Manufacture of the E5GN will be discontinued in March 2015. Operation for E5@N/E5@N-H/E5@N-HT Operation for E5@N/E5@N-H/E5@N-HT CSM_E5_N_E5_N-H_operation_TG_E_4_3 Operation Setting Levels Diagram This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Control stops when you move from the operation level to the initial setting level. Basic Type E5CN/E5CN-U/E5AN/E5EN/E5GN Power ON Start in manual mode. Start in automatic mode. Press the O Key or the PF Key for at least 1 s. *4 Operation Level Adjustment Level Press the O Key less than 1 s. a-m PF Key Manual mode *3 Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.) PF Key Press the O+ M Keys for at least 1 s. c 25 100 *5 *4 Press the PF Key for at least 1 s. Manual Control Level *5 Monitor/Setting Item Level Press the O+ M Keys for at least 3 s. (Display will flash after 1st second.) Press the O Key for at least 1 s. Control stops. c Press the O Key for at least 3 s. (Display will flash after 1st second.) 25 100 Protect Level *1 Note: The time taken to move to the protect level can be adjusted by changing the “Move to protect level time” setting. Communications Setting Level Initial Setting Level Press the O Key for less than 1 s. Input password while amoV is displayed. (Set value −169) Press the O Key for at least 1 s. Advanced Function Setting Level Control in progress Input password. Control stopped Calibration Level *2 Not displayed for some models Level change *1. You can return to the operation level by executing a software reset. *2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning OFF the power. *3. From the manual control level, key operations can be used to move to the operation level only. *4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/E5EN). *5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/E5EN). Error Displays (Troubleshooting) When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below. No.1 display Meaning Action s.err (S. Err) Input error *2 A/D converter error *2 Check the setting of the input type. Also check the input wiring and check for broken wires or short-circuits in the temperature sensor. Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. e333 (E333) e111 (E111) Memory error Status at error Control output *1 Alarm output Operates as above OFF the upper limit. OFF OFF OFF OFF Note: If the input value exceeds the display limit (-1999 to 9999), though it is within the control range, will be displayed under -1999 and above 9999. Under these conditions, control output and alarm output will operate normally. For details on the control range, refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156). *1. If the control output is assigned to the transfer output and the transfer output type is set to the present value, the upper limit value will be output for the present value when there is an input error. *2. Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status. 1 Operation for E5@N/E5@N-H/E5@N-HT Advanced Type E5CN-H/E5AN-H/E5EN-H Power ON Start in manual mode. Start in automatic mode. Press the O Key or the PF Key for at least 1 s. *4 Operation Level a-m Manual mode *3 Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.) Adjustment Level Press the O Key less than 1 s. Press the O Key less than 1 s. PID Setting Level Press the O Key less than 1 s. Bank Setting Level Press the PF Key for at least 1 s. *4 Manual Control Level PF Key Press the O Key less than 1 s. Press the O + M Keys for at least 3 s. (Display will flash after 1st second.) c 25.0 100.0 Protect Level Press the O Key for at least 3 s. (Display will flash after 1st second.) 25.0 c PF Key *5 Monitor/Setting Item Level *5 Press the O Key for at least 1 s. Press the O+ M Keys for at least 1 s. Note: The time taken to move to the protect level can be adjusted by changing the “Move to protect level time” setting. 100.0 *1 Control stops. Communications Setting Level Initial Setting Level Press the O Key for less than 1 s. Press the O Key for at least 1 s. Input password while amov is displayed. (Set value −169) Advanced Function Setting Level Input password. Control in progress Control stopped *2 Calibration Level Not displayed for some models Level change *1. You can return to the operation level by executing a software reset. *2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning OFF the power. *3. From the manual control level, key operations can be used to move to the operation level only. *4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H). *5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H). Error Displays (Troubleshooting) When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below. No.1 display Meaning s.err (S. Err) Input error *2 e333 (E333) e111 (E111) Action Status at error Control output *1 Alarm output Check the setting of the input type. Also check the input wiring and check for broken wires or short-circuits in the temperature sensor. OFF Operates as above the upper limit. A/D converter error *2 Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. OFF OFF Memory error Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. OFF OFF Note: If the input value exceeds the display limit (-19999 to 32400), though it is within the control range, will be displayed under -19999 and above 32400. Under these conditions, control output and alarm output will operate normally. For details on the control range, refer to the E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157). *1. If the control output is assigned to the transfer output and the transfer output type is set to the present value, the upper limit value will be output for the present value when there is an input error. *2. Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status. 2 Operation for E5@N/E5@N-H/E5@N-HT Programmable Type E5CN-HT/E5AN-HT/E5EN-HT Power ON Start in manual mode. Start in automatic mode. Operation Level a-m Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.) Manual mode Program Setting Level Press the O Key less than 1 s. Press the O Key less than 1 s. PID Setting Level Press the O Key less than 1 s. Adjustment Level Press the O Key less than 1 s. Press the O + M Keys for at least 3 s. (Display will flash after 1st second.) Press the O+ M Keys for at least 1 s. c Press the PF Key for at least 1 s. Manual Control Level c 25.0 100.0 Protect Level Monitor/Setting Item Level Press the O Key for at least 1 s. 25.0 Press the O Key for at least 3 s. (Display will flash after 1st second.) Note: The time taken to move to the protect level can be adjusted by changing the “Move to protect level time” setting. 100.0 Control stops. Communications Setting Level Initial Setting Level Press the O Key for less than 1 s. Press the O Key for at least 1 s. Advanced Function Setting Level Input password. Control in progress Control stopped Calibration Level Not displayed for some models Level change *1. You can return to the operation level by executing a software reset. *2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning OFF the power. *3. From the manual control level, key operations can be used to move to the operation level only. *4. When the PF Setting parameter is set to A-M. For the E5CN-HT, press the M+U Keys at the same time to implement the PF Key. *5. When the PF Setting parameter is set to PFDP. For the E5CN-HT, press the M+U Keys at the same time to implement the PF Key. Error Displays (Troubleshooting) When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below. No.1 display Meaning s.err (S. Err) Input error *2 e333 (E333) e111 (E111) Action Status at error Control output *1 Alarm output Check the setting of the input type. Also check the input wiring and check for broken wires or short-circuits in the temperature sensor. OFF Operates as above the upper limit. A/D converter error *2 Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. OFF OFF Memory error Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. OFF OFF Note: If the input value exceeds the display limit (-19999 to 32400), though it is within the control range, will be displayed under -19999 and above 32400. Under these conditions, control output and alarm output will operate normally. For details on the control range, refer to the E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers User's Manual Programmable Type (Cat. No. H169). *1. If the control output is assigned to the transfer output and the transfer output type is set to the present value, the upper limit value will be output for the present value when there is an input error. *2. Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status. 3 Operation for E5@N/E5@N-H/E5@N-HT Parameters Basic Type E5CN/E5CN-U/E5AN/E5EN/E5GN Some parameters are not displayed depending on the model of the Controller and parameter settings. For details, refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156). Starting in manual mode. PF Key *2 Power ON Manual Control Level Press the PF Key for at least 1 s. *1 Adjustment Level Press the O PID Key or the PF 25 Control Key for at least only 1 s. *1 PV/MV PF Key *2 Press the O Key for at least 3 s. Other than the Auto/Manual Switch display Starting in automatic mode. Initial Setting Level Press the O Key for at least 1 s. C Press the O Key less than 1 s. in-t Input Type 5 Press the O Key less than 1 s. M in-h Operation Level Press the O Key less than 1 s. C 0.0 Input Shift Value parameters. 