PDF Datasheet

Datasheet
SPD II 1 – Surge Protectors for AC Power Distribution
SPD II PV – Surge Protectors for Photovoltaic Installations
Weidmuller’s SPD II 1 series transient voltage surge protectors
consist of a range of innovative, compact modules for the
protection of low voltage AC distribution systems or (PV models)
for DC photovoltaic installations. In AC applications, the SPD II 1
would be installed downstream of the main circuit breaker and
fuse(s), connected between each live conductor to be protected
and ground. For multi-phase circuits, multiple modules are used
with jumper options between ground terminals and permitting
a single connection to ground. In photovoltaic applications,
the SPD II 1 PV would typically be in a combiner enclosure
protecting the DC output and return conductor to ground.
Voltage limiting technology is integrated, which differentiates
between transient pulses and longer-lasting overvoltages. This
circuitry eliminates the disadvantages of varistor devices (MOVs)
which, in competitive products, may switch-on inadvertently
in conditions where the supply voltage is not well-regulated.
Weidmuller’s hybrid arrester design ensures efficient MOV
operation and hence conserves energy, maximizes the operating
lifetime of the arrester and eliminates arcing when the thermal
disconnect operates.
Each module is a two-part construction, comprising a TS35 DINrail mountable base and a pluggable replaceable arrester, with
each single-conductor assembly only 18mm wide. Products are
specified by their working voltage level, or maximum continuous
operating voltage (MCOV) and each has a maximum surge
current rating of 50kA.
Base/arrester assemblies are available either with or without a
remote signaling option and arresters are available as spare parts.
• Models for LV AC distribution or photovoltaic installations
• Quick replacement with spare pluggable, replaceable arresters
• Nominal voltages up to 480VAC (550V MCOV) or 1200VDC
• Maximum surge current (Imax) 50kA
• Remote status signaling option
• UL1449 Ed3 approved and CSA equivalent
• No discharge path fuse needed (Type 2)
C
Weidmuller, Canada
10 Spy Court
Markham, Ontario L3R 5H6
Telephone: (800) 268-4080
Facsimile: (877) 300-5635
Email: [email protected]
Website: www.weidmuller.ca
Weidmuller, Mexico
Blvd. Hermanos Serdán 698,
Col. San Rafael Oriente
Puebla, Puebla, Mexico
C.P. 72029
Telephone: 01 222 2686267
Facsimile: 01 222 2686219
Email: [email protected]
Website: www.weidmuller.com.mx
Weidmuller, United States
821 Southlake Blvd.
Richmond, Virginia 23236
Telephone: (800) 849-9343
Facsimile: (804) 379-2593
Email: [email protected]
Website: www.weidmuller.com
US
SPD II AC Surge Protectors
For transient voltage protection of
single and multi-phase circuits, in the
main electrical panel, downstream
of the main circuit breaker, or in
control panels.
SPD II 0 150V/40kA
SPD II 1 150V/40kA
SPD II 1 R 150V/40kA
SPD II 0 280V/40KA
SPD II 1 280V/40KA
SPD II 1 R 280V/40KA
R model shown
Technical Data
R model shown
AC Network
120 V, Single phase
230 V, Single phase
Connection Mode
1 Pole, L-N or L-G.
1 Pole, L-N or L-G.
Max. Operating Voltage (MCOV)
150 VAC
277 VAC
Leakage Current at Uc
<1mA
<1mA
Follow Current
None
None
UL 1449 Category
Type 2
Type 2
UL Nominal Discharge Current (In),
15 Impulses 8/20 us
20 kA
20 kA
Max. Discharge Current (Imax),
1 Impulse 8/20 us
50 kA
50 kA
UL Voltage Protection Rating (VPR)
1.2 kV
1.6 kV
Protection Level (Up)
≤ 1200 V
≤ 1600 V
UL Short-Circuit Current Rating (SCCR)
200 kA
200 kA
Sparkover time / Drop-out time
<100 ns
<100 ns
Overcurrent Protection
No fuse required in discharge circuit
No fuse required in discharge circuit
Connection (network)
Screw connections (2 - 14AWG)
Screw connections (2 - 14AWG)
Remote Signal Option (Contact Rating)
250 V / 0,5 A, 48 VDC /0,1 A
250 V / 0,5 A, 48 VDC /0,1 A
Mounting
DIN-rail, TS 35
DIN-rail, TS 35
Operating Temp
-40°C...+70°C
-40°C...+70°C
Operating Altitude (Max.)
