OMRON E5CN-Y2MT-W-500

Digital Temperature Controllers/Digital Controllers
E5@N/E5@N-H
Upgraded 1/16, 1/8, and 1/4 DIN Controllers, the Best-selling E5@N Series.
Basic Type (Renewal E5@N) and Advanced Type (New E5@N-H).
• Improved indication accuracy and preventive maintenance (Basic Type E5@N).
• New high-performance Controllers (Advanced Type E5@N-H).
• Easy-to-use one-touch operation with PF Key (Only for 1/8 and 1/4 DIN).
• Logic operations.
E5@N Series
Basic Type (Renewal E5@N)
Advanced Type (New E5@N-H)
E5CN
E5EN
E5AN
E5CN-H
E5EN-H
E5AN-H
1/16 DIN
1/8 DIN
1/4 DIN
1/16 DIN
1/8 DIN
1/4 DIN
1
Contents
Digital Temperature Controllers
E5CN/E5CN-U .............................................
3
E5AN/E5EN .................................................
17
Digital Controllers
E5CN-H........................................................
31
E5AN-H/E5EN-H..........................................
43
Operation Procedure
2
• Operation .....................................................
Common to All Controllers
58
• Safety Precautions .......................................
CX-Thermo Support Software
66
• EST2-2C-MV4..............................................
70
(48 x 48 mm)
• Indication Accuracy
Thermocouple input: ±0.3% of PV (previous models: ±0.5%)
Pt input: ±0.2% of PV (previous models: ±0.5%)
Analog input: ±0.2% FS (previous models: ±0.5%)
• New E5CN-U Models (Plug-in Models) with analog inputs and
current outputs.
• A PV/SV-status display function can be set to automatically
alternate between displaying the status of the Temperature
Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV.
• Preventive maintenance for relays in the Temperature Controller
using a Control Output ON/OFF Counter.
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
New 48 x 48-mm Basic Temperature
Controller with Enhanced Functions and
Performance. Improved Indication
Accuracy and Preventive Maintenance
Function.
48 × 48-mm
E5CN
48 × 48-mm
E5CN-U
E5CN-H (48 x 48 mm)
E5CN/E5CN-U
E5CN
E5CN-U (48 x 48 mm)
Basic-type Digital Temperature Controller
Refer to Safety Precautions on page 66.
Indication Accuracy
• Thermocouple input: ±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input: ±0.2% FS
Sampling Period
• 250 ms
2-level Display: PV and SV
Control Output 2
• None
• Voltage output
(for driving SSR)
Auxiliary Outputs
• None
• One
• Two
4-digit Display
• Auto/manual switching
• Temperature Controller status display
• Simple program function
• Control output ON/OFF count alarm
• PV change rate alarm
• Models also available with RS-485
communications
Operation
Sensor Inputs
• Universal thermocouple/Pt inputs
(Models with temperature inputs)
• Analog current/voltage inputs
(Models with analog inputs)
E5CN
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Current output
• Long-life relay output (hybrid)
Safety Precautions
Event Inputs
• None
• Two
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Main I/O Functions
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156)
E5CN/E5AN/E5EN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158)
3
E5CN
E5CN-U (48 x 48 mm)
E5CN/E5CN-U
Lineup
1 control output
Temperature input
2 control outputs
2 auxiliary outputs
1 control output
0 or 2 auxiliary outputs
Terminal block
Analog input
E5CN
2 control outputs
2 auxiliary outputs
Temperature input
1 control output
0, 1, or 2 auxiliary
outputs
Analog input
1 control output
0, 1, or 2 auxiliary
outputs
Basic Type
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
0 or 2 auxiliary outputs
Plug-in
Note: Models with one control output and one or two auxiliary outputs and models with two control outputs can be used for heating/cooling control.
Model Number Structure
Model Number Legend
E5CN-H (48 x 48 mm)
Controllers
Option Units
E5CN-@@M@@-@-500
E53-CN@@@
1 2 3 4 5
1
6
7
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
1. Control Output 1
R: Relay output
Q: Voltage output (for driving SSR)
C: Current output
Y: Long-life relay output (hybrid) ✽1
2. Auxiliary Outputs ✽2
Blank: None
2: Two outputs
3. Option
M: Option Unit can be mounted.
4. Input Type
T: Universal thermocouple/platinum resistance thermometer
L: Analog current/voltage input
5. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
Operation
6. Case Color
Blank: Black
W: Silver
7. Terminal Cover
-500: With terminal cover
2 3 4
1. Applicable Controller
CN: E5CN or E5CN-H
2. Function 1
Blank: None
Q: Control output 2 (voltage for driving SSR)
P: Power supply for sensor
3. Function 2
Blank: None
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(CT2)
B: Two event inputs
03: RS-485 communications
H03: Heater burnout/SSR failure/Heater overcurrent detection
(CT1) + RS-485 communications
HB: Heater burnout/SSR failure/Heater overcurrent detection
(CT1) + Two event inputs
HH03: Heater burnout/SSR failure/Heater overcurrent detection
(CT2) + RS-485 communications
4. Version
N2: Applicable only to models released after January 2008
Safety Precautions
Note: Not all combinations of function 1 and function 2 specifications are possible for Option Units (E53-@@@@).
✽1. Always connect an AC load to a long-life relay output. The output will not turn OFF if a DC load is connected because a triac is used for
switching the circuit. For details, check the conditions in Ratings.
✽2. Auxiliary outputs are contact outputs that can be used to output alarms or results of logic operations.
4
Input type
Auxiliary outputs
Control output 1
Relay output
None
100 to 240 VAC
Thermocouple or
Resistance
thermometer
2
None
24 VAC/VDC
Thermocouple or
Resistance
thermometer
Black
2
None
1/16 DIN
48 × 48 × 78
(W × H × D)
100 to 240 VAC
Analog
(current/voltage)
2
24 VAC/VDC
Analog
(current/voltage)
2
None
100 to 240 VAC
Thermocouple or
Resistance
thermometer
Silver
24 VAC/VDC
2
2
Model
E5CN-RMT-500
Voltage output (for driving SSR)
E5CN-QMT-500
Current output
E5CN-CMT-500
Relay output
E5CN-R2MT-500
Voltage output (for driving SSR)
E5CN-Q2MT-500
Current output
E5CN-C2MT-500
Long-life relay output (hybrid)
E5CN-Y2MT-500
Relay output
E5CN-RMTD-500
Voltage output (for driving SSR)
E5CN-QMTD-500
Current output
E5CN-CMTD-500
Relay output
E5CN-R2MTD-500
Voltage output (for driving SSR)
E5CN-Q2MTD-500
Current output
E5CN-C2MTD-500
Relay output
E5CN-RML-500
Voltage output (for driving SSR)
E5CN-QML-500
Current output
E5CN-CML-500
Relay output
E5CN-R2ML-500
Voltage output (for driving SSR)
E5CN-Q2ML-500
Current output
E5CN-C2ML-500
Long-life relay output (hybrid)
E5CN-Y2ML-500
Relay output
E5CN-R2MLD-500
Voltage output (for driving SSR)
E5CN-Q2MLD-500
Current output
E5CN-C2MLD-500
Relay output
E5CN-RMT-W-500
Voltage output (for driving SSR)
E5CN-QMT-W-500
Current output
E5CN-CMT-W-500
Relay output
E5CN-R2MT-W-500
Voltage output (for driving SSR)
E5CN-Q2MT-W-500
Current output
E5CN-C2MT-W-500
Long-life relay output (hybrid)
E5CN-Y2MT-W-500
Relay output
E5CN-R2MTD-W-500
Voltage output (for driving SSR)
E5CN-Q2MTD-W-500
Current output
E5CN-C2MTD-W-500
Option Units
One of the following Option Units can be mounted to provide the E5CN with additional functions.