2-point shift M Limit insl Lower Temperature C 0.0 Input Shift Value off C 0.0 M Burnout hb1 Heater Detection 1 M i M d M Overcurrent oc1 Heater Detection 1 50.0 M hb2 0.0 M oc2 50.0 M lcr1 0.0 0.0 M hs1 Heating/cooling M c-db Dead Band C 0.0 M of-r 1.0 0.0 M hs2 C M soak Soak Time Leakage Current 2 Monitor HS Alarm 2 1 M wt-b C off M sp-0 M mv-s SP 0 M sp-2 MV at Stop M Current 2 lcr2 Leakage Monitor MV at PV Error SP used by multi-SP SP 2 M sp-3 SP 3 C M sprt SP Ramp Set Value off M ol-h 0 105.0 M M ol-l MV Upper Limit MV Lower Limit M orl MV Change Rate Limit 0.0 M sqrp 0.0 M C Extraction of Square Root Low-cut Point Alarm Value Upper Limit 2 M Value al2l Alarm Lower Limit 2 C M al-3 Alarm Value 3 0 M Value al3h Alarm Upper Limit 3 0 M prst Program Start C rset M Value al3l Alarm Lower Limit 3 M d-u c 0 C M M s-hc M Initial Setting/ Protect: icpt Communications This protect level restricts movement 1 to the initial setting, communications M levels. Change Protect: wtpt Setting Protects changes to setups by off operating the front panel keys. M Key Protect pfpt PF Restricts PF key operation off (E5AN/E5EN only) M Mask Enable: pmsk Parameter Displayed only when a on parameter mask is set. M to Move to Protect Level: prlp Password Password setting 0 M Standard or Heating/Cooling stnd M st ST (Self-tuning) on M ptrn For input type of temperature, standard control, or PID Program Pattern off When assigning PID or M control output to ON/OFF output cp Control Period (Heating) M o MV Monitor (Heating) 20 M c-cp Set the ON/OFF output cycle. Control Period (Cooling) 20 M orev Direct/Reverse Operation or-r Press the O and M Keys for at least 1 s. Operation/Adjustment Protect: oapt Restricts displaying and modifying menus in operation, 0 adjustment, and manual control levels. Limit the set point SP Lower Limit onof M Move to Protect Level: Displayed only when a password 0 is set. Restricts moving to protect level. M sl-l M cntl PID ON/OFF 0.0 Protect Level SP Upper Limit -200 M c-o MV Monitor (Cooling) Note: The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting. Temperature Unit °C, °F For input type of temperature 1300 0.0 M Press the O and M Keys for at least 3 s. M sl-h C 0 M sktr Soak Time Remain Decimal Point 0 For input type of analog 0 C setting, and advanced function setting -5.0 M al2h 0 0.0 pmov 0.0 0 C M mv-e SP 1 0 C M Current 1 lcr1 Leakage Monitor Wait Band 0.0 0 M sp-1 Heater Current 2 Value Monitor 1.0 50.0 C 0.0 M Hysteresis settings chys Hysteresis (Cooling) 50.0 M lcr2 Manual Reset Value Clear the offset during M hys Hysteresis (Heating) C C 0.0 M ct2 M al-2 Alarm Value 2 0 0.0 50.0 stabilization of P or PD C C M Current 1 Value ct1 Heater Monitor PID settings M Value al1l Alarm Lower Limit 1 0 M dp 0 M Point During sp-m Set SP Ramp Derivative Time control. HS Alarm 1 C Integral Time 1.00 Heater Overcurrent Detection 2 Leakage Current 1 Monitor 0 C Multi-SP Set Point Setting M Value al1h Alarm Upper Limit 1 0 0 M c-sc Cooling Coefficient Heater Current 2 Value Monitor Heater Burnout Detection 2 m-sp 40 0.0 C Added when auto/manual select M addition is ON. Press the O Key for at least 3 s. M al-1 Alarm Value 1 0 M Switch a-m Auto/Manual PID control only. 233 0.0 M ct2 M p Proportional Band 8.0 C 0 1-point shift M Set either Limit insh Upper of these Temperature AT Execute/Cancel M Current 1 ct1 Heater Value Monitor M Value/ 25 Process Set Point C 0.0 off M cmwt Communications Writing ins Temperature Input Shift run Set either of these parameters. M at C M in-l Scaling Lower Limit r-s RUN/STOP Process Value Added when Additional PV display is ON. Set either of these parameters. l.adj 25 Set either of these parameters. C Adjustment Level Display Displayed only once when entering adjustment level. Scaling Upper Limit 100 M alt1 Press the O Key less than 1 s. Communications Setting Level C Note: Displayed only for models with communications. Changes are effective after cycling power or after a software reset. Alarm 1 Type 2 M alh1 0.2 Alarm 1 Hysteresis M Setting: psel Protocol Switches between cwf CompoWay/F (SYSWAY) and Modbus. M u-no Communications Unit No. 1 M Communications bps Baud Rate 9.6 CompoWay/F (SYSWAY) only M len Communications Data Length 7 M sbit Communications Stop Bits 2 M prty Communications Parity even M sdwt *1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/E5EN). *2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/E5EN). Send Data Wait Time 20 M 4 Operation for E5@N/E5@N-H/E5@N-HT Monitor/Setting Item Level 25 C 0 Monitor/Setting Item Display 1 PF (E5AN/E5EN only) Monitor/Setting Item Display 2 Monitor/Setting Item Display 3 PF Monitor/Setting Item Display 4 PF Monitor/Setting Item Display 5 PF Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level). Press the O Key for at least 1 s. alt2 Advanced Function Setting Level Alarm 2 Type 0.2 2 M alh3 C 0.2 M mspu Multi-SP Uses M a2lt Alarm 2 Latch M spru M a3lt Alarm 3 Latch SP Ramp Time Unit Alarm 3 Hysteresis M Sequence rest Standby Reset M to Protect Level prlt Move Time M sb1n M sero Input Error Output off M tr-h Linear output n-o Transfer Output Upper Limit M sb2n 100.0 M Output tr-l Transfer Lower Limit n-o M sb3n 0.0 M o1-t Linear Current Output 4-20 n-o M hbu Linear output M of Multi-SP Uses ev-m Number Two SPs: 1 none M ev-2 stop on Method M Command rlrv MB Logic Switching Auxiliary Output 3 Open in Alarm off M colr PV Change Color HB ON/OFF red off M Burnout hbh Heater Hysteresis 0.1 Event Input Assignment 2 M of Square sqr Extraction Root Enable M Junction cjc Cold Compensation on Event Input Assignment 1 C 0.65 setting/communications M protect is set to 0. 