Download

DeviceNet Communications Unit
E5ZN-DRT
CSM_E5ZN-DRT_DS_E_3_2
Streamlined Communications from
Temperature Controller to PLC
• The E5ZN Modular Temperature Controller is connected to
the DeviceNet network.
• The I/O link function allows setting and monitoring (e.g., of
present values) for the E5ZN Modular Temperature Controller to
be performed without communications programming.
• Up to 16 E5ZN Modular Temperature Controllers can be connected to one Unit.
• All the parameters for the E5ZN can be uploaded or downloaded in one operation using DeviceNet Configurator.
Refer to Safety Precautions for All
Temperature Controllers.
Features
DeviceNet Communications Unit Enables Program-free Communications with Temperature
Controllers
DeviceNet
Master
DeviceNet
Configurator
Connect up to 16 E5ZN.
Modular Temperature Controller
E5ZN
DeviceNet Communications Unit
E5ZN-DRT
Setting Display Unit
E5ZN-SDL
Operational performance equivalent to
E5CN Digital Temperature Controllers.
1
E5ZN-DRT
Features
Startup Time Is Six Times Faster and No Communications Programs Are Needed
Previously, a time-consuming process of creating
communications programs, debugging, and checking
operations was required for the Temperature Controller to
communicate with the PLC.
● For example, setting 10 Units required 60 minutes.
● Incorrect inputs were a concern.
● Separate debugging for each Unit was needed.
No-protocol Example
DeviceNet Communications Units enable high-speed data
communications by allocating settings and monitoring
parameters in the PLCs I/O Memory Area, contributing to greater
reductions in the time required for communications program
development.
● For example, set 10 Units in 10 minutes.
● Batch download using the personal computer.
● Debugging is easy using the personal computer.
Trigger
ASC
DM000
K
Sd
← Converts SP data into ASCII.
PLC Memory
Trigger
FSC
C
S
Sf
← Calculates FSC.
TDX
S
C
N
← Sends command.
RXD
D
C
N
← Receives response.
OUT Area
IN Area
Trigger Send Ready Flag
NG
Wd 0 and 1
Receive Completion Flag
Beep
Receive Completion Flag
CMP
De
#3030
Beep
← Checks end code.
Wd 2 and 3
Wd 4 and 5
Wd 6 to 37
OUT enabled
Control ON/OFF
AT executing
Set value (SV)
Wd 0 and 1
Wd 2 and 3
Wd 4 and 5
Wd 6 and 7
Normal completion
Wd 38
D
'f
Receive Completion Flag
Beep
FCS
C
D
D'f
← Checks FCS.
CMP
Df
D'f
Wd 98
Wd 8 to 37
User-specified
allocations
are possible.
Wd 38
Wd 99
FCS check OK
User-specified
allocations
are possible.
Wd 98
Wd 100
Comm status
Control ON/OFF
AT executing
Alarm output
Process value (PV)
Wd 99
Wd 100
Manage All E5ZN Together from the DeviceNet Configurator
Use the DeviceNet Configurator for E5ZN
initial settings and temperature control wiring
to enable immediate execution.
Improved Maintenance with Monitoring, Comment, and Copying Functions
● Measure the heater control time (RUN
time monitor) to manage heater life
expectancy.
● Monitor supply voltages, such as those
for Temperature Controller and
Communications Unit power supplies,
and network power supplies.
● User-specified names can be set for
each heater and Communications Unit,
enabling the location of errors to be
checked quickly.
● Upload/download Temperature Controller
parameters to the Communications Unit.
This shortens the time required to
Check the actual
operating time
of the heater.
Maintenance data
DeviceNet
Master
Control data
Check the settings
for the heater of
oven No. 3.