Functions
Communications
RS-485
Model
3-phase heater burnout/SSR failure/
Heater overcurrent detection
Heater burnout/SSR failure/Heater
overcurrent detection
E53-CNHH03N2
Event inputs
Communications
RS-485
E53-CNHBN2
Control output 2
(Voltage for driving SSR)
Event inputs
Heater burnout/SSR failure/Heater
overcurrent detection
Communications
RS-485
Communications
RS-485
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Power supply
voltage
Heater burnout/SSR failure/Heater
overcurrent detection
Operation
Case color
E53-CNQ03N2
External power supply for
ES1B
E53-CNPBN2
External power supply for
ES1B
E53-CNPHN2
External power supply for
ES1B
E53-CNP03N2
E53-CNH03N2
Communications
RS-485
Safety Precautions
Size
E5CN-H (48 x 48 mm)
Controllers with Terminal Blocks
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Ordering Information
E5CN
E5CN-U (48 x 48 mm)
E5CN/E5CN-U
E53-CN03N2
Event inputs
E53-CNBN2
Heater burnout/SSR failure/Heater
overcurrent detection
Control output 2
(Voltage for driving SSR)
E53-CNQHN2
3-phase heater burnout/SSR failure/
Heater overcurrent detection
Control output 2
(Voltage for driving SSR)
E53-CNQHHN2
Control output 2
(Voltage for driving SSR)
E53-CNQBN2
Event inputs
Note: Option Units cannot be used for plug-in models.
These Option Units are applicable only to models released after January 2008.
5
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
E5CN
E5CN-U (48 x 48 mm)
E5CN/E5CN-U
Model Number Structure
Model Number Legend (Plug-in-type Controllers)
E5CN-@@@U
1 2 3 4
3. Input Type
T: Universal thermocouple/platinum resistance thermometer
L: Analog Input
4. Plug-in type
U: Plug-in type
1. Output Type
R: Relay output
Q: Voltage output (for driving SSR)
C: Current output
2. Number of Alarms
Blank: No alarm
1: One alarm
2: Two alarms
Ordering Information
Plug-in-type Controllers
Size
Case color
Power supply voltage
Input type
Auxiliary outputs
Control output 1
Relay output
E5CN-H (48 x 48 mm)
None
Thermocouple
or resistance
thermometer
1
2
100 to 240 VAC
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
1
1/16 DIN
Analog
(current/voltage)
Black
2
None
24 VAC/VDC
Thermocouple
or resistance
thermometer
1
Operation
2
Voltage output (for driving SSR) E5CN-QTU
Current output
E5CN-CTU
Relay output
E5CN-R1TU
Voltage output (for driving SSR) E5CN-Q1TU
Current output
E5CN-C1TU
Relay output
E5CN-R2TU
Voltage output (for driving SSR) E5CN-Q2TU
Current output
E5CN-C2TU
Relay output
E5CN-R1LU
Voltage output (for driving SSR) E5CN-Q1LU
Current output
E5CN-C1LU
Relay output
E5CN-R2LU
Voltage output (for driving SSR) E5CN-Q2LU
Current output
E5CN-C2LU
Relay output
E5CN-RTDU
Voltage output (for driving SSR) E5CN-QTDU
Current output
E5CN-CTDU
Relay output
E5CN-R1TDU
Voltage output (for driving SSR) E5CN-Q1TDU
Current output
E5CN-C1TDU
Relay output
E5CN-R2TDU
Voltage output (for driving SSR) E5CN-Q2TDU
Safety Precautions
Current output
6
Model
E5CN-RTU
E5CN-C2TDU
E5CN/E5CN-U
Note: Use this Adapter when the panel has been previously prepared
for the E5B@.
Terminal Cover
Connectable models
Terminal block models
Model
E53-COV17
Sockets (for Plug-in Models)
Type
Note: The Terminal Cover comes with the E5CN-@@@-500 models.
Waterproof Packing
Model
Y92S-29
Note: The Waterproof Packing is included with the Controller only for
models with terminal blocks.
Current Transformers (CTs)
Model
Front-connecting Socket
P2CF-11
Front-connecting Socket with Finger Protection
P2CF-11-E
Back-connecting Socket
P3GA-11
Terminal Cover for Back-connecting socket with
Finger Protection
Y92A-48G
CX-Thermo Support Software
Model
Hole diameter
Model
5.8 dia.
E54-CT1
12.0 dia.
E54-CT3
EST2-2C-MV4
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Model
Y92F-45
E5CN-H (48 x 48 mm)
Connectable models
Terminal block models
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Model
E58-CIFQ1
Operation
Adapter
Safety Precautions
USB-Serial Conversion Cable
E5CN
E5CN-U (48 x 48 mm)
Accessories (Order Separately)
7
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
E5CN
E5CN-U (48 x 48 mm)
E5CN/E5CN-U
Specifications
Ratings
Power supply voltage
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range
85% to 110% of rated supply voltage
Power
consumption
E5CN
100 to 240 VAC: 7.5 VA (max.) (E5CN-R2T at 100 VAC: 3.0 VA)
24 VAC/VDC: 5 VA/3 W (max.) (E5CN-R2TD at 24 VAC: 2.7 VA)
E5CN-U
100 to 240 VAC: 6 VA (max.)
24 VAC/VDC: 3 VA/2 W (max.) (models with current output: 4 VA/2 W)
Sensor input
Models with temperature inputs
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Voltage input: 0 to 50 mV
Models with analog inputs
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Input impedance
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
Control method
ON/OFF control or 2-PID control (with auto-tuning)
E5CN
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable
load: 5 V, 10 mA
E5CN-U
SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load:
5 V, 10 mA
Voltage output
(for driving SSR)
E5CN
E5CN-U
Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection
circuit
Current output
E5CN
4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000
Long-life relay
output
E5CN
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply
voltage: 75 to 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA,
leakage current: 5 mA max. (250 VAC, 60 Hz)
E5CN-H (48 x 48 mm)
Relay output
Control
outputs
Operation
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Auxiliary
outputs
Event
inputs
Number of outputs 1 or 2 max. (Depends on the model.)
Output specifications
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum
applicable load: 5 V, 10 mA
Number of inputs
2
External contact
input specifications
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Current flow: Approx. 7 mA per contact
External power supply for ES1B 12 VDC ±10%, 20 mA, short-circuit protection circuit provided
Setting method
Digital setting using front panel keys
Indication method
11-segment digital display and individual indicators (7-segment display also possible)
Character height: PV: 11 mm, SV: 6.5 mm
Multi SP
Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial
communications.
