© Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements 1 SITRANS P500 - Technical description ■ Overview SITRANS P500 pressure transmitters are digital pressure transmitters featuring extensive user-friendliness and which fulfil the most stringent demands of accuracy, long-term stability, speed and lots more. Extensive functionality allows you to set the pressure transmitter specifically to your own requirements. Despite their many settings options, local set-up is easy. A multi-lingual menu with clear text instructions guides you through the process. There are also help texts available. The innovative EDD with integrated QuickStart assistance is also quick and easy to configure by computer using the HART protocol. Extensive diagnostic functions, e.g. min/max pointer for pressure and temperature, or limit value indicator, make sure you always have the process under control. You can also display additional process values such as temperature or static pressure. The simultaneous display of mass, resulting from a volume, is also easy. The SITRANS P500 pressure transmitters can be configured to measure: • Differential pressure • Level • Volume • Mass • Volume flow • Mass flow ■ Benefits • • • • • • • • High measuring accuracy Very fast response time Extremely good long-term stability High reliability even under extreme chemical and mechanical loads For aggressive and non-aggressive gases, vapors and liquids Extensive diagnosis and simulation functions which can be used both on site as well as via HART. Optional separate replacement of measuring cell and electronics without recalibration. Extremely low conformity error values 1/176 Siemens FI 01 · 2015 US Edition • Infinitely adjustable spans of 1 mbar to 32 bar (0.0145 to 465 psi; 0.4 to 12860 inH2O) • Extremely good total performance and conformity error values with no loss of performance up to a turndown of 10 guaranteed. • Additional integrated sensor for static pressure • Parameterization via on-site control keys or HART • Short process flanges nable space-saving installation. ■ Application The SITRANS P500 pressure transmitters can be used in industrial areas with extreme chemical and mechanical loads. Electromagnetic compatibility in the range 10 kHz to 1 GHz makes them suitable for locations with high electromagnetic emissions. Pressure transmitters with ratings "Intrinsic safety" and "Explosion-proof" may be installed within potentially explosive atmospheres (zone 1) or in zone 0. The pressure transmitter comes with a CE-declaration of conformity and fulfils the corresponding unified European directives (ATEX). Pressure transmitters with the type of protection "Intrinsic safety" for use in zone 0 may be operated with power supply units of category "ia" and "ib". With newly designed measuring cell, it is possible to work with process temperatures of -40 to 125 °C (-40 to +257 °F)) without having to use a remote seal. The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of highly viscous fluids. The pressure transmitter can be fully parameterized locally via the three operating keys and externally via HART. © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 - Technical description Pressure transmitters for differential pressure and flow • Measured variables: - Differential pressure - Small positive or negative pressure - Flow q ~ p (together with a primary element (see Chapter "Flow Meters")) • Span (freely adjustable) for SITRANS P500: 1 mbar to 32 bar (0.0145 to 465 psi; 0.4 to 12860 inH2O) Pressure transmitters for level • Measured variable: Level of aggressive and non-aggressive liquids in open and closed vessels. • Span (freely adjustable) for SITRANS P500: 1.25 to 6250 mbar (0.5 to 2509 inH2O) • Nominal diameter of the mounting flange - DN 50 / PN 40 - DN 80 / PN 40 - DN 100/ PN 16, PN 40 - 2 inch/class 150, class 300 - 3 inch/class 150, class 300 - 4 inch/ class 150, class 300 - customized special version In the case of level measurements in open vessels, the low-pressure connection of the measuring cell remains open (measurement "compared to atmospheric"). In the case of measurements in closed vessels, the lower-pressure connection has to be connected to the vessel in order to compensate the static pressure. The wetted parts are made from a variety of materials, depending on the degree of corrosion resistance required. ■ Design 10 9 1 8 14 2 7 11 3 13 4 6 12 5 1 2 3 4 5 6 7 8 Cover for the pushbuttons Cover, optionally with window Display (optional) TAG plate Process flange with process connection Lock screws (on two sides) for the measuring cell Approval plate Safety catch 9 10 11 12 13 14 Blanking plug Terminal compartment Cover for terminal compartment PE/ground terminal Nameplate Cable inlet, optionally with cable gland or plug-in connection View of transmitter • The electronics housing is made of coated die-cast aluminum. • The casing has round screwed covers front and back. • Depending on the design the front cover is fitted with an inspection window. You can read off the measured value directly from the optional display through the window. • The inlet to the terminal compartment is located either on the left or right side. The unused opening in each case is sealed by a blanking plug. • The PE/ground terminal is on the back of the housing. • Access to the terminal compartment for auxiliary power and shielding by unscrewing the cover. • Beneath the electronic housing is the measuring cell with its process flanges at which the process connections are available. The modular design of the pressure transmitter lets you replace the measuring cell, electronics and connection board as required. • On the top of the housing you can see the screwed cover of the three local pushbuttons of the transmitter. Siemens FI 01 · 2015 US Edition 1/177 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 - Technical description ■ Function Mode of operation of the measuring cells Operation of electronics with HART communication Measuring cell for differential pressure and flow SIEMENS EEPROM A μC D D μC 9 Ia A UH 1 T R 8 2 3 HART modem Sensor EEPROM Sensor 1 EEPROM Electronics 7 Application electronics Sensor of the measuring cell Measuring amplifier Analog-to-digital converter Microcontroller Digital-to-analog converter One EEPROM each in the measuring cell and in the electronics HART modem Keys (local operation) Digital display Output current Auxiliary power Function diagram of electronics • The input pressure is converted into an electrical signal by the sensor. • This signal is amplified by the measuring amplifier and digitalized in an analog-to-digital converter. • The digital signal is analyzed in a microcontroller and corrected according to linearity and thermal characteristics. • In a digital-to-analog converter it is then converted into the output current of 4 to 20 mA. When connected to supply lines, a diode circuit provides reverse polarity protection. • The measuring cell-specific data, the electronic data and the parameterization data is held in two EEPROMs. One EEPROM is incorporated into the measuring cell electronics, the other is incorporated into the application electronics. Operation • The three local pushbuttons enable you both to navigate and carry out configuration and to visually track messages and process values, provided a display is available. • If you have a device without a display, you can carry out zero adjustment using the three local pushbuttons. It is possible to retrofit a display at any time. • You can also carry out settings by computer via a HART modem. 1/178 6 5 4 Measuring cell electronics 1 2 3 4 5 6 7 8 9 IA UH Siemens FI 01 · 2015 US Edition 1 2 3 4 5 6 7 8 9 Input pressure PProcess flange with process connection O-Ring Measuring cell body Silicon pressure sensor Overload diaphragm Filling liquid Seal diaphragm Input pressure P+ Measuring cell for differential pressure and flow, function diagram • The differential pressure is transmitted via the seal diaphragm and the filling liquid to the silicon pressure sensor. • If the measuring limits are exceeded, the overload diaphragm flexes until the seal diaphragm touches the body of the measuring cell. This protects the sensor module from overload. • The differential pressure causes the measuring diaphragm of the silicon pressure sensor to flex. • The displacement changes the resistance value of the 4 piezo resistors in the measuring diaphragm in a bridge circuit. • The change in the resistance causes a bridge output voltage proportional to the input pressure. © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 - Technical description Measuring cell for level Configuration using HART 1 3 2 Parameterization using HART is carried out using a HART Communicator or a PC in conjunction with a HART modem. 