01)
7ME5933-0AC06
M20 cable gland set for
power and output connection, gray PA plastic, 2 pcs.
• cables Ø 6 ... 12 mm
(0.24" ... 0.47")
• -40 ... +100 °C
(-40 ... +212 °F)
A5E02246350
1/2" NPT cable gland set for A5E02246396
power and output connection, gray PA plastic, 2 pcs.
• cables Ø 6 ... 12 mm
(0.24" ... 0.47")
• -40 ... +100 °C
(-40 ... +212 °F)
M16 x 1.5 cable gland set for A5E02246369
sensor connection, brass
chrome, 2 pcs. and
2 pcs. blind
• cables Ø 5 ... 9 mm
(0.20" ... 0.35")
• -20 ... +105°C
(-4 ... +221 °F)
3/108
Siemens FI 01 · 2016
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter TRANSMAG 2 with sensor 911/E
■ Dimensional drawings
■ Schematics
70
(2.76)
Transmitter
1
2
150 (5.91)
90
(3.54)
Power supply L/N
PE conductor
95 (3.74)
90
(3.54)
7
8
SITRANS F M transmitter TRANSMAG 2 with wall mounting bracket,
dimensions in mm (inch)
92 (3.62)
100 ... 230 V AC ±15%
47-63 Hz
0/4 ... 20mA
Load 600 Ω
max. 15 V
7
8
5
6
205 (8.07)
Power supply
Digital output 1
5
active 24 V DC max. 24 mA Ri 170 Ω
6
(active/passive)
Passive open collector max. 30 V DC 200 mA
150 (5.91)
248 (9.76)
89 (3.50) 105 (4.13)
Sensor connection
154 (6.06)
Ø80 (3.15)
SITRANS F M transmitter TRANSMAG 2 with wall and pipeline
mounting bracket, dimensions in mm (inch)
PROFIBUS
Digital output 1
Passive open
collector
max. 30 DC
100 mA
Digital output 2 (Relay)
NC/NO max. 5W, 50 V DC, 200 mA or
Digital input
High +11 ... +30 V DC
Low -30 ... +5 V DC
153 (6.02)
5
6
7
7
8
Coil cable
Magnetic fieldcorrent 1
Magnetic fieldcorrent 2
PE
Sensor
5
6
7
brown
white
green/yellow
29
22
30
SmartPlug connect
Supply (-6V)
Ground (0V)
Supply (+6V)
29
22
30
green
red/orange
blue
23
24
Electrode connect
Electr. 1 (EL 1)
Electr. 2 (EL 2)
23
24
brown
white
55
66
Reference coil
Ref. 1
Ref. 2
55
66
black/gray
yellow
SITRANS F M transmitter TRANSMAG 2, connection diagram
Siemens FI 01 · 2016
3/109
3
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter TRANSMAG 2 with sensor 911/E
911/E sensor
Protection rings for liners
Process connection
Nominal diameters
DN 15 ... 1000 (½" ... 40")
Metering tube connections
EN 1092-1, ANSI B16.5, AWWA
C-207 and JIS 10 K
Rated operating conditions
3
Function
To protect the edges of liners from
abrasion (e.g. gravel, sand etc.).
Used mainly with soft rubber liners
and for PTFE liners at high
temperatures from 100 to 150 °C
(212 to 302 °F).
Installation conditions
See system information
Contact with
medium
Yes, please always check resistance
to measured medium.
• Soft rubber liner
0 ... 70 °C (32 ... 158 °F)
Material
• Hard rubber liner
0 ... 90 °C (32 ... 194 °F)
Option: 100 °C (212 °F)
Stainless steel AISI 316Ti/1.4571,
optionally Hastelloy C276/2.4819
• PTFE liner
• -20 ... +150 °C (-4 ... +302 °F)
at 25 bar (363 psi)
• -20 ... +100 °C (-4 ... +212 °F)
at 40 bar (580 psi)
• Linatex (rubber) liner
-40 ... +70 °C (-40 ... +158 °F) (for
temperatures below -20 °C (-4 °F)
AISI 316L/1.4404 flanges must be
used)
• Novolak liner
130 °C (266 °F) at 40 bar (580 psi)
Degree of protection
IP67/NEMA 4X
Optional IP68/NEMA 6
Material thickness The overall length of the sensor is
increased by
•6 mm for DN 15 to DN 150
(0.24“ for ½“ to 6“) or
•10 mm for DN 200 to DN 600
(0.4“ for 8“ to 24“)
Standard
Optional for all liners.