2,000m
2,000m
Relative Humidity
0 - 95% non-condensing
0 - 95% non-condensing
Enclosure Material
Thermoplastic UL94-V0
Thermoplastic UL94-V0
Environmental Rating
IP 20
IP 20
Weight (g) and Dimensions (mm)
SPD II 0
SPD II 1
SPD II 1 R
66 g; 18W x 45H x 60D
138 g; 18W x 90H x 73.5D
142 g; 18W x 100H x 73.5D
66 g; 18W x 45H x 60D
140 g; 18W x 90H x 73.5D
142 g; 18W x 100H x 73.5D
UL File E354261, Type 2 UL1449 Ed. 3, CSA
Electrical Notice No. 516
UL File E354261, Type 2 UL1449 Ed. 3, CSA
Electrical Notice No. 516
Surge Protector
Spare arrester 120V nom.
Type
SPD II 0 150V/40kA
Type
—
Spare arrester 230V nom.
—
—
SPD II 0 280V/40kA
1348370000
SPD assembly w/o relay
SPD II 1 150V/40kA
1348340000
SPD II 1 280V/40kA
1348380000
SPD assembly with relay
SPD II 1 R 150V/40kA.
1348350000
SPD II 1 R 280V/40kA.
1348390000
Bus bars
2-pole jumper
Type
QB 18-2
Part No.
8877540000
Type
QB 18-2
Part No.
8877540000
3-pole jumper
QB 18-3
8877500000
QB 18-3
8877500000
4-pole jumper
QB 18-4
8877520000
QB 18-4
8877520000
Approvals
UL 1449 (USA and CANADA)
C
US
Ordering Data
73
9
Part No.
1348330000
Part No.
—
18
90.5
2
Dimensions
Electrical Function
2-, 3- and 4-pole Jumpers
SPD II AC Surge Protectors
For transient voltage protection of
single and multi-phase circuits, in the
main electrical panel, downstream
of the main circuit breaker, or in
control panels.
SPD II 0 400V/40KA
SPD II 1 400V/40KA
SPD II 1 R 400V/40KA
SPD II 0 550V/40kA
SPD II 1 550V/40kA
SPD II 1 R 550V/40kA
R model shown
Technical Data
R model shown
AC Network
277/347 V, Single phase
480 V, Single phase
Connection Mode
1 Pole, L-N or L-G.
1 Pole, L-N or L-G.
Max. Operating Voltage (MCOV)
385 VAC
550 VAC
Leakage Current at Uc
<1mA
<1mA
Follow Current·
None
None
UL Category
Type 2
Type 2
UL Nominal Discharge Current (In),
15 Impulses 8/20 us
20 kA
20 kA
Max. Discharge Current (Imax),
1 Impulse 8/20 us
UL Voltage Protection Rating (VPR)
50 kA
50 kA
1.8 kV
2.5 kV
Protection Level (Up)
≤ 1800 V
≤ 2500 V
UL Short-Circuit Current Rating (SCCR)
200 kA
200 kA
Sparkover time / Drop-out time
<100 ns
<100 ns
Overcurrent Protection
No fuse required in discharge circuit
No fuse required in discharge circuit
Connection (network)
Screw connections (2 - 14AWG)
Screw connections (2 - 14AWG)
Remote Signal (Contact Rating)
250 V / 0,5 A, 48 VDC /0,1 A
250 V / 0,5 A, 48 VDC /0,1 A
Mounting
DIN-rail, TS 35
DIN-rail, TS 35
Operating Temp
-40°C...+70°C
-40°C...+70°C
Operating Altitude (Max.)
2,000m
2,000m
Relative Humidity
0 - 95% non-condensing
0 - 95% non-condensing
Enclosure Material
Thermoplastic UL94-V0
Thermoplastic UL94-V0
Environmental Rating
IP 20
IP 20
Weight (g) and Dimensions (mm)
SPD II 0
SPD II 1
SPD II 1 R
66 g; 18W x 45H x 60D
138 g; 18W x 90H x 73.5D
150 g; 18W x 100H x 73.5D
66 g; 18W x 45H x 60D
138 g; 18W x 90H x 73.5D
150 g; 18W x 100H x 73.5D
UL File E354261, Type 2 UL1449 Ed. 3, CSA
Electrical Notice No. 516
UL File E354261, Type 2 UL1449 Ed. 3, CSA
Electrical Notice No. 516
Type
SPD II 0 400V/40kA
Type
—
Approvals
UL 1449 (USA and CANADA)
C
US
Ordering Data
Surge Protector
Spare arrester 277V nom.