4 + 230 ... 1100 Ω SITRANS P500 transmitter Power supply HART communicator 5 9 8 7 6 Communication between a HART Communicator and a pressure transmitter When parameterizing with the HART Communicator, the connection is made directly to the 2-wire cable. + 1 2 3 4 5 6 7 8 9 Process flange with process connection O-Ring Measuring cell body Silicon pressure sensor Overload diaphragm Filling liquid of the measuring cell Capillary tube with filling liquid of the mounting flange Flange with optional tube Seal diaphragm for mounting flange Measuring cell for level, function diagram • The input pressure (hydrostatic pressure) acts hydraulically on the measuring cell via the seal diaphragm on the mounting flange. • The differential pressure applied to the measuring cell is transmitted via the seal diaphragm and the filling liquid to the silicon pressure sensor. • If the measuring limits are exceeded, the overload diaphragm flexes until the seal diaphragm touches the body of the measuring cell. This protects the sensor module from overload. • The differential pressure causes the measuring diaphragm of the silicon pressure sensor to flex. • The displacement changes the resistance value of the 4 piezo resistors in the measuring diaphragm in a bridge circuit. • The change in the resistance causes a differential pressure proportional to the input pressure. Configuration of SITRANS P500 HART Depending on the version, there are a range of options for configuring the pressure transmitter and for setting or reading the parameters. Configuration using the pushbuttons (local operation) You can configure the transmitter in situ using the three keys provided a display is available. If you have no display, you can only carry out zero adjustment. It is possible to retrofit a display. See accessories. 230 ... 500 Ω SITRANS P500 transmitter HART modem Power supply PC or laptop USB/RS 232 HART communication between a PC communicator and a pressure transmitter For configuring via PC a HART modem is used which connects the transmitter to the PC. The signals needed for communication in conformity with the HART 6.0 protocols are superimposed on the output current using the Frequency Shift Keying (FSK) method. The necessary device files are available for download on the Internet. SITRANS P500 configuration options The transmission offers you full configuring options both via HART as well as in situ provided the optional display is available. For simple parameterizing we also offer the easy to understand QuickStart function with guided commissioning. SITRANS P500 diagnostic functions • Maintenance timer • Min/Max pointer (both resetable and non-resetable) - Pressure (incl. time and temperature stamp) - Static pressure (incl. time and temperature stamp) - Sensor temperature (incl. time stamp) - Electronic temperature (incl. time stamp) • Limit monitor block • Diagnostic warning • Diagnostic alarm • Simulation functions • Display of trends and histograms • Operating hours meter Siemens FI 01 · 2015 US Edition 1/179 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements 1 SITRANS P500 - Technical description Physical dimensions available for the SITRANS P500 HART display Physical variable Physical dimensions Pressure (setting can also be made in the factory) Pa, MPa, kPa, bar, mbar, torr, atm, psi, g/cm2, kg/cm2, mmH2O (4 °C), inH2O (4 °C), inH2O (20 °C), mmH2O, mmH2O (4 °C), ftH2O (20 °C), inHg, mmHg, hPA Level m, cm, mm, ft, in Volume m3, dm3, hl, yd3, ft3, in3, gallon, lmp. gallon, bushel, barrel, barrel liquid, I; Norm (standard) I; Norm (standard) m3, Norm (standard) feet3 Mass g, kg, t (metric), lb, Ston, Lton, oz Volume flow m3/d, m3/h, m3/s, l/min, l/s, ft3/d, ft3/min, ft3/s, US gallon/min, gallon/s, l/h, milL/d, gallon/d, gallon/h, milgallon/d, lmp.gallon/s, Imp.gallon/m, Imp.gallon/h, lmp.gallon/d, Norm (standard) m3/h, Norm (standard) l/h, Norm (standard) ft3/h, Norm (standard) ft3/m, barrel liquid/s, barrel liquid/m, barrel liquid/h Mass flow t/d, t/h, t/min, kg/d, kg/h, kg/min, kg/s, g/h, g/min, g/s, lb/d, lb/min, lb/s, LTon/d, LTon/h, STon/d, STon/h, STon/min Temperature K, °C, °F, °R Miscellaneous %, mA 1/180 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 for differential pressure and flow ■ Technical specifications Input Measuring accuracy Measured variable Differential pressure and flow Span (infinitely adjustable) Span (min. ... max.) Maximum operating pressure (static pressure) Reference conditions (in accor- • Rising characteristic curve dance with IEC 60770-1) • Start of scale 0 bar All error information always • Stainless steel seal diaphragm refers to the set span. • Measuring cell with silicone oil filling • Room temperature (25 °C (77 °F)) 160 bar (2320 psi) Error in measurement at limit setting incl. hysteresis and reproducibility r: Span ratio (r: Span ratio (r = max. span / set span)) 1,00 ... 50 mbar (0.4 ... 20 inH2O) 1.25 ... 250 mbar (0.5 ... 100 inH2O) 6.25 ... 1250 mbar (2.5 ... 502 inH2O) 31.25 ... 6250 mbar (12.54 ... 2509 inH2O) 0.16 ... 32 bar (2.33 ... 465 psi) Lower range limit • Measuring cell with silicone oil -100 % of max. span and/or filling 30 mbar a (0.44 psia) Upper range limit 100 % of max. span Start of scale Between measuring limits (freely adjustable) Output Linear characteristic r 10 r 10 • 50 mbar (20 inH2O) 0.06 % (0.006 . r) % • 250 mbar (100 inH2O) 1250 mbar (502 inH2O) 6250 mbar (2509 inH2O) 32 bar (465 psi) 0.03 % (0.003 . r) % r 10 r 10 - 50 mbar (20 inH2O) 0.06 % (0.006. r) % - 250 mbar (100 inH2O) 1250 mbar (502 inH2O) 6250 mbar (2509 inH2O) 32 bar (465 psi) 0.03 % (0.003 . r) % Square-rooted characteristic • Flow > 50 % Output current signal 4 ... 20 mA • Lower current limit (freely adjustable) 3.55 mA, factory setting 3.8 mA • Upper current limit (freely adjustable) 23 mA, factory setting 20.5 mA • Ripple (without HART communication) Ipp 0.4 % of max. output current • adjustable damping 0... 100 s in steps of 0.1 s, factory-seting: 2 s Influence of ambient temperature per 28 °C (50 °F) • current transmitter 3.55 ... 23 mA • 50 mbar (20 inH2O) (0.04 . r + 0.05) % • Failure signal adjustable within limits:: • Bottom: 3.55 … 3.7 mA (default value: 3.6 mA) • Top: 21.0 … 23 mA (default value: 22.8 mA) • 250 mbar (100 inH2O) (0.025 . r + 0.014) % • 1250 mbar (502 inH2O) 6250 mbar (2509 inH2O) 32 bar (465 psi) (0.006 . r + 0.03) % Load • Without HART communication RB (UH - 10.5 V)/0.023 A in , UH : Power supply in V r 10 r 10 - 50 mbar (20 inH2O) 0.12 % (0.012 . r) % - 250 mbar (100 inH2O) 1250 mbar (502 inH2O) 6250 mbar (2509 inH2O) 32 bar (465 psi) 0.06 % (0.006 . r) % • Flow 25 % … 50 % Influence of static pressure • At the start of scale value (PKN) - 50 mbar (20 inH2O) (0.1 . r) % per 70 bar (1015 psi) correction via zero point correction - 250 mbar (100 inH2O) (0.035 . r) % per 70 bar (1015 psi) correction via zero point correction - 1250 mbar (502 inH2O) 6250 mbar (2509 inH2O) 32 bar (465 psi) (0.007 . r) % per 70 bar (1015 psi) correction via zero point correction • With HART communication - HART Communicator RB = 230 ... 1100 - HART modem RB = 230 ... 500 Characteristic curve Linearly rising, linearly falling, square rooted characteristic rising, bidirectional square rooted characteristic and user-specific • On the span (PKS) - 50 mbar (20 inH2O) 0.13 % per 70 bar (1015 psi) - 250 mbar (100 inH2O) 1250 mbar (502 inH2O) 0.03 % per 70 bar (1015 psi) - 6250 mbar (2509 inH2O) 0.09 % per 70 bar (1015 psi) - 32 bar (465 psi) 0.05 % per 70 bar (1015 psi) Siemens FI 01 · 2015 US Edition 1/181 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements 1 SITRANS P500 for differential pressure and flow Total Performance1) Design r5 5 < r 10 Weight (without options) - 50 mbar (20 inH2O) 0,27 % 0,46 % - 250 mbar (100 inH2O) 0.14 % 0.27 % - 1250 mbar (502 inH2O) 6250 mbar (2509 inH2O) 32 bar (465 psi) 0.09 % 0.14 % Material of parts in contact with the medium • Seal diaphragm Stainless steel, mat. no. 1.4404/316L, Hastelloy C276, Monel 400 • Process connection and seal- PN 160: stainless steel, mat.-No. ing screw 1.4404/316L r5 5 < r 10 • Sealing material in the process connections - 50 mbar (20 inH2O) 0,27 % 0,46 % - 250 mbar (100 inH2O) 0.14 % 0.27 % - 1250 mbar (502 inH2O) 6250 mbar (2509 inH2O) 32 bar (465 psi) 0.09 % 0.14 % • Linear characteristic Square rooted characteristic • Flow > 50 % - O-Ring Approx. 