Must be ordered separately.
Article No.
7ME5912-...., 7ME5943-...
Grounding rings
Function
Electrical reference and grounding of
the medium. Required if the pipelines
are not electrically conducting or are
lined (plastic pipelines, concrete
pipelines etc.). All grounding rings
must be connected to the grounding
screw present on the sensor.
Contact with
medium
Yes, please always check resistance
to measured medium.
Material
Stainless steel AISI 316Ti/1.4571 or
Hastelloy C4/2.4610
Medium conditions
Maximum flow velocity
12 m/s (39.4 ft/s)
Full scale value of flow velocity
0.15 ... 12 m/s (0.49 ... 39.4 ft/s)
Design
Weight
See dimensional drawings
Flange and housing material
Mild steel (1.0460/1.0570, with
corrosion resistant two component epoxy coating (min. 150 m)
or
AISI 316L/1.4404 flanges and carbon steel housing, with corrosionresistant two-component epoxy
coating (min. 150 m)
Measuring pipe material
Stainless steel AISI 304 or higher
Electrode material
• AISI 316Ti/1.4571
• PTFE: Hastelloy C276/2.4819
• Platinum
• Titanium
• Tantalum
Grounding electrode material
3/110
Siemens FI 01 · 2016
Defined via the Order code
Material thickness The overall length of the sensor is
increased by 2 mm (0.08“) per
grounding ring.
Standard
Optional for all liners. Required
between the medium and sensor for
equipotential bonding between nonconducting pipelines or lined pipelines.
Article No.
7ME5902-...., 7ME5942-...
Important:
The rings must be ordered together with the sensor. Gaskets are
not included. In case of replacement please include the sensor
MLFB code on the order.
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter TRANSMAG 2 with sensor 911/E
Notes on pressure equipment directive
The devices are designed for liquids of danger group "Gases of
fluid group 1". The categories differ according to the version,
and are listed in the table below.
The minimum temperature is defined at -10 °C (14 °F) for the
flange materials C22.8 (1.0460).
The minimum temperature is defined at -20 °C (-4 °F) for the
flange material 1.4404/316L. For further information on the PED
standard and requirements, see page 9/6.
Classification according to pressure equipment directive (PED 2014/68/EU)
Nominal diameter
Nominal pressure
DN
(inch)
PN
(MWP psi)
Permissible media
Category
15 ... 25
(½" ... 1")
40
200 ... 300
(8" ... 12")
10
(580)
Gases fluid group 1 and liquids fluid group 1
Article 4.3
(145)
Gases fluid group 1 and liquids fluid group 1
65 ... 250
(2½" ... 10")
II
16
(232)
Gases fluid group 1 and liquids fluid group 1
40 ... 100
II
(1½" ... 4")
40
(580)
Gases fluid group 1 and liquids fluid group 1
II
350 ... 1000
(14" ... 40")
10
(145)
Gases fluid group 1 and liquids fluid group 1
III
300 ... 1000
(12" ... 40")
16
(232)
Gases fluid group 1 and liquids fluid group 1
III
200 ... 600
(8" ... 24")
25
(363)
Gases fluid group 1 and liquids fluid group 1
III
125 ... 600
(5" ... 24")
40
(580)
Gases fluid group 1 and liquids fluid group 1
III
Siemens FI 01 · 2016
3
3/111
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter TRANSMAG 2 with sensor 911/E
Selection and Ordering data
Article No.
Selection and Ordering data
Flowsensor SITRANS F M 911/E
7 ME 5 6 1 0 -
Additional information
77777 - 7AA7
Please add “-Z“ to Article No. and specify Order
code(s) and plain text.