Bank switching
Not supported
Other functions
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout
detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop,
protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic
operations, PV/SV status display, simple program, automatic cooling coefficient adjustment
Safety Precautions
Ambient operating temperature −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C
8
Ambient operating humidity
25% to 85%
Storage temperature
−25 to 65°C (with no condensation or icing)
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal Inputs)
Input
Type
Platinum resistance
thermometer
Name
Pt100
Infrared temperature
sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PL
II
10 to
70°C
60 to
120
°C
115
to
165
°C
140
to
260
°C
Analog
input
0 to
50 mV
2300
2300
E5CN
E5CN-U (48 x 48 mm)
E5CN/E5CN-U
1800
1800
1700 1700
1700
1600
1300
1300
1300
1300
Usable
in the
following
ranges
by
scaling:
−1999 to
9999 or
−199.9
to 999.9
1200
1100
900
850
850
850
800
700
600
600
500.0
500
500.0
500.0
400.0
400
400
400.0
400
400.0
260
300
200
100.0
100
0.0
−100.0
Setting
number
165
90
100
0
−200.0
100.0
120
E5CN-H (48 x 48 mm)
1000
0.0
−20.0 −100 −20.0
−200 −199.9
0
1
−199.9
2
3
−200
4
5
−200 −199.9 −200
6
7
8
9
10
11
12
13
14
15
Current
4 to 20mA
Voltage
0 to 20 mA
1 to 5 V
0 to 5 V
0 to 10 V
Setting range
Usable in the following ranges by scaling:
−1999 to 9999, −199.9 to 999.9, −19.99 to 99.99 or −1.999 to 9.999
Setting number
0
1
2
16
17
0
0
0
0
0
0
18
24
25
19
20
21
22
23
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously
Engelhard)
Models with Analog Inputs
Input Type
0
−200 −199.9 −200
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
Input specification
0
−100
3
4
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Temperature range (°C)
1400
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
1500
Safety Precautions
Operation
Shaded settings are the default settings.
9
E5CN
E5CN-U (48 x 48 mm)
E5CN/E5CN-U
Alarm Outputs
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Set
value
0
1
✽1
2
3
4
Safety Precautions
Operation
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
✽1
10
5
✽1
Alarm output operation
Alarm type
Alarm function
OFF
When X is
positive
ON
OFF
Upper limit
ON
OFF
Upper- and lowerlimit range
Upper- and lowerlimit with standby
sequence
Absolute-value
upper-limit
ON
OFF
9
Absolute-value
lower-limit
ON
OFF
10
Absolute-value
upper-limit with
standby sequence
ON
OFF
Absolute-value
lower-limit with
standby sequence
ON
OFF
11
12
LBA
(for alarm 1 only)
---
13
PV change rate
alarm
---
H
✽2
ON
OFF
H SP
H < 0, L > 0
H < L
X
H
SP L H
H > 0, L < 0
H > L
H
SP
L
H < 0, L > 0
H ≥ L
L SP
SP H
SP
L
✽3. Set value: 4, Upper- and lower-limit range
X
Case 1
SP
L
Case 3 (Always OFF)
Case 2
H SP
H < 0, L > 0
H < L
H
SP L
H
H
H > 0, L < 0
H > L
H
SP
L
L SP
✽4
SP
SP H L
X
SP
X
SP
X
0
X
0
X
0
X
0
H > 0, L < 0
H ≤ L
H < 0, L < 0
✽3
SP
L
Case 3 (Always ON)
H < 0, L < 0
L
ON
OFF
SP
L
✽5
ON
OFF
8
X
ON
OFF
Lower-limit with
standby sequence
7
X
SP
ON
OFF
ON
OFF
H
SP
ON
OFF
Upper-limit with
standby sequence
6
L
Case 2
Case 1
Output OFF
Upper- and lowerlimit
Lower limit
When X is
negative
✽1. With set values 1, 4 and 5, the upper and lower limit values can
be set independently for each alarm type, and are expressed as
“L” and “H.”
✽2. Set value: 1, Upper- and lower-limit alarm
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
H < 0, L > 0
H ≥ L
H > 0, L < 0
H ≤ L
✽4. Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above
X
SP
X
SP
X
0
X
0
X
0
X
0
• Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
• Case 3: Always OFF
✽5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
E5CN
E5CN-U (48 x 48 mm)
E5CN/E5CN-U
Characteristics
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Influence of voltage ✽2
Input sampling period
250 ms
Hysteresis
Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) ✽4
Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) ✽4
Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0 to 3999 s (in units of 1 s)
Derivative time (D)
0 to 3999 s (in units of 1 s) ✽5
Control period
0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
−1999 to 9999 (decimal point position depends on input type)
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Vibration
resistance
Malfunction
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Destruction
10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
Shock
resistance
Malfunction
100 m/s2, 3 times each in X, Y, and Z directions
Destruction
300 m/s2, 3 times each in X, Y, and Z directions
E5CN
Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g
E5CN-U
Controller: Approx. 110 g, Mounting Bracket: Approx. 10 g
E5CN
Front panel: IP66, Rear case: IP20, Terminals: IP00
Degree of
protection
E5CN-U
Front panel: IP50, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool
CX-Thermo version 4.0 or higher
Setup Tool port
Provided on the bottom of the E5CN. Use this port to connect a computer to the E5CN when using the Setup Tool. An
E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN. ✽6
Standards
EMC
Approved
standards ✽7
UL 61010-1, CSA C22.2 No. 1010-1
Conformed
standards
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMI:
Radiated Interference Electromagnetic Field Strength:
Noise Terminal Voltage:
EMS:
ESD Immunity:
Electromagnetic Field Immunity:
Burst Noise Immunity:
Conducted Disturbance Immunity:
Surge Immunity:
Power Frequency Magnetic Field Immunity:
Voltage Dip/Interrupting Immunity:
Operation
Weight
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Affect of signal source resis- Thermocouple: 0.1°C/Ω max. (100 Ω max.)
tance
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
E5CN-H (48 x 48 mm)
Influence of temperature ✽2
Thermocouple input (R, S, B, W, PL II):
Terminal block models (E5CN): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Plug-in models (E5CN-U): (±2% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: ✽3
Terminal block models (E5CN): (±1% of PV or ±4°C, whichever is greater) ±1 digit max.
Plug-in models (E5CN-U): (±2% of PV or ±4°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer input:
Terminal block models (E5CN) and plug-in models (E5CN-U):
(±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input:
Terminal block models (E5CN) and plug-in models (E5CN-U): (±1%FS) ±1 digit max.
EN 61326
EN 55011 Group 1, class A
EN 55011 Group 1, class A
EN 61326
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
EN 61000-4-5
EN 61000-4-8
EN 61000-4-11
✽1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U and L
thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified.
The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature
of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C, whichever is greater, ±1 digit max. The indication
accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max.
✽2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
✽3. K thermocouple at −100°C max.: ±10° max.
✽4. “EU” stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is °C or °F.
✽5. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s).
✽6. External communications (RS-485) and cable communications for the Setup Tool can be used at the same time.
✽7. The E5CN-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket.
The P3GA-11 is not certified for UL listing.
Safety Precautions
Indication accuracy
Thermocouple: ✽1
Terminal block models (E5CN): (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max.
Plug-in models (E5CN-U): (±1% of indicated value or ±2°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer input:
Terminal block models (E5CN) and plug-in models (E5CN-U): (±0.2% of indicated value or ±0.8°C, whichever is greater)
±1 digit max.
