SITRANS FCS 400 Catalog specification sheet

© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
1
SITRANS P500 - Technical description
■ Overview
SITRANS P500 pressure transmitters are digital pressure transmitters featuring extensive user-friendliness and which fulfil the
most stringent demands of accuracy, long-term stability, speed
and lots more.
Extensive functionality allows you to set the pressure transmitter
specifically to your own requirements. Despite their many settings options, local set-up is easy. A multi-lingual menu with clear
text instructions guides you through the process. There are also
help texts available.
The innovative EDD with integrated QuickStart assistance is also
quick and easy to configure by computer using the HART protocol.
Extensive diagnostic functions, e.g. min/max pointer for pressure and temperature, or limit value indicator, make sure you always have the process under control. You can also display additional process values such as temperature or static pressure.
The simultaneous display of mass, resulting from a volume, is
also easy.
The SITRANS P500 pressure transmitters can be configured to
measure:
• Differential pressure
• Level
• Volume
• Mass
• Volume flow
• Mass flow
■ Benefits
•
•
•
•
•
•
•
•
High measuring accuracy
Very fast response time
Extremely good long-term stability
High reliability even under extreme chemical and mechanical
loads
For aggressive and non-aggressive gases, vapors and liquids
Extensive diagnosis and simulation functions which can be
used both on site as well as via HART.
Optional separate replacement of measuring cell and electronics without recalibration.
Extremely low conformity error values
1/176
Siemens FI 01 · 2015 US Edition
• Infinitely adjustable spans of 1 mbar to 32 bar (0.0145 to
465 psi; 0.4 to 12860 inH2O)
• Extremely good total performance and conformity error
values with no loss of performance up to a turndown of 10
guaranteed.
• Additional integrated sensor for static pressure
• Parameterization via on-site control keys or HART
• Short process flanges nable space-saving installation.
■ Application
The SITRANS P500 pressure transmitters can be used in industrial areas with extreme chemical and mechanical loads. Electromagnetic compatibility in the range 10 kHz to 1 GHz makes them
suitable for locations with high electromagnetic emissions.
Pressure transmitters with ratings "Intrinsic safety" and "Explosion-proof" may be installed within potentially explosive atmospheres (zone 1) or in zone 0. The pressure transmitter comes
with a CE-declaration of conformity and fulfils the corresponding
unified European directives (ATEX).
Pressure transmitters with the type of protection "Intrinsic safety"
for use in zone 0 may be operated with power supply units of category "ia" and "ib".
With newly designed measuring cell, it is possible to work with
process temperatures of -40 to 125 °C (-40 to +257 °F)) without
having to use a remote seal.
The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of
highly viscous fluids.
The pressure transmitter can be fully parameterized locally via
the three operating keys and externally via HART.
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 - Technical description
Pressure transmitters for differential pressure and flow
• Measured variables:
- Differential pressure
- Small positive or negative pressure
- Flow q ~ p (together with a primary element
(see Chapter "Flow Meters"))
• Span (freely adjustable)
for SITRANS P500: 1 mbar to 32 bar (0.0145 to 465 psi; 0.4 to
12860 inH2O)
Pressure transmitters for level
• Measured variable: Level of aggressive and non-aggressive
liquids in open and closed vessels.
• Span (freely adjustable)
for SITRANS P500: 1.25 to 6250 mbar (0.5 to 2509 inH2O)
• Nominal diameter of the mounting flange
- DN 50 / PN 40
- DN 80 / PN 40
- DN 100/ PN 16, PN 40
- 2 inch/class 150, class 300
- 3 inch/class 150, class 300
- 4 inch/ class 150, class 300
- customized special version
In the case of level measurements in open vessels, the low-pressure connection of the measuring cell remains open (measurement "compared to atmospheric").
In the case of measurements in closed vessels, the lower-pressure connection has to be connected to the vessel in order to
compensate the static pressure.
The wetted parts are made from a variety of materials, depending on the degree of corrosion resistance required.
■ Design
10
9
1
8
14
2
7
11
3
13
4
6
12
5
1
2
3
4
5
6
7
8
Cover for the pushbuttons
Cover, optionally with window
Display (optional)
TAG plate
Process flange with process connection
Lock screws (on two sides) for the measuring cell
Approval plate
Safety catch
9
10
11
12
13
14
Blanking plug
Terminal compartment
Cover for terminal compartment
PE/ground terminal
Nameplate
Cable inlet, optionally with cable gland or plug-in connection
View of transmitter
• The electronics housing is made of coated die-cast aluminum.
• The casing has round screwed covers front and back.
• Depending on the design the front cover is fitted with an inspection window. You can read off the measured value directly
from the optional display through the window.
• The inlet to the terminal compartment is located either on the
left or right side. The unused opening in each case is sealed
by a blanking plug.
• The PE/ground terminal is on the back of the housing.
• Access to the terminal compartment for auxiliary power and
shielding by unscrewing the cover.
• Beneath the electronic housing is the measuring cell with its
process flanges at which the process connections are available. The modular design of the pressure transmitter lets you
replace the measuring cell, electronics and connection board
as required.
• On the top of the housing you can see the screwed cover of
the three local pushbuttons of the transmitter.
Siemens FI 01 · 2015 US Edition
1/177
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 - Technical description
■ Function
Mode of operation of the measuring cells
Operation of electronics with HART communication
Measuring cell for differential pressure and flow
SIEMENS
EEPROM
A
μC
D
D
μC
9
Ia
A
UH
1
T
R
8
2
3
HART modem
Sensor
EEPROM
Sensor
1
EEPROM
Electronics
7
Application electronics
Sensor of the measuring cell
Measuring amplifier
Analog-to-digital converter
Microcontroller
Digital-to-analog converter
One EEPROM each in the measuring cell and in the electronics
HART modem
Keys (local operation)
Digital display
Output current
Auxiliary power
Function diagram of electronics
• The input pressure is converted into an electrical signal by the
sensor.
• This signal is amplified by the measuring amplifier and digitalized in an analog-to-digital converter.
• The digital signal is analyzed in a microcontroller and corrected according to linearity and thermal characteristics.
• In a digital-to-analog converter it is then converted into the
output current of 4 to 20 mA. When connected to supply lines,
a diode circuit provides reverse polarity protection.
• The measuring cell-specific data, the electronic data and the
parameterization data is held in two EEPROMs. One EEPROM
is incorporated into the measuring cell electronics, the other is
incorporated into the application electronics.
Operation
• The three local pushbuttons enable you both to navigate and
carry out configuration and to visually track messages and
process values, provided a display is available.
• If you have a device without a display, you can carry out zero
adjustment using the three local pushbuttons. It is possible to
retrofit a display at any time.
• You can also carry out settings by computer via a HART modem.
1/178
6
5
4
Measuring cell electronics
1
2
3
4
5
6
7
8
9
IA
UH
Siemens FI 01 · 2015 US Edition
1
2
3
4
5
6
7
8
9
Input pressure PProcess flange with process connection
O-Ring
Measuring cell body
Silicon pressure sensor
Overload diaphragm
Filling liquid
Seal diaphragm
Input pressure P+
Measuring cell for differential pressure and flow, function diagram
• The differential pressure is transmitted via the seal diaphragm
and the filling liquid to the silicon pressure sensor.
• If the measuring limits are exceeded, the overload diaphragm
flexes until the seal diaphragm touches the body of the measuring cell. This protects the sensor module from overload.
• The differential pressure causes the measuring diaphragm of
the silicon pressure sensor to flex.
• The displacement changes the resistance value of the 4 piezo
resistors in the measuring diaphragm in a bridge circuit.
• The change in the resistance causes a bridge output voltage
proportional to the input pressure.
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 - Technical description
Measuring cell for level
Configuration using HART
1
3
2
Parameterization using HART is carried out using a HART Communicator or a PC in conjunction with a HART modem.
4
+
230 ... 1100 Ω
SITRANS P500
transmitter
Power supply
HART
communicator
5
9
8
7
6
Communication between a HART Communicator and a pressure transmitter
When parameterizing with the HART Communicator, the connection is made directly to the 2-wire cable.
+
1
2
3
4
5
6
7
8
9
Process flange with process connection
O-Ring
Measuring cell body
Silicon pressure sensor
Overload diaphragm
Filling liquid of the measuring cell
Capillary tube with filling liquid of the mounting flange
Flange with optional tube
Seal diaphragm for mounting flange
Measuring cell for level, function diagram
• The input pressure (hydrostatic pressure) acts hydraulically
on the measuring cell via the seal diaphragm on the mounting
flange.
• The differential pressure applied to the measuring cell is transmitted via the seal diaphragm and the filling liquid to the silicon pressure sensor.
• If the measuring limits are exceeded, the overload diaphragm
flexes until the seal diaphragm touches the body of the measuring cell. This protects the sensor module from overload.
• The differential pressure causes the measuring diaphragm of
the silicon pressure sensor to flex.
• The displacement changes the resistance value of the 4 piezo
resistors in the measuring diaphragm in a bridge circuit.
• The change in the resistance causes a differential pressure
proportional to the input pressure.
Configuration of SITRANS P500 HART
Depending on the version, there are a range of options for configuring the pressure transmitter and for setting or reading the
parameters.
Configuration using the pushbuttons (local operation)
You can configure the transmitter in situ using the three keys provided a display is available. If you have no display, you can only
carry out zero adjustment.
It is possible to retrofit a display. See accessories.
230 ... 500 Ω
SITRANS P500
transmitter
HART
modem
Power supply
PC or
laptop
USB/RS 232
HART communication between a PC communicator and a pressure
transmitter
For configuring via PC a HART modem is used which connects
the transmitter to the PC.
The signals needed for communication in conformity with the
HART 6.0 protocols are superimposed on the output current using the Frequency Shift Keying (FSK) method.
The necessary device files are available for download on the Internet.
SITRANS P500 configuration options
The transmission offers you full configuring options both via
HART as well as in situ provided the optional display is available.
For simple parameterizing we also offer the easy to understand
QuickStart function with guided commissioning.