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
3
Order Code
Two grounding electrodes made of
stainless steel AISI 316Ti/1.4571
A02
1V
2D
2R
Two grounding electrodes made of
Hastelloy C276/2.4819
A04
Two grounding electrodes made of Platinum
A05
DN 50 (2")
DN 65 (2½")
DN 80 (3")
2Y
3F
3M
Two grounding electrodes made of Titanum
A06
Two grounding electrodes made of Tantalum
A07
Factory certificate to EN 10204-2.2
3T
4B
4H
C14
DN 100 (4")
DN 125 (5")
DN 150 (6")
Acceptance test B to DIN 50049, section 3.1 and
EN 10204
C16
DN 200 (8")
DN 250 (10")
DN 300 (12")
4P
4V
5D
Power supply 110 V/60 Hz
P01
Tag name plate, stainless steel, add plain text
Y17
Other postproduction requirements, add plain text
Y99
DN 350 (14")
DN 400 (16")
DN 450 (18")
5K
5R
5Y
DN 500 (20")
DN 600 (24")
DN 700 (28")
6F
6P
6Y
DN 800 (32")
DN 900 (36")
DN 1000 (40")
7H
7M
7R
Nominal diameter
DN 15 (½")
DN 25 (1")
DN 40 (1½")
Flange norm and pressure rating
EN 1092-1, PN 10 (DN 200 ... 1000 (8" ... 40"))
EN 1092-1, PN 16 (DN 65 ... 1000 (2½" ... 40"))
EN 1092-1, PN 25 (DN 200 ... 1000 (8" ... 40"))
EN 1092-1, PN 40 (DN 15 ... 1000 (½" ... 40"))
B
C
E
F
ANSI B16.5, Class 150 (½" ... 24")1)
ANSI B16.5, Class 300 (½" ... 24")2)
J
K
AWWA C-207 Class D (28" ... 40")
JIS 10 K (½" ... 24")
L
R
Flange material
Mid steel flanges 1.0460/1.0570
Stainless steel flanges, AISI 316L/1.4404
Liner material
Soft rubber (DN 25 to DN 1000)
PTFE (DN 15 to DN 600)
Hardrubber (DN 15 to DN 1000)
Linatex (DN 40 to DN 1000)
Novolak (sealing material FFKM)
(DN 50 to DN 1000)
Electrode material
AISI 316Ti/1.4571
Hastelloy C276/2.4819
Platinum
Titanium
Tantalum
Cable glands/terminal box
Metric: Polyamide terminal box
½" NPT: Polyamide terminal box
Metric: Stainless steel terminal box
½" NPT: Stainless steel terminal box
3/112
Siemens FI 01 · 2016
1)
20 °C (68 °F), max. 19.6 bar (285 psi) for steel flanges and max. 15.9 bar
(231 psi) for stainless seel flanges
2)
20 °C (68 °F), max. 51.1 bar (741 psi) for steel flanges and max. 41.4 bar
(600 psi) for stainless seel flanges
Selection and Ordering data
Article No. Order code
SITRANS F M TRANSMAG 2 and
sensor 911/E
7 ME 5 9 3 0 -
Cable
5 7A 0 0 - 0 AA 0 777
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Cable kit for sensor 911/E with alternating
field, Magnet current cable 3 x 1.0 mm2
(3 x 0.0016 inch2), electrode/reference
cable 7 x 0.5 mm2 (7 x 0.0008 inch2) with
shield PVC
• Length: 5 m (16.4 ft)
• Length: 10 m (32.8 ft)
• Length: 20 m (65.6 ft)
• Length: 30 m (98.4 ft)
• Other length (specify in plain text):
max. 100 m (328 ft)
1
3
1
3
4
5
6
1
2
3
4
5
1
2
3
4
B
C
D
E
Z
J1Y
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter TRANSMAG 2 with sensor 911/E
Selection and Ordering data
Article No.
Order code
SITRANS F M
electromagnetic flowmeter
Protection ring for flow sensor 911E
(per pair). Gaskets not included.
7 ME 5 9 1 2 - 7777 777
Protection rings for flow sensor 911E
(per pair)
7 ME 5 9 4 2 - 77777
Grounding rings for flow sensor 911E
(per unit)
7 ME 5 9 4 3 - 77777
Click on the Article No. for the online
configuration in the PIA Life Cycle
Portal.