Analog input:
Terminal block models (E5CN) and plug-in models (E5CN-U): ±0.2% FS ±1 digit max.
CT input:
Terminal block models (E5CN): ±5% FS ±1 digit max.
11
USB-Serial Conversion Cable
Applicable OS
Windows 2000, XP, or Vista
Applicable software
Thermo Mini, CX-Thermo version 4.0 or
higher
Applicable models
E5AN/E5EN/E5CN/E5CN-U/E5AN-H/
E5EN-H/E5CN-H
E5CN-H (48 x 48 mm)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
USB interface standard Conforms to USB Specification 1.1.
DTE speed
38400 bps
Connector
specifications
Computer: USB (type A plug)
Temperature Controller: Setup Tool port
(on bottom of Controller)
Power supply
Bus power (Supplied from USB host
controller.)
Power supply voltage
5 VDC
Current consumption
70 mA
Ambient operating
temperature
0 to 55°C (with no condensation or icing)
Ambient operating
humidity
10% to 80%
Storage temperature
−20 to 60°C (with no condensation or
icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 100 g
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
Communications Specifications
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Transmission line
RS-485: Multipoint
connection method
RS-485 (two-wire, half duplex)
Synchronization
method
Start-stop synchronization
Protocol
CompoWay/F, SYSWAY, or Modbus
Baud rate
1200, 2400, 4800, 9600, 19200, 38400, or
57600 bps
Transmission code ASCII
Operation
Safety Precautions
Communications
Data bit length ✽
7 or 8 bits
Stop bit length ✽
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Frame check sequence (FCS) with SYSWAY
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
Dielectric strength
1,000 VAC for 1 min
Vibration resistance 50 Hz, 98 m/s2
Weight
E54-CT1: Approx. 11.5 g, E54-CT3: Approx.
50 g
Accessories
(E54-CT3 only)
Armatures (2)
Plugs (2)
Heater Burnout Alarms, SSR Failure
Alarms, and Heater Overcurrent Alarms
Models with detection for single-phase
heaters: One input
Models with detection for single-phase
or three-phase heaters: Two inputs
CT input
(for heater current detection)
Maximum heater current 50 A AC
Input current indication
accuracy
±5% FS ±1 digit max.
Heater burnout alarm
setting range ✽1
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
SSR failure alarm setting range ✽2
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms
Heater overcurrent
alarm setting range ✽3
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
✽1. For heater burnout alarms, the heater current will be measured
when the control output is ON, and the output assigned to the
alarm 1 function will turn ON if the heater current is lower than the
set value (i.e., heater burnout detection current value).
✽2. For SSR failure alarms, the heater current will be measured when
the control output is OFF, and the output assigned to the alarm 1
function will turn ON if the heater current is higher than the set
value (i.e., SSR failure detection current value).
✽3. For heater overcurrent alarms, the heater current will be
measured when the control output is ON, and the output assigned
to the alarm 1 function will turn ON if the heater current is higher
than the set value (i.e., heater overcurrent detection current
value).
Electrical Life Expectancy Curve for
Relays (Reference Values)
500
300
100
50
30
Flow control
None
Interface
RS-485
Retry function
None
Communications
buffer
217 bytes
3
Communications
response wait time
0 to 99 ms
Default: 20 ms
1
10
5
✽ The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
12
Current Transformer (Order Separately)
Ratings
Life (× 104 operations)
E5CN
E5CN-U (48 x 48 mm)
E5CN/E5CN-U
E5CN
250 VAC, 30 VDC
(resistive load)
cosφ = 1
0
1
2
3
4
5
6
Switching current (A)
Note: Do not connect a DC load to a Controller with a Long-life Relay
Output.
External Connections
• A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. (If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.)
• Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose.
E5CN
Auxiliary outputs
(relay outputs)
−
+ DO NOT DO NOT
USE
mA
−
USE
−
−
Auxiliary output 1
B
V
DO NOT
USE
Auxiliary output 2
A
+
Analog input
A heater burnout alarm, heater short alarm,
heater overcurrent alarm, or input alarm is
sent to the output to which the alarm 1
function is assigned.
Input power supply
B
+
TC/Pt
universalinput
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
Option Units
E53-CNHH03N2
Communications
(RS-485) and CT2
B(+)
E53-CNHBN2
Event inputs
and CT
11
11
B(+)
12
RS-485
RS-485
A(−)
12
13
CT2
EV1
13
EV2
14
CT1
A(−)
15
Control output 2
−
E53-CN03N2
Communications
(RS-485)
E53-CNH03N2
Communications
(RS-485) and CT
B(+)
B(+)
11
RS-485
A(−)
DO NOT
USE
12
DO NOT
USE
+
13
14
15
E53-CNBN2
Event inputs
11
13
14
CT1
15
A(−)
EV1
12
−
13
EV2
+
14 12 VDC,
External
power supply
20 mA
−
15
11
Control output 2
12
DO NOT
USE
DO NOT
USE
13
DO NOT
USE
15
14
EV1
EV2
DO NOT
USE
DO NOT
USE
12
−
12
13
DO NOT
USE
13
14
DO NOT
USE
12
A(−)
DO NOT
USE
13
14
11
12
13
+
14
External
12 VDC,
power supply
20 mA
14
CT1
−
+
15
E53-CNQBN2
Event Inputs and
Control Output 2
E53-CNQHHN2
Control Output 2
and CT2
11
11
Control output 2
−
12
EV1
13
CT2
EV2
+
14
CT1
CT1
15
B(+)
RS-485
15
E53-CNQHN2
Control Output 2
and CT
+
E53-CNP03N2
Communications (RS-485)
and External Power Supply
E53-CNPHN2
External Power
Supply and CT
External +
11 12 VDC,
power supply
20 mA
11
11
RS-485
12
E53-CNPBN2
Event Inputs and
External Power Supply
11
14
CT1
15
E53-CNQ03N2
Communications
(RS-485) and
Control Output 2
13
14
Control output 2
15
15
12
−
15
E5CN-U
Auxiliary output
250 VAC, 3 A (resistive load)
(Relay outputs)
Control output 1
Relay output
(three terminals used)
SPDT, 250 VAC, 3 A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 21 mA
Current output
4 to 20 mA DC
0 to 20 mA DC
Load: 600 W max.
Control output 1
DO NOT
USE
mA
DO NOT
USE
A
Auxiliary output 1
Auxiliary output 2
(Control output (cooling side))
An input error is sent to the
output to which the alarm 1
function is assigned.
B
V
DO NOT
USE
Analog input
B
TC/Pt
universal input
Note: For the Wiring Socket, purchase the P2CF-11 or PG3A-11 separately.
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Control output 2
Voltage output (for driving SSR)
12 VDC, 21 mA
Input power supply
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
Operation
+
Control output 1
E5CN-H (48 x 48 mm)
Auxiliary outputs (relay outputs)
250 VAC, 3 A
(resistive load)
Safety Precautions
Control output 1
Long-life relay output
250 VAC, 3 A (resistive load)
Relay output
250 VAC, 3 A (resistive load)
Voltage output (for driving SSR)
12 VDC, 21 mA
Current output
0 to 20 mA DC
4 to 20 mA DC
Load: 600 Ω max.