SITRANS P500 diagnostic functions
• Maintenance timer
• Min/Max pointer (both resetable and non-resetable)
- Pressure (incl. time and temperature stamp)
- Static pressure (incl. time and temperature stamp)
- Sensor temperature (incl. time stamp)
- Electronic temperature (incl. time stamp)
• Limit monitor block
• Diagnostic warning
• Diagnostic alarm
• Simulation functions
• Display of trends and histograms
• Operating hours meter
Siemens FI 01 · 2015 US Edition
1/179
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
1
SITRANS P500 - Technical description
Physical dimensions available for the SITRANS P500 HART
display
Physical variable
Physical dimensions
Pressure (setting can also be made
in the factory)
Pa, MPa, kPa, bar, mbar, torr, atm,
psi, g/cm2, kg/cm2, mmH2O
(4 °C), inH2O (4 °C), inH2O
(20 °C), mmH2O, mmH2O (4 °C),
ftH2O (20 °C), inHg, mmHg, hPA
Level
m, cm, mm, ft, in
Volume
m3, dm3, hl, yd3, ft3, in3, gallon,
lmp. gallon, bushel, barrel, barrel
liquid, I; Norm (standard) I; Norm
(standard) m3, Norm (standard)
feet3
Mass
g, kg, t (metric), lb, Ston, Lton, oz
Volume flow
m3/d, m3/h, m3/s, l/min, l/s, ft3/d,
ft3/min, ft3/s, US gallon/min,
gallon/s, l/h, milL/d, gallon/d, gallon/h, milgallon/d, lmp.gallon/s,
Imp.gallon/m, Imp.gallon/h,
lmp.gallon/d, Norm (standard)
m3/h, Norm (standard) l/h, Norm
(standard) ft3/h, Norm (standard)
ft3/m, barrel liquid/s, barrel liquid/m, barrel liquid/h
Mass flow
t/d, t/h, t/min, kg/d, kg/h, kg/min,
kg/s, g/h, g/min, g/s, lb/d, lb/min,
lb/s, LTon/d, LTon/h, STon/d,
STon/h, STon/min
Temperature
K, °C, °F, °R
Miscellaneous
%, mA
1/180
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 for differential pressure and flow
■ Technical specifications
Input
Measuring accuracy
Measured variable
Differential pressure and flow
Span (infinitely adjustable)
Span (min. ... max.)
Maximum
operating
pressure
(static
pressure)
Reference conditions (in accor- • Rising characteristic curve
dance with IEC 60770-1)
• Start of scale 0 bar
All error information always
• Stainless steel seal diaphragm
refers to the set span.
• Measuring cell with silicone oil filling
• Room temperature (25 °C (77 °F))
160 bar
(2320 psi)
Error in measurement at limit
setting incl. hysteresis and
reproducibility
r: Span ratio
(r: Span ratio (r = max. span /
set span))
1,00 ... 50 mbar
(0.4 ... 20 inH2O)
1.25 ... 250 mbar
(0.5 ... 100 inH2O)
6.25 ... 1250 mbar
(2.5 ... 502 inH2O)
31.25 ... 6250 mbar
(12.54 ... 2509 inH2O)
0.16 ... 32 bar
(2.33 ... 465 psi)
Lower range limit
• Measuring cell with silicone oil -100 % of max. span and/or
filling
30 mbar a (0.44 psia)
Upper range limit
100 % of max. span
Start of scale
Between measuring limits (freely
adjustable)
Output
Linear characteristic
r  10
r  10
• 50 mbar (20 inH2O)
0.06 %
(0.006 . r) %
• 250 mbar (100 inH2O)
1250 mbar (502 inH2O)
6250 mbar (2509 inH2O)
32 bar (465 psi)
0.03 %
(0.003 . r) %
r  10
r  10
- 50 mbar (20 inH2O)
0.06 %
(0.006. r) %
- 250 mbar (100 inH2O)
1250 mbar (502 inH2O)
6250 mbar (2509 inH2O)
32 bar (465 psi)
0.03 %
(0.003 . r) %
Square-rooted characteristic
• Flow > 50 %
Output current signal
4 ... 20 mA
• Lower current limit
(freely adjustable)
3.55 mA, factory setting 3.8 mA
• Upper current limit
(freely adjustable)
23 mA, factory setting 20.5 mA
• Ripple (without HART
communication)
Ipp  0.4 % of max. output current
• adjustable damping
0... 100 s in steps of 0.1 s,
factory-seting: 2 s
Influence of ambient temperature per 28 °C (50 °F)
• current transmitter
3.55 ... 23 mA
• 50 mbar (20 inH2O)
(0.04 . r + 0.05) %
• Failure signal
adjustable within limits::
• Bottom: 3.55 … 3.7 mA
(default value: 3.6 mA)
• Top: 21.0 … 23 mA
(default value: 22.8 mA)
• 250 mbar (100 inH2O)
(0.025 . r + 0.014) %
• 1250 mbar (502 inH2O)
6250 mbar (2509 inH2O)
32 bar (465 psi)
(0.006 . r + 0.03) %
Load
• Without HART communication RB  (UH - 10.5 V)/0.023 A in ,
UH : Power supply in V
r  10
r  10
- 50 mbar (20 inH2O)
0.12 %
(0.012 . r) %
- 250 mbar (100 inH2O)
1250 mbar (502 inH2O)
6250 mbar (2509 inH2O)
32 bar (465 psi)
0.06 %
(0.006 . r) %
• Flow 25 % … 50 %
Influence of static pressure
• At the start of scale value
(PKN)
- 50 mbar (20 inH2O)
(0.1 . r) % per 70 bar (1015 psi) correction via zero point correction
- 250 mbar (100 inH2O)
(0.035 . r) % per 70 bar (1015 psi)
correction via zero point correction
- 1250 mbar (502 inH2O)
6250 mbar (2509 inH2O)
32 bar (465 psi)
(0.007 . r) % per 70 bar (1015 psi)
correction via zero point correction
• With HART communication
- HART Communicator
RB = 230 ... 1100 
- HART modem
RB = 230 ... 500 
Characteristic curve
Linearly rising, linearly falling, square
rooted characteristic rising, bidirectional square rooted characteristic
and user-specific
• On the span (PKS)
- 50 mbar (20 inH2O)
 0.13 % per 70 bar (1015 psi)
- 250 mbar (100 inH2O)
1250 mbar (502 inH2O)
 0.03 % per 70 bar (1015 psi)
- 6250 mbar (2509 inH2O)
 0.09 % per 70 bar (1015 psi)
- 32 bar (465 psi)
 0.05 % per 70 bar (1015 psi)
Siemens FI 01 · 2015 US Edition
1/181
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
1
SITRANS P500 for differential pressure and flow
Total Performance1)
Design
r5
5 < r  10
Weight (without options)
- 50 mbar (20 inH2O)
0,27 %
0,46 %
- 250 mbar (100 inH2O)
0.14 %
0.27 %
- 1250 mbar (502 inH2O)
6250 mbar (2509 inH2O)
32 bar (465 psi)
0.09 %
0.14 %
Material of parts in contact with
the medium
• Seal diaphragm
Stainless steel, mat. no. 1.4404/316L,
Hastelloy C276, Monel 400
• Process connection and seal- PN 160: stainless steel, mat.-No.
ing screw
1.4404/316L
r5
5 < r  10
• Sealing material in the process connections
- 50 mbar (20 inH2O)
0,27 %
0,46 %
- 250 mbar (100 inH2O)
0.14 %
0.27 %
- 1250 mbar (502 inH2O)
6250 mbar (2509 inH2O)
32 bar (465 psi)
0.09 %
0.14 %
• Linear characteristic
Square rooted characteristic
• Flow > 50 %
- O-Ring
Approx. 3.3 kg (7.3 lb)
• Standard:
Viton (FKM (FPM))
• Optional:
NBR
PTFE (virginal)
PTFE (glass fiber-reinforced)
FFPM (Kalrez)2)
Graphite
r5
5 < r  10
- 50 mbar (20 inH2O)
0,54 %
0,92 %
- 250 mbar (100 inH2O)
0.28 %
0.54 %
Material of parts not in contact
with media
- 1250 mbar (502 inH2O)
6250 mbar (2509 inH2O)
32 bar (465 psi)
0.18 %
0.28 %
Electronics housing
• Low copper die-cast aluminum
AC-AlSi12 (Fe) or AC-AlSi 10 Mg (Fe)
to DIN EN 1706
• Lacquer on polyurethane base, optional epoxy-based primer
• Stainless steel name plates
(mat. no. 1.4404/316L)
• Flow 25 % … 50 %
Step response time T63 without
electrical damping
• 50 mbar (20 inH2O)
 140 ms, contains a dead time of
 45 ms
• 250 mbar (100 inH2O)
1250 mbar (502 inH2O)
6250 mbar (2509 inH2O)
32 bar (465 psi)
 88 ms, contains a dead time of
 45 ms
Process connection screws
Stainless steel, mat. no. 1.4404/316L
Mounting bracket
Steel or stainless steel
mat. no. 1.4301
Long-term stability
 (0.05 . r) % per 5 years
 (0.08 . r) % per 10 years
Measuring cell filling
Silicone oil
Process connection
Influence of power supply
 0.005 %/1 V
¼-18 NPT female thread and flange
connection with M10 to DIN 19213 or
7/16-20 UNF mounting thread to IEC
61518
Electrical connection
• Screw terminals
• Cable entry via the following
screwed glands:
- M20 x 1.5
- ½-14 NPT
- Han 7D/Han 8D connector
- M12 plug
Rated conditions
Mounting position
Any
Ambient conditions
• Ambient temperature
(Note: Observe the temperature class in areas subject to
explosion hazard.)