3.3 kg (7.3 lb) • Standard: Viton (FKM (FPM)) • Optional: NBR PTFE (virginal) PTFE (glass fiber-reinforced) FFPM (Kalrez)2) Graphite r5 5 < r 10 - 50 mbar (20 inH2O) 0,54 % 0,92 % - 250 mbar (100 inH2O) 0.28 % 0.54 % Material of parts not in contact with media - 1250 mbar (502 inH2O) 6250 mbar (2509 inH2O) 32 bar (465 psi) 0.18 % 0.28 % Electronics housing • Low copper die-cast aluminum AC-AlSi12 (Fe) or AC-AlSi 10 Mg (Fe) to DIN EN 1706 • Lacquer on polyurethane base, optional epoxy-based primer • Stainless steel name plates (mat. no. 1.4404/316L) • Flow 25 % … 50 % Step response time T63 without electrical damping • 50 mbar (20 inH2O) 140 ms, contains a dead time of 45 ms • 250 mbar (100 inH2O) 1250 mbar (502 inH2O) 6250 mbar (2509 inH2O) 32 bar (465 psi) 88 ms, contains a dead time of 45 ms Process connection screws Stainless steel, mat. no. 1.4404/316L Mounting bracket Steel or stainless steel mat. no. 1.4301 Long-term stability (0.05 . r) % per 5 years (0.08 . r) % per 10 years Measuring cell filling Silicone oil Process connection Influence of power supply 0.005 %/1 V ¼-18 NPT female thread and flange connection with M10 to DIN 19213 or 7/16-20 UNF mounting thread to IEC 61518 Electrical connection • Screw terminals • Cable entry via the following screwed glands: - M20 x 1.5 - ½-14 NPT - Han 7D/Han 8D connector - M12 plug Rated conditions Mounting position Any Ambient conditions • Ambient temperature (Note: Observe the temperature class in areas subject to explosion hazard.) - Total device - Readable display - Storage temperature -40 ... +85 °C (-40 ... +185 °F) -20 ... +85 °C (-4 ... +185 °F) -50 ... +90 °C (-58 ... +194 °F) Climatic class • Condensation Relative humidity 0 … 100 % (condensation permissible) Degree of protection (to IEC 60529) IP66/IP 68 and NEMA 4X (with corresponding cable gland) Electromagnetic Compatibility • Emitted interference and inter- Acc. to IEC 61326 and NAMUR NE 21 ference immunity Permissible pressures According to 97/23/EC pressure equipment directive Temperature of medium • Measuring cell with silicone oil -40 ... +125 °C (-40 ... +257 °F) filling 1/182 Siemens FI 01 · 2015 US Edition Displays and controls Pushbuttons 3 for local programming directly on transmitter Display • With or without integrated display • Cover with or without window Auxiliary power supply Terminal voltage on transmitter • DC 10.6 ... 44 V • With intrinsically-safe operation DC 10.6 ... 30 V © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 for differential pressure and flow Explosion protection for USA (to FM) Certificates and approvals Classification according to PED 97/23/EC • PN 160 (MAWP 2320 psi) For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) Certificate of Compliance No. 3033013 • Identification (XP/DIP) or (IS) XP CL I, DIV 1, GP ABCDEFG T4 / T6 DIP CL II, III, DIV1, GP EFG T4/T6 IS CL I, II, III, DIV1, GP ABCDEFG T4 CL I, Zone 0, AEx ia IIC T4 CL I, Zone 1, AEx ib IIC T4 Explosion protection Explosion protection for Europe (to ATEX) • Intrinsic safety "i" - Marking - Permissible ambient temperature - Connection PTB 09 ATEX 2004 X Ex II 1/2 G Ex ia/ib IIC T4 -40 ... +85 °C (-40 ... +185 °F) To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 Li = 400 µH - Permissible Ambient Temperature Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F) - Entity parameters According to "control drawing": A5E02189134N Um = 30 V, Im = 100 mA, Pi = 750 mW, Li = 400µH , Ci = 6 nF • Marking (NI/NO) NI CL I, DIV 2, GP ABCD T4/T6 NI CL I, Zone 2, GP IIC T4/T6 S CL II, III, GPFG T4/T6 NI CL I, DIV 2, GP ABCD T4/T6, NIFW NI CL I, Zone 2, GP IIC T4/T6, NIFW NI CLII, III, DIV 2, GP FG T4/T6, NIFW - Effective internal inductance: - Effective inner capacitance: Ci = 6 nF • Explosion-proof "d" - Marking - Permissible ambient temperature - Connection • Dust explosion protection for zone 20 - Marking - Permissible ambient temperature - Max. surface temperature - Connection BVS 09 ATEX E 027 Ex II 1/2 G Ex d IIC T4/T6 -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 To circuits with values: Um = DC 10.5 ... 45 V PTB 09 ATEX 2004 X Ex II 1 D Ex iaD 20 T 120 °C -40 ... +85 °C (-40 ... +185 °F) 120 °C (248 °F) To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 Li = 400 µH - Effective internal inductance: - Effective inner capacitance: Ci = 6 nF • Dust explosion protection for zone 21/22 - Marking - Connection - Permissible Ambient Temperature Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F) - (NI/S) parameters According to "control drawing": A5E02189134N Um = 45 V, Li = 400 µH, Ci = 6 nF, Explosion protection for Canada (to CCSAUS ) Certificate of Compliance No. 2280963 • Marking (XP/DIP) CL I, DIV 1, GP ABCD T4 /T6; CL II, DIV 1, GP EFG T4/T6 - Permissible ambient temperature Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F) - Entity parameters According to "control drawing": A5E02189134N Um = 45 V • Marking (ia/ib) CL I, Ex ia/Ex ib IIC, T4 CL II, III, Ex ia/Ex ib, GP EFG, T4 CL I, AEx ia/AEx ib IIC, T4 CL II, III, AEx ia/ AEx ib, GP EFG, T4 BVS 09 ATEX E 027 Ex II 2 D Ex tD A21 IP68 T120 °C Ex ia D21 To circuits with values: Um = 10.5 ... 45 V DC; Pmax = 1.2 W • Type of protection "n" (zone 2) PTB 09 ATEX 2004 X Ex II 3 G Ex nA II T4/T6 - Marking Ex II 2/3 G Ex ib/nL IIC T4/T6 Ex II 2/3 G Ex ib/ic IIC T4/T6 - "nA" connection Um = 45 V DC - "nL, ic" connection Ui = 45 V Li = 400 µH - Effective internal inductance: - Effective inner capacitance: Ci = 6 nF - Permissible ambient temperature Ta = T4: -40 ... +85 °C (-40 ... +185 °F) - Entity parameters Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 , Li = 400 µH, Ci = 6 nF CL I, DIV 2, GP ABCD T4/T6 CL II, III, DIV 2, GP FG T4/T6 Ex nA IIC T4/T6 AEx nA IIC T4/T6 Ex nL IIC T4/T6 AEx nL IIC T4/T6 • Marking (NI/n) - Permissible ambient temperature Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F) - NI/nA parameters According to "control drawing": A5E02189134N Um = 45 V - nL parameters According to "control drawing": A5E02189134N Ui = 45 V, Ii = 100 mA, Li = 400 µH, Ci = 6 nF Siemens FI 01 · 2015 US Edition 1/183 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements 1 SITRANS P500 for differential pressure and flow Explosion protection for China (acc. to NEPSI) • Intrinsic safety "i" GYJ111111X Ex ia/ib IIB/IIC T4 - Marking - Perm. ambient temperature 40 ... +85 °C (-40 ... +185 °F) - Connection To certified intrinsically-safe circuits with maximum values: Ui = 30 V Ii = 100 mA, Pi = 750 mW - Effective internal inductance Li = 400 mH - Effective inner capacitance • Explosion-proof "d" Ci = 6 nF GYJ111112 - Marking Ex dia IIC T4/T6 - Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 - Connection To circuits with values: Um = DC 10.5 ... 45 V • Dust explosion protection for zone 21/22 GYJ111112 - Marking DIP A21 TA,T120 °C IP68 D21 - Connection To circuits with values: Um = DC 10.5 ... 45 V • Type of protection "n" (zone 2) GYJ111111X - Marking Ex nL IIB/IIC T4/T6 Ex nA II T4/T6 - Connection Ui = 45 V DC - Effective internal inductance Li = 400 mH - Effective inner capacitance Ci = 6 nF 1) The total performance includes the errors caused by temperature effects, static pressure effects and conformity error, including hysteresis and repeatability. 2) Not in combination wiht span "G". HART communication Load with connection of • HART communicator RB = 230 ... 1100 • HART modem RB = 230 ... 500 Cable 2 wire shielded: 3.0 km (1.86 miles), multiwire shielded: 1.5 km (0.93 miles) Protocol HART Version 6.0 PC/laptop requirements IBM compatible, RAM > 32 MByte, hard disk > 70 MByte, depending on modem type: RS 232-interface or USB connection, VGA graphics Software for computer SIMATIC PDM 6.0 1/184 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 for differential pressure and flow Selection and Ordering data Article No. Pressure transmitters for differential pressure and flow, SITRANS P500 HART, PN 160 (MAWP 2320 psi) 7 MF 5 4 77 - 7777 0 Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Enclosure Thread for cable gland Die-cast aluminum, dual compartment M20x1.5 0 Die-cast aluminum, dual compartment ½-14 NPT 1 Output 4 ... 20 mA, HART 3 Measuring cell filling Measuring cell cleaning Silicone oil normal 1 Measuring span 1.00 ... 50 mbar (0.4 ... 20 inH2O) C 1.25 ... 250 mbar (0.5 ... 100.4 inH2O) D 6.25 ... 1250 mbar (2.5 ... 502 inH2O) E 31.25 ... 6250 mbar (12.54 ... 2509 inH2O) F 0.16 ... 32 bar (2.33 ... 465 psi) G Wetted parts materials (stainless steel process flanges) Seal diaphragm Process connection Stainless steel 1.4404/316L Stainless steel 1.4404/316L A Hastelloy C2761) Stainless steel 1.4404/316L B Monel 4001) Stainless steel 1.4404/316L C Process connection Female thread ¼-18 NPT • Sealing screw opposite process connection - Mounting thread 7/16 - 20 UNF according to EN 61518 - Mounting thread M10 to DIN 19213 0 1 • Vent on side of process flange2) - Mounting thread 7/16 - 20 UNF according to EN 61518 - Mounting thread M10 to DIN 19213 4 5 1) Not together with Measuring span "C". 