MAG 6000i Catalog Specifications Sheet

© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter MAG 6000 I/6000 I Ex
■ Overview
• Limit switches and pulse output
• Batch control
The MAG 6000 I/6000 I Ex is a microprocessor-based transmitter with a build-in alphanumeric display in several languages.
The transmitters evaluate the signals from the associated electromagnetic sensors and also fulfil the task of a power supply
unit which provides the magnet coils with a constant current.
Further information on connection, mode of operation and installation can be found in the data sheets for the sensors.
Displays and keypads
Operation of the transmitter can be carried out using:
• Keypad and display unit
• HART communicator
• PC/laptop and SIMATIC PDM software via HART communication
• PC/laptop and SIMATIC PDM software using PROFIBUS or
Modbus communication
The SITRANS F M MAG 6000 I/MAG 6000 I Ex transmitter is designed for the demands in the process industry. The robust die
cast aluminum housing provides superb protection, even in the
most harsh industrial environments. Full input and output functionality is given even in the Ex version.
■ Benefits
• Full range of Ex-rated flowmeters with intrinsically safe rated
input and outputs
• For compact or remote installation
• HART, FOUNDATION Fieldbus H1, DeviceNet, PROFIBUS PA
and DP, Modbus RTU/RS 485 add-on communication modules available
• Superior signal resolution for optimum turn down ratio
• Digital signal processing with many possibilities
• Automatic reading of SENSORPROM data for easy commissioning
• User configurable operation menu with password protection
- 3 lines, 20 characters display in 11 languages
- Flow rate in various units
- Totalizer for forward, reverse and net flow as well as much
more information available.
• Multiple functional outputs for process control, minimum configuration with analogue, pulse/frequency and relay output
(status, flow direction, limits)
• Comprehensive self-diagnostic for error indication and error
logging
• Batch control
• MAG 6000 I NAMUR: compliant with NAMUR NE 21, NE 32,
NE 43, NE 53 and NE 70
■ Design
The transmitter is designed for either compact or remote installation in non-hazardous or hazardous areas (compact mounted
transmitter to be ordered together with the sensors).
■ Function
The following functions are available:
• Flow rate
• 2 measuring ranges
• 2 totalizers
• Low flow cut-off
• Flow direction
• Error system
• Operating time
• Uni-/bidirectional flow
■ Technical specifications
Mode of operation and design
Measuring principle
Electromagnetic with pulsed constant field
Empty pipe
Detection of empty pipe (special
cable required in remote mounted
installation)
Excitation frequency
Depend on sensor size
Electrode input impedance
> 1 x 1014 
Input
Digital input
11 ... 30 V DC, Ri = 4.4 k
• Activation time
50 ms
• Current
I11 V DC = 2.5 mA, I30 V DC = 7 mA
Output
Current output
• Signal range
4 ... 20 mA (active/ passive)
• Load
< 560 
• Time constant
0.1 … 30 s, adjustable
Digital output
• Frequency
0 … 10 kHz, 50 % duty cycle
(uni-/bidirectional)
• Time constant
0.1 … 30 s, adjustable
• Pulse (passive)
3 … 30 V DC, max 110 mA
(30 mA Ex version),
200   Ri  10 k (powered from
connected equipment)
• Time constant
0.1 … 30 s, adjustable
Relay output
• Time constant
Changeover relay, same as
current output
• Load
42 V AC/2 A, 24 V DC/1 A
Low flow cut off
0 … 9.9 % of maximum flow
Galvanic isolation
All inputs and outputs are
galvanic isolated
Max. measuring error
MAG 6000 I/MAG 6000 I Ex
(incl. sensor)
 0.2 %  1 mm/s
Siemens FI 01 · 2016
3/45
3
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter MAG 6000 I/6000 I Ex
Rated operation conditions
Cable entries
Remote installation
Ambient temperature
MAG 6000 I
2 x M25 (for supply/output) and
2 x M16 (for sensor connection) or
2 x ½" NPT (for supply/output) and
2 x M16 (for sensor connection)
MAG 6000 I Ex ATEX 2G D
2 x M20 (for supply/output) and
2 x M16 (for sensor connection)
• Operation
3
- MAG 6000 I
-20 … +60 °C (-4 … +140 °F)
- MAG 6000 I Ex
-20 … +60 °C (14 … 140 °F)
• Storage
-40 … +70 °C (-40 … +158 °F)
Mechanical load
18 ... 1000 Hz random in x, y, z,
directions for 2 hours according
to EN 60068-2-36
Transmitter: 1.14 g RMS
Degree of protection
IP67/NEMA 4X to IEC 529 and
DIN 40050 (1 mH2O 30 min.)