- Total device
- Readable display
- Storage temperature
-40 ... +85 °C (-40 ... +185 °F)
-20 ... +85 °C (-4 ... +185 °F)
-50 ... +90 °C (-58 ... +194 °F)
Climatic class
• Condensation
Relative humidity 0 … 100 %
(condensation permissible)
Degree of protection
(to IEC 60529)
IP66/IP 68 and NEMA 4X (with corresponding cable gland)
Electromagnetic Compatibility
• Emitted interference and inter- Acc. to IEC 61326 and NAMUR NE 21
ference immunity
Permissible pressures
According to 97/23/EC pressure
equipment directive
Temperature of medium
• Measuring cell with silicone oil -40 ... +125 °C (-40 ... +257 °F)
filling
1/182
Siemens FI 01 · 2015 US Edition
Displays and controls
Pushbuttons
3 for local programming directly on
transmitter
Display
• With or without integrated display
• Cover with or without window
Auxiliary power supply
Terminal voltage on transmitter
• DC 10.6 ... 44 V
• With intrinsically-safe operation
DC 10.6 ... 30 V
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 for differential pressure and flow
Explosion protection for USA
(to FM)
Certificates and approvals
Classification according to PED
97/23/EC
• PN 160 (MAWP 2320 psi)
For gases of fluid group 1 and liquids
of fluid group 1; complies with
requirements of article 3, paragraph 3
(sound engineering practice)
Certificate of Compliance
No. 3033013
• Identification (XP/DIP) or (IS)
XP CL I, DIV 1, GP ABCDEFG T4 / T6
DIP CL II, III, DIV1, GP EFG T4/T6
IS CL I, II, III, DIV1, GP ABCDEFG T4
CL I, Zone 0, AEx ia IIC T4
CL I, Zone 1, AEx ib IIC T4
Explosion protection
Explosion protection for Europe
(to ATEX)
• Intrinsic safety "i"
- Marking
- Permissible ambient temperature
- Connection
PTB 09 ATEX 2004 X
Ex II 1/2 G Ex ia/ib IIC T4
-40 ... +85 °C (-40 ... +185 °F)
To certified intrinsically-safe circuits
with peak values:
Ui = 30 V, Ii = 100 mA, Pi = 750 mW;
Ri = 300 
Li = 400 µH
- Permissible Ambient Temperature
Ta = T4: -40 ... +85 °C
(-40 ... +185 °F)
Ta = T6: -40 ... +60 °C
(-40 ... +140 °F)
- Entity parameters
According to "control drawing":
A5E02189134N
Um = 30 V, Im = 100 mA,
Pi = 750 mW, Li = 400µH , Ci = 6 nF
• Marking (NI/NO)
NI CL I, DIV 2, GP ABCD T4/T6
NI CL I, Zone 2, GP IIC T4/T6
S CL II, III, GPFG T4/T6
NI CL I, DIV 2, GP ABCD T4/T6, NIFW
NI CL I, Zone 2, GP IIC T4/T6, NIFW
NI CLII, III, DIV 2, GP FG T4/T6, NIFW
- Effective internal inductance:
- Effective inner capacitance: Ci = 6 nF
• Explosion-proof "d"
- Marking
- Permissible ambient temperature
- Connection
• Dust explosion protection for
zone 20
- Marking
- Permissible ambient temperature
- Max. surface temperature
- Connection
BVS 09 ATEX E 027
Ex II 1/2 G Ex d IIC T4/T6
-40 ... +85 °C (-40 ... +185 °F)
temperature class T4;
-40 ... +60 °C (-40 ... +140 °F)
temperature class T6
To circuits with values:
Um = DC 10.5 ... 45 V
PTB 09 ATEX 2004 X
Ex II 1 D Ex iaD 20 T 120 °C
-40 ... +85 °C (-40 ... +185 °F)
120 °C (248 °F)
To certified intrinsically-safe circuits
with peak values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW, Ri = 300 
Li = 400 µH
- Effective internal inductance:
- Effective inner capacitance: Ci = 6 nF
• Dust explosion protection for
zone 21/22
- Marking
- Connection
- Permissible Ambient Temperature
Ta = T4: -40 ... +85 °C
(-40 ... +185 °F)
Ta = T6: -40 ... +60 °C
(-40 ... +140 °F)
- (NI/S) parameters
According to "control drawing":
A5E02189134N
Um = 45 V, Li = 400 µH, Ci = 6 nF,
Explosion protection for
Canada (to CCSAUS )
Certificate of Compliance
No. 2280963
• Marking (XP/DIP)
CL I, DIV 1, GP ABCD T4 /T6;
CL II, DIV 1, GP EFG T4/T6
- Permissible ambient temperature
Ta = T4: -40 ... +85 °C (-40 ... +185 °F)
Ta = T6: -40 ... +60 °C (-40 ... +140 °F)
- Entity parameters
According to "control drawing":
A5E02189134N
Um = 45 V
• Marking (ia/ib)
CL I, Ex ia/Ex ib IIC, T4
CL II, III, Ex ia/Ex ib, GP EFG, T4
CL I, AEx ia/AEx ib IIC, T4
CL II, III, AEx ia/ AEx ib, GP EFG, T4
BVS 09 ATEX E 027
Ex II 2 D Ex tD A21 IP68 T120 °C Ex ia
D21
To circuits with values:
Um = 10.5 ... 45 V DC; Pmax = 1.2 W
• Type of protection "n" (zone 2) PTB 09 ATEX 2004 X
Ex II 3 G Ex nA II T4/T6
- Marking
Ex II 2/3 G Ex ib/nL IIC T4/T6
Ex II 2/3 G Ex ib/ic IIC T4/T6
- "nA" connection
Um = 45 V DC
- "nL, ic" connection
Ui = 45 V
Li = 400 µH
- Effective internal inductance:
- Effective inner capacitance: Ci = 6 nF
- Permissible ambient temperature
Ta = T4: -40 ... +85 °C
(-40 ... +185 °F)
- Entity parameters
Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri
= 300  , Li = 400 µH, Ci = 6 nF
CL I, DIV 2, GP ABCD T4/T6
CL II, III, DIV 2, GP FG T4/T6
Ex nA IIC T4/T6
AEx nA IIC T4/T6
Ex nL IIC T4/T6
AEx nL IIC T4/T6
• Marking (NI/n)
- Permissible ambient temperature
Ta = T4: -40 ... +85 °C (-40 ... +185 °F)
Ta = T6: -40 ... +60 °C (-40 ... +140 °F)
- NI/nA parameters
According to "control drawing":
A5E02189134N
Um = 45 V
- nL parameters
According to "control drawing":
A5E02189134N
Ui = 45 V, Ii = 100 mA, Li = 400 µH,
Ci = 6 nF
Siemens FI 01 · 2015 US Edition
1/183
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
1
SITRANS P500 for differential pressure and flow
Explosion protection for China
(acc. to NEPSI)
• Intrinsic safety "i"
GYJ111111X
Ex ia/ib IIB/IIC T4
- Marking
- Perm. ambient temperature 40 ... +85 °C (-40 ... +185 °F)
- Connection
To certified intrinsically-safe circuits
with maximum values:
Ui = 30 V Ii = 100 mA, Pi = 750 mW
- Effective internal inductance Li = 400 mH
- Effective inner capacitance
• Explosion-proof "d"
Ci = 6 nF
GYJ111112
- Marking
Ex dia IIC T4/T6
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
- Connection
To circuits with values:
Um = DC 10.5 ... 45 V
• Dust explosion protection for
zone 21/22
GYJ111112
- Marking
DIP A21 TA,T120 °C IP68 D21
- Connection
To circuits with values:
Um = DC 10.5 ... 45 V
• Type of protection "n" (zone 2) GYJ111111X
- Marking
Ex nL IIB/IIC T4/T6
Ex nA II T4/T6
- Connection
Ui = 45 V DC
- Effective internal inductance Li = 400 mH
- Effective inner capacitance
Ci = 6 nF
1)
The total performance includes the errors caused by temperature effects,
static pressure effects and conformity error, including hysteresis and repeatability.
2)
Not in combination wiht span "G".
HART communication
Load with connection of
• HART communicator
RB = 230 ... 1100 
• HART modem
RB = 230 ... 500 
Cable
2 wire shielded:  3.0 km
(1.86 miles),
multiwire shielded:  1.5 km
(0.93 miles)
Protocol
HART Version 6.0
PC/laptop requirements
IBM compatible, RAM > 32 MByte,
hard disk > 70 MByte, depending
on modem type: RS 232-interface
or USB connection,
VGA graphics
Software for computer
SIMATIC PDM 6.0
1/184
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 for differential pressure and flow
Selection and Ordering data
Article No.
Pressure transmitters for differential pressure and flow,
SITRANS P500 HART, PN 160 (MAWP 2320 psi)
7 MF 5 4 77 - 7777 0
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Enclosure
Thread for cable gland
Die-cast aluminum, dual compartment
M20x1.5
0
Die-cast aluminum, dual compartment
½-14 NPT
1
Output
4 ... 20 mA, HART
3
Measuring cell filling
Measuring cell cleaning
Silicone oil
normal
1
Measuring span
1.00 ... 50 mbar
(0.4 ... 20 inH2O)
C
1.25 ... 250 mbar
(0.5 ... 100.4 inH2O)
D
6.25 ... 1250 mbar
(2.5 ... 502 inH2O)
E
31.25 ... 6250 mbar
(12.54 ... 2509 inH2O)
F
0.16 ... 32 bar
(2.33 ... 465 psi)
G
Wetted parts materials
(stainless steel process flanges)
Seal diaphragm
Process connection
Stainless steel 1.4404/316L
Stainless steel 1.4404/316L
A
Hastelloy C2761)
Stainless steel 1.4404/316L
B
Monel 4001)
Stainless steel 1.4404/316L
C
Process connection
Female thread ¼-18 NPT
• Sealing screw opposite process connection
- Mounting thread 7/16 - 20 UNF according to EN 61518
- Mounting thread M10 to DIN 19213
0
1
• Vent on side of process flange2)
- Mounting thread 7/16 - 20 UNF according to EN 61518
- Mounting thread M10 to DIN 19213
4
5
1) Not together with Measuring span "C".
2) Not in conjunction with remote seals (option V00).
Siemens FI 01 · 2015 US Edition
1/185
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
1
SITRANS P500 for differential pressure and flow
Order code
Selection and Ordering data
Further designs
Add "-Z" to Article No. and specify Order code.