2) Not in conjunction with remote seals (option V00). Siemens FI 01 · 2015 US Edition 1/185 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements 1 SITRANS P500 for differential pressure and flow Order code Selection and Ordering data Further designs Add "-Z" to Article No. and specify Order code. Mounting bracket made of steel A01 Mounting bracket made of stainless steel A02 Display (Standard: no display, cover closed) With display and blanking cover A10 With display and glass cover A11 Special casing / cover version A20 Electrical connection and cable entry (Standard: no cable gland, only dust protection caps) Cable gland made of plastic (IP66/68)4) A50 Cable glands made of metal (IP66/68) A51 Cable glands made of stainless steel (IP66/68) A52 M12 connectors without cable socket (IP66/67)4) Order code Further designs Add "-Z" to Article No. and specify Order code. Attachments Two coats of lacquer on casing, cover (PU on epoxy) Selection and Ordering data A60 M12 connectors complete with cable socket (IP66/67)4) A61 Han 7D connectors, plastic, straight (with cable socket) (IP65)4) A71 Han 7D connectors, plastic, angled (with cable socket) (IP65)4) A72 Han 7D connectors, metal enclosure, straight (with cable socket) (IP65)4) A73 Han 7D connectors, metal enclosure, angled (with cable socket) (IP65)4) A74 Han 8D connectors, plastic, straight (with cable socket) (IP65)4)8) A75 Han 8D connectors, plastic, angled (with cable socket) (IP65)4)8) A76 Han 8D connectors, metal enclosure, straight (with cable socket) (IP65)4)8) Degree of protection approvals: Ex ia/ib (intrinsic safety) Ex ia/ib protection (ATEX) (T4) Ex IS protection (FM) (T4) Ex IS protection (CCSAUS) (T4) Ex ia/ib protection (NEPSI) (T4) E00 E01 E02 E06 Degree of protection approvals: Ex d (flameproof) Ex d explosion-proof (ATEX)(T4/T6) Ex XP explosion-proof and DIP (FM)(T4/T6) Ex XP explosion-proof and DIP (CCSAUS)(T4/T6) Ex d explosion-proof (NEPSI)(T4/T6) E20 E21 E22 E26 Degree of protection approvals: n/NI Zone 2 (nA, nL, ic) (ATEX) (T4/T6) Div2 NI, Div2 NI-field wiring (FM) (T4/T6) Zone 2 (nA, nL), Div2 NI (CCSAUS) (T4/T6) Zone 2 (nA, nL) (NEPSI) (T4/T6) E40 E41 E42 E46 Degree of protection approvals: Dust Zone 20/21/22 Use in Zone 21/22 (Ex tD) (ATEX) Use in Zone 20/21/22 (Ex iaD) (ATEX) Use in Zone 21/22 (Ex DIP) (NEPSI) E60 E61 E66 Degree of protection approvals: Combinations IS protection and XP and DIP (FM) IS protection and XP and DIP (CCSAUS) IS protection and XP and DIP (FM/CCSAUS) E71 E72 E73 Supplementary approvals/degree of protection Dual Seal approval5) Export approval Korea E85 E86 Special process connection versions (diff. pressure) Side vents for gas measurements7) L32 Swap process connection: high-pressure side at front L33 A77 Mosquito protection 4 pcs. for ¼-18 NPT thread L36 Han 8D connectors, metal enclosure, angled (with cable socket) (IP65)4)8) A78 Process flanges, O-rings, special material Standard: Viton (FKM (FPM) PG 13.5 adapters4) A82 Process conn. sealing rings made of PTFE (Teflon), virginal L60 Process connection sealing rings made of PTFE (Teflon), glass fiber-reinforced Language for labels, leporellos, menu language default 9) (instead of English as standard) L61 Process connection sealing rings made of FFPM (Kalrez)10) L62 German B10 Process connection sealing rings made of NBR L63 French B12 Process connection sealing rings made of graphite L64 Spanish B13 Drain/Vent valve (1 set = 2 units) Italian B14 2 ventilation valves ¼- 18 NPT, in material of process flanges) L80 Chinese B15 Remote seals Russian B16 Japanese B17 Transmitters with connection of remote seal6) (For premounted valve manifolds see page 1/203) English with units psi/inH2O/°F B21 Special version: Supplementary menu languages (Standard: English, German, French, Spanish, Italian) Asia language package (in addition: Chinese, Japanese, Russian) B80 Certificates (available online for downloading)1) Quality inspection certificate (Five-step factory calibration) according to IEC 60770-22) C11 Acceptance test certificate according to EN 10204-3.13) C12 1/186 Siemens FI 01 · 2015 US Edition 1) V00 Enclosed in print or as CD: see page 1/201. When also ordering the quality inspection certificate (factory calibration) according to IEC 60770-2 for transmitters with mounted diaphragm seals: Order this certificate only together with the remote seals. The measuring accuracy of the total combination is certified here. 3) When also ordering the acceptance test certificate according to EN 102043.1 for transmitters with mounted diaphragm seals: Order this certificate as well in addition to the respective remote seals. 4) Not together with types of protection "Explosion-proof", "Ex nA" and "Intrinsic safety and explosion-proof" 5) Only in conjunction with FM and/or CCSAUS 6) Please select a remote seal separately. Also refer to the information under footnote 2). Remote seals see page 1/199. 7) Only in conjunction with process connection "Vent on side". 8) The Han 8D plug is identical with the former Han 8U version. 9) For option B15, B16 and B17 the menu language default is english. Otherwise the Option B80 (Asia language package) is necessary. 10) Not together with Measuring span "G". 2) © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 for differential pressure and flow Selection and Ordering data Order code Additional data Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring range to be set Specify in plain text: • In the case of linear characteristic curve (max. 5 characters): Y01: ... up to ... mbar, bar, kPa, MPa, psi Y01 • In the case of square rooted characteristic (max. 5 characters): Y02: ... up to ... mbar, bar, kPa, MPa, psi Y02 Measuring point number and measuring point identifier (only standard ASCII character set) Specify in plain text: Measuring point number (TAG No.), max. 16 characters Y15: ......................................... Y15 Measuring point text (max. 27 char.) Y16: ......................................... Y16 Entry of HART address (TAG), max. 32 characters Y17: ......................................... Y17 Setting of pressure indication in pressure units Y21 Specify in plain text (standard setting: mbar) Y21: bar, kPa, MPa, psi, ... Note: The following pressure units are selectable: bar, mbar, mm H2O*), in H2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, Torr, ATM, % or mA *) Reference temperature 20 °C Setting of pressure indication in non-pressure units1) Y22 + Y01 or Y02 Specify in plain text: Y22: ... up to ... l/min, m3/h, m, USgpm, ... (specification of measuring range in pressure units "Y01" is essential, unit with max. 5 characters) Customer-specific settings Damping setting (range: 0 ... 100 s) (Standard setting: 2 s) 1) Y30 Preset values can only be changed over SIMATIC PDM. Siemens FI 01 · 2015 US Edition 1/187 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 for differential pressure and flow ■ Dimensional drawings [ 139 (5.48) 87 (3.4) \ approx. 30 (approx. 1.2) 45 (1.8) 23 (0.92) FIELD TERMINALS X Z XW XP approx. 259 (approx.10.1) XP 157 (6.1) 125 (5) Ø81 (Ø3.24) 58 (2.29 65 (2.6) ` _ 102 (4) Y 134 (5.36) 1 43 (1.68) approx. 98 (approx. 3.82) ^Y OYU_Z ^ ] ]^ OYU]P XX` O[U]P XW[ O[UX]P 1 2 3 4 5 6 Terminal side Process connection: ¼-18 NPT (EN 61518) Electronics side, digital display Protective cover for the pushbuttons Cable entry: - Screwed gland M20 x 1.53) - Screwed gland ½-14 NPT - Han 7D/Han 8D connector2)3) - M12 connector Mounting bracket (optional) 7 Electrical connection: - Han 7D/Han 8D connector/socket2)3) 8 Vent valve (optional) 9 Safety catch 10 Blanking plug 1) 2) 3) Allow approx. 20 mm (0.79 inch) additional thread length Not with type of protection "Explosion-proof" Not with type of protection "FM + CCSAUS [IS + XP]" SITRANS P pressure transmitter for differential pressure and flow, P500 series, measurements in mm (inch) 1/188 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 for level ■ Technical specifications (0.05 . r) % per 5 years Long-term stability Input Measured variable Level Span (infinitely adjustable) Span (min. ... max.) (0.08 . r) % per 10 years Maximum operating pressure 1.25 ... 250 mbar (0.5 … 100 inH2O) 6.25 ... 1250 mbar (2.5 ... 500 inH2O) See "Mounting flange" 31.25 ... 6250 mbar (12.54 ... 