0.8 Move by setting password (−169). C M at-h AT Hysteresis 0.8 M a2on Alarm 2 ON Delay M a3on Alarm 3 ON Delay M a1of Alarm 1 OFF Delay 0 M a2of Alarm 2 OFF Delay 0 M Cycle MV lcma Limit Amplitude 20.0 M inf Input Digital Filter 0.0 M pvad Additional PV Display off M o-dp M a1on Alarm 1 ON Delay 0 M at-g AT Calculated Gain 0 Displayed when initial 5.0 0 M alfa α M to Advanced amov Move Function Setting Level: C M pv-b PV Stable Band 0 M st-b ST Stable Range 15.0 off M hsh HS Alarm Hysteresis 0.1 M a3of Alarm 3 OFF Delay 0 M istp Input Shift Type ins1 M at Stop and Error mvse MV Addition off MV Display off M Display ret Automatic Return Time 0 C M Select amad Auto/Manual Addition off M rt RT off off M M M lbal LBA Level M (E5AN/E5EN only) pfd2 Monitor/Setting Item 2 M pfd3 Monitor/Setting Item 3 0 M pfd4 Monitor/Setting Item 4 0 8.0 C M pfd1 Monitor/Setting Item 1 0 M lba LBA Detection Time off Auxiliary Output 2 Open in Alarm M hbl Heater Burnout Latch 1 Four SPs: 2 M ev-1 Auxiliary Output 1 Open in Alarm PF Setting (E5AN/E5EN only) 1 off 3 a tr-t Transfer Output Type pf a-m M hsl HS Alarm Latch off m HS Alarm Use on off off M alt3 Alarm 3 Type hsu off off M 2 alh2 Alarm Hysteresis C a1lt Alarm 1 Latch init Parameter Initialization 2 M lbab LBA Band 3.0 M pfd5 Monitor/Setting Item 5 0 M Output 1 out1 Control Assignment M spdp M out2 Control Output 2 Assignment M odsl MV Display Selection Auxiliary Output 1 Assignment M Decimal Point pvdp PV Display o none M sub1 alm1 M sub2 Auxiliary Output 2 Assignment alm3 "PV/SP" Display Screen Selection o on M PV Status Display pvst Function off alm2 M sub3 4 Auxiliary Output 3 Assignment (E5AN/E5EN only) M csel Character Select on M t-u Soak Time Unit m M alsp Alarm SP Selection sp-m M MV manl Manual Limit Enable off M Rate of Change pvrp PV Calculation Period 4 M csca off Automatic Cooling Coefficient Adjustment M Status Display svst SV Function off M Refresh d.ref Display Period 0.25 M Output 1 ra1m Control ON/OFF Count 0 Monitor M ra2m Control Output 2 ON/OFF Count 0 Monitor M ra1 Control Output 1 ON/OFF Count 0 Alarm Set Value M Output 2 ra2 Control ON/OFF Count 0 Alarm Set Value M Counter rac ON/OFF Reset 0 M Overcurrent ocu Heater Use M to Calibration cmov Move Level M Overcurrent ocl Heater Latch M exfn Expansion Functions on 0 off 0 M och M 0.1 Heater Overcurrent Hysteresis M 5 Operation for E5@N/E5@N-H/E5@N-HT Advanced Type E5CN-H/E5AN-H/E5EN-H Some parameters are not displayed depending on the model of the Controller and parameter settings. For details, refer to the E5CN-H/E5AN-H/ E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157). Power ON Manual Control Level Protect Level Operation Level Adjustment Level Initial Setting Level Communications Setting Level PID Setting Level Bank Setting Level Monitor/Setting Item Level Advanced Function Setting Level Press the O Key less than 1 s. Bank Setting Level PID Setting Level Press the O Key less than 1 s. Display PID Selection Press the O Key less than 1 s. Display Bank Selection d.bnk Bank0 d.pid PID1 1 d.pid 0 2 PID2 d.bnk Bank1 1 d.pid d.bnk d. bnk 3 PID3 22 Bank2 d.pid 8 d.bnk Bank7 PID8 7 M M 1.i c M 8.d PID 1 Derivative Time 8.olh M 8.oll M PID 1 Automatic Selection 1320.0 Range Upper Limit PID 1 Cooling Coefficient 1.00 M c c PID 8 Automatic Selection 1320.0 Range Upper Limit M PID 8 Cooling Coefficient 1.00 PID 1 LBA Detection Time c M 8.lba 0 M c 7.pid M 0.a3h c c c 0.0 M 0.a1h M c 0.a3l M 0.0 0.a1l 0.0 M 0.sok M 1 M 0.a-2 M 1 M 0.a-1 0.0 PID 8 LBA Detection Time 0.a2l 0.a-3 c 0.wtb Bank 7 SP 0.0 0.0 c 7.lsp M 0.0 0.0 M 8.aut 8.csc M 0 PID 8 MV Lower Limit c M M 0.0 -5.0 1.aut 1.lba c 105.0 PID 1 MV Lower Limit -5.0 M 1.csc PID 8 MV Upper Limit c M 0.spr off M 105.0 c c 0.a 2h 0.0 0.pid 40.0 PID 8 MV Upper Limit c M 1 PID 8 Derivative Time M 0.lsp 0.0 233.0 40.0 M 1.oll c M 8.i PID 8 Integral Time PID 1 Integral Time M M 1.olh M PID 8 Proportional Band 8.0 233.0 1.d M 8.p c 7.a-2 c 7.a 2h c 7.a2l M 7.spr Bank 7 0.0 Alarm Value 1 M 7.a1h Bank 7 Alarm Value 0.0 Upper Limit 1 Bank 7 Alarm Value 0.0 Lower Limit 1 7.a1l Bank 7 Alarm Value 0.0 Upper Limit 2 M Bank 7 SP off Ramp Set Value M 7.a-1 Bank 7 0.0 Alarm Value 2 M Bank 7 PID Set No. M c c c Bank 7 Alarm Value 0.0 Lower Limit 2 M 7.a-3 Bank 7 0.0 Alarm Value 3 c c M M 7.a3h Bank 7 Alarm Value 0.0 Upper Limit 3 M 7.a3l Bank 7 Alarm Value 0.0 Lower Limit 3 M 7.sok off M Set either of these parameters PID 1 Proportional Band 8.0 Set either of these parameters 1.p Set either of these parameters c Bank 7 Soak Time 1 c M 7.wtb Bank 7 Wait Band off M 6 Operation for E5@N/E5@N-H/E5@N-HT Power ON Starting in manual mode. Manual Control Level PID Press the O 25.0 Control Key or the PF 100.0 only Key for at least 1 s. *1 PV/MV Press the PF Key for at least 1 s. Starting in automatic mode. c *1 Press the O and M Keys for at