Mounting bracket made of steel
A01
Mounting bracket made of stainless steel
A02
Display
(Standard: no display, cover closed)
With display and blanking cover
A10
With display and glass cover
A11
Special casing / cover version
A20
Electrical connection and cable entry
(Standard: no cable gland, only dust protection
caps)
Cable gland made of plastic
(IP66/68)4)
A50
Cable glands made of metal (IP66/68)
A51
Cable glands made of stainless steel (IP66/68)
A52
M12 connectors without cable socket
(IP66/67)4)
Order code
Further designs
Add "-Z" to Article No. and specify Order code.
Attachments
Two coats of lacquer on casing, cover (PU on epoxy)
Selection and Ordering data
A60
M12 connectors complete with cable socket (IP66/67)4)
A61
Han 7D connectors, plastic, straight
(with cable socket) (IP65)4)
A71
Han 7D connectors, plastic, angled
(with cable socket) (IP65)4)
A72
Han 7D connectors, metal enclosure, straight
(with cable socket) (IP65)4)
A73
Han 7D connectors, metal enclosure, angled
(with cable socket) (IP65)4)
A74
Han 8D connectors, plastic, straight
(with cable socket) (IP65)4)8)
A75
Han 8D connectors, plastic, angled
(with cable socket) (IP65)4)8)
A76
Han 8D connectors, metal enclosure, straight
(with cable socket) (IP65)4)8)
Degree of protection approvals: Ex ia/ib (intrinsic safety)
Ex ia/ib protection (ATEX) (T4)
Ex IS protection (FM) (T4)
Ex IS protection (CCSAUS) (T4)
Ex ia/ib protection (NEPSI) (T4)
E00
E01
E02
E06
Degree of protection approvals: Ex d (flameproof)
Ex d explosion-proof (ATEX)(T4/T6)
Ex XP explosion-proof and DIP (FM)(T4/T6)
Ex XP explosion-proof and DIP (CCSAUS)(T4/T6)
Ex d explosion-proof (NEPSI)(T4/T6)
E20
E21
E22
E26
Degree of protection approvals: n/NI
Zone 2 (nA, nL, ic) (ATEX) (T4/T6)
Div2 NI, Div2 NI-field wiring (FM) (T4/T6)
Zone 2 (nA, nL), Div2 NI (CCSAUS) (T4/T6)
Zone 2 (nA, nL) (NEPSI) (T4/T6)
E40
E41
E42
E46
Degree of protection approvals: Dust Zone 20/21/22
Use in Zone 21/22 (Ex tD) (ATEX)
Use in Zone 20/21/22 (Ex iaD) (ATEX)
Use in Zone 21/22 (Ex DIP) (NEPSI)
E60
E61
E66
Degree of protection approvals: Combinations
IS protection and XP and DIP (FM)
IS protection and XP and DIP (CCSAUS)
IS protection and XP and DIP (FM/CCSAUS)
E71
E72
E73
Supplementary approvals/degree of protection
Dual Seal approval5)
Export approval Korea
E85
E86
Special process connection versions (diff. pressure)
Side vents for gas measurements7)
L32
Swap process connection: high-pressure side at front
L33
A77
Mosquito protection
4 pcs. for ¼-18 NPT thread
L36
Han 8D connectors, metal enclosure, angled
(with cable socket) (IP65)4)8)
A78
Process flanges, O-rings, special material
Standard: Viton (FKM (FPM)
PG 13.5 adapters4)
A82
Process conn. sealing rings made of PTFE (Teflon), virginal L60
Process connection sealing rings made of PTFE (Teflon),
glass fiber-reinforced
Language for labels, leporellos, menu language
default 9)
(instead of English as standard)
L61
Process connection sealing rings made of FFPM (Kalrez)10) L62
German
B10
Process connection sealing rings made of NBR
L63
French
B12
Process connection sealing rings made of graphite
L64
Spanish
B13
Drain/Vent valve (1 set = 2 units)
Italian
B14
2 ventilation valves ¼- 18 NPT, in material of process flanges) L80
Chinese
B15
Remote seals
Russian
B16
Japanese
B17
Transmitters with connection of remote seal6)
(For premounted valve manifolds see page 1/203)
English with units psi/inH2O/°F
B21
Special version: Supplementary menu languages
(Standard: English, German, French, Spanish, Italian)
Asia language package
(in addition: Chinese, Japanese, Russian)
B80
Certificates
(available online for downloading)1)
Quality inspection certificate (Five-step factory calibration)
according to IEC 60770-22)
C11
Acceptance test certificate according to EN 10204-3.13)
C12
1/186
Siemens FI 01 · 2015 US Edition
1)
V00
Enclosed in print or as CD: see page 1/201.
When also ordering the quality inspection certificate (factory calibration)
according to IEC 60770-2 for transmitters with mounted diaphragm seals:
Order this certificate only together with the remote seals. The measuring
accuracy of the total combination is certified here.
3)
When also ordering the acceptance test certificate according to EN 102043.1 for transmitters with mounted diaphragm seals: Order this certificate as
well in addition to the respective remote seals.
4)
Not together with types of protection "Explosion-proof", "Ex nA" and
"Intrinsic safety and explosion-proof"
5)
Only in conjunction with FM and/or CCSAUS
6)
Please select a remote seal separately. Also refer to the information under
footnote 2). Remote seals see page 1/199.
7) Only in conjunction with process connection "Vent on side".
8)
The Han 8D plug is identical with the former Han 8U version.
9)
For option B15, B16 and B17 the menu language default is english. Otherwise the Option B80 (Asia language package) is necessary.
10) Not together with Measuring span "G".
2)
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 for differential pressure and flow
Selection and Ordering data
Order code
Additional data
Please add "-Z" to Article No. and specify Order code(s)
and plain text.
Measuring range to be set
Specify in plain text:
• In the case of linear characteristic curve
(max. 5 characters):
Y01: ... up to ... mbar, bar, kPa, MPa, psi
Y01
• In the case of square rooted characteristic
(max. 5 characters):
Y02: ... up to ... mbar, bar, kPa, MPa, psi
Y02
Measuring point number and measuring point identifier
(only standard ASCII character set)
Specify in plain text:
Measuring point number (TAG No.), max. 16 characters
Y15: .........................................
Y15
Measuring point text (max. 27 char.)
Y16: .........................................
Y16
Entry of HART address (TAG), max. 32 characters
Y17: .........................................
Y17
Setting of pressure indication in pressure units
Y21
Specify in plain text (standard setting: mbar)
Y21: bar, kPa, MPa, psi, ...
Note: The following pressure units are selectable:
bar, mbar, mm H2O*), in H2O*), ftH2O*), mmHG, inHG, psi,
Pa, kPa, MPa, g/cm2, kg/cm2, Torr, ATM, % or mA
*) Reference temperature 20 °C
Setting of pressure indication in non-pressure units1)
Y22 +
Y01 or Y02
Specify in plain text:
Y22: ... up to ... l/min, m3/h, m, USgpm, ...
(specification of measuring range in pressure units "Y01" is
essential, unit with max. 5 characters)
Customer-specific settings
Damping setting (range: 0 ... 100 s)
(Standard setting: 2 s)
1)
Y30
Preset values can only be changed over SIMATIC PDM.
Siemens FI 01 · 2015 US Edition
1/187
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 for differential pressure and flow
■ Dimensional drawings
[
139
(5.48)
87
(3.4)
\
approx. 30
(approx. 1.2)
45
(1.8)
23
(0.92)
FIELD TERMINALS
X
Z
XW
XP
approx. 259
(approx.10.1)
XP
157
(6.1)
125
(5)
Ø81
(Ø3.24)
58
(2.29
65
(2.6)
`
_
102
(4)
Y
134
(5.36)
1
43
(1.68)
approx. 98
(approx. 3.82)
^Y
OYU_Z
^
]
]^
OYU]P XX`
O[U]P
XW[
O[UX]P
1
2
3
4
5
6
Terminal side
Process connection: ¼-18 NPT (EN 61518)
Electronics side, digital display
Protective cover for the pushbuttons
Cable entry:
- Screwed gland M20 x 1.53)
- Screwed gland ½-14 NPT
- Han 7D/Han 8D connector2)3)
- M12 connector
Mounting bracket (optional)
7
Electrical connection:
- Han 7D/Han 8D connector/socket2)3)
8 Vent valve (optional)
9 Safety catch
10 Blanking plug
1)
2)
3)
Allow approx. 20 mm (0.79 inch) additional thread length
Not with type of protection "Explosion-proof"
Not with type of protection "FM + CCSAUS [IS + XP]"
SITRANS P pressure transmitter for differential pressure and flow, P500 series, measurements in mm (inch)
1/188
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 for level
■ Technical specifications
 (0.05 . r) % per 5 years
Long-term stability
Input
Measured variable
Level
Span (infinitely adjustable)
Span (min. ... max.)
 (0.08 . r) % per 10 years
Maximum
operating
pressure
1.25 ... 250 mbar
(0.5 … 100 inH2O)
6.25 ... 1250 mbar
(2.5 ... 500 inH2O)
See "Mounting
flange"
31.25 ... 6250 mbar
(12.54 ...
2509 inH2O)
Influence of ambient temperature per 28 °C (50 °F)1)
• 250 mbar (100 inH2O)
(0.025 . r + 0.014) %
• 1250 mbar (502 inH2O)
6250 mbar (2509 inH2O)
(0.006 . r + 0.03) %
Influence of static pressure
• At the start of scale value
(PKN)
- 250 mbar (100 inH2O)
(0.035 . r) % je 70 bar (1015 psi)
correction via zero point correction
- 1250 mbar (502 inH2O)
6250 mbar (2509 inH2O)
(0.007 . r) % je 70 bar (1015 psi)
correction via zero point correction
Lower range limit
• Measuring cell with silicone oil -100 % of max. span or 500 mbar a
filling
(7.25 psia) vacuum resistance
Also available as vacuum-resistant
remote seal: 30 mbar a (0.44 psia)
Upper range limit
100% of max. span
Start of scale
Between measuring limits (freely
adjustable)
Output
• On the span (PKS)
- 250 mbar (100 inH2O)
1250 mbar (502 inH2O)
 0.03 % je 70 bar (1015 psi)
- 6250 mbar (2509 inH2O)
 0.09 % je 70 bar (1015 psi)
Influence of power supply
 0.005 %/1 V
Rated conditions
Output current signal
4 ... 20 mA
Mounting position
• Lower current limit
(freely adjustable)
3.55 mA, factory setting 3.8 mA
Ambient conditions
• Upper current limit
(freely adjustable)
23 mA, factory setting 20.5 mA
Defined by flange
• adjustable damping
0... 100 s in steps of 0.1 s, factory setting 2 s
• Ambient temperature
(Note: Observe the temperature class in areas subject to
explosion hazard.)