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Controllers
E5CN
E5CN-U (48 x 48 mm)
E5CN/E5CN-U
13
E5CN
E5CN-U (48 x 48 mm)
E5CN/E5CN-U
Nomenclature
E5CN
E5CN-U
Temperature unit
The front panel is the same for the E5CN and E5CN-U.
No.1 display
Operation indicators
No. 2 display
Up Key
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Level Key
Mode Key
Down Key
Dimensions
(Unit: mm)
E5CN
Terminal Models
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
6
48 × 48
Panel Cutout
Mounted Separately
Group Mounted
91
(48 × number of units − 2.5)
78
+1.0
0
1.5
+0.6
0
45
44.8 × 44.8 48.8
58
Group mounting does not
allow waterproofing.
60 min.
+0.6
0
45
Waterproof Mounting Adapter
Packing
(Accessory)
(Accessory)
Terminal Cover
(E53-COV17)
(Accessory)
+0.6
0
45
Note: The terminal block cannot be removed.
E5CN-U
Plug-in Models
(84.7)
70.5
6
48 × 48
• Recommended panel thickness is 1 to
5 mm.
• Group mounting is not possible in the
vertical direction. (Maintain the specified
mounting space between Controllers.)
• To mount the Controller so that it is
waterproof, insert the waterproof packing
onto the Controller.
• When two or more Controllers are
mounted, make sure that the surrounding
temperature does not exceed the
allowable operating temperature
specified in the specifications.
Panel Cutout
Mounted Separately
Group Mounted
14.2
+1.0
0
(48 × number of units − 2.5)
+0.6
0
45
44.8 × 44.8
58
Operation
60 min.
+0.6
0
45
Mounting Adapter
(Accessory)
45
+0.6
0
• Recommended panel thickness is 1 to 5
mm.
• Group mounting is not possible in the
vertical direction. (Maintain the specified
mounting space between Controllers.)
• When two or more Controllers are
mounted, make sure that the surrounding
temperature does not exceed the
allowable operating temperature specified
in the specifications.
Accessories (Order Separately)
USB-Serial Conversion Cable
Safety Precautions
E58-CIFQ1
14
250
USB connector (type A plug)
(2,100)
LED indicator (SD)
LED indicator (RD)
1,765
Serial connector
Waterproof Packing
E53-COV17
Y92S-29 (for DIN 48 × 48)
Order the Waterproof Packing separately if it becomes lost or
damaged.
The Waterproof Packing can be used to achieve an IP66 degree of
protection.
(Deterioration, shrinking, or hardening of the waterproof packing may
occur depending on the operating environment. Therefore, periodic
replacement is recommended to ensure the level of waterproofing
specified in IP66. The time for periodic replacement depends on the
operating environment. Be sure to confirm this point at your site.
Consider one year a rough standard. OMRON shall not be liable for
the level of water resistance if the customer does not perform periodic
replacement.)
The Waterproof Packing does not need to be attached if a waterproof
structure is not required.
Note: The E53-COV10
cannot be used.
48
48.8
22
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Terminal Cover
E5CN
E5CN-U (48 x 48 mm)
E5CN/E5CN-U
Current Transformers
E54-CT1
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
21
15
2.8
5.8 dia.
7.5
Output voltage (Eo) V (r.m.s.)
3
10.5
40
Two, 3.5 dia.
10
30
100 V
50 Hz
∞
10
Distortion
factor 10%
1 kΩ
1
3%
1%
100 mV
100 Ω
10
E54-CT3
RL = 10 Ω
1
2.36 dia.
30
12 dia.
100 µV
9
10
1
10
100 mA
1
E54-CT3 Accessory
Connection Example
Armature
Plug
Lead
• Plug
Output voltage (Eo) V (r.m.s.)
30
18
E54-CT3
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for the
Temperature Controller is 50 A.)
Number of windings: 400±2
Winding resistance: 8±0.8 Ω
15
Approx. 3 dia.
100 1,000 A
100 V
50 Hz
Distortion
factor
10%
3%
1%
∞
10
1 kΩ
500 Ω
1
100 mV
100 Ω
50 Ω
10
RL = 10 Ω
1
100 µV
Approx. 6 dia.
(22)
10
1
10
100 mA
1
10
100 1,000 A
Operation
Two, M3 (depth: 4)
• Armature
10
Thru-current (Io) A (r.m.s.)
40 × 40
Safety Precautions
25
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
Winding resistance: 18±2 Ω
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E54-CT1
E5CN-H (48 x 48 mm)
9.1
Thru-current (Io) A (r.m.s.)
15
E5CN
E5CN-U (48 x 48 mm)
E5CN/E5CN-U
Adapter
Y92F-45
Note: Use this Adapter when the panel has already been prepared for the E5B@.
Fixture (Accessory)
76
4.7
69.6 to 77.6
72 × 72
Mounted to E5CN
Panel (1 to 8 mm)
72 × 72
E5CN-H (48 x 48 mm)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
67 × 67 87
48 × 48
2.2
4.7
77.3 (to back of E5CN)
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-U Wiring Socket
Front-connecting Socket
Eleven, M3.5 × 7.5
sems screws
P2CF-11
3
Terminal Layout/Internal Connections
(Top View)
4.5
7.8
8 7 6 5
Mounting Holes
4
Two, 4.5 dia. mounting holes
35.4
70 max.
Two,
4.5-dia.
holes
4
9
3
10 11 1 2
40±0.2
Note: Can also be mounted to a DIN track.
50 max.
31.2 max.
Operation
Note: A model with finger protection (P2CF-11-E) is also available.
Back-connecting Socket
P3GA-11
27 dia.
4
7
3
Terminal Layout/Internal Connections
(Bottom View)
5 6 7 8
4
45
25.6
Safety Precautions
3
9
2 1 11 10
45
4.5 16.3 6.2
6
8.7
Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets.
2. A Protective Cover for finger protection (Y92A-48G) is also available.
16
• Indication Accuracy
Thermocouple input: ±0.3% of PV (previous models: ±0.5%)
Pt input: ±0.2% of PV (previous models: ±0.5%)
Analog input: ±0.2% FS (previous models: ±0.5%)
• A PV/SV-status display function can be set to automatically
alternate between displaying the status of the Temperature
Controller (auto/manual, RUN/STOP, and alarms) and the PV or
SV.
96 × 96 mm
48 × 96 mm
• Preventive maintenance for relays in the Temperature Controller
E5AN
E5EN
using a Control Output ON/OFF Counter.
• Three-level display that simultaneously displays the PV, SV, and
MV.
• One-touch operation with PF Key that can be assigned to auto/manual, RUN/
Refer to Safety Precautions on page 66.
STOP, or other functions.
Main I/O Functions
E5AN
E5EN
3-level Display ✽
Simultaneously displays set items,
such as the PV, SV, and MV.
Event Inputs
• None
• Two
✽ A 2-level display when shipped from the factory. A
3-level display is activated if parameters are
initialized. For details on the third display level, refer
to the User’s Manual, Basic Type (Cat. No. H156).