least 3 s. Press the O Key less than 1 s. at off c c 8.0 M i AT Execute/Cancel M M cmwt d M irda 40.0 Infrared Communications Use SP Mode lsp 0.0 M ct1 M of-r Heater Current 1 M hys Heater Burnout 1.0 0.0 Detection 1 M oc1 M chys M M soak Heater Overcurrent 50.0 Detection 1 ct2 Heater Current 2 M hb2 0.0 M oc2 50.0 Heater Burnout Detection 2 mv-s M mv-e M hs1 M sprt Leakage Current 1 0.0 Monitor 0.0 M hs2 50.0 0.0 HS Alarm 1 0.00 M c c M ol-h Leakage Current 2 Monitor 105.0 ol-l HS Alarm 2 -5.0 M orl Temperature Input Shift M c Bank No. 0.0 Lower Limit 1 c Remote SP Monitor c Set Point During M ct1 c Heater Current 1 Value M c ct2 Heater Current 2 Value 0.0 Monitor lcr2 Alarm Value M al2l Press the O and M Keys for at least 1 s. Alarm Value 0.0 Lower Limit 2 0.0 Monitor lcr1 al2h 0.0 Upper Limit 2 0.0 SP Ramp M al-3 0.0 Alarm Value 3 M al3h Alarm Value Leakage Current 1 0.0 Upper Limit 3 M al3l Alarm Value Leakage Current 2 0.0 Lower Limit 3 0.0 Monitor M M MV at PV Error Alarm Value 2 0.0 M 0.0 Monitor MV at Stop al-2 M M Wait Band M al1l Alarm Value M M Soak Time Alarm Value 0.0 Upper Limit 1 0.0 sp-m Hysteresis settings al1h o prst Program Start rset 0.0 M M c-o sktr Soak Time Remain MV Monitor (Heating) MV Monitor (Cooling) 0.0 0 M M v-m SP Ramp Set Value Valve Opening Monitor 0.0 M MV Upper Limit Lower Limit Temperature Input Shift Value 0.0 MV Lower Limit PF Key *2 MV Change Rate Limit Monitor/Setting Item Level (E5AN-H/E5EN-H only) M 1-point shift Upper Limit Temperature 0.00 Input Shift Value 2-point shift M 0.00 rsp control. Hysteresis (Heating) c M c Manual Reset Value Clear the offset during Auto/Manual Switch PID control only. Added when auto/manual select addition is ON. 0 Heating/cooling Alarm Value 1 0.0 M insh insl bank al-1 M off M ins M Dead Band 0.0 lcr1 M lcr2 a-m Press the O Key for at least 3 s. M M 50.0 PID settings Derivative Time off Heater Overcurrent Detection 2 M c M 1 M wt-b run Process Value/ 0.0 Set Point Integral Time 1.0 Hysteresis (Cooling) 0.0 Value Monitor r-s RUN/STOP 25.0 50.0 stabilization of P or PD 0.0 Value Monitor M hb1 c M c-sc Cooling Coefficient M c-db M Process Value Added when Additional PV display is ON. M 1.00 off spmd 25.0 Proportional Band 233.0 Communications off Writing c p Set either of these parameters. M Adjustment Level Display Displayed only once when entering adjustment level. Set either of these parameters. l.adj Operation Level Set either of these parameters. Adjustment Level Set either of these parameters. db 2.0 Position Proportional Dead Band oc-h 25.0 Monitor/Setting Item Display 1 Monitor/Setting Item Display 2 PF PF Monitor/Setting Item Display 3 0.0 M PF Open/Close Hysteresis 0.8 M sqrp Extraction of Square Root 0.0 Low-cut Point M Monitor/Setting Item Display 4 PF Monitor/Setting Item Display 5 Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level). PF Key *2 *1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H). *2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H). 7 Operation for E5@N/E5@N-H/E5@N-HT Press the O Key for at least 1 s. Press the O Key for at least 3 s. Other than the Auto/Manual Switch display Initial Setting Level Press the O Key less than 1 s. Press the O Key less than 1 s. Protect Level The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting. to Protect Level: pmov Move Displayed only when a password 0 is set. Restricts moving to protect level. M Operation/Adjustment Protect: oapt Restricts displaying and modifying menus in 0 operation, adjustment, and M manual control levels. icpt 0 M Initial Setting/ Communications Protect: This protect level restricts movement to the initial setting, communications setting, and advanced function setting levels. Change Protect: wtpt Setting Protects changes to setups off by operating the front panel keys. M pfpt PF Key Protect Restricts PF key operation off (E5AN-H/E5EN-H only) M Mask Enable: pmsk Parameter Displayed only when a on parameter mask is set. M Password to Move to Protect Level: 0 Password setting prlp M in-t Communications Setting Level 5 Input Type Displayed only for models with communications. Changes are effective after cycling power or after a software reset. in-h M in-l M Scaling Upper Limit dp M bps 7 d-u c Communications Data Length c M sbit 2 M sl-h c Decimal Point Temperature Unit °C, °F For input type of temperature M s-hc 20 M 100.0 0.0 M o1-t Standard or Heating/Cooling ST (Self-tuning) For input type of temperature, standard control, or PID Program Pattern off cp c-cp When assigning PID or control output to ON/OFF output Control Period (Heating) Set the ON/OFF output cycle. Control Period (Cooling) 20 M orev Direct/Reverse Operation or-r M alt1 2 0.2 M Bank Numbers Used M ev-1 none Event Input Assignment 1 M M ev-3 none Event Input Assignment 3 M ev-4 none Event Input Assignment 4 M clfl Closed/Floating flot M calb Motor Calibration off Alarm 1 Type M alh1 Linear output M stop Valid Program Bank 20 M Linear Current Output Input