- total device
- Readable display
- Storage temperature
• current transmitter
3.55 ... 23 mA
Climatic class
• Failure signal
Adjustable within limits:
• Lower: 3.55 … 3.7 mA (factory setting 3.6 mA)
• Upper: 21.0 … 23 mA (factory setting 22.8 mA)
• Condensation
Relative humidity 0 … 100 %
(condensation permissible)
Degree of protection
to IEC 60529
IP66/IP68 and NEMA 4X (with corresponding cable gland)
• Ripple (without HART commu- Ipp  0.4 of max. output current
nication)
Load
• Without HART communication RB  (UH - 10.5 V)/0.023 A in ,
UH : Power supply in V
Electromagnetic Compatibility
• Emitted interference and inter- Acc. to IEC 61326 and NAMUR NE 21
ference immunity
Permissible pressures
According to 97/23/EC pressure
equipment directive
• With HART communication
- HART Communicator
RB = 230 ... 1100 
- HART modem
RB = 230 ... 500 
Characteristic curve
Medium temperature of highpressure side
Linearly rising or linearly falling and
user-specific
Measuring accuracy
Reference conditions
(in accordance with
IEC 60770-1)
All error information always
refers to the set span.
-40 ... +85 °C (-40 ... +185 °F)
-20 ... +85 °C (-4 ... +185 °F)
-50 ... +90 °C (-58 ... +194 °F)
• Rising characteristic curve
• Start of scale 0 bar
• Stainless steel seal diaphragm
• Measuring cell with silicone oil filling
• Room temperature (25 °C (77 °F))
Error in measurement at limit
setting incl. hysteresis and
reproducibility
r: Span ratio
(r = max. span / set span)
• Measuring cell with silicone oil
filling
- pabs  1 bar
-40 ... +1752) °C (-40 ... +3472) °F)
- pabs  1 bar
-40 ... +80 °C (-40 ... +176 °F)
Design
Weight
• To EN (pressure transmitter
approx. 9.8 … 11.8 kg (21.6… 26.0
with mounting flange, without (lb)
tube)
• To ASME (pressure transmitter approx. 9.8 … 16.8 kg (21.6 … 37.0
with mounting flange, without lb)
tube)
Linear characteristic
r  10
r  10
• 250 mbar (100 inH2O)
1250 mbar (502 inH2O)
6250 mbar (2509 inH2O)
0.03 %
(0.003 . r) %
Siemens FI 01 · 2015 US Edition
1/189
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
1
SITRANS P500 for level
Material of wetted parts at the
high-pressure side
• Seal diaphragm of mounting
flange
• Sealing face
Auxiliary power supply
Terminal voltage on transmitter
Stainless steel 1.4404/316L,
Hastelloy C276, mat. no. 2.4819,
Monel 400, mat. no. 2.4360, Tantal,
PFA auf Edelstahl 1.4404/316L,
PTFE auf Edelstahl 1.4404/316L
Smooth to EN 1092-1, Form B1 and/or
ASME B16.5 RF 125 … 250 AA for
stainless steel316L, EN1092-1 Form
B2 and/or ASME B16.5 RFSF in the
case of other materials
• Sealing material in the process connection
- O-Ring
- For vacuum application of
mounting flange
• Standard:
Viton (FKM (FPM))
• Optional:
NBR
PTFE (virginal)
PTFE (glas fiber-reinforced)
FFPM (Kalrez)
Graphite
copper
Stainless steel, mat. no. 1.4404/316L,
Hastelloy C276, Monel 400
• Process connection and seal- • Stainless steel, mat. no. 1.4404/316L
ing screw
• Sealing material in the process connection
- O-Ring
• Standard:
Viton (FKM (FPM))
• Optional:
NBR
PTFE (virginal)
PTFE (glas fiber-reinforced)
FFPM (Kalrez)
Graphite
Material of parts not in contact
with media
Electronics housing
Certificates and approvals
Classification according to PED
97/23/EC
• PN 160 (MAWP 2320 psi)
For gases of fluid group 1 and liquids
of fluid group 1; complies with
requirements of article 3, paragraph 3
(sound engineering practice)
Explosion protection
Material of wetted parts at the
low-pressure side
• Seal diaphragm
• DC 10.6 ... 44 V
• With intrinsically-safe operation
DC 10.6 ... 30 V
• Low copper die-cast aluminum ACAlSi12 (Fe) or AC-AlSi 10 Mg (Fe) to
DIN EN 1706
• Lacquer on polyurethane base, optional epoxy-based primer
• Stainless steel serial plate
Process connection screws
Stainless steel
Measuring cell filling
Silicone oil
• Liquid mounting flange
Silicone oil or other material
Process connection
Explosion protection for Europe
(to ATEX)
• Intrinsic safety "i"
PTB 09 ATEX 2004 X
- Marking
Ex II 1/2 G Ex ia/ib IIC T4
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F)
- Connection
To certified intrinsically-safe circuits
with peak values:
Ui = 30 V, Ii = 100 mA, Pi = 750 mW;
Ri = 300 
- Effective internal inductance:
Li = 400 µH
- Effective inner capacitance: Ci = 6 nF
• Explosion-proof "d"
BVS 09 ATEX E 027
- Marking
Ex II 1/2 G Ex d IIC T4/T6
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F)
temperature class T4;
-40 ... +60 °C (-40 ... +140 °F)
temperature class T6
- Connection
To circuits with values:
Um = DC 10.5 ... 45 V
• Dust explosion protection for
zone 20
PTB 09 ATEX 2004 X
- Marking
Ex II 1 D Ex iaD 20 T 120 °C
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F)
- Max. surface temperature
120 °C (248 °F)
- Connection
To certified intrinsically-safe circuits
with peak values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW, Ri = 300 
- Effective internal inductance:
Li = 400 µH
- Effective inner capacitance: Ci = 6 nF
• Dust explosion protection for
zone 21/22
BVS 09 ATEX E 027
• High-pressure side
Flange to EN and ASME
- Marking
• Low-pressure side
¼-18 NPT female thread and flange
connection with M10 to DIN 19213 or
7/16-20 UNF mounting thread to IEC
61518
Ex II 2 D Ex tD A21 IP68 T120 °C Ex ia
D21
- Connection
To circuits with values:
UH = 10.5 ... 45 V DC; Pmax = 1.2 W
Electrical connection
• Screw terminals
• Cable entry via the following
screwed glands:
- M20 x 1.5
- ½-14 NPT
- Han 7D/Han 8D connector
- M12 plug
Displays and controls
Push buttons
3; for operation directly on the device
Display
• With or without integrated display
• Cover with or without window
1/190
Siemens FI 01 · 2015 US Edition
• Type of protection "n"
(zone 2)
PTB 09 ATEX 2004 X
- Marking
Ex II 3 G Ex nA II T4/T6
Ex II 2/3 G Ex ib/nL IIC T4/T6
Ex II 2/3 G Ex ib/ic IIC T4/T6
- "nA" connection
Um = 45 V DC
- "nL, ic" connection
Ui = 45 V
- Effective internal inductance Li = 400 µH
- Effective inner capacitance
Ci = 6 nF
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 for level
Explosion protection for USA
(to FM)
Explosion protection for China
(acc. to NEPSI)
Certificate of Compliance
No. 3033013
• Identification (XP/DIP) or (IS)
XP CL I, DIV 1, GP ABCDEFG T4 / T6
DIP CL II, III, DIV1, GP EFG T4/T6
IS CL I, II, III, DIV1, GP ABCDEFG T4
CL I, Zone 0, AEx ia IIC T4
CL I, Zone 1, AEX ib IIC T4
- Permissible Ambient Temperature
Ta = T4: -40 ... +85 °C
(-40 ... +185 °F)
Ta = T6: -40 ... +60 °C
(-40 ... +140 °F)
- Entity parameters
According to "control drawing":
A5E02189134N
Um = 30 V, Im = 100 mA,
Pi = 750 mW, Li = 400 µH , Ci = 6 nF
• Marking (NI/NO)
- Permissible Ambient Temperature
- (NI/S) parameters
• Intrinsic safety "i"
According to "control drawing":
A5E02189134N
Um = 45 V, Li = 400 µH, Ci = 6 nF
Certificate of Compliance
No. 2280963
CL I, DIV 1, GP ABCD T4 /T6;
CL II, DIV 1, GP EFG T4/T6
- Permissible Ambient Temperature
Ta = T4: -40 ... +85 °C
(-40 ... +185 °F)
Ta = T6: -40 ... +60 °C
(-40 ... +140 °F)
- Entity parameters
According to "control drawing":
A5E02189134N, Um = 45 V
• Marking (ia/ib)
CL I, Ex ia/Ex ib IIC, T4
CL II, III, Ex ia/Ex ib, GP EFG, T4
CL I, AEx ia/AEx ib IIC, T4
CL II, III, AEx ia/ AEx ib, GP EFG, T4
- Permissible Ambient Temperature
Ta = T4: -40 ... +85 °C
(-40 ... +185 °F)
- Entity parameters
Ui = 30 V, Ii = 100 mA, Pi = 750 mW,
Ri = 300  , Li = 400 µH, Ci = 6 nF
• Marking (NI/n)
CL I, DIV2, GP ABCD T4/T6
CL II, III, DIV2, GP FG T4/T6
Ex nA IIC T4/T6
AEx nA IIC T4/T6
Ex nL IIC T4/T6
AEx nL IIC T4/T6
- Permissible Ambient Temperature
Ta = T4: -40 ... +85 °C
(-40 ... +185 °F)
Ta = T6: -40 ... +60 °C
(-40 ... +140 °F)
- NI/nA parameters
According to "control drawing":
A5E02189134N, Um = 45 V
- nL parameters
According to "control drawing":
A5E02189134N, Ui = 45 V,
Ii = 100 mA, Li = 400 µH,
Ci = 6 nF
40 ... +85 °C (-40 ... +185 °F)
- Connection
To certified intrinsically-safe circuits
with maximum values:
Ui = 30 V Ii = 100 mA, Pi = 750 mW
- Effective inner capacitance
• Explosion-proof "d"
Ci = 6 nF
GYJ111112
- Marking
Ex dia IIC T4/T6
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
- Connection
To circuits with values:
Um = DC 10.5 ... 45 V
• Dust explosion protection for
zone 21/22
GYJ111112
- Marking
DIP A21 TA,T120 °C IP68 D21
- Connection
To circuits with values:
Um = DC 10.5 ... 45 V
• Type of protection "n" (zone 2) GYJ111111X
Explosion protection for
Canada
(to CCSAUS )
• Marking (XP/DIP)
Ex ia/ib IIB/IIC T4
- Permissible ambient temperature
- Effective internal inductance Li = 400 mH
NI CL I, DIV 2, GP ABCD T4/T6
NI CL I, Zone 2, GP IIC T4/T6
S CL II, III, GPFG T4/T6
NI CL I, DIV 2, GP ABCD T4/T6, NIFW
NI CL I, Zone 2, GP IIC T4/T6, NIFW
NI CLII, III, DIV 2, GP FG T4/T6, NIFW
Ta = T4: -40 ... +85 °C
(-40 ... +185 °F)
Ta = T6: -40 ... +60 °C
(-40 ... +140 °F)
GYJ111111X
- Marking
- Marking
Ex nL IIB/IIC T4/T6
Ex nA II T4/T6
- Connection
Ui = 45 V DC
- Effective internal inductance Li = 400 mH
- Effective inner capacitance
Ci = 6 nF
1)
Only relevant for the pressure transmitter. The temperature error of the
remote seal must calculated separately.