2509 inH2O) Influence of ambient temperature per 28 °C (50 °F)1) • 250 mbar (100 inH2O) (0.025 . r + 0.014) % • 1250 mbar (502 inH2O) 6250 mbar (2509 inH2O) (0.006 . r + 0.03) % Influence of static pressure • At the start of scale value (PKN) - 250 mbar (100 inH2O) (0.035 . r) % je 70 bar (1015 psi) correction via zero point correction - 1250 mbar (502 inH2O) 6250 mbar (2509 inH2O) (0.007 . r) % je 70 bar (1015 psi) correction via zero point correction Lower range limit • Measuring cell with silicone oil -100 % of max. span or 500 mbar a filling (7.25 psia) vacuum resistance Also available as vacuum-resistant remote seal: 30 mbar a (0.44 psia) Upper range limit 100% of max. span Start of scale Between measuring limits (freely adjustable) Output • On the span (PKS) - 250 mbar (100 inH2O) 1250 mbar (502 inH2O) 0.03 % je 70 bar (1015 psi) - 6250 mbar (2509 inH2O) 0.09 % je 70 bar (1015 psi) Influence of power supply 0.005 %/1 V Rated conditions Output current signal 4 ... 20 mA Mounting position • Lower current limit (freely adjustable) 3.55 mA, factory setting 3.8 mA Ambient conditions • Upper current limit (freely adjustable) 23 mA, factory setting 20.5 mA Defined by flange • adjustable damping 0... 100 s in steps of 0.1 s, factory setting 2 s • Ambient temperature (Note: Observe the temperature class in areas subject to explosion hazard.) - total device - Readable display - Storage temperature • current transmitter 3.55 ... 23 mA Climatic class • Failure signal Adjustable within limits: • Lower: 3.55 … 3.7 mA (factory setting 3.6 mA) • Upper: 21.0 … 23 mA (factory setting 22.8 mA) • Condensation Relative humidity 0 … 100 % (condensation permissible) Degree of protection to IEC 60529 IP66/IP68 and NEMA 4X (with corresponding cable gland) • Ripple (without HART commu- Ipp 0.4 of max. output current nication) Load • Without HART communication RB (UH - 10.5 V)/0.023 A in , UH : Power supply in V Electromagnetic Compatibility • Emitted interference and inter- Acc. to IEC 61326 and NAMUR NE 21 ference immunity Permissible pressures According to 97/23/EC pressure equipment directive • With HART communication - HART Communicator RB = 230 ... 1100 - HART modem RB = 230 ... 500 Characteristic curve Medium temperature of highpressure side Linearly rising or linearly falling and user-specific Measuring accuracy Reference conditions (in accordance with IEC 60770-1) All error information always refers to the set span. -40 ... +85 °C (-40 ... +185 °F) -20 ... +85 °C (-4 ... +185 °F) -50 ... +90 °C (-58 ... +194 °F) • Rising characteristic curve • Start of scale 0 bar • Stainless steel seal diaphragm • Measuring cell with silicone oil filling • Room temperature (25 °C (77 °F)) Error in measurement at limit setting incl. hysteresis and reproducibility r: Span ratio (r = max. span / set span) • Measuring cell with silicone oil filling - pabs 1 bar -40 ... +1752) °C (-40 ... +3472) °F) - pabs 1 bar -40 ... +80 °C (-40 ... +176 °F) Design Weight • To EN (pressure transmitter approx. 9.8 … 11.8 kg (21.6… 26.0 with mounting flange, without (lb) tube) • To ASME (pressure transmitter approx. 9.8 … 16.8 kg (21.6 … 37.0 with mounting flange, without lb) tube) Linear characteristic r 10 r 10 • 250 mbar (100 inH2O) 1250 mbar (502 inH2O) 6250 mbar (2509 inH2O) 0.03 % (0.003 . r) % Siemens FI 01 · 2015 US Edition 1/189 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements 1 SITRANS P500 for level Material of wetted parts at the high-pressure side • Seal diaphragm of mounting flange • Sealing face Auxiliary power supply Terminal voltage on transmitter Stainless steel 1.4404/316L, Hastelloy C276, mat. no. 2.4819, Monel 400, mat. no. 2.4360, Tantal, PFA auf Edelstahl 1.4404/316L, PTFE auf Edelstahl 1.4404/316L Smooth to EN 1092-1, Form B1 and/or ASME B16.5 RF 125 … 250 AA for stainless steel316L, EN1092-1 Form B2 and/or ASME B16.5 RFSF in the case of other materials • Sealing material in the process connection - O-Ring - For vacuum application of mounting flange • Standard: Viton (FKM (FPM)) • Optional: NBR PTFE (virginal) PTFE (glas fiber-reinforced) FFPM (Kalrez) Graphite copper Stainless steel, mat. no. 1.4404/316L, Hastelloy C276, Monel 400 • Process connection and seal- • Stainless steel, mat. no. 1.4404/316L ing screw • Sealing material in the process connection - O-Ring • Standard: Viton (FKM (FPM)) • Optional: NBR PTFE (virginal) PTFE (glas fiber-reinforced) FFPM (Kalrez) Graphite Material of parts not in contact with media Electronics housing Certificates and approvals Classification according to PED 97/23/EC • PN 160 (MAWP 2320 psi) For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) Explosion protection Material of wetted parts at the low-pressure side • Seal diaphragm • DC 10.6 ... 44 V • With intrinsically-safe operation DC 10.6 ... 30 V • Low copper die-cast aluminum ACAlSi12 (Fe) or AC-AlSi 10 Mg (Fe) to DIN EN 1706 • Lacquer on polyurethane base, optional epoxy-based primer • Stainless steel serial plate Process connection screws Stainless steel Measuring cell filling Silicone oil • Liquid mounting flange Silicone oil or other material Process connection Explosion protection for Europe (to ATEX) • Intrinsic safety "i" PTB 09 ATEX 2004 X - Marking Ex II 1/2 G Ex ia/ib IIC T4 - Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) - Connection To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 - Effective internal inductance: Li = 400 µH - Effective inner capacitance: Ci = 6 nF • Explosion-proof "d" BVS 09 ATEX E 027 - Marking Ex II 1/2 G Ex d IIC T4/T6 - Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 - Connection To circuits with values: Um = DC 10.5 ... 45 V • Dust explosion protection for zone 20 PTB 09 ATEX 2004 X - Marking Ex II 1 D Ex iaD 20 T 120 °C - Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) - Max. surface temperature 120 °C (248 °F) - Connection To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 - Effective internal inductance: Li = 400 µH - Effective inner capacitance: Ci = 6 nF • Dust explosion protection for zone 21/22 BVS 09 ATEX E 027 • High-pressure side Flange to EN and ASME - Marking • Low-pressure side ¼-18 NPT female thread and flange connection with M10 to DIN 19213 or 7/16-20 UNF mounting thread to IEC 61518 Ex II 2 D Ex tD A21 IP68 T120 °C Ex ia D21 - Connection To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W Electrical connection • Screw terminals • Cable entry via the following screwed glands: - M20 x 1.5 - ½-14 NPT - Han 7D/Han 8D connector - M12 plug Displays and controls Push buttons 3; for operation directly on the device Display • With or without integrated display • Cover with or without window 1/190 Siemens FI 01 · 2015 US Edition • Type of protection "n" (zone 2) PTB 09 ATEX 2004 X - Marking Ex II 3 G Ex nA II T4/T6 Ex II 2/3 G Ex ib/nL IIC T4/T6 Ex II 2/3 G Ex ib/ic IIC T4/T6 - "nA" connection Um = 45 V DC - "nL, ic" connection Ui = 45 V - Effective internal inductance Li = 400 µH - Effective inner capacitance Ci = 6 nF © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 for level Explosion protection for USA (to FM) Explosion protection for China (acc. to NEPSI) Certificate of Compliance No. 3033013 • Identification (XP/DIP) or (IS) XP CL I, DIV 1, GP ABCDEFG T4 / T6 DIP CL II, III, DIV1, GP EFG T4/T6 IS CL I, II, III, DIV1, GP ABCDEFG T4 CL I, Zone 0, AEx ia IIC T4 CL I, Zone 1, AEX ib IIC T4 - Permissible Ambient Temperature Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F) - Entity parameters According to "control drawing": A5E02189134N Um = 30 V, Im = 100 mA, Pi = 750 mW, Li = 400 µH , Ci = 6 nF • Marking (NI/NO) - Permissible Ambient Temperature - (NI/S) parameters • Intrinsic safety "i" According to "control drawing": A5E02189134N Um = 45 V, Li = 400 µH, Ci = 6 nF Certificate of Compliance No. 2280963 CL I, DIV 1, GP ABCD T4 /T6; CL II, DIV 1, GP EFG T4/T6 - Permissible Ambient Temperature Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F) - Entity parameters According to "control drawing": A5E02189134N, Um = 45 V • Marking (ia/ib) CL I, Ex ia/Ex ib IIC, T4 CL II, III, Ex ia/Ex ib, GP EFG, T4 CL I, AEx ia/AEx ib IIC, T4 CL II, III, AEx ia/ AEx ib, GP EFG, T4 - Permissible Ambient Temperature Ta = T4: -40 ... +85 °C (-40 ... +185 °F) - Entity parameters Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 , Li = 400 µH, Ci = 6 nF • Marking (NI/n) CL I, DIV2, GP ABCD T4/T6 CL II, III, DIV2, GP FG T4/T6 Ex nA IIC T4/T6 AEx nA IIC T4/T6 Ex nL IIC T4/T6 AEx nL IIC T4/T6 - Permissible Ambient Temperature Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F) - NI/nA parameters According to "control drawing": A5E02189134N, Um = 45 V - nL parameters According to "control drawing": A5E02189134N, Ui = 45 V, Ii = 100 mA, Li = 400 µH, Ci = 6 nF 40 ... +85 °C (-40 ... +185 °F) - Connection To certified intrinsically-safe circuits with maximum values: Ui = 30 V Ii = 100 mA, Pi = 750 mW - Effective inner capacitance • Explosion-proof "d" Ci = 6 nF GYJ111112 - Marking Ex dia IIC T4/T6 - Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 - Connection To circuits with values: Um = DC 10.5 ... 