ev-2 Event Assignment 2 M 7 Transfer Output Lower Limit 4-20 1 M Transfer Output Upper Limit M tr-l ev-b pbnk Linear output M M st M ptrn c M stnd on Alarm 3 Hysteresis tr-t Transfer Output Type tr-h Limit the set point M sl-l SP Lower Limit pid Send Data Wait Time M alh3 off SP Upper Limit M cntl PID ON/OFF M c 0.2 -200.0 even Alarm 3 Type 2 1300.0 Communications Stop Bits M prty Communications Parity sdwt alt3 M M Alarm 2 Hysteresis M Scaling Lower Limit 0 For input type of analog Communications Baud Rate 9.6 CompoWay/F (SYSWAY) only M alh2 0.2 M 1 len c 0 Communications Unit No. Alarm 2 Type 2 100 Protocol Setting: psel Switches between cwf CompoWay/F (SYSWAY) and Modbus. u-no alt2 M M mot Travel Time 30 Alarm 1 Hysteresis M sqr off Extraction of Square Root Enable M Move to Advanced Function Level: amov Setting Displayed when initial 0 setting/ communications M protect is set to 0. Move by setting password (−169). 8 Operation for E5@N/E5@N-H/E5@N-HT Power ON Manual Control Level Protect Level Operation Level Adjustment Level Initial Setting Level Communications Setting Level PID Setting Level Bank Setting Level Monitor/Setting Item Level Advanced Function Setting Level Press the O Key for at least 1 s. Advanced Function Setting Level o-dp init Parameter Initialization off SP Ramp Time Unit m a Standby Sequence Reset 3 HB ON/OFF Heater Burnout Hysteresis off ST Stable Range M 0.65 M AT Calculated Gain M c PV Stable Band M Limit Cycle MV Amplitude M 0.0 00 Additional PV Display M M odsl MV Display Selection M o M PID Set Automatic Selection Hysteresis pvdp on pvst off svst off Direct Setting of off Position Proportional MV M pvrp Control Output 2 Assignment M Auxiliary Output 1 Assignment Auxiliary Output 2 Assignment M ra2m Automatic Cooling off Coefficient Adjustment M on M ocl M Soak Time Unit Use Heater Overcurrent Hysteresis pf M ra1 Control Output 1 ON/OFF Count 0 Alarm Set Value ra2 Control Output 2 ON/OFF Count 0 Alarm Set Value M Counter rac ON/OFF Reset 0 M a-m Control Output 2 ON/OFF Count 0 Monitor M M 0.1 Control Output 1 ON/OFF Count M Heater Overcurrent Heater Overcurrent off Latch och Display Refresh Period 0 Monitor M M M ra1m csca alm2 Character Select 0.25 SV Status Display Function M PV Rate of Change 17 Calculation Period ocu M PV Status Display Function M Manual MV Limit Enable M M PV Decimal Point Display M PV Dead Band d.ref m Alarm 3 OFF Delay PID Set Automatic Selection Data "PV/SP" Display 4 Screen Selection M t-u M M spdp pmvd Control Output 1 Assignment Monitor/Setting Item 5 Remote SP Input Error Output 3.0 on 0 0 LBA Band pfd5 M csel a2of Alarm 2 OFF Delay a3of lbab Monitor/Setting Item 4 0 0.0 off sub2 M LBA Level p-db pfd4 M SP Tracking M c M alm1 Alarm 3 ON Delay a1of Alarm 1 OFF Delay M 0.50 manl sub1 0 Input Digital Filter pidh LBA Detection Time Monitor/Setting Item 3 0 0 M 8.0 none Alarm 2 ON Delay M a3on pv HS Alarm Hysteresis M out2 0 20.0 lbal o Alarm 1 ON Delay M a2on pidi out1 0 AT Hysteresis 0.8 M PV Change Color M a1on M M M c 5.0 1.0 off pv-b off pfd3 M Remote SP Lower Limit off 0 M c M rseo lba MB Command Logic Switching red α on M Monitor/Setting Item 2 M Remote SP Upper Limit off HS Alarm Use M Cold Junction M colr sptr 0.1 M rlrv M M hsh on Compensation Method 15.0 pvad Input Error Output M cjc -200.0 RT hsl HS Alarm Latch off M inf Time rspl pfd2 0 M c off hsu M sero off lcma Alarm 3 Latch M M at-h rt prlt Move to Protect Level M c on 1300.0 Auto/Manual Select Addition M Alarm 2 Latch off Burnout hbl Heater Latch at-g amad rsph Monitor/Setting Item 1 M Remote SP Enable M c pfd1 1 off MV at Stop and Error Addition M M on alfa off a3lt M st-b M off sb2n Auxiliary Output 2 n-o Open in Alarm c mvse M M 0.1 rspu a2lt sb1n Auxiliary Output 1 n-o Open in Alarm hbh M off M hbu ins1 a1lt Alarm 1 Latch M rest M M off Alarm SP Selection sp-m Input Shift Type istp Display ret Automatic Return Time M spru alsp MV Display off M PF Setting cmov 0 Move to Calibration Level M exfn Expansion Functions 0 M 9 Operation for E5@N/E5@N-H/E5@N-HT Programmable Type E5CN-HT/E5AN-HT/E5EN-HT Some parameters are not displayed depending on the model of the Controller and parameter settings. For details, refer to the E5CN-HT/E5AN-HT/ E5EN-HT Digital Controllers User's Manual Programmable Type (Cat. No. H169). Power ON Manual Control Level Operation Level Program Setting Level Initial Setting Level Communications Setting Level Protect Level Adjustment Level Monitor/Setting Item Level PID Setting Level Advanced Function Setting Level Adjustment Level Press the O Key less than 1 s. Press the O Key less than 1 s. PID Setting Level Press the O Key less than 1 s. l.adj at d.pid PID1 1 d.pid M cmwt 2 PID2 off d.pid d.pid 8 M 1.p M 1.i c M 8.d PID 8 Derivative Time 40. 0 8.ol h PID 1 MV Lower Limit -5. 0 M 1.aut M 1.csc Range Upper Limit PID 1 Cooling 1. 00 Coefficient M 1.lba PID 1 LBA Detection 0 Time M c PID 8 Automatic Selection 1320. 0 Range Upper Limit 8.aut M 8.c sc PID 8 Cooling Coefficient 1. 