Sensor Inputs
• Universal thermocouple/Pt inputs
(Models with temperature inputs)
• Analog current/voltage inputs
(Models with analog inputs)
Sampling Period
• 250 ms
PF Key
(Programmable function key)
Auxiliary Outputs
• Three
Control Output 2
• Voltage output
(for driving SSR)
• Long-life relay
output (hybrid)
• Auto/manual switching
• Temperature Controller
status display
• Simple program function
• Control output ON/OFF
count alarm
• PV change rate alarm
• Models also available with
RS-485 or RS-232C
communications
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Current output
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156)
Operation
4-digit Display
Safety Precautions
Indication Accuracy
• Thermocouple input: ±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input: ±0.2% FS
E5CN
E5CN-U (48 x 48 mm)
New 96 x 96-mm and 48 x 96-mm Basic Temperature Controllers with
Enhanced Functions and Performance.
Improved Indication Accuracy and
Preventive Maintenance Function.
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
(96 x 96 mm and 48 x 96 mm)
E5CN-H (48 x 48 mm)
E5AN/E5EN
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Basic-type Digital Temperature Controller
E5CN/E5AN/E5EN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158)
17
E5AN/E5EN
E5CN
E5CN-U (48 x 48 mm)
Lineup
1 control output
3 auxiliary outputs
2 control outputs
3 auxiliary outputs
1 control output
3 auxiliary outputs
2 control outputs
3 auxiliary outputs
Temperature input
E5AN/E5EN
Basic Type
Terminal block
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Analog input
Note: Models with one control output or two control outputs can be used for heating/cooling control.
Model Number Structure
Model Number Legend
Controllers
Option Units
E5AN/E5EN-@3@M@@-@-500-N
Operation
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
1 2 3 4 5 6
7
8
9
1. Control Output 1
R: Relay output
Q: Voltage output (for driving SSR)
C: Current output
2. Auxiliary Outputs
3: Three outputs
3. Heater Burnout/SSR Failure, Control Output 2, or External
Power Supply for ES1B
Blank: None
Q: Control output 2 (voltage output for driving SSR)
Y: Long-life relay output (hybrid)
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(CT2)
P: Power supply for sensor
4. Option
M: Option Unit can be mounted.
5. Input Type
T: Universal thermocouple/platinum resistance thermometer input
L: Analog current/voltage input
6. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
7. Case Color
Blank: Black
W: Silver
Safety Precautions
8. Terminal Cover
-500: With terminal cover
9. Version
N: Available only to models released after January 2008.
18
E53-@
1
1. Function
EN01: RS-232C communications
EN03: RS-485 communications
AKB: Event input
E5AN/E5EN
E5AN
Controllers with Terminal Blocks
Control output
1
Functions
Heater Power supply Control
burnout
for Sensor output 2
Relay output
E5AN-R3MT-500-N
Voltage output
(for driving SSR)
E5AN-Q3MT-500-N
Current output
Thermocouple
or
Resistance
thermometer
3
100 to
240 VAC
E5AN-C3MT-500-N
Relay output
1
E5AN-R3HMT-500-N
Voltage output
for driving SSR)
1
E5AN-Q3HMT-500-N
Relay output
2
E5AN-R3HHMT-500-N
Voltage output
for driving SSR)
2
E5AN-Q3HHMT-500-N
Relay output
Voltage
output
E5AN-R3QMT-500-N
Voltage output
(for driving SSR)
Voltage
output
E5AN-Q3QMT-500-N
Current output
Voltage
output
E5AN-C3QMT-500-N
E5AN-R3YMT-500-N
Long-life
E5AN-Q3YMT-500-N
relay
output
E5AN-C3YMT-500-N
Relay output
Voltage output
(for driving SSR)
Current output
Black
1/4 DIN
96 × 96 × 78
(W × H × D)
Analog
(current/voltage)
3
Relay output
Sensor Power
E5AN-R3PMT-500-N
Voltage output
(for driving SSR)
Sensor Power
E5AN-Q3PMT-500-N
Relay output
E5AN-R3ML-500-N
Voltage output
(for driving SSR)
E5AN-Q3ML-500-N
Current output
E5AN-C3ML-500-N
Relay output
1
E5AN-R3HML-500-N
Voltage output
1
(for driving SSR)
E5AN-Q3HML-500-N
Long-life
relay
E5AN-Q3YML-500-N
output
Voltage output
(for driving SSR)
24 VAC/
VDC
Thermocouple
or
Resistance
thermometer
100 to
240 VAC
24 VAC/
VDC
E5AN-R3MTD-500-N
Voltage output
(for driving SSR)
E5AN-Q3MTD-500-N
Relay output
E5AN-C3MTD-500-N
1
E5AN-R3HMTD-500-N
Voltage output
1
(for driving SSR)
E5AN-Q3HMTD-500-N
Relay output
2
E5AN-R3HHMTD-500-N
Voltage output
2
(for driving SSR)
E5AN-Q3HHMTD-500-N
Relay output
E5AN-R3MT-W-500-N
Voltage output
(for driving SSR)
E5AN-Q3MT-W-500-N
Current output
Thermocouple or
Resistance
3
thermometer
Silver
Relay output
Current output
3
Model
Relay output
E5AN-C3MT-W-500-N
1
E5AN-R3HMT-W-500-N
Voltage output
1
(for driving SSR)
E5AN-Q3HMT-W-500-N
Relay output
E5AN-R3MTD-W-500-N
Voltage output
(for driving SSR)
E5AN-Q3MTD-W-500-N
Current output
E5AN-C3MTD-W-500-N
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Auxiliary
outputs
E5CN-H (48 x 48 mm)
Input type
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Power
supply
voltage
Operation
Case
color
Safety Precautions
Size
E5CN
E5CN-U (48 x 48 mm)
Ordering Information
19
E5CN
E5CN-U (48 x 48 mm)
E5AN/E5EN
E5EN
Controllers with Terminal Blocks
Size
Case
color
Power
supply
voltage
Input type
Auxiliary
outputs
Control
output 1
Functions
Heater Power supply
burnout
for Sensor
Control
output 2
Relay output
E5EN-R3MT-500-N
Voltage output
(for driving SSR)
E5EN-Q3MT-500-N
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Current output
Relay output
E5CN-H (48 x 48 mm)
Thermocouple
or
3
Resistance
thermometer
100 to
240 VAC
1/8 DIN
48 × 96 × 78
(W × H × D)
Analog
(current/voltage)
Safety Precautions
20
3
24 VAC/
VDC
Thermocouple
or
3
Resistance
thermometer
100 to
240 VAC
E5EN-R3HMT-500-N
Voltage output
1
(for driving SSR)
E5EN-Q3HMT-500-N
Relay output
2
E5EN-R3HHMT-500-N
Voltage output
2
(for driving SSR)
E5EN-Q3HHMT-500-N
Relay output
Voltage
output
E5EN-R3QMT-500-N
Voltage output
(for driving SSR)
Voltage
output
E5EN-Q3QMT-500-N
Current output
Voltage
output
E5EN-C3QMT-500-N
Relay output
Long-life
E5EN-R3YMT-500-N
relay output
Voltage output
(for driving SSR)
Long-life
E5EN-Q3YMT-500-N
relay output
Current output
Long-life
E5EN-C3YMT-500-N
relay output
Relay output
Sensor Power
E5EN-R3PMT-500-N
Voltage output
(for driving SSR)
Sensor Power
E5EN-Q3PMT-500-N
Relay output
E5EN-R3ML-500-N
Voltage output
(for driving SSR)
E5EN-Q3ML-500-N
Current output
Relay output
24 VAC/
VDC
E5EN-C3ML-500-N
1
1
E5EN-Q3HML-500-N
Relay output
E5EN-R3MTD-500-N
Voltage output
(for driving SSR)
E5EN-Q3MTD-500-N
Current output
Relay output
E5EN-C3MTD-500-N
1
E5EN-R3HMTD-500-N
Voltage output
1
(for driving SSR)
E5EN-Q3HMTD-500-N
Relay output
2
E5EN-R3HHMTD-500-N
Voltage output
2
(for driving SSR)
E5EN-Q3HHMTD-500-N
Relay output
E5EN-R3MT-W-500-N
Voltage output
(for driving SSR)
E5EN-Q3MT-W-500-N
Relay output
3
E5EN-R3HML-500-N
Long-life
E5EN-Q3YML-500-N
relay output
Current output
Thrmocouple
or
Resistance
thermometer
Silver
E5EN-C3MT-500-N
1
Voltage output
(for driving SSR)
Operation
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Black
Model
E5EN-C3MT-W-500-N
1
E5EN-R3HMT-W-500-N
Voltage output
1
(for driving SSR)
E5EN-Q3HMT-W-500-N
Relay output
E5EN-R3MTD-W-500-N
Voltage output
(for driving SSR)
E5EN-Q3MTD-W-500-N
Current output
E5EN-C3MTD-W-500-N
Option Units
Name
Function
Event Input Unit
E53-EN01
RS-485 communications
E53-EN03
Event inputs
E53-AKB
Accessories (Order Separately)
USB-Serial Conversion Cable
Current Transformers (CTs)
Model
Hole diameter
Model
E58-CIFQ1
5.8 dia.