EMC performance
IEC/EN 61326-1 (all environments)
IEC/EN 61326-2-5
NAMUR NE 21
Display and keypad
Totalizer
Two eight-digit counters for
forward, net or reverse flow
Display
Background illumination with
alphanumeric text, 3 x 20 characters to indicate flow rate, totalized
values, settings and faults;
Reverse flow indicated by negative sign
Keypad
Capacitive touch keypad with
LED light for feedback indication
Time constant
Time constant as current output
time constant
Design
Enclosure material
Die cast aluminum, with corrosion
resistant Basic Polyester powder
coating (min. 60 µm)
• Wall mounting
Wall mounting bracket enclosed
for remote version
Dimensions
See dimensional drawings
Weight
See dimensional drawings
Power supply
• Standard transmitter:
18 ... 90 V DC;
115 ... 230 V AC +10 %/-15 %;
50 ... 60 Hz
• Ex transmitter: 18 ... 30 V DC
• Ex transmitter: 115 ... 230 V AC;
50 ... 60 Hz
• Ex transmitter NAMUR:
18 ... 30 V DC;
115 ... 230 V AC; 50 ... 60 Hz
Power consumption
• 230 V AC: 20 VA
• 24 V DC: 9.6 W, IN = 0.4 A,
IST = 1 A (3 ms)
Certificates and approvals
MAG 6000 I
• CE
• C-tick
• FM Class I, Div 2
• FM Class I, Zone 2
• CSA Class I, Div 2
• CMC/CPA
MAG 6000 I Ex
3/46
Siemens FI 01 · 2016
• IEC Ex de [ia] [ib] ia IIC T6 Gb
Ex tDa 21 IP67
• ATEX II 2(1)(2) GD EEx de [ia] ia
[ib] IIC T6
• FM Class I, Div 11)
• FM Class I, Zone 1
• CSA Class I, Zone 1/21
Communication
Standard versions
HART, Modbus RTU/RS 485,
FOUNDATION Fieldbus H1, DeviceNet, PROFIBUS PA, PROFIBUS DP add-on modules
Ex versions
HART, PROFIBUS PA,
1)
Applicable for: Compact mounted MAG 6000 I Ex on MAG 3100
(sizes DN 15 ... DN 300 (½" ... 12"))
Selection and Ordering data
Article No.
SITRANS F M Transmitter MAG 6000 I/Ex
Remote with standard wall mounting bracket, local
display, die cast aluminum
7 ME 6 9 3 0 2 B A77 - 1 7 A 7
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Supply voltage
Standard transmitter:
18 ... 90 V DC; 115 ... 230 V AC, 50 ... 60 Hz
Standard transmitter (NAMUR):
18 ... 30 V DC; 115 ... 230 V AC, 50 ... 60 Hz
Ex transmitter: 18 ... 30 V DC
Ex transmitter: 115 ... 230 V AC, 50 ... 60 Hz
Ex transmitter (NAMUR):
18 ... 30 V DC; 115 ... 230 V AC, 50 ... 60 Hz

3


Ex approval
Standard sensor: FM Class I, Div 2, CSA Class I, 
Div 2
Ex sensor: Hazardous area (ATEX 2 GD;

FM Class I, Zone 1; CSA Class I, Zone 1)
Communication
None
HART
PROFIBUS PA Profile 3
PROFIBUS DP Profile 3 (not for Ex version)
Modbus RTU/RS 485 (not for Ex version)
FOUNDATION Fieldbus H1
Cable gland entries
Metric
½" NPT
2
4
5
6
0
2





A
B
F
G
E
J


0
2
 We can offer shorter delivery times for configurations designated with
the Quick Ship Symbol . For details see page 9/5 in the appendix.