00 M 8.lba PID 8 LBA Detection 0 Time M Fixed SP M ct1 0. 0 M hb1 0. 0 Integral Time PID settings M Heating/cooling c-db Dead Band 0.0 Manual Reset Value Clear the offset during 500 . stabilization of P or PD control. of-r M oc2 M hys 1. 0 Heater Overcurrent 50. 0 Detection 2 c M lcr1 Leakage Current 1 Monitor M chys 1.0 c M wt-b Hysteresis (Heating) Hysteresis settings Hysteresis (Cooling) 50 0 . Wait Band M Current 2 lcr2 Leakage Monitor 0. 0 M 0. 0 M db Position Proportional 2. 0 Dead Band M oc-h Open/Close Hysteresis M Extraction of sqrp Square Root M stb MV at Reset Standby Time 0.00 M SP psps Program Shift Value 0. 0 M -200.0 M ps1 -2 00.0 RSP 0 before Correction RSP 1 before Correction M ps10 -2 00.0 RSP 10 before Correction M 0 bc1 M mv-r M Change orl MV Rate Limit bc0 of f HS Alarm 1 -5. 0 ps0 M c M ol-l MV Lower Limit 0. 0 Low-cut Point Derivative Time 1.00 c MV Upper Limit 105 0 . 0. 8 M c-sc Cooling Coefficient Heater Burnout Detection 1 Heater Burnout 0. 0 Detection 2 M Input Shift Value M p Proportional Band 400 . M hb2 0. 0 Limit inslLower Temperature M d 0. 0 M hs1 1-point shift Set either Upper Limit of these Temperature 0. 00 Input Shift Value parameters M 2-point shift 23 3 0 . Heater Current 1 Value Monitor 50.0 Detection 1 0.0 M insh M i M ol-h Temperature Input Shift 8. 0 PID 8 MV Lower Limit M PID 1 Automatic c M Current 2 ct2 Heater Value Monitor -5. 0 13 20. 0 Selection c SP Mode PID 8 MV Upper Limit 10 5. 0 M 8.ol l M fs p M ins 0. 00 M oc1 Heater Overcurrent M PID 1 MV Upper Limit 105. 0 c c 0. 0 233. 0 PID 1 Derivative Time 40. 0 M 1.oll PID 8 Proportional Band M 8.i PID 8 Integral Time PID 1 Integral Time M M 1.olh 8.p 8. 0 23 3. 0 1.d M spmd psp M PID 1 Proportional Band 8. 0 c 0. 00 Communications Writing off Use PID8 HS Alarm 2 50 0 . AT Execute/ Cancel MV at PV Error 0.0 M irda Infrared Communications 3 PID3 c mv-e hs2 M off Display PID Selection Adjustment Level Display Displayed only once when entering adjustment level. 0 RSP Broken-line Correction Value 0 RSP Broken-line Correction Value 1 M bc10 0 RSP Broken-line Correction Value 10 M 10 Operation for E5@N/E5@N-H/E5@N-HT Power ON Starting in manual mode. Manual Control Level Press the PF Key for at least 1 s.*1 c Press the O Key or the PF Key for at least 1 s. *1 PID 25 .0 Control 100.0 only PV/MV Starting in automatic mode. Press the O and M Keys for at least 3 s. Press the O Key less than 1 s. Operation Level Program Setting Level Operation Level d.prg d.prg 0 d.prg 1 Press the O Key for at least 3 s. Display Program Selection d.prg 2 7 c s-n o Number of Segments 8 Used, 1 to 32 c 25.0 ct 2 PV 0.0 Display Segment Selection, END or 0 to Number of Segments −1 d.seg d.seg end d.seg 0 d.se g 1 M lcr 1 M lcr 2 Switch prg M Program Number r-r 0 pid styp 1 c al-1 Alarm Value 1 c 0.0 M c Ral1h 0.0 M Ra l1 l c 0.0 M Alarm Upper Limit 1 Alarm Lower Limit 1 al-2 Alarm Value 2 c Alarm Upper Limit 2 c 0.0 M Ral2l 0.0 M c al-3 Alarm Lower Limit 2 Alarm Value 3 0.0 M c Ral3h 0.0 Alarm Upper Limit 3 M al3l c 0.0 Alarm Lower Limit 3 M Rrp t 0 sp 0 Segment n SP Hold Rpr 0.0 M time Segment n Ramp Rate Segment n Time M c- o MV Monitor (Cooling) Hold off M adv 0.0 M V-m Advance Valve Opening 0.0 Monitor off M stb m Press the O and M Keys for at least 1 s. 0.0 M 0.0 M c M o MV Monitor (Heating) M Remaining Standby 0.00 Time Monitor M Program prg t Elapsed Time Monitor 0.00 M 0.00 0.0 M Ral2h Segment n Format Run/Reset rst M No. seg Segment Monitor ramp M M Leakage Current 2 0.0 Value Monitor M PID Set No. Leakage Current 1 0.0 Value Monitor (See note.) M a-m Auto/Manual 7 Heater Current 2 0.0 Value Monitor M 25.0 PV/SP Program Repetitions lin k end M Program Link Destination ts1 s Time Signal 1 on1 Time Signal 1 ON Time 0 Set Segment M 0.00 M of1 M rptm Program Execution 0 Repetition Monitor c M rsp Remote SP Monitor 0.0 Heater Current 1 ct1 0.0 Value Monitor M Time Signal 1 0.00 OFF Time M ts2s 0 Time Signal 2 Set Segment M on2 0.00 Time Signal 2 ON Time M of2 0.00 Time Signal 2 OFF Time PF Key *2 Monitor/Setting Item Level 25 .0 0.0 Monitor/Setting Item Display 1 (E5AN/EN-HT only) Monitor/Setting PF Item Display 2 PF Monitor/Setting Item Display 3 PF Monitor/Setting Item Display 4 PF Monitor/Setting Item Display 5 Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level). PF Key *2 *1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/EN-HT). *2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/EN-HT). 