2)
This value may be increased if the process connection is sufficiently insulated.
HART communication
Load with connection of
• HART Communicator
RB = 230 ... 1100 
• HART modem
RB = 230 ... 500 
Cable
2 wire shielded:
 3.0 km (1.86 miles),
multiwire shielded:
 1.5 km (0.93 miles)
Protocol
HART Version 6.0
PC/laptop requirements
IBM compatible, RAM > 32 MByte,
hard disk > 70 MByte,
depending on modem type:
RS 232-interface or
USB connection,
VGA graphics
Software for computer
SIMATIC PDM 6.0
Siemens FI 01 · 2015 US Edition
1/191
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
1
SITRANS P500 for level
Article No.
Order code
777
7 MF 5 6 77 - 7777 0 - 7777
Selection and Ordering data
Pressure transmitters for level, SITRANS P500 HART
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Enclosure
Die-cast aluminum, dual compartment
Die-cast aluminum, dual compartment
Output
4 ... 20 mA, HART
Measuring cell filling
Measuring cell cleaning
Silicone oil
normal
Measuring span (min. ... max.)
1.25 ... 250 mbar
(0.5 ... 100 inH2O)
6.25 ... 1250 mbar
(2.5 ... 500 inH2O)
31.25 ... 6250 mbar
(12.54 ... 2509 inH2O)
Thread for cable gland
M20x1.5
½-14 NPT
0
1
3
1
D
E
F
Wetted parts of the low-pressure side
(stainless steel process flanges)
Seal diaphragm
Process connection
Stainless steel 1.4404/316L
Stainless steel 1.4404/316L
Hastelloy C276
Stainless steel 1.4404/316L
Monel 400
Stainless steel 1.4404/316L
Process connection of low-pressure side
A
B
C
Female thread ¼-18 NPT
• Sealing screw opposite process connection
- Mounting thread 7/16 - 20 UNF according to IEC 61518
- Mounting thread M10 to DIN 19213
0
1
• Vent on side of process flange
- Mounting thread 7/16 - 20 UNF according to IEC 61518
- Mounting thread M10 to DIN 19213
4
5
Wetted parts materials (high-pressure side)
Stainless steel 1.4404/316L
Hastelloy C276 mat. no. 2.4819
Monel 400 mat. no. 2.4360
Tantalum
PFA coated on stainless steel
PTFE on stainless steel 1.4404/316L (not in combination with an extension)
Other version
Add Order code and plain text:
Material: ... ; Extension length: ...
0
1
2
3
4
6A
9Y
N1Y
Process connection on high-pressure side: Extension length
None
50 mm (1.97 inch)
100 mm (3.94 inch)
150 mm (5.90 inch)
200 mm (7.87 inch)
Other version: See option "9" for "Wetted parts materials"
A
B
C
D
E
Process connection on high-pressure side: Nominal diameter/Nominal pressure
DN 50, PN 406)
DN 80, PN 40
DN 100, PN 16
DN 100, PN 40
2", class 1506)
2", class 3006)
3", class 150
3", class 300
4", class 150
4", class 300
Other version, add
Order code and plain text:
Nominal diameter: ... ; Nominal pressure: ...
1/192
Siemens FI 01 · 2015 US Edition
B
D
G
H
L
M
Q
R
T
U
Z
Q1Y
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 for level
Selection and Ordering data
Article No.
Pressure transmitters for level, SITRANS P500 HART
7 MF 5 6 77 - 7777 0 - 7777
777
0
1
2
3
4
9
R1Y
Process connection on high-pressure side: Filling liquid
Silicone oil M5
Silicone oil M50
High-temperature oil
Halocarbon (for oxygen measurement)
FDA compliant oil
Other version, add
Order code and plain text:
Filling liquid: ...
Siemens FI 01 · 2015 US Edition
Order code
1/193
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
1
SITRANS P500 for level
Order code
Selection and Ordering data
Selection and Ordering data
Further designs
Add "-Z" to Article No. and specify Order code.
Further designs
Add "-Z" to Article No. and specify Order code.
Display
(Standard: no display, cover closed)
Degree of protection approvals: Ex d (flameproof)
With display and blanking cover
A10
With display and glass cover
A11
Special version: cover/casing
Two coats of lacquer on casing, cover (PU on epoxy)
A20
Electrical connection and cable entry
(Standard: no cable gland, only dust protection
caps)
(IP66/68)4)
Order code
Ex d explosion-proof (ATEX)(T4/T6)
E20
Ex XP explosion-proof and DIP (FM)(T4/T6)
E21
Ex XP explosion-proof and DIP (CCSAUS)(T4/T6)
Ex d explosion-proof (NEPSI)(T4/T6)
E22
E26
Degree of protection approvals: n/NI
Zone 2 (nA, nL, ic) (ATEX) (T4/T6)
E40
Div2 NI, Div2 NI-field wiring (FM) (T4/T6)
E41
E42
E46
Cable glands made of metal (IP66/68)
A51
Zone 2 (nA, nL), Div2 NI (CCSAUS) (T4/T6)
Zone 2 (nA, nL) (NEPSI) (T4/T6)
Cable glands made of stainless steel (IP66/68)
A52
Degree of protection approvals: Zone 20/21/22
A60
Use in Zone 21/22 (Ex tD) (ATEX)
E60
Cable gland made of plastic
M12 connectors without cable socket
(IP66/67)4)
A50
A61
Use in Zone 20/21/22 (Ex iaD) (ATEX)
E61
Han 7D connectors, plastic, straight
(with cable socket) (IP65)4)
A71
Use in Zone (Ex DIP) (ATEX)
E66
Han 7D connectors, plastic, angled
(with cable socket) (IP65)4)
A72
Han 7D connectors, metal enclosure, straight
(with cable socket) (IP65)4)
A73
Han 7D connectors, metal enclosure, angled
(with cable socket) (IP65)4)
A74
Han 8D connectors, plastic, straight
(with cable socket) (IP65)4)7)
A75
M12 connectors, cable socket
(IP66/67)4)
Degree of protection approvals: Combinations
IS protection and XP and DIP (FM)
E71
IS protection and XP and DIP (CCSAUS)
E72
IS protection and XP and DIP (FM/CCSAUS)
E73
Supplementary approvals / degree of protection
Dual Seal approval5)
E85
Export approval Korea
E86
Special process connection versions (diff. pressure)
Han 8D connectors, plastic, angled
(with cable socket) (IP65)4)7)
A76
Swap process connection: high-pressure side at front
L33
Han 8D connectors, metal enclosure, straight
(with cable socket) (IP65)4)7)
A77
Mosquito protection
4 pcs. for ¼-18 NPT thread
L36
Han 8D connectors, metal enclosure, angled
(with cable socket) (IP65)4)7)
A78
Process flanges, O-rings, special material
Standard: Viton (FKM (FPM)
PG 13.5 adapters4)
A82
Process connection sealing rings made of PTFE (Teflon),
virginal
L60
Process connection sealing rings made of PTFE (Teflon),
glass fiber-reinforced
L61
Language for labels, leporellos and menu language
default8)
(instead of English as standard)
German
B10
Process connection sealing rings made of FFPM (Kalrez)
L62
French
B12
Process connection sealing rings made of NBR
L63
Spanish
B13
Process connection sealing rings made of graphite
L64
Italian
B14
Chinese
B15
Drain/Vent valve
(1 set = 2 units)
Russian
B16
Japanese
B17
English with units: psi/inH2O
B21
Special version: Supplementary menu languages
(Standard: English, German, French, Spanish, Italian)
Asia language package (in addition: Chinese, Japanese,
Russian)
Certificates (available online for
B80
downloading)1)
Quality inspection certificate (Five-step factory calibration)
according to IEC 60770-22)
C11
Acceptance test certificate according to EN 10204-3.13)
C12
Degree of protection approvals: Ex ia/ib (intrinsic
safety)
2 ventilation valves ¼- 18 NPT, in material of process
flange)
L80
Vacuum-proof design
Vacuum service
V04
Spark arrester
For mounting on zone 0 (including documentation)
V05
1)
Enclosed in print or as CD: see page 1/201.
2)
When also ordering the quality inspection certificate (factory calibration)
according to IEC 60770-2 for transmitters with mounted diaphragm seals:
Order this certificate only together with the remote seals. The measuring
accuracy of the total combination is certified here.
