OMRON DCN1-1C

Peripheral Devices
T-branch Taps and Terminal-block
Terminator
T-branch Taps Create One or Three
Branch Lines
Ordering Information
Product
Appearance
Model
Specification
T-branch Tap for 1 branch line
DCN1-1C
Provided with 3 connectors,
standard terminating resistor
T-branch Tap for 2 branch lines
DCN1-3C
Provided with 5 connectors,
standard terminating resistor
Connector
XW4B-05C1-H1-D
---
Thin cables
DCA1-5C10
Outer diameter: 7.00 mm
Length: 100 m
Thick cables
DCA2-5C10
Outer diameter: 11.6 mm
Length: 100 m
DRS1-T
Resistance of 121 W
DeviceNet Cables
Terminal-block Terminator
136
Peripheral Devices
Peripheral Devices
Connectors for DCN1-jC
Model
Comments
Manufacturer
MSTB2.5/5-ST-5.08-AU
For node connection
Phoenix Contact Corporation
MSTBP2.5/5-STF-5.08-AB AU SO
For T-branch Tap connection (with screws
to secure the connector)
Phoenix Contact Corporation
Specifications
Ratings/Characteristics
Rated current
Between main lines:
Between main and branch lines:
8 A (power supply line) and 2 A (signal line)
3 A (power supply line) and 1 A (signal line)
Insulation resistance
100 MW min. (at 500 VDC)
Dielectric strength
500 VAC for 1 min, leakage current: 1 mA max.
Ambient temperature
Operating: 0°C to 55°C
Materials
Item
Component
Unit
Terminal block connector (see note)
PBT resin with glass (UL14V-0)/gray
DIN track lock
POM resin/yellow
Housing
PA66 resin (UL94V-0)/gray
Contact
Phosphor bronze coated with gold
PCB
Note:
Materials
Main and Expansion Units
Glass epoxy resin
The DCD1-1C is a product of Phoenix Contact.
Dimensions
Note:
All units are in millimeters unless otherwise indicated.
DCN1-1 (With No Branching Connector)
DCN1-1C (With Three Branching Connectors)
Internal Circuit
*(See
Main line
note)
Main line
Socket for terminator connection
Branch line
Two, 4 dia. or M4
Mounting Dimensions
Note:
Terminal no.
1
V--
2
CAN-L
3
DRAIN
4
CAN-H
5
V+
When connecting a branch line to the main line, connect the main line to the connector marked with an asterisk because the resistance
between the asterisked portion is minimal.
137
Peripheral Devices
Peripheral Devices
DCN1-3 (With No Branching Connector)
DCN1-3C (With Five Branching Connectors)
* (See note)
Socket for terminator
connection
Two, 4 dia. or M4
Mounting Dimensions
Internal Circuit
Main line
Main line
Terminal no.
Branch line
Note:
Branch line
Branch line
1
V--
2
CAN-L
3
DRAIN
4
CAN-H
5
V+
When connecting a branch line to the main line, connect the main line to the connector marked with an asterisk because the resistance between the asterisked portion is minimal.
XW4B-05C1-H1-D (Connector)
Cable insertion port
Cable insertion port
138
Peripheral Devices
Peripheral Devices
DRS1-T Terminal-block Terminator
Mounting Holes
Two, 4.2 dia. or M4
30±0.2
Two, 4.4 dia.
20 max.
6 +0.1
--0
41 max.
21 max.
Precautions
Refer to the DeviceNet Operation Manual (W267) before using the
Unit.
Correct Use
Refer to the DeviceNet Operation Manual (W267) for connecting or
wiring T-branch Taps.
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
R
OMRON ELECTRONICS, INC.
OMRON CANADA, INC.
1-800-55-OMRON
416-286-6465
One East Commerce Drive
Schaumburg, IL 60173
Cat. No. P10FAX1A
6/00
885 Milner Avenue
Scarborough, Ontario M1B 5V8
Specifications subject to change without notice.
Printed in U.S.A.
139