45 V • Dust explosion protection for zone 21/22 GYJ111112 - Marking DIP A21 TA,T120 °C IP68 D21 - Connection To circuits with values: Um = DC 10.5 ... 45 V • Type of protection "n" (zone 2) GYJ111111X Explosion protection for Canada (to CCSAUS ) • Marking (XP/DIP) Ex ia/ib IIB/IIC T4 - Permissible ambient temperature - Effective internal inductance Li = 400 mH NI CL I, DIV 2, GP ABCD T4/T6 NI CL I, Zone 2, GP IIC T4/T6 S CL II, III, GPFG T4/T6 NI CL I, DIV 2, GP ABCD T4/T6, NIFW NI CL I, Zone 2, GP IIC T4/T6, NIFW NI CLII, III, DIV 2, GP FG T4/T6, NIFW Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F) GYJ111111X - Marking - Marking Ex nL IIB/IIC T4/T6 Ex nA II T4/T6 - Connection Ui = 45 V DC - Effective internal inductance Li = 400 mH - Effective inner capacitance Ci = 6 nF 1) Only relevant for the pressure transmitter. The temperature error of the remote seal must calculated separately. 2) This value may be increased if the process connection is sufficiently insulated. HART communication Load with connection of • HART Communicator RB = 230 ... 1100 • HART modem RB = 230 ... 500 Cable 2 wire shielded: 3.0 km (1.86 miles), multiwire shielded: 1.5 km (0.93 miles) Protocol HART Version 6.0 PC/laptop requirements IBM compatible, RAM > 32 MByte, hard disk > 70 MByte, depending on modem type: RS 232-interface or USB connection, VGA graphics Software for computer SIMATIC PDM 6.0 Siemens FI 01 · 2015 US Edition 1/191 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements 1 SITRANS P500 for level Article No. Order code 777 7 MF 5 6 77 - 7777 0 - 7777 Selection and Ordering data Pressure transmitters for level, SITRANS P500 HART Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Enclosure Die-cast aluminum, dual compartment Die-cast aluminum, dual compartment Output 4 ... 20 mA, HART Measuring cell filling Measuring cell cleaning Silicone oil normal Measuring span (min. ... max.) 1.25 ... 250 mbar (0.5 ... 100 inH2O) 6.25 ... 1250 mbar (2.5 ... 500 inH2O) 31.25 ... 6250 mbar (12.54 ... 2509 inH2O) Thread for cable gland M20x1.5 ½-14 NPT 0 1 3 1 D E F Wetted parts of the low-pressure side (stainless steel process flanges) Seal diaphragm Process connection Stainless steel 1.4404/316L Stainless steel 1.4404/316L Hastelloy C276 Stainless steel 1.4404/316L Monel 400 Stainless steel 1.4404/316L Process connection of low-pressure side A B C Female thread ¼-18 NPT • Sealing screw opposite process connection - Mounting thread 7/16 - 20 UNF according to IEC 61518 - Mounting thread M10 to DIN 19213 0 1 • Vent on side of process flange - Mounting thread 7/16 - 20 UNF according to IEC 61518 - Mounting thread M10 to DIN 19213 4 5 Wetted parts materials (high-pressure side) Stainless steel 1.4404/316L Hastelloy C276 mat. no. 2.4819 Monel 400 mat. no. 2.4360 Tantalum PFA coated on stainless steel PTFE on stainless steel 1.4404/316L (not in combination with an extension) Other version Add Order code and plain text: Material: ... ; Extension length: ... 0 1 2 3 4 6A 9Y N1Y Process connection on high-pressure side: Extension length None 50 mm (1.97 inch) 100 mm (3.94 inch) 150 mm (5.90 inch) 200 mm (7.87 inch) Other version: See option "9" for "Wetted parts materials" A B C D E Process connection on high-pressure side: Nominal diameter/Nominal pressure DN 50, PN 406) DN 80, PN 40 DN 100, PN 16 DN 100, PN 40 2", class 1506) 2", class 3006) 3", class 150 3", class 300 4", class 150 4", class 300 Other version, add Order code and plain text: Nominal diameter: ... ; Nominal pressure: ... 1/192 Siemens FI 01 · 2015 US Edition B D G H L M Q R T U Z Q1Y © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 for level Selection and Ordering data Article No. Pressure transmitters for level, SITRANS P500 HART 7 MF 5 6 77 - 7777 0 - 7777 777 0 1 2 3 4 9 R1Y Process connection on high-pressure side: Filling liquid Silicone oil M5 Silicone oil M50 High-temperature oil Halocarbon (for oxygen measurement) FDA compliant oil Other version, add Order code and plain text: Filling liquid: ... Siemens FI 01 · 2015 US Edition Order code 1/193 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements 1 SITRANS P500 for level Order code Selection and Ordering data Selection and Ordering data Further designs Add "-Z" to Article No. and specify Order code. Further designs Add "-Z" to Article No. and specify Order code. Display (Standard: no display, cover closed) Degree of protection approvals: Ex d (flameproof) With display and blanking cover A10 With display and glass cover A11 Special version: cover/casing Two coats of lacquer on casing, cover (PU on epoxy) A20 Electrical connection and cable entry (Standard: no cable gland, only dust protection caps) (IP66/68)4) Order code Ex d explosion-proof (ATEX)(T4/T6) E20 Ex XP explosion-proof and DIP (FM)(T4/T6) E21 Ex XP explosion-proof and DIP (CCSAUS)(T4/T6) Ex d explosion-proof (NEPSI)(T4/T6) E22 E26 Degree of protection approvals: n/NI Zone 2 (nA, nL, ic) (ATEX) (T4/T6) E40 Div2 NI, Div2 NI-field wiring (FM) (T4/T6) E41 E42 E46 Cable glands made of metal (IP66/68) A51 Zone 2 (nA, nL), Div2 NI (CCSAUS) (T4/T6) Zone 2 (nA, nL) (NEPSI) (T4/T6) Cable glands made of stainless steel (IP66/68) A52 Degree of protection approvals: Zone 20/21/22 A60 Use in Zone 21/22 (Ex tD) (ATEX) E60 Cable gland made of plastic M12 connectors without cable socket (IP66/67)4) A50 A61 Use in Zone 20/21/22 (Ex iaD) (ATEX) E61 Han 7D connectors, plastic, straight (with cable socket) (IP65)4) A71 Use in Zone (Ex DIP) (ATEX) E66 Han 7D connectors, plastic, angled (with cable socket) (IP65)4) A72 Han 7D connectors, metal enclosure, straight (with cable socket) (IP65)4) A73 Han 7D connectors, metal enclosure, angled (with cable socket) (IP65)4) A74 Han 8D connectors, plastic, straight (with cable socket) (IP65)4)7) A75 M12 connectors, cable socket (IP66/67)4) Degree of protection approvals: Combinations IS protection and XP and DIP (FM) E71 IS protection and XP and DIP (CCSAUS) E72 IS protection and XP and DIP (FM/CCSAUS) E73 Supplementary approvals / degree of protection Dual Seal approval5) E85 Export approval Korea E86 Special process connection versions (diff. pressure) Han 8D connectors, plastic, angled (with cable socket) (IP65)4)7) A76 Swap process connection: high-pressure side at front L33 Han 8D connectors, metal enclosure, straight (with cable socket) (IP65)4)7) A77 Mosquito protection 4 pcs. for ¼-18 NPT thread L36 Han 8D connectors, metal enclosure, angled (with cable socket) (IP65)4)7) A78 Process flanges, O-rings, special material Standard: Viton (FKM (FPM) PG 13.5 adapters4) A82 Process connection sealing rings made of PTFE (Teflon), virginal L60 Process connection sealing rings made of PTFE (Teflon), glass fiber-reinforced L61 Language for labels, leporellos and menu language default8) (instead of English as standard) German B10 Process connection sealing rings made of FFPM (Kalrez) L62 French B12 Process connection sealing rings made of NBR L63 Spanish B13 Process connection sealing rings made of graphite L64 Italian B14 Chinese B15 Drain/Vent valve (1 set = 2 units) Russian B16 Japanese B17 English with units: psi/inH2O B21 Special version: Supplementary menu languages (Standard: English, German, French, Spanish, Italian) Asia language package (in addition: Chinese, Japanese, Russian) Certificates (available online for B80 downloading)1) Quality inspection certificate (Five-step factory calibration) according to IEC 60770-22) C11 Acceptance test certificate according to EN 10204-3.13) C12 Degree of protection approvals: Ex ia/ib (intrinsic safety) 2 ventilation valves ¼- 18 NPT, in material of process flange) L80 Vacuum-proof design Vacuum service V04 Spark arrester For mounting on zone 0 (including documentation) V05 1) Enclosed in print or as CD: see page 1/201. 2) When also ordering the quality inspection certificate (factory calibration) according to IEC 60770-2 for transmitters with mounted diaphragm seals: Order this certificate only together with the remote seals. The measuring accuracy of the total combination is certified here. 3) When also ordering the acceptance test certificate according to EN 10204-3.1 for transmitters with mounted diaphragm seals: Order this certificate as well in addition to the respective remote seals. 