3)
When also ordering the acceptance test certificate according to
EN 10204-3.1 for transmitters with mounted diaphragm seals: Order this
certificate as well in addition to the respective remote seals.
4)
Not together with types of protection "Explosion-proof", "Ex nA" and
"Intrinsic safety and explosion-proof"
Ex ia/ib protection (ATEX) (T4)
E00
5)
Ex IS protection (FM) (T4)
E01
Only in conjunction with FM and/or CCSAUS
6)
Not recommended for Measuring span "D"
Ex IS protection (CCSAUS) (T4)
Ex ia/ib protection (NEPSI) (T4)
E02
E06
7)
The Han 8D plug is identical with the former Han 8U version.
8)
For option B15, B16 and B17 the menu language default is english. Otherwise the Option B80 (Asia language package) is necessary.
1/194
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 for level
Selection and ordering data
Order code
Additional data
Please add "-Z" to Article No. and specify Order code(s)
and plain text.
Measuring range to be set
Specify in plain text:
Linear characteristic curve (max. 5 characters):
Y01: ... up to ... mbar, kPa, MPa, psi
Y01
Measuring point number and measuring point identifier
(only standard ASCII character set)
Specify in plain text:
Measuring point number (TAG No.), max. 16 characters
Y15: .........................................
Y15
Measuring point text (max. 27 char.)
Y16: .........................................
Y16
Entry of HART address (TAG), max. 32 characters
Y17: .........................................
Y17
Setting of pressure indication in pressure units
Y21
Specify in plain text (standard setting: mbar)
Y21: bar, kPa, MPa, psi, ...
Note: The following pressure units are selectable:
bar, mbar, mm H2O*), in H2O*), ftH2O*), mmHG, inHG, psi,
Pa, kPa, MPa, g/cm2, kg/cm2, Torr, ATM, % or mA
*) Reference temperature 20 °C
Setting of pressure indication in non-pressure units1)
Y22 +
Specify in plain text:
Y01
Y22: ... up to ... l/min, m3/h, m, USgpm, ...
(specification of measuring range in pressure units "Y01" is
essential, unit with max. 5 characters)
Customer-specific settings
Damping setting (range: 0 ... 100 s)
(Standard setting: 2 s)
1)
Y30
Preset values can only be changed over SIMATIC PDM.
Siemens FI 01 · 2015 US Edition
1/195
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 for level
■ Dimensional drawings
178 (7)
appr. 30
(appr. 1.18)
87 (3.43)
58 (2.29)
2
139 (5.48)
74 (2.92)
10
1
3
5
7
154 (6.2)
4
L
70 (2.75)
6
11
d5
d4
k
D
1
8
54 (2.1)
108 (4.25)
n d2
f
b
9
98 (3.81)
4
2
5
1
Electrical connection
- M20 x 1.53) or ½-14 NPT screwed gland
- Han 7D/Han 8D connector2)3) or M12
2 Cover for the push buttons
3 Dummy screwed gland
4 Terminal side 1)
5 Electronics side, display1)
6 Process connection low-pressure side, with valve (optional) or screwed gland
(optional)
7 Safety catch
(only for type of protection "Explosion-proof"; not shown in the diagram)
8 Process connection: low-pressure side ¼-18NPT (IEC 61518)
9 Electrical connection:
- Han 7D/Han 8D connector/socket2)3)
10 Mounting flange according to EN 1092-1 or ASME B16.5
11 Clearance for turning the casing
SITRANS P pressure transmitter for filling level, P500 series, measurements in mm (inch)
1/196
Siemens FI 01 · 2015 US Edition
1)
Allow approx. 20 mm (0.79 inch) additional thread length
Not with type of protection "Explosion-proof"
3)
Not with type of protection "FM + CCSAUS [IS + XP]"
2)
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 for level
Connection to EN 1092-1
Nominal Nominal b
diameter pressure
D
d
d2
d4
d5
dM
f
k
n
mm
mm
mm
mm
mm
mm
mm
mm
mm
DN50
PN 40
20
165
61
18
102
48.3
451)
2
125
4
DN 80
PN 40
24
200
90
18
138
76
722)
2
160
8
DN 100
PN 16
20
220
115
18
158
94
89
2
180
8
PN 40
24
235
115
22
162
94
89
2
190
8
L
mm
0, 50, 100,
150 or 200
Connection to ASME B16.5
Nominal
diameter
2 inch
3 inch
4 inch
Nominal
pressure
b
D
d2
d4
d5
dM
f
k
n
lb/sq.in.
inch (mm)
inch (mm)
inch (mm)
inch (mm)
inch (mm)
inch (mm)
inch (mm)
inch (mm)
class 150
0.77 (19.5) 5.91 (150)
0.75 (19.0) 3.62 (92)
1.9 (48.3)
1.77 (45)1) 0.079 (2.0) 4.75 (120.7) 4
class 300
0.89 (22.7) 6.49 (165)
0.75 (19.0) 3.62 (92)
1.9 (48.3)
1.77 (45)1) 0.079 (2.0) 5.0 (127)
8
class 150
0.96 (24.3) 7.5 (190.5) 0.75 (19.0) 5 (127)
3.0 (76)
2.83 (72)2) 0.079 (2.0) 6 (152.4)
4
class 300
1.14 (29.0) 8.27 (210)
0.87 (22.2) 5 (127)
3.0 (76)
2.83 (72)2) 0.079 (2.0) 6.69 (168.3) 8
class 150
0.96 (24.3) 9.06 (230)
0.75 (19.0) 6.19 (157.2) 3.69 (94)
3.5 (89)
0.079 (2.0) 7.5 (190.5)
8
class 300
1.27 (32.2) 10.04 (255) 0.87 (22.2) 6.19 (157.2) 3.69 (94)
3.5 (89)
0.079 (2.0) 7.88 (200)
8
L
inch (mm)
0, 2, 3.94,
5.94 or
7.87
(0, 50,
100, 150
or 200)
Explanations of tables:
d: Internal diameter of gasket to DIN 2690
dM: Effective diaphragm diameter
d5: Diameter of extension
f: Milling edge
L: Extension length
1)
59 mm = 2.32 inch with tube length L = 0.
2)
89 mm = 3½ inch with tube length L = 0.
Siemens FI 01 · 2015 US Edition
1/197
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
1
SITRANS P500 - Supplementary electronics for 4-wire connection
■ Overview
Structural design
Dimensions (W x H x D) in mm
(inch)
80 x 120 x 60 (3.15 x 4.72 x 2.36)
Electrical connection
Screw terminals (Pg 13.5 cable
inlet) or Han 7D / Han 8D plug
Power supply
Supply voltage
230 V AC (-10 ... +6 %,
47 ... 63 Hz, approx. 6 VA) or
24 V AC/DC (24 V AC  10 %,
47 ... 63 Hz, approx. 3 VA)
Permissible ripple (within the specified limits)
Approx. 2.5 Vpp
■ Dimensional drawings
218 (8.58)
87 (3.43)
SITRANS P pressure transmitter with supplementary electronics for
4-wire connection
Direct connection of the supplementary electronics to a
SITRANS P pressure transmitter from the P500 series produces
a transmitter for four-wire connection.
The supplementary electronics cannot be attached to explosionprotected pressure transmitters. The supplementary electronics
is fitted in a light metal housing which is mounted on the left side
of the pressure transmitter.
Note on ordering:
The supplementary electronics has to be be ordered through the
supplementary options of the pressure transmitter in question.
■ Technical specifications
Output
Output signal
0 ... 20 mA or 4 ... 20 mA
Load
Max. 750 
Voltage measurement
Linear (square-rooting in transmitter if necessary)
Electrical isolation
Between power supply and input/
output
Measuring accuracy
According to IEC 60770-1
Conformity error (in addition to
transmitter)
 0.15 % of set span
Influence of ambient temperature
 0.1 % per 10 K
Power supply effect
 0.1 % per 10 % change in voltage or frequency
Load effect
 0.1 % per 100 % change
Rated conditions
Ambient temperature
• 24 V version
-20 ... +80 °C (-4 ... +176 °F)
• 230 V version
-20 ... +60 °C (-4 ... +140 °F)
Storage temperature
-50 ... +85 °C (-58 ... +185 °F)
Degree of protection
IP54 to IEC 60529
Electromagnetic compatibility
(EMC)
IEC 61236-1
Condensation
Relative humidity 0 ... 95 %
condensation permissible
1/198
Siemens FI 01 · 2015 US Edition
95 (3.74)
SITRANS P pressure transmitters with supplementary electronics for fourwire connection, dimension drawing, dimensions in mm (inch)
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 - Supplementary electronics for 4-wire connection
■ Schematics
1
Terminals
2
+
3
Ia
1 Han 8D/7D
plug
6
7
5
1
2 plugs
5
1
4
6
SL
Supplementary electronics for 4-wire
connection
Article No. of the transmitter
7MF54..-.....-.... or 7MF56..-.....-.... add "-Z"
and Order code.
V77
Power supply
24 V AC/DC
SL
2
Ia -
UH
6
7
2
5
1
3
4
+ Ia -
SL
2
3
UH
AC 230 V
UC 24 V
Han 7D
Han 7D
Han 7D
Han 8D
Ia
SL
UH Power supply
Output current
Order code
3
+
7
5
UH
4
6
4
-
Selection and Ordering data
Protective earth
conductor
Supplementary electronics for 4-wire connection, connection diagram
(the HAN 8D conector is identical to the previous version of the HAN 8U)
230 V AC
Electrical connection
Terminals; 2 Pg screwed
glands, to left
2 Han 7D/Han 8D plugs
incl. mating connector, to left
1 Han 7D plug incl. mating
connector, angled
Terminals; 1 Pg screwed
gland, downwards
1 Han 8D plug incl. mating
connector, downwards
(observe arrangement of
plug and differential pressure
line)
Terminals; 2 Pg screwed
glands, to left
2 Han 7D plugs incl. mating
connector, to left
Output current
0 ... 20 mA
4 ... 20 mA
1
3
5
6
9
7
8
0
1
Accessories
Article No.