Order code
Selection and Ordering data
Further design
Please add “-Z“ to Article No. and specify Order
code(s) and plain text.
Tag name plate, stainless steel fixed with SS wire
(add plain text)
Y17
Tag name plate, plastic (self adhesive)
Y18
Other, post-production requirements (add plain text)
Y99
Operating instructions for SITRANS F M MAG 6000 I
Description
Article No.
• English
A5E02083319
• German
A5E02210835
This device is shipped with a Quick Start guide and a CD containing
further SITRANS F literature.
All literature is available to download for free, in a range of languages, at
www.siemens.com/processinstrumentation/documentation
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter MAG 6000 I/6000 I Ex
Communication modules for MAG 6000 I
(All standard outputs can still be used)
Article No.
Description
HART (only for MAG 6000 I/Ex)  FDK:085U0321
Modbus RTU/RS 4851)
PROFIBUS PA Profile 3
PROFIBUS DP Profile
31)
DeviceNet1)
FOUNDATION Fieldbus H11)
 FDK:085U0234
 FDK:085U0236
 FDK:085U0237
 FDK:085U0229
A5E02054250
 We can offer shorter delivery times for configurations designated with
the Quick Ship Symbol . For details see page 9/5 in the appendix.
1)
Not for Ex versions
Operating instructions for SITRANS F add-on modules
Cable kit with standard coil
cable, 3 x 1.5 mm²/18 gage
with shield PVC and electrode cable double shielded,
3 x 0.25 mm²
• 5 m (16.5 ft)
 A5E02296329
• 10 m (33 ft)
 A5E01181647
• 15 m (49 ft)
 A5E02296464
• 20 m (65 ft)
 A5E01181656
• 25 m (82 ft)
 A5E02296490
• 30 m (98 ft)
 A5E02296494
• 40 m (130 ft)
 A5E01181686
• 50 m (164 ft)
 A5E02296498
• 60 m (200 ft)
A5E01181689
• 100 m (330 ft)
A5E01181691
Description
Article No.
• 150 m (500 ft)
A5E01181699
HART, English
A5E03089708
• 200 m (650 ft)
A5E01181703
• 500 m (1650 ft)
A5E01181705
PROFIBUS PA/DP
• English
• German
A5E00726137
A5E01026429
Modbus
• English
• German
A5E00753974
A5E03089262
FOUNDATION Fieldbus
• English
• German
A5E02318728
A5E02488856
DeviceNet, English
A5E03089720
This device is shipped with a Quick Start guide and a CD containing
further SITRANS F literature.
All literature is available to download for free, in a range of languages, at
www.siemens.com/processinstrumentation/documentation
3
Low noise electrode coax
cable for low conductivity
and high vibration levels of
cables, 3 x 0.13 mm2
• 2 m (6.6 ft)
A5E02272692
• 5 m (16.5 ft)
A5E02272723
• 10 m (33 ft)
A5E02272730
 We can offer shorter delivery times for configurations designated with
the Quick Ship Symbol . For details see page 9/5 in the appendix.
Spare parts
Description
Article No.
MAG 6000 I Display
FDK:085U3122
Accessory bag including
cable gland inserts, coil and
electrode connectors
FDK:085U3144
Accessories MAG 6000 I/MAG 6000 I Ex
Description
Article No.
Cable for standard electrode
or coil, 3 x 1.5 mm²/
18 gage with shield PVC.
Temperature range:
-30 ... +70 °C (-22 ... +158 °F)
• 10 m (33 ft)
 FDK:083F0121
• 20 m (65 ft)
 FDK:083F0210
• 40 m (130 ft)
 FDK:083F0211
• 60 m (200 ft)
 FDK:083F0212
• 100 m (330 ft)
FDK:083F0213
• 150 m (500 ft)
FDK:083F3052
• 200 m (650 ft)
FDK:083F3053
• 500 m (1650 ft)
FDK:083F3054
Electrode cable for empty
pipe or low conductivity, double shielded, 3 x 0.25 mm²
Temperature range:
-30 ... +70 °C (-22 ... +158 °F)
• 10 m (33 ft)
 FDK:083F3020
• 20 m (65 ft)
 FDK:083F3095
• 40 m (130 ft)
FDK:083F3094
• 60 m (200 ft)
FDK:083F3093
• 100 m (330 ft)
FDK:083F3092
• 150 m (500 ft)
FDK:083F3056
• 200 m (650 ft)
FDK:083F3057
• 500 m (1650 ft)
FDK:083F3058
Electronics cover with Ex glass 7ME5933plate. Die cast aluminum, with 0AC01
corrosion-resistant Basic Polyester powder coating (min.