UNIT
UNIT
UNIT
UNIT
UNIT
UNIT
UNIT
UNIT
BPS
BPS
BPS
BPS
BPS
BPS
BPS
BPS
POWER
POWER
POWER
POWER
POWER
POWER
POWER
ERROR
ERROR
ERROR
ERROR
ERROR
ERROR
ERROR
SD/RD
SD/RD
SD/RD
SD/RD
SD/RD
SD/RD
SD/RD
OUT 1
OUT 1
OUT 1
OUT 1
OUT1
OUT1
OUT1
OUT2
OUT2
OUT2
OUT2
OUT2
OUT2
OUT2
SUB 1
SUB 1
SUB 1
SUB 1
SUB 1
SUB 1
SUB 1
SUB2
SUB2
E5ZN
E5ZN
UNIT
UNIT
SUB2
E5ZN
UNIT
BPS
BPS
SUB2
E5ZN
UNIT
BPS
SUB2
E5ZN
UNIT
BPS
UNIT
UNIT
BPS
SUB2
E5ZN
E5ZN
UNIT
BPS
BPS
POWER
ERROR
SD/RD
OUT 1
OUT2
SUB 1
SUB2
E5ZN
SUB2
E5ZN
UNIT
BPS
E5ZN
UNIT
BPS
BPS
POWER
POWER
POWER
POWER
POWER
POWER
POWER
POWER
POWER
POWER
ERROR
ERROR
ERROR
ERROR
ERROR
ERROR
ERROR
ERROR
ERROR
ERROR
SD/RD
SD/RD
SD/RD
SD/RD
SD/RD
SD/RD
SD/RD
SD/RD
SD/RD
OUT 1
OUT 1
OUT 1
OUT 1
OUT 1
OUT2
OUT2
OUT2
OUT2
OUT2
SUB 1
SUB 1
SUB 1
SUB 1
SUB 1
SUB2
SUB2
SUB2
SUB2
SUB2
E5ZN
E5ZN
E5ZN
E5ZN
E5ZN-SCT24S
E5ZN-SCT24S
replace Temperature Controllers.
DeviceNet
Configurator
E5ZN
OUT 1
OUT 1
OUT1
OUT 1
OUT2
OUT2
OUT2
OUT2
SUB 1
SUB 1
SUB 1
SUB 1
SUB2
SUB2
SUB2
SUB2
E5ZN
E5ZN
E5ZN
SD/RD
OUT 1
OUT2
SUB 1
SUB2
E5ZN
E5ZN
2
E5ZN-DRT
Model Number Structure
■ Model Number Legend
1.
E5ZN-DRT
DRT: DeviceNet communications
1
Ordering Information
■ List of Models
Name
External input power
supply voltage
DeviceNet Communications Unit 24 VDC
Applicable Temperature
Controller
E5ZN
Model
E5ZN-DRT
Terminal Unit
E5ZN-SCT24S
Note: A DeviceNet Communications Unit and Terminal Unit are required to connect to DeviceNet. Two End Plates are provided with E5ZN-SCT24S
Terminal Units. When mounting to a DIN track, be sure to mount End Plates on both sides.
Specifications
■ Ratings
Power supply voltage
Allowable voltage range
Power consumption
(See note 2.)
DeviceNet
24 VDC (for internal circuits)
External input power supply
24 VDC (for RS-485 communications circuits and Temperature Controllers)
DeviceNet
11 to 25 VDC
External input power supply
20.4 to 26.4 VDC
DeviceNet
Approx. 1.1 W (for a current of 45 mA at 24 VDC)
External input power supply
Approx. 0.5 W (for a current of 20 mA at 24 VDC)
Connectable Temperature Controllers
E5ZN Series
Maximum number of connectable Temperature Controllers 16
Ambient operating temperature
−10 to 55°C (with no icing or condensation)
Ambient operating humidity
25% to 85%
Ambient storage temperature
−25 to 65°C (with no icing or condensation)
Note: 1. Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)
2. The power consumption for the Temperature Controllers is not included.
3
E5ZN-DRT
■ Characteristics
Insulation resistance
20 MΩ min. (at 100 VDC)
Dielectric strength
500 VAC, 50/60 Hz for 1 min between the DIN track and all DeviceNet connector terminals and between the DIN track
and all terminal socket terminals
Vibration resistance
10 to 55 Hz, 10 m/s2 for 2 hrs each in ±X, ±Y, and ±Z directions
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Weight
100 g max.