Instruction Manual
German/English
A5E00322799
Siemens FI 01 · 2015 US Edition
1/199
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
1
SITRANS P500 Accessories/Spare parts
Selection and ordering data
Article No.
Replacement measuring cells for differential
pressure
SITRANS P pressure transmitters for differential
pressure and flow, P500 HART PN 160 series
(MAWP 2320 psi)
7777 1
7MF 5 9 9 4 -
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Measuring cell cleaning
normal
1
Measuring span (min. ... max.)
1,00 ... 50 mbar
(0.4 ... 20 inH2O)
1.25 ... 250 mbar
(0.5 ... 100 inH2O)
6.25 ... 1250 mbar
(2.5 ... 502 inH2O)
31.25 ... 6250 mbar
(12.54 ... 2509 inH2O)
0.16 ... 32 bar
(2.33 ... 465 psi)
C
D
E
F
G
Wetted parts materials
(stainless steel process flanges)
Seal diaphragm
Parts of measuring cell
Stainless steel
1.4404/316L
Stainless steel
1.4404/316L
A
Hastelloy C2761)
Stainless
steel1.4404/316L
B
Monel 4001)
Stainless
steel1.4404/316L
C
Process connection
Female thread ¼-18 NPT
• Sealing screw opposite process connection
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M10 to DIN 19213
• Vent on side of process flange
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M10 to DIN 19213
Further designs
0
1
4
5
Order code
Add "-Z" to Article No. and specify Order code.
Acceptance test certificate
Acc. to EN 10204-3.1
C12
Without process flanges
K00
Vent on side for gas measurements2)
L32
Process flanges, O-ring, special material
Standard: Viton (FKM (FPM))
Process connection sealing rings made of PTFE
(Teflon), virginal
L60
Process connection sealing rings made of PTFE
(Teflon), glass fiber-reinforced
L61
Process connection sealing rings made of FFPM
(Kalrez)2)
L62
Process flanges, O-rings made of NBR
L63
Process flanges, O-rings made of graphite
L64
1)
Not together with Measuring span "C".
2)
Only in conjunction with process connection code 4 or 5.
2)
Not together with Measuring span "G".
1/200
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 Accessories/Spare parts
■ Selection and Ordering data
■ Selection and Ordering data
Article No.
Mounting brackets
For differential pressure transmitters with
flange thread M10
(7MF54..-…10 and 7MF54..-…50)
• Made of steel
• Made of stainless steel
Mounting brackets
for differential pressure transmitter with
flange thread 7/16-20 UNF
(7MF54..-…00 and 7MF54..-…40)
• Made of steel
• Made of stainless steel
7MF5987-1AA
7MF5987-1AD
Digital indicator
Including mounting material
7MF5987-1AC
7MF5987-1AF
7MF5987-1BE
7MF5987-1BF
7MF5987-1BR
TAG plate (incl. fastening material)
7MF5987-1CA
Printed (1 pc.)
Data according to Y01 or Y02, Y15 and Y16
(see "SITRANS P transmitters")
7MF5987-1CB-Z
Y..: ......................
Mounting screws
7MF5987-1CC
Sealing plugs for process flange
(1 set = 2 units)
• Made of stainless steel
• Made of Hastelloy
7MF4997-1CG
7MF4997-1CH
Vent valve
Complete (1 set = 2 units)
• Made of stainless steel
• Made of Hastelloy
7MF4997-1CP
7MF4997-1CQ
Electronics module
HART, intrinsically safe Ex ia
for installation in transmitter casing (observe
warranty conditions)
7MF5987-1DC
Connection board (incl. fastening material)
HART, intrinsically safe Ex ia
for installation in transmitter casing (observe
warranty conditions)
O-rings for process flanges made of:
• Viton (FKM (FPM)) (10 pcs.)
• NBR (Buna N) (10 pcs.)
Push buttons assembly (incl. fastening
material)
A5E02344527
English
A5E02344528
French
A5E02344529
Italian
A5E02344530
Spanish
A5E02344531
English, German, Spanish, French, Italian,
Dutch
A5E02344532
English, Estonian, Latviaan,
Lithuanian, Polish, Romanian
A5E02307339
English, Bulgarian, Czech,
Finnish, Slovakian, Slovenian
A5E02307340
English, Danish, Greek, Portuguese,
Swedish, Hungarian
A5E02307341
Russian
A5E02307338
Brief instructions (Leporello)
Without inscription (5 pcs.)
For TAG plate, grounding and connection
terminals and securing and locking screws
(30 units)
German
Compact operating instructions1)
Cover
Made of die-cast aluminum, including O-ring
• Without window
• With window
Article No.
Operating Instructions1)
7MF5987-1DM
7MF5987-2DA
7MF5987-2DE
German, English, French, Italian, Spanish,
Chinese
A5E02344536
DVD with SITRANS P documentation
German, English, French, Spanish, Italian
Compact operating instructions in 21 EU
languages
Service Instructions1)
for replacement of electronics, measuring
cell and terminal board
• German
• English
A5E00090345
A5E02822443
A5E02344534
HART modem
With USB interface
7MF4997-1DB
Operating instruction1)
Supplementary electronics for 4-wire
connection
German, English
A5E00322799
Certificates (order only via SAP) additional to internet download
• Hard copy (to order)
A5E03252406
• On CD (to order)
A5E03252407
1)
You can download these operating instructions free-of-charge from our
Internet site at www.siemens.com/sitransp.
For power supply units, see catalog FI01 "Supplementary Compontents".
7MF5987-2AF
For replacement of operating keys for onsite operation of the transmitter
Sealing ring for
• Process connection
• NBR sealing ring for screw cover (10 pcs.)
• NBR sealing ring for interface measuring
cell/housing (10 pcs.)
See catalog FI01,
"Fittings"
7MF4997-2EA
7MF5987-2EB
Siemens FI 01 · 2015 US Edition
1/201
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 Accessories/Spare parts
■ Dimensional drawings
33,15 (1.31) 33,35 (1.32)
20,65
(0.81)
54 (2.13)
41,3 (1.63)
27 (1.06)
20,65
(0.81)
R30
R6,56)
(0.2
8)
(1.1
3 (0.12)
Ø 20
(0.79)
41,3 (1.63)
54 (2.13)
134 (5.28)
52,5 (2.07)
72 (2.83)
Ø 11 (0.43)
16,5
(0.65)
115 (4.53)
R30 )
8
(1.1
3
72 (2.83)
Mounting bracket for SITRANS P pressure transmitter, P500 series, measurements in mm (inch)
Mounting bracket material: Sheet-steel Mat. No. 1.0330, chrome-plated, or stainless steel Mat. No. 1.4301 (304)
1/202
Siemens FI 01 · 2015 US Edition
120 (4.72)
105 (4.13)
21 (0.83)
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 Factory-mounting of valve manifolds on transmitters
■ Overview
■ Design
The SITRANS P500 transmitter can be delivered factory-fitted
with the following manifolds:
• Valve manifolds 7MF9411-5BA: Three valve manifold for differential pressure transmitter
• Valve manifolds 7MF9411-5CA: Three valve manifold for differential pressure transmitter
The 7MF9411-5BA and 7MF9411-5CA manifolds are sealed with
PTFE sealing rings between the transmitter and the manifold.
Once installed, the complete unit is checked under pressure for
leaks (compressed air 6 bar (2411 inH2O)) and is certified leakproof with a test report to EN 10204 - 2.2.
All manifolds should preferably be secured with the respective
mounting brackets. The transmitters are mounted on the manifold and not on the unit itself.
If you order a mounting bracket when choosing the option "Factory mounting of manifolds", you will receive a mounting bracket
for the manifold instead of a bracket for mounting the transmitter.
If you order an acceptance test certificate 3.1 to EN10204 when
choosing the option "Factory mounting of manifolds", a separate
certificate is provided for the transmitters and the manifolds respectively.
■ Selection and ordering Data
Manifold 7MF9411-5BA on SITRANS P pressure transmitter P500
for differential pressure and flow
Add -Z to the Article No. of the transmitter and add Order codes
Order
code
Manifold 7MF9411-5CA on SITRANS P500 pressure transmitter for
differential pressure and flow
Add -Z to the Article No. of the transmitter and add Order codes
SITRANS P500 7MF54..-...
SITRANS P500 7MF54..-...
mounted with gaskets made of PTFE and
screws made of
mounted with gaskets made of PTFE and
screws made of
• Chromized steel
• Stainless steel
Order
code
U01
• Chromized steel
U03
U02
• Stainless steel
U04
Delivery incl. high-pressure test certified
by factory certificate to EN10204-2.2
Delivery incl. high-pressure test certified
by factory certificate to EN10204-2.2
Further designs:
Further designs:
Delivery includes mounting bracket and
mounting clips made of
Delivery includes mounting bracket and
mounting clips made of
• Steel
A01
• Steel
A01
• Stainless steel
A02
• Stainless steel
A02
(instead of the mounting bracket supplied with the transmitter)
(instead of the mounting bracket supplied with the transmitter)
Supplied acceptance test certificate to
EN10204-3.1 for transmitters and
mounted valve manifold
C12
Supplied acceptance test certificate to
EN10204-3.1 for transmitters and
mounted valve manifold
Siemens FI 01 · 2015 US Edition
C12
1/203
1
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 Factory-mounting of valve manifolds on transmitters
■ Dimensional drawings
Manifold 7MF9411-5BA with attached SITRANS P500 pressure transmitter for differential pressure and flow (incl. mounting bracket)
160 (6.3)
1
0
R3 18)
.
(1
232 (9.13)
215 (8.46)
Manifold 7MF9411-5BA with attached SITRANS P500 pressure transmitter for differential pressure and flow, measurements in mm (inch)
1/204
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for High Performance requirements
SITRANS P500 Factory-mounting of valve manifolds on transmitters
Manifold 7MF9411-5CA with attached SITRANS P500 pressure transmitter for differential pressure and flow (incl. mounting bracket)
R
(1 30
.1
8)
158 (6.22)
256 (10.1)
233 (9.17)
Manifold 7MF9411-5CA with attached SITRANS P500 pressure transmitter for differential pressure and flow, measurements in mm (inch)
Siemens FI 01 · 2015 US Edition
1/205
1