4) Not together with types of protection "Explosion-proof", "Ex nA" and "Intrinsic safety and explosion-proof" Ex ia/ib protection (ATEX) (T4) E00 5) Ex IS protection (FM) (T4) E01 Only in conjunction with FM and/or CCSAUS 6) Not recommended for Measuring span "D" Ex IS protection (CCSAUS) (T4) Ex ia/ib protection (NEPSI) (T4) E02 E06 7) The Han 8D plug is identical with the former Han 8U version. 8) For option B15, B16 and B17 the menu language default is english. Otherwise the Option B80 (Asia language package) is necessary. 1/194 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 for level Selection and ordering data Order code Additional data Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring range to be set Specify in plain text: Linear characteristic curve (max. 5 characters): Y01: ... up to ... mbar, kPa, MPa, psi Y01 Measuring point number and measuring point identifier (only standard ASCII character set) Specify in plain text: Measuring point number (TAG No.), max. 16 characters Y15: ......................................... Y15 Measuring point text (max. 27 char.) Y16: ......................................... Y16 Entry of HART address (TAG), max. 32 characters Y17: ......................................... Y17 Setting of pressure indication in pressure units Y21 Specify in plain text (standard setting: mbar) Y21: bar, kPa, MPa, psi, ... Note: The following pressure units are selectable: bar, mbar, mm H2O*), in H2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, Torr, ATM, % or mA *) Reference temperature 20 °C Setting of pressure indication in non-pressure units1) Y22 + Specify in plain text: Y01 Y22: ... up to ... l/min, m3/h, m, USgpm, ... (specification of measuring range in pressure units "Y01" is essential, unit with max. 5 characters) Customer-specific settings Damping setting (range: 0 ... 100 s) (Standard setting: 2 s) 1) Y30 Preset values can only be changed over SIMATIC PDM. Siemens FI 01 · 2015 US Edition 1/195 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 for level ■ Dimensional drawings 178 (7) appr. 30 (appr. 1.18) 87 (3.43) 58 (2.29) 2 139 (5.48) 74 (2.92) 10 1 3 5 7 154 (6.2) 4 L 70 (2.75) 6 11 d5 d4 k D 1 8 54 (2.1) 108 (4.25) n d2 f b 9 98 (3.81) 4 2 5 1 Electrical connection - M20 x 1.53) or ½-14 NPT screwed gland - Han 7D/Han 8D connector2)3) or M12 2 Cover for the push buttons 3 Dummy screwed gland 4 Terminal side 1) 5 Electronics side, display1) 6 Process connection low-pressure side, with valve (optional) or screwed gland (optional) 7 Safety catch (only for type of protection "Explosion-proof"; not shown in the diagram) 8 Process connection: low-pressure side ¼-18NPT (IEC 61518) 9 Electrical connection: - Han 7D/Han 8D connector/socket2)3) 10 Mounting flange according to EN 1092-1 or ASME B16.5 11 Clearance for turning the casing SITRANS P pressure transmitter for filling level, P500 series, measurements in mm (inch) 1/196 Siemens FI 01 · 2015 US Edition 1) Allow approx. 20 mm (0.79 inch) additional thread length Not with type of protection "Explosion-proof" 3) Not with type of protection "FM + CCSAUS [IS + XP]" 2) © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 for level Connection to EN 1092-1 Nominal Nominal b diameter pressure D d d2 d4 d5 dM f k n mm mm mm mm mm mm mm mm mm DN50 PN 40 20 165 61 18 102 48.3 451) 2 125 4 DN 80 PN 40 24 200 90 18 138 76 722) 2 160 8 DN 100 PN 16 20 220 115 18 158 94 89 2 180 8 PN 40 24 235 115 22 162 94 89 2 190 8 L mm 0, 50, 100, 150 or 200 Connection to ASME B16.5 Nominal diameter 2 inch 3 inch 4 inch Nominal pressure b D d2 d4 d5 dM f k n lb/sq.in. inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) class 150 0.77 (19.5) 5.91 (150) 0.75 (19.0) 3.62 (92) 1.9 (48.3) 1.77 (45)1) 0.079 (2.0) 4.75 (120.7) 4 class 300 0.89 (22.7) 6.49 (165) 0.75 (19.0) 3.62 (92) 1.9 (48.3) 1.77 (45)1) 0.079 (2.0) 5.0 (127) 8 class 150 0.96 (24.3) 7.5 (190.5) 0.75 (19.0) 5 (127) 3.0 (76) 2.83 (72)2) 0.079 (2.0) 6 (152.4) 4 class 300 1.14 (29.0) 8.27 (210) 0.87 (22.2) 5 (127) 3.0 (76) 2.83 (72)2) 0.079 (2.0) 6.69 (168.3) 8 class 150 0.96 (24.3) 9.06 (230) 0.75 (19.0) 6.19 (157.2) 3.69 (94) 3.5 (89) 0.079 (2.0) 7.5 (190.5) 8 class 300 1.27 (32.2) 10.04 (255) 0.87 (22.2) 6.19 (157.2) 3.69 (94) 3.5 (89) 0.079 (2.0) 7.88 (200) 8 L inch (mm) 0, 2, 3.94, 5.94 or 7.87 (0, 50, 100, 150 or 200) Explanations of tables: d: Internal diameter of gasket to DIN 2690 dM: Effective diaphragm diameter d5: Diameter of extension f: Milling edge L: Extension length 1) 59 mm = 2.32 inch with tube length L = 0. 2) 89 mm = 3½ inch with tube length L = 0. Siemens FI 01 · 2015 US Edition 1/197 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements 1 SITRANS P500 - Supplementary electronics for 4-wire connection ■ Overview Structural design Dimensions (W x H x D) in mm (inch) 80 x 120 x 60 (3.15 x 4.72 x 2.36) Electrical connection Screw terminals (Pg 13.5 cable inlet) or Han 7D / Han 8D plug Power supply Supply voltage 230 V AC (-10 ... +6 %, 47 ... 63 Hz, approx. 6 VA) or 24 V AC/DC (24 V AC 10 %, 47 ... 63 Hz, approx. 3 VA) Permissible ripple (within the specified limits) Approx. 2.5 Vpp ■ Dimensional drawings 218 (8.58) 87 (3.43) SITRANS P pressure transmitter with supplementary electronics for 4-wire connection Direct connection of the supplementary electronics to a SITRANS P pressure transmitter from the P500 series produces a transmitter for four-wire connection. The supplementary electronics cannot be attached to explosionprotected pressure transmitters. The supplementary electronics is fitted in a light metal housing which is mounted on the left side of the pressure transmitter. Note on ordering: The supplementary electronics has to be be ordered through the supplementary options of the pressure transmitter in question. ■ Technical specifications Output Output signal 0 ... 20 mA or 4 ... 20 mA Load Max. 750 Voltage measurement Linear (square-rooting in transmitter if necessary) Electrical isolation Between power supply and input/ output Measuring accuracy According to IEC 60770-1 Conformity error (in addition to transmitter) 0.15 % of set span Influence of ambient temperature 0.1 % per 10 K Power supply effect 0.1 % per 10 % change in voltage or frequency Load effect 0.1 % per 100 % change Rated conditions Ambient temperature • 24 V version -20 ... +80 °C (-4 ... +176 °F) • 230 V version -20 ... +60 °C (-4 ... +140 °F) Storage temperature -50 ... +85 °C (-58 ... +185 °F) Degree of protection IP54 to IEC 60529 Electromagnetic compatibility (EMC) IEC 61236-1 Condensation Relative humidity 0 ... 95 % condensation permissible 1/198 Siemens FI 01 · 2015 US Edition 95 (3.74) SITRANS P pressure transmitters with supplementary electronics for fourwire connection, dimension drawing, dimensions in mm (inch) © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 - Supplementary electronics for 4-wire connection ■ Schematics 1 Terminals 2 + 3 Ia 1 Han 8D/7D plug 6 7 5 1 2 plugs 5 1 4 6 SL Supplementary electronics for 4-wire connection Article No. of the transmitter 7MF54..-.....-.... or 7MF56..-.....-.... add "-Z" and Order code. V77 Power supply 24 V AC/DC SL 2 Ia - UH 6 7 2 5 1 3 4 + Ia - SL 2 3 UH AC 230 V UC 24 V Han 7D Han 7D Han 7D Han 8D Ia SL UH Power supply Output current Order code 3 + 7 5 UH 4 6 4 - Selection and Ordering data Protective earth conductor Supplementary electronics for 4-wire connection, connection diagram (the HAN 8D conector is identical to the previous version of the HAN 8U) 230 V AC Electrical connection Terminals; 2 Pg screwed glands, to left 2 Han 7D/Han 8D plugs incl. mating connector, to left 1 Han 7D plug incl. mating connector, angled Terminals; 1 Pg screwed gland, downwards 1 Han 8D plug incl. mating connector, downwards (observe arrangement of plug and differential pressure line) Terminals; 2 Pg screwed glands, to left 2 Han 7D plugs incl. mating connector, to left Output current 0 ... 20 mA 4 ... 20 mA 1 3 5 6 9 7 8 0 1 Accessories Article No. Instruction Manual German/English A5E00322799 Siemens FI 01 · 2015 US Edition 1/199 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements 1 SITRANS P500 Accessories/Spare parts Selection and ordering data Article No. Replacement measuring cells for differential pressure SITRANS P pressure transmitters for differential pressure and flow, P500 HART PN 160 series (MAWP 2320 psi) 7777 1 7MF 5 9 9 4 - Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Silicone oil Measuring cell cleaning normal 1 Measuring span (min. ... max.) 1,00 ... 50 mbar (0.4 ... 20 inH2O) 1.25 ... 250 mbar (0.5 ... 100 inH2O) 6.25 ... 1250 mbar (2.5 ... 502 inH2O) 31.25 ... 6250 mbar (12.54 ... 2509 inH2O) 0.16 ... 