Part No.
1348400000
Part No.
—
Spare arrester 440/480V nom.
—
—
SPD II 0 550V/40kA
1348440000
SPD assembly w/o relay
SPD II 1 400V/40kA
1348420000
SPD II 1 550V/40kA
1348450000
SPD assembly with relay
SPD II 1 R 400V/40kA.
1348430000
SPD II 1 R 550V/40kA.
1348470000
Bus bars
2-pole jumper
Type
QB 18-2
Part No.
8877540000
Type
QB 18-2
Part No.
8877540000
3-pole jumper
QB 18-3
8877500000
QB 18-3
8877500000
4-pole jumper
QB 18-4
8877520000
QB 18-4
8877520000
73
9
18
90.5
Dimensions
Electrical Function
2-, 3- and 4-pole Jumpers
3
SPD II AC Surge Protectors
Basic AC configurations 1 (with remote signaling options)
L/N
L/N
TF
L/N
TF
L1
TF
TF
L2
TF
L3
TF
SPD parts needed:
Nom. V
Description
Qty
Qty
Qty
110/120V
SPD II 150V/40kA
1
2
3
1348350000
Part No.
230/240V
SPD II 280V/40kA
1
2
3
1348390000
277V
SPD II 400V/40kA
1
2
3
1348430000
480V
SPD II 550V/40kA
1
2
3
1348470000
All
QB18-2
0
1
0
8877540000
All
QB18-3
0
0
1
8877500000
Basic AC configurations 2 (with remote signaling options)
L1
L2
TF
TF
L3
N
TF
TF
SPD parts needed:
Nom. V
Description
110/120V
SPD II 1 R 150V/40kA
Qty
4
1348350000
Part No.
230/240V
SPD II 1 R 280V/40kA
4
1348390000
277V
SPD II 1 R 400V/40kA
4
1348430000
480V
SPD II 1 R 550V/40kA
4
1348470000
All
QB 18-4
1
8877520000
4
SPD II DC Surge Protectors
For use on the DC side of
SPD II 0 PV 600VDC
SPD II 2 PV 600VDC
photovoltaic installations,
SPD II 2 R PV 600VDC
typically in a combiner
enclosure, protecting the DC
output and return conductor
to the ground.
Technical Data
SPD II 0 PV 1000VDC
SPD II 2 PV 1000VDC
SPD II 2 R PV 1000VDC
R model shown
SPD II 0 PV 1200VDC
SPD II 3 PV 1200VDC
SPD II 3 R PV 1200VDC
R model shown
R model shown
DC Network
600 VDC
1000 VDC
1200 VDC
Connection Mode
Screw connection
Screw connection
Screw connection
Max. Operating Voltage (MCOV)
550 VDC
1000 VDC
1200 VDC
Leakage Current at Uc
<1mA
<1mA
<1mA
UL Category
Type 2
Type 2
Type 2
UL Nominal Discharge Current (In),
5 Impulses 8/20 us
20 kA
20 kA
20 kA
Max. Discharge Current (Imax),
1 Impulse 8/20 us
50 kA
50 kA
50 kA
UL Voltage Protection Rating (VPR)
2 kV
4 kV
4 kV
Protection Level (Up)
≤ 2000 V
≤ 4000 V
≤ 4000 V
UL Short-Circuit Current Rating (SCCR)
200 kA
200 kA
200 kA
Sparkover time / Drop-out time
<100 ns
<100 ns
<100 ns
Overcurrent Protection
No fuse required in discharge circuit
No fuse required in discharge circuit
No fuse required in discharge circuit
Connection (network)
Screw connection, pluggable
Screw connection, pluggable
Screw connection, pluggable
Remote Signal (Contact Rating)
250 V / 0,5 A, 48 VDC /0,1 A
250 V / 0,5 A, 48 VDC /0,1 A
250 V / 0,5 A, 48 VDC /0,1 A
Mounting
DIN-rail, TS 35, TS 35 x 15, TS 35 x 7.5
DIN-rail, TS 35, TS 35 x 15, TS 35 x 7.5
DIN-rail, TS 35, TS 35 x 15, TS 35 x 7.5
Operating Temp
-40°C...+70°C
-40°C...+70°C
-40°C...+70°C
Operating Altitude (Max.)