E54-CT1
12.0 dia.
E54-CT3
Terminal Cover
Connectable models
E5AN
E5EN
Model
E53-COV16
CX-Thermo Support Software
Model
EST2-2C-MV4
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Communications Unit
Model
RS-232C communications
E5CN
E5CN-U (48 x 48 mm)
E5AN/E5EN
Note: The Terminal Cover comes with the E5CN-@@@-500 models.
E5EN
Y92S-P5
Note: The Waterproof Packing is included with the Controller.
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Y92S-P4
Operation
Model
E5AN
Safety Precautions
Connectable models
E5CN-H (48 x 48 mm)
Waterproof Packing
21
E5AN/E5EN
Ratings
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range
85% to 110% of rated supply voltage
Power
100 to 240 VAC: 10 VA
consumption
24 VAC/VDC: 5.5 VA (24 VAC)/4 W (24 VDC)
Models with temperature inputs
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Sensor input
Voltage input: 0 to 50 mV
Models with analog inputs
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Input impedance
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
Control method
ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,
Relay output
10 mA
Voltage output
Output voltage: 12 VDC ±15% (PNP), max. load current: 40 mA,
With short-circuit protection circuit: Max. load current of 21 mA for control output 2
Control (for driving SSR)
output
Current output
4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply voltage: 75
Long-life relay outto 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA, leakage current: 5 mA
put
max. (250 VAC, 60 Hz)
Number of outputs
3
Auxiliary
Output specificaRelay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable
output
tions
load: 5 V, 10 mA
Number of inputs
2
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Event
External contact ininput
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
put specifications
Current flow: Approx. 7 mA per contact
External power supply for ES1B 12 VDC ±10%, 20 mA, short-circuit protection circuit provided
Setting method
Digital setting using front panel keys
11-segment digital display and individual indicators (7-segments displays also possible)
Character height: E5AN: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN: PV: 11.8 mm, SV: 8.1 mm,
Indication method
MV: 5.8 mm
Content of 3-level display: PV/SV/MV, PV/SV/multi-SP, or soak time remain ✽
Number of digits: 4 for PV, SV, and MV
Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial
Multi SP
communications.
Bank switching
Not supported.
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout
detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop,
Other functions
protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic
operations, PV/SV status display, simple program, automatic cooling coefficient adjustment
Ambient operating temperature −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C
Ambient operating humidity
25% to 85%
Storage temperature
−25 to 65°C (with no condensation or icing)
Power supply voltage
✽ A 2-level display when shipped from the factory. A 3-level display is activated if parameters are initialized. For details on the third display level,
refer to the User’s Manual, Basic Type (Cat. No. H156).
Safety Precautions
Operation
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
E5CN
E5CN-U (48 x 48 mm)
Specifications
22
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Input
type
Platinum resistance
thermometer
Name
Pt100
Infrared temperature
sensor
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W
PL
II
10 to
70°C
60 to
120
°C
115
to
165
°C
140
to
260
°C
Analog
input
0 to
50 mV
2300
2300
E5CN
E5CN-U (48 x 48 mm)
E5AN/E5EN
1800
1800
1700 1700
1700
1600
1300
1300
1300
1300
Usable
in the
following
ranges
by
scaling:
−1999 to
9999 or
−199.9
to 999.9
1200
1100
900
850
850
850
800
700
600
600
500.0
500
500.0
500.0
400.0
400
400
400.0
400
400.0
260
300
200
100.0
100
0.0
−100.0
Setting
number
165
90
100
0
−200.0
100.0
120
0.0
−20.0 −100 −20.0
−200 −199.9
0
1
−199.9
2
3
−200
4
5
−200 −199.9 −200
6
7
8
9
10
11
12
13
14
15
Current
4 to 20mA
Voltage
0 to 20 mA
1 to 5 V
0 to 5 V
0 to 10 V
Setting range
Usable in the following ranges by scaling:
−1999 to 9999, −199.9 to 999.9, −19.99 to 99.99 or −1.999 to 9.999
Setting number
0
1
2
16
17
0
0
0
0
0
0
18
24
25
19
20
21
22
23
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously
Engelhard)
Models with Analog Inputs
Input type
0
−200 −199.9 −200
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
Input specification
0
−100
3
4
E5CN-H (48 x 48 mm)
1000
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Temperature range (°C)
1400
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
1500
Safety Precautions
Operation
Shaded settings are the default settings.
23
E5CN
E5CN-U (48 x 48 mm)
E5AN/E5EN
Alarm Outputs
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Set
value
1
✽1
Upper- and
lower-limit
ON
OFF
2
Upper limit
ON
OFF
3
E5CN-H (48 x 48 mm)
5
✽1
6
7
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
8
Operation
When X is
positive
Alarm function
OFF
✽1
Safety Precautions
Alarm type
0
4
24
Alarm output operation
9
10
11
Lower limit
Upper- and
lower-limit range
Upper- and
lower-limit with
standby
sequence
When X is
negative
X
SP
X
L
✽2
L
ON
OFF
ON
OFF
SP
ON
OFF
H
L
ON
OFF
Lower-limit with
standby
sequence
ON
OFF
Absolute-value
upper-limit
ON
OFF
Absolute-value
lower-limit
ON
OFF
Absolute-value
upper-limit with
standby
sequence
ON
OFF
Absolute-value
lower-limit with
standby
sequence
ON
OFF
12
LBA (for alarm 1
--only)
13
PV change rate
alarm
---
X
0
X
0
X
0
X
0
L
H < 0, L > 0
H ≥ L
L SP
SP H
L
Case 1
Case 3 (Always OFF)
Case 2
H < 0, L < 0
✽3
L
H SP
H < 0, L > 0
H < L
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
H > 0, L < 0
H ≤ L
✽3. Set value: 4, Upper- and lower-limit range
X
SP
SP L
H
H
H > 0, L < 0
H > L
H
SP
L
L SP
SP H L
X
SP
H
SP
✽4
SP
X
H > 0, L < 0
H > L
SP
H
SP
H
SP L H
X
✽5
Upper-limit with
standby
sequence
H SP
H < 0, L > 0
H < L
SP
ON
OFF
Case 3 (Always ON)
H < 0, L < 0
H
SP
ON
OFF
Case 2
Case 1
Output OFF
L
✽1. With set values 1, 4 and 5, the upper and lower limit values can
be set independently for each alarm type, and are expressed as
“L” and “H.”