60 m).
Cover for connection board
7ME5933incl. gasket (for remote ver0AC02
sion). Die cast aluminum, with
corrosion-resistant Basic Polyester powder coating (min.
60 m).
Cover for mains supply/communication. Die cast aluminum, with corrosion-resistant
Basic Polyester powder coating (min. 60 m).
7ME59330AC03
Siemens FI 01 · 2016
3/47
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter MAG 6000 I/6000 I Ex
Description
Article No.
Safety clamp
7ME59330AC06
■ Dimensional drawings
98.5 (3.88)
205 (8.07)
248 (9.76)
3
153 (6.08)
33.5 (1.32)
250 (9.84)
Standard wall mounting bracket. 7ME5933Steel AISI 316L/EN10088-20AC04
1.4404
220 (8.66)
100 (3.94)
Wall-/pipe mounting bracket kit, 7ME5933BI 2.5 DIN59382 X6Cr17
0AC05
Ø 80 (3.15)
Dimensions in mm (inch), weight: 6 kg (13.5 lb)
Complete spare part PCB unit
Description
Article No.
MAG 6000 I PCBA (not for Ex) FDK:085U3123
MAG 6000 I std. (NAMUR),
A5E31426892
18 ... 30 V DC; 115 ... 230 V AC
Spare PCBA unit
A5E314268771)
MAG 6000 I Ex (NAMUR),
18 ... 30 V DC; 115 ... 230 V AC
Spare PCBA unit for use with Ex
sensors with increased safety e
(For Ex sensors: 7ME6110,
7ME6120, 7ME6140,
7ME6310, 7ME6320,
7ME6340) (For 7ME6330 >
DN300)
MAG 6000 I Ex d 115 ... 230 V A5E01013127
AC Spare PCB unit for use with
ATEX sensors with increased
safety e
MAG 6000 I Ex d 18 ... 30 V DC A5E01013340
Spare PCB unit for use with
ATEX sensors with increased
safety e
1)
Ex spare parts may only be exchanged by ”Siemens Ex Authorized
personnel”.
Please use online Product selector to get latest updates.
Product selector link:
www.pia-portal.automation.siemens.com
3/48
Siemens FI 01 · 2016
© Siemens AG 2016
Flow Measurement
SITRANS F M
Transmitter MAG 6000 I/6000 I Ex
■ Schematics
Power supply
Transmitter
L1
L
N
N
PE
Ex 18 - 30 V DC
Ex 115 - 230 V AC
Non Ex 18-90 V DC/ 115-230 V DC
Outputs
3
Current
Active
(Powered from transmitter)
Factory setting non Ex
Passive
(External powered)
Factory setting Ex
4-20 mA
Load ≤ 560 Ω
31
+
32
-
0/4-20 mA
Load ≤ 560 Ω
+
-
Digital
56
57
Vx 3-30 V max. 110 mA
+
-
+
y
PLC-Digital Input
Negativ:
Menu setup:
Positiv: ydGwœ““Gœ—Vk–ž•G™Œšš›–™GXTXWGrΩ
”ˆ G‰ŒG™Œ˜œ™Œ‹T‹Œ—Œ•‹•ŽG–•
GŠˆ‰Œ“šVp•—œ›G™Œšš›ˆ•ŠŒU
Relay
44
uv
45
uj
46
j–””–•
kŽ›ˆ“G•—œ›
77 78
yŒ“ˆ Y[G}GkjVXGh
[YG}GhjVYGh
XXTZWG}Gkj p•—œ›
+
Bus communication
91 92 93 94 95 96 97
zŒ•š–™
Sensor connection (remote transmitter)
81
Electrode cable
_X
_Y
82
0
W
83
84
_Z
_[
Coil cable
85
_\
86
_]
wl
”•UG[G””Y O–•“ GlŸGŒ™š–•šP
Siemens FI 01 · 2016
3/49