2000m
2000m
2000m
Relative Humidity
0 - 95% non-condensing
0 - 95% non-condensing
0 - 95% non-condensing
Enclosure Material
Thermoplastic UL94-V0
Thermoplastic UL94-V0
Thermoplastic UL94-V0
Environmental Rating
IP 20
IP 20
IP 20
Weight (g)
274
292
402
Dimensions (mm)
36W x 100H x 73.5D
36W x 100H x 73.5D
54W x 100H x 73.5D
UL File E354261, Type 2 UL1449
Ed. 3, CSA Electrical Notice No. 516
UL File E354261, Type 2 UL1449
Ed. 3, CSA Electrical Notice No. 516
UL File E354261, Type 2 UL1449
Ed. 3, CSA Electrical Notice No. 516
Surge Protector
Type
Type
Spare arrester 600V nom.
SPD II 0 PV 600VDC
Spare arrester 1000V nom.
—
—
SPD II 0 PV 1000VDC
Spare arrester 1200V nom.
—
—
—
PV SPD assembly w/o relay
SPD II 2 PV 600VDC
PV SPD assembly with relay
SPD II 2 R PV 600VDC 1348430000
Approvals
UL 1449 (USA and CANADA)
C
US
Ordering Data
73
9
36
54
SPD II 2 PV
SPD II 3 PV
Part No.
1348520000
1348540000
—
SPD II 2 PV 1000VDC
Part No.
Type
—
—
1348480000
—
—
—
SPD II 0 PV 1200VDC
1348550000
1348490000
SPD II 3 PV 1200VDC
1348570000
SPD II 2 R PV 1000VDC 1348500000
SPD II 3 R PV 1200VDC 1348580000
90.5
Dimensions
5
Electrical Function
PSPD II 2 R PV
Part No.
—
Electrical Function
PSPD II 3 PV
SPD II Surge Protectors
6
Subject to technical changes · 05/13 ·1M · LIT1308
SPD II DC Surge Protectors
SPD II Surge Protectors
For use on the DC side of
SPD II 0 PV 600VDC
SPD II 2 PV 600VDC
photovoltaic installations,
SPD II 2 R PV 600VDC
typically in a combiner
enclosure, protecting the DC
output and return conductor
to the ground.
TRIM
Technical Data
SPD II 0 PV 1000VDC
SPD II 2 PV 1000VDC
SPD II 2 R PV 1000VDC
SPD II 0 PV 1200VDC
SPD II 3 PV 1200VDC
SPD II 3 R PV 1200VDC
Datasheet
SPD II 1 – Surge Protectors for AC Power Distribution
SPD II PV – Surge Protectors for Photovoltaic Installations
R model shown
R model shown
Weidmuller’s SPD II 1 series transient voltage surge protectors
consist of a range of innovative, compact modules for the
protection of low voltage AC distribution systems or (PV models)
for DC photovoltaic installations. In AC applications, the SPD II 1
would be installed downstream of the main circuit breaker and
fuse(s), connected between each live conductor to be protected
and ground. For multi-phase circuits, multiple modules are used
with jumper options between ground terminals and permitting
a single connection to ground. In photovoltaic applications,
the SPD II 1 PV would typically be in a combiner enclosure
protecting the DC output and return conductor to ground.