32 bar (2.33 ... 465 psi) C D E F G Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel 1.4404/316L Stainless steel 1.4404/316L A Hastelloy C2761) Stainless steel1.4404/316L B Monel 4001) Stainless steel1.4404/316L C Process connection Female thread ¼-18 NPT • Sealing screw opposite process connection - Mounting thread 7/16-20 UNF to IEC 61518 - Mounting thread M10 to DIN 19213 • Vent on side of process flange - Mounting thread 7/16-20 UNF to IEC 61518 - Mounting thread M10 to DIN 19213 Further designs 0 1 4 5 Order code Add "-Z" to Article No. and specify Order code. Acceptance test certificate Acc. to EN 10204-3.1 C12 Without process flanges K00 Vent on side for gas measurements2) L32 Process flanges, O-ring, special material Standard: Viton (FKM (FPM)) Process connection sealing rings made of PTFE (Teflon), virginal L60 Process connection sealing rings made of PTFE (Teflon), glass fiber-reinforced L61 Process connection sealing rings made of FFPM (Kalrez)2) L62 Process flanges, O-rings made of NBR L63 Process flanges, O-rings made of graphite L64 1) Not together with Measuring span "C". 2) Only in conjunction with process connection code 4 or 5. 2) Not together with Measuring span "G". 1/200 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 Accessories/Spare parts ■ Selection and Ordering data ■ Selection and Ordering data Article No. Mounting brackets For differential pressure transmitters with flange thread M10 (7MF54..-…10 and 7MF54..-…50) • Made of steel • Made of stainless steel Mounting brackets for differential pressure transmitter with flange thread 7/16-20 UNF (7MF54..-…00 and 7MF54..-…40) • Made of steel • Made of stainless steel 7MF5987-1AA 7MF5987-1AD Digital indicator Including mounting material 7MF5987-1AC 7MF5987-1AF 7MF5987-1BE 7MF5987-1BF 7MF5987-1BR TAG plate (incl. fastening material) 7MF5987-1CA Printed (1 pc.) Data according to Y01 or Y02, Y15 and Y16 (see "SITRANS P transmitters") 7MF5987-1CB-Z Y..: ...................... Mounting screws 7MF5987-1CC Sealing plugs for process flange (1 set = 2 units) • Made of stainless steel • Made of Hastelloy 7MF4997-1CG 7MF4997-1CH Vent valve Complete (1 set = 2 units) • Made of stainless steel • Made of Hastelloy 7MF4997-1CP 7MF4997-1CQ Electronics module HART, intrinsically safe Ex ia for installation in transmitter casing (observe warranty conditions) 7MF5987-1DC Connection board (incl. fastening material) HART, intrinsically safe Ex ia for installation in transmitter casing (observe warranty conditions) O-rings for process flanges made of: • Viton (FKM (FPM)) (10 pcs.) • NBR (Buna N) (10 pcs.) Push buttons assembly (incl. fastening material) A5E02344527 English A5E02344528 French A5E02344529 Italian A5E02344530 Spanish A5E02344531 English, German, Spanish, French, Italian, Dutch A5E02344532 English, Estonian, Latviaan, Lithuanian, Polish, Romanian A5E02307339 English, Bulgarian, Czech, Finnish, Slovakian, Slovenian A5E02307340 English, Danish, Greek, Portuguese, Swedish, Hungarian A5E02307341 Russian A5E02307338 Brief instructions (Leporello) Without inscription (5 pcs.) For TAG plate, grounding and connection terminals and securing and locking screws (30 units) German Compact operating instructions1) Cover Made of die-cast aluminum, including O-ring • Without window • With window Article No. Operating Instructions1) 7MF5987-1DM 7MF5987-2DA 7MF5987-2DE German, English, French, Italian, Spanish, Chinese A5E02344536 DVD with SITRANS P documentation German, English, French, Spanish, Italian Compact operating instructions in 21 EU languages Service Instructions1) for replacement of electronics, measuring cell and terminal board • German • English A5E00090345 A5E02822443 A5E02344534 HART modem With USB interface 7MF4997-1DB Operating instruction1) Supplementary electronics for 4-wire connection German, English A5E00322799 Certificates (order only via SAP) additional to internet download • Hard copy (to order) A5E03252406 • On CD (to order) A5E03252407 1) You can download these operating instructions free-of-charge from our Internet site at www.siemens.com/sitransp. For power supply units, see catalog FI01 "Supplementary Compontents". 7MF5987-2AF For replacement of operating keys for onsite operation of the transmitter Sealing ring for • Process connection • NBR sealing ring for screw cover (10 pcs.) • NBR sealing ring for interface measuring cell/housing (10 pcs.) See catalog FI01, "Fittings" 7MF4997-2EA 7MF5987-2EB Siemens FI 01 · 2015 US Edition 1/201 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 Accessories/Spare parts ■ Dimensional drawings 33,15 (1.31) 33,35 (1.32) 20,65 (0.81) 54 (2.13) 41,3 (1.63) 27 (1.06) 20,65 (0.81) R30 R6,56) (0.2 8) (1.1 3 (0.12) Ø 20 (0.79) 41,3 (1.63) 54 (2.13) 134 (5.28) 52,5 (2.07) 72 (2.83) Ø 11 (0.43) 16,5 (0.65) 115 (4.53) R30 ) 8 (1.1 3 72 (2.83) Mounting bracket for SITRANS P pressure transmitter, P500 series, measurements in mm (inch) Mounting bracket material: Sheet-steel Mat. No. 1.0330, chrome-plated, or stainless steel Mat. No. 1.4301 (304) 1/202 Siemens FI 01 · 2015 US Edition 120 (4.72) 105 (4.13) 21 (0.83) 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 Factory-mounting of valve manifolds on transmitters ■ Overview ■ Design The SITRANS P500 transmitter can be delivered factory-fitted with the following manifolds: • Valve manifolds 7MF9411-5BA: Three valve manifold for differential pressure transmitter • Valve manifolds 7MF9411-5CA: Three valve manifold for differential pressure transmitter The 7MF9411-5BA and 7MF9411-5CA manifolds are sealed with PTFE sealing rings between the transmitter and the manifold. Once installed, the complete unit is checked under pressure for leaks (compressed air 6 bar (2411 inH2O)) and is certified leakproof with a test report to EN 10204 - 2.2. All manifolds should preferably be secured with the respective mounting brackets. The transmitters are mounted on the manifold and not on the unit itself. If you order a mounting bracket when choosing the option "Factory mounting of manifolds", you will receive a mounting bracket for the manifold instead of a bracket for mounting the transmitter. If you order an acceptance test certificate 3.1 to EN10204 when choosing the option "Factory mounting of manifolds", a separate certificate is provided for the transmitters and the manifolds respectively. ■ Selection and ordering Data Manifold 7MF9411-5BA on SITRANS P pressure transmitter P500 for differential pressure and flow Add -Z to the Article No. of the transmitter and add Order codes Order code Manifold 7MF9411-5CA on SITRANS P500 pressure transmitter for differential pressure and flow Add -Z to the Article No. of the transmitter and add Order codes SITRANS P500 7MF54..-... SITRANS P500 7MF54..-... mounted with gaskets made of PTFE and screws made of mounted with gaskets made of PTFE and screws made of • Chromized steel • Stainless steel Order code U01 • Chromized steel U03 U02 • Stainless steel U04 Delivery incl. high-pressure test certified by factory certificate to EN10204-2.2 Delivery incl. high-pressure test certified by factory certificate to EN10204-2.2 Further designs: Further designs: Delivery includes mounting bracket and mounting clips made of Delivery includes mounting bracket and mounting clips made of • Steel A01 • Steel A01 • Stainless steel A02 • Stainless steel A02 (instead of the mounting bracket supplied with the transmitter) (instead of the mounting bracket supplied with the transmitter) Supplied acceptance test certificate to EN10204-3.1 for transmitters and mounted valve manifold C12 Supplied acceptance test certificate to EN10204-3.1 for transmitters and mounted valve manifold Siemens FI 01 · 2015 US Edition C12 1/203 1 © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 Factory-mounting of valve manifolds on transmitters ■ Dimensional drawings Manifold 7MF9411-5BA with attached SITRANS P500 pressure transmitter for differential pressure and flow (incl. mounting bracket) 160 (6.3) 1 0 R3 18) . (1 232 (9.13) 215 (8.46) Manifold 7MF9411-5BA with attached SITRANS P500 pressure transmitter for differential pressure and flow, measurements in mm (inch) 1/204 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for High Performance requirements SITRANS P500 Factory-mounting of valve manifolds on transmitters Manifold 7MF9411-5CA with attached SITRANS P500 pressure transmitter for differential pressure and flow (incl. mounting bracket) R (1 30 .1 8) 158 (6.22) 256 (10.1) 233 (9.17) Manifold 7MF9411-5CA with attached SITRANS P500 pressure transmitter for differential pressure and flow, measurements in mm (inch) Siemens FI 01 · 2015 US Edition 1/205 1