Safety standards
cULus508
EMS:
Electrostatic Discharge (ESD)
Radiated Electromagnetic Fields
Electrical Fast transients/BURST
Surge Transients
EMI:
EN61006-2, EN61000-4-2 (4 kV/contact, 8 kV/air)
EN61006-2, EN61000-4-3 (10 V/m)
EN61006-2, EN61000-4-4 (2 kV/DC power-line, 1 kV/Signal-line)
EN61006-2, EN61000-4-5 (line to ground : 1 kV/DC power-line)
: 2 kV/Signal-line
line to line
: 0.5 kV/DC power-line)
Conducted Disturbances
EN61006-2, EN61000-4-6 (10 V)
Radiated Emissions (electric field) EN50081-2 Class A
■ Communications (for Temperature Controller Expansion)
Transmission line
connection method
RS-485 multipoint
Communications method RS-485 (2-wire, half-duplex)
Synchronization
method
Start-stop synchronization
Baud rate
38,400 bps
Transmission code
ASCII
Data bit length
7 bits
Stop bit length
2 bits
Error detection
Vertical parity (even)
BCC (block check character)
Flow control
None
Number of Units that can 16 Units max. (32 channels)
be connected in parallel
Connections
■ Terminal Arrangement
E5ZN-DRT
E5ZN-SCT24S
×10
MS
NODE
ADR
×1
NS
(TOP VIEW)
+
External input power
supply (24VDC)
−
B (+)
ON
UP/DN
19
13
7
1
20
14
8
2
21
15
9
3
22
16
10
4
23
17
11
5
24
18
12
6
TS
COPY
Signal
Color
Red
Communications power, positive (+V)
White
Communications signal, high (CAN H)
--Blue
Black
Shield
Communications signal, low (CAN L)
Communications power, negative (–V)
Setting Display Unit
communications
A (−)
B (+)
Communications for
Temperature
A (−)
Controller expansion
Not used with the DeviceNet
Communications Unit
4
E5ZN-DRT
Nomenclature
E5ZN-DRT
Back Panel DIP Switch
Front Panel Rotary Switches
Used to set the node address when
functioning as a DeviceNet slave.
×10
Used to specify whether the connection
configuration and I/O allocation is set
using simple I/O allocation or Configurator
I/O allocation.
Pin 1: I/O allocation setting switch
Pin 2: Not used (Set to OFF.)
Back Panel Rotary Switch
MS
NODE
ADR
×1
NS
89
67 A
345
Front Panel DIP Switch
TS
UP/DN
01
EF 2
BCD
ON
COPY
Used to copy (backup) parameters between
the Temperature Controllers and DeviceNet.
Used to set the maximum unit number
when simple I/O allocation is used.
UP/DN (Pin 2): Sets the copy operation mode
(i.e., upload or download).
COPY (Pin 1): Starts the copying.
Terminal Unit Connector
Connects to the E5ZN-SCT24S
Terminal Unit.
DeviceNet Connector
Connects to DeviceNet communications
cables. Power for DeviceNet communications is also supplied though this
connector. An FKC2.5/5-STF-5.08AU
connector (Phoenix Contact) is provided.
Indicators
Dimensions
Note: All units are in millimeters unless otherwise indicated.
E5ZN-DRT
Dimensions when Mounted to the
E5ZN-SCT24S Terminal Unit
130
72.8
4.7
30
27
35
46
89.6
(107.5)
Note: Be sure to read the precautions for correct use and other precautions in the following user’s manuals before using the
Communications Unit.
E5ZN-DRT DeviceNet Communications Unit Operation Manual (Cat. No. H119)
DeviceNet Operation Manual (Cat. No. W267)
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
5
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2016.4
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2016 All Right Reserved.