R model shown
DC Network
600 VDC
1000 VDC
1200 VDC
Connection Mode
Screw connection
Screw connection
Screw connection
Max. Operating Voltage (MCOV)
550 VDC
1000 VDC
1200 VDC
Leakage Current at Uc
<1mA
<1mA
<1mA
UL Category
Type 2
Type 2
Type 2
UL Nominal Discharge Current (In),
5 Impulses 8/20 us
20 kA
20 kA
20 kA
Max. Discharge Current (Imax),
1 Impulse 8/20 us
50 kA
50 kA
50 kA
UL Voltage Protection Rating (VPR)
2 kV
4 kV
4 kV
Protection Level (Up)
≤ 2000 V
≤ 4000 V
≤ 4000 V
UL Short-Circuit Current Rating (SCCR)
200 kA
200 kA
200 kA
Sparkover time / Drop-out time
<100 ns
<100 ns
<100 ns
Overcurrent Protection
No fuse required in discharge circuit
No fuse required in discharge circuit
No fuse required in discharge circuit
Connection (network)
Screw connection, pluggable
Screw connection, pluggable
Screw connection, pluggable
Remote Signal (Contact Rating)
250 V / 0,5 A, 48 VDC /0,1 A
250 V / 0,5 A, 48 VDC /0,1 A
250 V / 0,5 A, 48 VDC /0,1 A
Mounting
DIN-rail, TS 35, TS 35 x 15, TS 35 x 7.5
DIN-rail, TS 35, TS 35 x 15, TS 35 x 7.5
DIN-rail, TS 35, TS 35 x 15, TS 35 x 7.5
Operating Temp
-40°C...+70°C
-40°C...+70°C
-40°C...+70°C
Operating Altitude (Max.)
2000m
2000m
2000m
Relative Humidity
0 - 95% non-condensing
0 - 95% non-condensing
0 - 95% non-condensing
Enclosure Material
Thermoplastic UL94-V0
Thermoplastic UL94-V0
Thermoplastic UL94-V0
Environmental Rating
IP 20
IP 20
IP 20
Weight (g)
274
292
402
Dimensions (mm)
36W x 100H x 73.5D
36W x 100H x 73.5D
54W x 100H x 73.5D
UL File E354261, Type 2 UL1449
Ed. 3, CSA Electrical Notice No. 516
UL File E354261, Type 2 UL1449
Ed. 3, CSA Electrical Notice No. 516
UL File E354261, Type 2 UL1449
Ed. 3, CSA Electrical Notice No. 516
Surge Protector
Type
Type
Spare arrester 600V nom.
SPD II 0 PV 600VDC
Voltage limiting technology is integrated, which differentiates
between transient pulses and longer-lasting overvoltages. This
circuitry eliminates the disadvantages of varistor devices (MOVs)
which, in competitive products, may switch-on inadvertently
in conditions where the supply voltage is not well-regulated.
Weidmuller’s hybrid arrester design ensures efficient MOV
operation and hence conserves energy, maximizes the operating
lifetime of the arrester and eliminates arcing when the thermal
disconnect operates.
Each module is a two-part construction, comprising a TS35 DINrail mountable base and a pluggable replaceable arrester, with
each single-conductor assembly only 18mm wide. Products are
specified by their working voltage level, or maximum continuous
operating voltage (MCOV) and each has a maximum surge
current rating of 50kA.
Base/arrester assemblies are available either with or without a
remote signaling option and arresters are available as spare parts.
• Models for LV AC distribution or photovoltaic installations
• Quick replacement with spare pluggable, replaceable arresters
• Nominal voltages up to 480VAC (550V MCOV) or 1200VDC
• Maximum surge current (Imax) 50kA
• Remote status signaling option
• UL1449 Ed3 approved and CSA equivalent
• No discharge path fuse needed (Type 2)
Approvals
UL 1449 (USA and CANADA)
C
US
Ordering Data
Part No.
1348520000
—
Spare arrester 1000V nom.
—
—
SPD II 0 PV 1000VDC
Spare arrester 1200V nom.
—
—
—
PV SPD assembly w/o relay
SPD II 2 PV 600VDC
PV SPD assembly with relay
SPD II 2 R PV 600VDC 1348430000
73
9
36
54
SPD II 2 PV
SPD II 3 PV
1348540000
SPD II 2 PV 1000VDC
Part No.
—
1348480000
Type
Part No.
—
—
—
—
—
SPD II 0 PV 1200VDC
1348550000
1348490000
SPD II 3 PV 1200VDC
1348570000
SPD II 2 R PV 1000VDC 1348500000
C
SPD II 3 R PV 1200VDC 1348580000
Weidmuller, Canada
10 Spy Court
Markham, Ontario L3R 5H6
Telephone: (800) 268-4080
Facsimile: (877) 300-5635
Email: [email protected]
Website: www.weidmuller.ca
90.5
Dimensions
5
Electrical Function
PSPD II 2 R PV
Electrical Function
PSPD II 3 PV
6
Subject to technical changes · 05/13 ·1M · LIT1308
Weidmuller, Mexico
Blvd. Hermanos Serdán 698,
Col. San Rafael Oriente
Puebla, Puebla, Mexico
C.P. 72029
Telephone: 01 222 2686267
Facsimile: 01 222 2686219
Email: [email protected]
Website: www.weidmuller.com.mx
Weidmuller, United States
821 Southlake Blvd.
Richmond, Virginia 23236
Telephone: (800) 849-9343
Facsimile: (804) 379-2593
Email: [email protected]
Website: www.weidmuller.com
US
SPD II AC Surge Protectors
SPD II AC Surge Protectors
For transient voltage protection of
single and multi-phase circuits, in the
main electrical panel, downstream
of the main circuit breaker, or in
control panels.