1
7
0
Nominal diameter
for PTFE, mat. no. 1.4571/316 Ti
DN 15 (½")
DN 25 (1")
AA
CA
DN 40 (1½")
DN 50 (2")
EA
FA
DN 65 (2½")
DN 80 (3")
DN 100 (4")
GA
HA
JA
DN 125 (5")
DN 150 (6")
DN 200 (8")
KA
LA
MA
DN 250 (10")
DN 300 (12")
NA
PA
Other nominal diameters:
specify in plain text
ZA
for Hard/Soft rubber, Novolak, mat. no.
1.471/316 Ti
DN 15 (½")
DN 25 (1")
AB
CB
DN 40 (1½")
DN 50 (2")
EB
FB
DN 65 (2½")
DN 80 (3")
DN 100 (4")
GB
HB
JB
DN 125 (5")
DN 150 (6")
DN 200 (8")
KB
LB
MB
DN 250 (10")
DN 300 (12")
NB
PB
Other nominal diameters:
specify in plain text
ZB
Flange design
Flange to DIN
Flange to ANSI
Flange to JIS
Order code
Gaskets not included.
Click on the Article No. for the online
configuration in the PIA Life Cycle
Portal.
Liner
Hard rubber/soft rubber/Linatex
Novolak
PTFE
Article No.
Selection and Ordering data
J1Y
J1Y
1
2
3
Nominal diameter
DN 15 (½")
DN 25 (1")
DN 40 (1½")
1V
2D
2R
DN 50 (2")
DN 65 (2½")
DN 80 (3")
2Y
3F
3M
DN 100 (4")
DN 125 (5")
DN 150 (6")
3T
4B
4H
DN 200 (8")
DN 250 (10")
DN 300 (12")
4P
4V
5D
DN 350 (14")
DN 400 (16")
DN 450 (18")
5K
5R
5Y
DN 500 (20")
DN 600 (24")
DN 700 (28")
6F
6P
6Y
DN 800 (32")
DN 900 (36")
DN 1000 (40")
7H
7M
7R
3
Flange design
EN 1092-1, PN10
EN 1092-1, PN16
B
C
EN 1092-1, PN25
EN 1092-1, PN40
E
F
AISI B16.5, class 150
AISI B16.5, class 300
J
K
AWWA C-207, class D
JIS B2220, 10K
L
R
Material
Stainless steel AISI 316Ti/1.4571
Hastelloy C4/2.4610
1
2
Flange design
Soft rubber
PTFE
Hard rubber
1
3
4
Linatex
Novolak
5
6
Siemens FI 01 · 2016
3/113
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter TRANSMAG 2 with sensor 911/E
Selection and Ordering data
Article No.
Order code
SITRANS F M
electromagnetic flowmeter
Grounding rings for flow sensor 911E
(per unit). Gaskets not included.
7 ME 5 9 0 2 - 7777 777
Click on the Article No. for the online
configuration in the PIA Life Cycle
Portal.
3
Liner
Hard rubber/soft rubber
Novolak
PTFE
1
7
0
Nominal diameter
Mat. no. 1.4571/316 Ti
DN 15 (½")
DN 25 (1")
AA
CA
DN 40 (1½")
DN 50 (2")
EA
FA
DN 65 (2½")
DN 80 (3")
DN 100 (4")
GA
HA
JA
DN 125 (5")
DN 150 (6")
DN 200 (8")
KA
LA
MA
DN 250 (10")
DN 300 (12")
DN 350 (14")
NA
PA
QA
DN 400 (16")
DN 500 (20")
DN 600 (24")
RA
SA
TA
DN 700 (28")
DN 800 (32")
DN 900 (36")
DN 1000 (40")
UA
VA
WA
XA
Other nominal diam.: specify in plain text
ZA
Material Hastelloy C4/2.4610
DN 15 (½")
DN 25 (1")
AB
CB
DN 40 (1½")
DN 50 (2")
EB
FB
DN 65 (2½")
DN 80 (3")
DN 100 (4")
GB
HB
JB
DN 125 (5")
DN 150 (6")
DN 200 (8")
KB
LB
MB
DN 250 (10")
DN 300 (12")
DN 350 (14")
NB
PB
QB
DN 400 (16")
DN 500 (20")
DN 600 (24")
RB
SB
TB
Other nominal diam.: specify in plain text
ZB
Flange design
Flange to DIN
Flange to ANSI
Flange to JIS
3/114