11 Operation for E5@N/E5@N-H/E5@N-HT Press the O Key for at least 1 s. Press the O Key for at least 3 s. Other than the Auto/Manual Switch display Initial Setting Level Press the O Key less than 1 s. Press the O Key less than 1 s. Protect Level The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting. to Protect Level: pmov Move Displayed only when a password is set. Restricts moving to protect 0 M level. Communications Setting Level Operation/Adjustment 0 M 9.6 0 dp len d-u Setting Change Protect sbit 2 M prty Communications Parity pfptPF Key Protect off M c Send Data Wait Time sl-l SP Lower Limit M Password to Move to s-hc 0 M Standard or Heating/Cooling stnd Control Period (Heating) M Control Period (Cooling) 20 M Alarm 1 Type 2 Alarm 2 Type Hysteresis Alarm 3 Type Alarm 3 Hysteresis 0.2 M M Tt-u Program Time Unit Time/Rate of t-pr Step Rise Programming pru Time Unit of Ramp Rate m rtsm Reset Operation p-on Operation after Power ON cont eset Operation at End of Operation M M off Extraction of Square Root Enable rst 2 tr-t sqr Travel Time M M alh3 30 M M Alarm 2 0.2 c M stop 2 M alt3 Motor Calibration M M alh2 calb M Alarm 1 Hysteresis 0.2 c flot M time M alt2 clfl Closed/Floating h-m M M alh1 Input ev-4 Event Assignment 4 M or-r c Event Input Assignment 3 off orev Direct/Reverse Operation alt1 ev-3 mot 20 c-cp Event Input Assignment 2 off M cp ev-2 none M pid Level: prlp Protect Password setting Event Input Assignment 1 none M none M cntl PID ON/OFF on M M ev-1 M SP Upper Limit -200.0 M M Linear Current Output none 1300.0 M 20 Parameter Mask Enable Temperature Unit M sl-h c even sdwt M Decimal Point c Communications Stop Bits o1-t 4-20 M Communications Data Length Transfer Output Lower Limit M Scaling Lower Limit 0 M off M pmsk Communications Baud Rate CompoWay/F only tr-l 0.0 0 M M 7 M wtpt 1 M bps Initial Setting/ Communications Protect in-l Transfer Output Upper Limit M Scaling Upper Limit 100 M Communications Unit No. tr-h 100.0 M in-h M oapt Protect Input Type 5 Protocol Setting: psel Switches between cwf CompoWay/F and Modbus. u-no icpt in-t Displayed only for models with communications. Changes are effective after cycling power or after a software reset. pvst PV Start sp M Transfer Output Type amov Move to Advanced Function Setting Level 0 M 12 Operation for E5@N/E5@N-H/E5@N-HT Power ON Manual Control Level Operation Level Program Setting Level Initial Setting Level Communications Setting Level Protect Level Adjustment Level Monitor/Setting Item Level PID Setting Level Advanced Function Setting Level Press the O Key for at least 1 s. Advanced Function Setting Level init Parameter Initialization cjc on off a M sb1n n-o Standby Sequence Reset colr PV Change Color sub2 c pv-b PV Stable Band Auxiliary Output 2 Auxiliary Output 3 Open in Alarm a2on Alarm 2 ON Delay hbu HB ON/OFF a3on hbl Heater Burnout Latch a1of Heater Burnout Hysteresis a2of sb3n n-o 0.1 M alfa at-g at-h 20.0 M inf M on M rt Input Digital Filter MV Display M ret off Automatic Display Return Time c Move to Protect Level Time off M out1 o out2 none M ocu ocl off och pf 0.25 ra2m SV Status Display Function Display Refresh Period 0 Control Output 1 ON/OFF Count Monitor M 0 Control Output 2 ON/OFF Count Monitor M Manual MV Limit Enable ra1 Direct Setting of Position Proportional MV ra2 0 Control Output 1 ON/OFF Count Alarm Set Value M 0 Control Output 2 ON/OFF Count Alarm Set Value M PV Rate of Change rac 0 ON/OFF Counter Reset M Automatic Cooling Coefficient Adjustment pend Program End ON Time 0.0 M Heater Overcurrent Heater Overcurrent Latch s-u Standby Time Unit h-m M psad off Program SP Shift Value Addition M Heater Overcurrent 0.1 Hysteresis r-r M d.ref PV Dead Band rcad off RSP Broken-line Correction Display Addition M M Control Output 2 Assignment PV Status Display Function M M Control Output 1 Assignment off ra1m M LBA Band M Input Error Output csca svst PID Set Automatic Selection Hysteresis on Use M M sero lbab pvst M PID Set Automatic Selection Data M lbal LBA Level 3.0 M 3 c pvrp off M Alarm 3 Latch Remote SP Input Error Output M LBA Detection Time 8.0 M SP Tracking 17 Calculation Period M Alarm 2 Latch off prlt HS Alarm Hysteresis 0 off a3lt M lba M a2lt pmvd M M M off manl off 0.1 a1lt Alarm 1 Latch p-db PV Decimal Point Display M M off hsh on M pidh MV Display Selection M M hsl HS Alarm Latch off pvdp off M on M M Remote SP Lower Limit off pidi "PV/SP" Display Screen Selection o off rseo Monitor/Setting Item 5 M odsl 0.0 HS Alarm Use spdp Remote SP Upper Limit M RT pfd5 3 0.50 M hsu sptr Monitor/Setting Item 4 M Remote SP Enable M Auto/Manual Select Addition off Additional PV Display rspl pv M amad rsph pfd4 0 M off Limit Cycle MV Amplitude Alarm SP Selection off at Reset and Error mvre MV Addition AT Hysteresis off o-dp Input Shift Type ins1 0.0 M pvad Alarm 3 OFF Delay 0 M istp rspu Monitor/Setting Item 3 0 0 M sp-m -200.0 M M 0.8 M lcma Alarm 2 OFF Delay 0 AT Calculated Gain Character Select 1300 .0 M M 1.0 M alsp pfd3 M M Alarm 1 OFF Delay 0 a3of Auxiliary Output 3 Assignment off M α csel Monitor/Setting Item 2 0 M M Alarm 3 ON Delay 0 0.65 M sub3 Monitor/Setting Item 1 1 M M M off M pfd2 on 0 on M hbh Alarm 1 ON Delay 0 M M Auxiliary Output 2 Assignment M a1on n-o M pfd1 alm3 (E5AN/E5EN-HT only) 5.0 M Open in Alarm sb2n Auxiliary Output 1 Assignment M M Auxiliary Output 1 Open in Alarm alm1 alm2 M red M c sub1 M M rest Cold Junction Compensation Method PF Setting cmov 0 Move to Calibration Level M 13