SPD II 0 150V/40kA
SPD II 1 150V/40kA
SPD II 1 R 150V/40kA
SPD II 0 280V/40KA
SPD II 1 280V/40KA
SPD II 1 R 280V/40KA
For transient voltage protection of
single and multi-phase circuits, in the
main electrical panel, downstream
of the main circuit breaker, or in
control panels.
SPD II 0 400V/40KA
SPD II 1 400V/40KA
SPD II 1 R 400V/40KA
SPD II 0 550V/40kA
SPD II 1 550V/40kA
SPD II 1 R 550V/40kA
SPD II AC Surge Protectors
Basic AC configurations 1 (with remote signaling options)
L/N
L/N
TF
R model shown
Technical Data
R model shown
R model shown
Technical Data
120 V, Single phase
230 V, Single phase
AC Network
277/347 V, Single phase
480 V, Single phase
Connection Mode
1 Pole, L-N or L-G.
1 Pole, L-N or L-G.
Connection Mode
1 Pole, L-N or L-G.
1 Pole, L-N or L-G.
Max. Operating Voltage (MCOV)
150 VAC
277 VAC
Max. Operating Voltage (MCOV)
385 VAC
550 VAC
Leakage Current at Uc
<1mA
<1mA
Leakage Current at Uc
<1mA
<1mA
Follow Current
None
None
Follow Current·
None
None
UL 1449 Category
Type 2
Type 2
UL Category
Type 2
Type 2
UL Nominal Discharge Current (In),
15 Impulses 8/20 us
20 kA
20 kA
UL Nominal Discharge Current (In),
15 Impulses 8/20 us
20 kA
20 kA
Max. Discharge Current (Imax),
1 Impulse 8/20 us
50 kA
50 kA
50 kA
50 kA
UL Voltage Protection Rating (VPR)
1.2 kV
Max. Discharge Current (Imax),
1 Impulse 8/20 us
UL Voltage Protection Rating (VPR)
1.8 kV
Description
Qty
Qty
Qty
SPD II 150V/40kA
1
2
3
1348350000
230/240V
SPD II 280V/40kA
1
2
3
1348390000
277V
SPD II 400V/40kA
1
2
3
1348430000
2.5 kV
480V
SPD II 550V/40kA
1
2
3
1348470000
QB18-2
0
1
0
8877540000
QB18-3
0
0
1
8877500000
≤ 1600 V
Protection Level (Up)
≤ 1800 V
≤ 2500 V
UL Short-Circuit Current Rating (SCCR)
200 kA
200 kA
UL Short-Circuit Current Rating (SCCR)
200 kA
200 kA
All
Sparkover time / Drop-out time
<100 ns
<100 ns
Sparkover time / Drop-out time
<100 ns
<100 ns
Overcurrent Protection
No fuse required in discharge circuit
No fuse required in discharge circuit
Overcurrent Protection
No fuse required in discharge circuit
No fuse required in discharge circuit
Screw connections (2 - 14AWG)
Connection (network)
Screw connections (2 - 14AWG)
Screw connections (2 - 14AWG)
250 V / 0,5 A, 48 VDC /0,1 A
250 V / 0,5 A, 48 VDC /0,1 A
Remote Signal Option (Contact Rating)
250 V / 0,5 A, 48 VDC /0,1 A
250 V / 0,5 A, 48 VDC /0,1 A
Mounting
DIN-rail, TS 35
DIN-rail, TS 35
Mounting
DIN-rail, TS 35
DIN-rail, TS 35
Operating Temp
-40°C...+70°C
-40°C...+70°C
Operating Temp
-40°C...+70°C
-40°C...+70°C
Operating Altitude (Max.)
2,000m
2,000m
Operating Altitude (Max.)