Siemens FI 01 · 2016
J1Y
J1Y
1
2
3
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter TRANSMAG 2 with sensor 911/E
■ Dimensional drawings
131 (5.16)
155 (6.1)
A
3
D1
B
L
D
SITRANS F M flow sensor 911/E, remote version, dimensions in mm (inch)
Build-in length 911/E [in mm and inch]
Nominal diameter
DN 15
½“
DN 25
1“
DN 40
1 ½“
DN 50
2“
DN 65
2 ½“
DN 80
3“
DN 100
4“
DN 125
5“
DN 150
6“
DN 200
8“
DN 250
10“
Build-in length L1)
Hard rubber version
Linatex/soft rubber version
270
(10.63)
280
(11.02)
330
(12.99)
340
(13.39)
370
(14.57)
410
(16.14)
470
(18.50)
PTFE-liner without protection rings
270
(10.63)
280
(11.02)
330
(12.99)
340
(13.39)
370
(14.57)
410
(16.14)
470
(18.50)
-
275
(10.83)
325
(12.79)
362
(14.25)
401
(15.79)
460
(18.11)
Novolak-version
335
(13.19)
333
(13.11)
Dimensions of sensor housing
Housing width B
Height A
170 (6.69)
240 (9.45)
206 (8.11)
222
(8.74)
229
(9.02)
262
(10.32)
274
(10.79)
286
(11.26)
299
(11.78)
334
(13.15)
358
(14.10)
135
(5.35)
167
(6.58)
182
(7.17)
247
(9.73)
272
(10.71)
296
(11.65)
322
(12.68)
392
(15.43)
440
(17.32)
Housing diameter D1
Weight of PN16 version in kg
8.0
(MWP 232 psi version in lb) approx. (17.64)
8.5
(18.74)
11.5
(25.35)
25.0
(55.12)
26
(57.32)
27
(59.53)
28
(61.73)
34
(74.95)
38
(83.78)
68
(149.9)
81
(178.6)
Nominal diameter
DN 300
12“
DN 350
14“
DN 400
16“
DN 450
18“
DN 500
20“
DN 600
24“
DN 700
28“
DN 750
30“
DN 800
32“
DN 900
36“
DN 1000
40“
Hard rubber version
Linatex/soft rubber version
500
(19.68)
550
(21.65)
600
(23.62)
650
(25.59)
650
(25.59)
780
(30.71)
1040
(40.95)
1170
(46.06)
1300
(51.18)
PTFE-liner without protection rings
500
(19.68)
550
(21.65)
600
(23.62)
660
(25.98)
650
(25.59)
780
(30.71)
Novolak-version
489
(19.25)
538
(21.18)
592
(23.31)
638
(25.12)
638
(25.12)
772
(30.39)
1033
(40.63)
1163
(45.79)
1293
(50.91)
Housing width B
240
(9.45)
225
(8.86)
250
(9.84)
270
(10.63)
300
(11.81)
360
(14.17)
500
(19.69)
560
(22.05)
620
(24.41)
Height A
383
(15.08)
375
(14.76)
400
(15.75)
433
(17.05)
453
(17.84)
505
(19.88)
558
(21.97)
590
(23.23)
608
(23.94)
658
(25.91)
713
(28.07)
Housing diameter D1
490
(19.29)
474
(18.66)
524
(20.63)
591
(23.26)
629
(24.76)
734
(28.90)
839
(33.03)
904
(35.59)
939
(36.97)
1039
(40.91)
1150
(45.28)
Weight of PN10 Version in kg
95
(MWP 145 psi version in lb) approx. (209.4)
118
(260.2)
161
(354.9)
185
(407.9)
233
(513.7)
401
(884.1)
420
(925.9)
450
(992.1)
500
560
620
(1102.3) (1234.6) (1366.9)
Build-in length L1)
910
(35.83)
903
(35.55)
Dimensions of sensor housing
1)
420
(16.54)
Tolerance for build-in lenght: L + 0.0/-4.0 mm (+0.00/-0.157 inch)
With protection rings for > DN25 + 6.0 mm, > DN200 + 10.0 mm (> 1” + 0.236 inch, > 8” + 0.394 inch)
Siemens FI 01 · 2016
3/115