2,000m
2,000m
Relative Humidity
0 - 95% non-condensing
0 - 95% non-condensing
Relative Humidity
0 - 95% non-condensing
0 - 95% non-condensing
Enclosure Material
Thermoplastic UL94-V0
Thermoplastic UL94-V0
Enclosure Material
Thermoplastic UL94-V0
Thermoplastic UL94-V0
Environmental Rating
IP 20
IP 20
Environmental Rating
IP 20
IP 20
66 g; 18W x 45H x 60D
138 g; 18W x 90H x 73.5D
142 g; 18W x 100H x 73.5D
66 g; 18W x 45H x 60D
140 g; 18W x 90H x 73.5D
142 g; 18W x 100H x 73.5D
Weight (g) and Dimensions (mm)
SPD II 0
SPD II 1
SPD II 1 R
66 g; 18W x 45H x 60D
138 g; 18W x 90H x 73.5D
150 g; 18W x 100H x 73.5D
66 g; 18W x 45H x 60D
138 g; 18W x 90H x 73.5D
150 g; 18W x 100H x 73.5D
UL File E354261, Type 2 UL1449 Ed. 3, CSA
Electrical Notice No. 516
UL File E354261, Type 2 UL1449 Ed. 3, CSA
Electrical Notice No. 516
UL File E354261, Type 2 UL1449 Ed. 3, CSA
Electrical Notice No. 516
UL File E354261, Type 2 UL1449 Ed. 3, CSA
Electrical Notice No. 516
Type
SPD II 0 400V/40kA
Type
—
C
US
Approvals
UL 1449 (USA and CANADA)
C
US
Type
—
Part No.
—
Part No.
1348400000
Spare arrester 230V nom.
—
—
SPD II 0 280V/40kA
1348370000
Spare arrester 440/480V nom.
—
—
SPD II 0 550V/40kA
SPD assembly w/o relay
SPD II 1 150V/40kA
1348340000
SPD II 1 280V/40kA
1348380000
SPD assembly w/o relay
SPD II 1 400V/40kA
1348420000
SPD II 1 550V/40kA
SPD assembly with relay
SPD II 1 R 150V/40kA.
1348350000
SPD II 1 R 280V/40kA.
1348390000
SPD assembly with relay
SPD II 1 R 400V/40kA.
1348430000
Bus bars
2-pole jumper
Type
QB 18-2
Part No.
8877540000
Type
QB 18-2
Part No.
8877540000
Bus bars
2-pole jumper
Type
QB 18-2
Part No.
8877540000
3-pole jumper
QB 18-3
8877500000
QB 18-3
8877500000
3-pole jumper
QB 18-3
4-pole jumper
QB 18-4
8877520000
QB 18-4
8877520000
4-pole jumper
QB 18-4
18
73
90.5
2
Dimensions
9
L2
TF
Part No.
—
Type
SPD II 0 150V/40kA
9
Part No.
1348330000
Surge Protector
Spare arrester 277V nom.
Surge Protector
Spare arrester 120V nom.
73
L1
Ordering Data
Ordering Data
L3
TF
Part No.
Basic AC configurations 2 (with remote signaling options)
Remote Signal (Contact Rating)
Approvals
UL 1449 (USA and CANADA)
TF
110/120V
≤ 1200 V
Weight (g) and Dimensions (mm)
SPD II 0
SPD II 1
SPD II 1 R
TF
Nom. V
Protection Level (Up)
Screw connections (2 - 14AWG)
TF
L2
SPD parts needed:
All
Connection (network)
TF
L1
R model shown
AC Network
1.6 kV
L/N
TF
L3
N
TF
TF
SPD parts needed:
Nom. V
Description
1348440000
110/120V
SPD II 1 R 150V/40kA
Qty
4
1348350000
Part No.
1348450000
230/240V
SPD II 1 R 280V/40kA
4
1348390000
SPD II 1 R 550V/40kA.
1348470000
277V
SPD II 1 R 400V/40kA
4
1348430000
Type
QB 18-2
Part No.
8877540000
480V
SPD II 1 R 550V/40kA
4
1348470000
8877500000
QB 18-3
8877500000
All
QB 18-4
1
8877520000
8877520000
QB 18-4
8877520000
18
90.5
Electrical Function
2-, 3- and 4-pole Jumpers
Dimensions
Electrical Function
2-, 3- and 4-pole Jumpers
3
4