✽2. Set value: 1, Upper- and lower-limit alarm
H < 0, L > 0
H ≥ L
H > 0, L < 0
H ≤ L
✽4. Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above
X
SP
X
SP
X
0
X
0
X
0
X
0
• Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
• Case 3: Always OFF
✽5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
E5CN
E5CN-U (48 x 48 mm)
E5AN/E5EN
Characteristics
Thermocouple: (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1
Platinum resistance thermometer: (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Transfer output accuracy ±0.3% FS max.
Influence of temperature Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
✽2
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. ✽3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage ✽2
Analog input: (±1%FS) ±1 digit max.
Input sampling period
250 ms
Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1
Hysteresis
EU) ✽4
Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS)
Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1
Proportional band (P)
EU) ✽4
Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0 to 3999 s (in units of 1 s)
Derivative time (D)
0 to 3999 s (in units of 1 s) ✽5
Control period
0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
−1999 to 9999 (decimal point position depends on input type)
Affect of signal source
Thermocouple: 0.1°C/Ω max. (100 Ω max.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
resistance
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Malfunction
10
to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
resistance Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
resistance Destruction 300 m/s2, 3 times each in X, Y, and Z directions
EMC
E5CN-H (48 x 48 mm)
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Approved
standards
Standards
Conformed
standards
UL 61010-1, CSA C22.2 No. 1010-1
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMI:
EN 61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EN 55011 Group 1, class A
EMS:
EN 61326
ESD Immunity:
EN 61000-4-2
Electromagnetic Field Immunity:
EN 61000-4-3
Burst Noise Immunity:
EN 61000-4-4
Conducted Disturbance Immunity:
EN 61000-4-6
Surge Immunity:
EN 61000-4-5
Power Frequency Magnetic Field Immunity:
EN 61000-4-8
Voltage Dip/Interrupting Immunity:
EN 61000-4-11
✽1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U
and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S
thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C,
whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max.
✽2. Ambient temperature: −10°C to 23°C to 55°, Voltage range: −15% to 10% of rated voltage
✽3. K thermocouple at −100°C max.: ±10°C max.
✽4. “EU” stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is °C or °F.
✽5. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s).
✽6. External communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the same time.
Operation
Setup Tool port
Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g
Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g
Front panel: IP66, Rear case: IP20, Terminals: IP00
Non-volatile memory (number of writes: 1,000,000 times)
CX-Thermo version 4.0 or higher
Provided on the bottom of the E5AN and E5EN.
An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN and E5EN ✽6
Safety Precautions
E5AN
E5EN
Degree of protection
Memory protection
Setup Tool
Weight
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Indication accuracy
25
Applicable OS
Windows 2000, XP, or Vista
Applicable software
Thermo Mini, CX-Thermo version
4.0 or higher
Applicable models
E5AN/E5EN/E5CN/E5CN-U/E5ANH/E5EN-H/E5CN-H
USB interface standard
Conforms to USB Specification 1.1.
DTE speed
38400 bps
Connector specifications
Computer: USB (type A plug)
Temperature Controller: Setup Tool
port (on bottom of Controller)
Power supply
Bus power (Supplied from USB host
controller.)
Power supply voltage
5 VDC
Current consumption
70 mA
Ambient operating temperature
0 to 55°C (with no condensation or
icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 100 g
Communications Specifications
Transmission line
connection method
RS-485: Multipoint
RS-232C: Point-to-point
Communications
RS-485 (two-wire, half duplex) or RS232C
Synchronization method Start-stop synchronization
Operation
Safety Precautions
Storage temperature
−20 to 60°C (with no condensation
or icing)
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
Ambient operating humidity 10% to 80%
Protocol
CompoWay/F, SYSWAY, or Modbus
Baud rate
1200, 2400, 4800, 9600, 19200, 38400,
or 57600 bps
Transmission code
ASCII
Data bit length ✽
7 or 8 bits
Stop bit length ✽
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Frame check sequence (FCS) with
SYSWAY
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
Flow control
None
Interface
RS-485, RS-232C
Retry function
None
Communications buffer
217 bytes
Communications
response wait time
0 to 99 ms
Default: 20 ms
✽ The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
26
Current Transformer (Order Separately)
Ratings
Dielectric strength
1,000 VAC for 1 min
Vibration resistance 50 Hz, 98 m/s2
Weight
E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Accessories
(E54-CT3 only)
Armatures (2)
Plugs (2)
Heater Burnout Alarms, SSR Failure
Alarms, and Heater Overcurrent Alarms
CT input (for heater current detection)
Models with detection for singlephase heaters: One input
Models with detection for singlephase or three-phase heaters: Two
inputs
Maximum heater current
50 A AC
Input current indication
accuracy
±5% FS ±1 digit max.
Heater burnout alarm setting range ✽1
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
SSR failure alarm setting
range ✽2
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms
Heater overcurrent alarm
setting range ✽3
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
✽1. For heater burnout alarms, the heater current will be measured
when the control output is ON, and the output assigned to the
alarm 1 function will turn ON if the heater current is lower than the
set value (i.e., heater burnout detection current value).
✽2. For SSR failure alarms, the heater current will be measured when
the control output is OFF, and the output assigned to the alarm 1
function will turn ON if the heater current is higher than the set
value (i.e., SSR failure detection current value).
✽3. For heater overcurrent alarms, the heater current will be
measured when the control output is ON, and the output assigned
to the alarm 1 function will turn ON if the heater current is higher
than the set value (i.e., heater overcurrent detection current
value).
Electrical Life Expectancy Curve for
Relays (Reference Values)
Life (× 104 operations)
USB-Serial Conversion Cable
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
E5CN
E5CN-U (48 x 48 mm)
E5AN/E5EN
500
300
E5AN/E5EN
250 VAC, 30 VDC
(resistive load)
cosφ = 1
100
50
30
10
5
3
1
0
1
2
3
4
5
6
Switching current (A)
Note: Do not connect a DC load to a Controller with a Long-life Relay
Output.
E5AN/E5EN
• A voltage output (control output 1, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.
The voltage output (control output 2, for driving SSR) has basic insulation provided for the internal circuit.
• Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose.
Controllers
Option Units
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
11
Input power supply
2
12
3
13
4
14
Control output 1
CT1/CT2 Control Output 2
+
15
6
16
7
17
DO NOT
USE
8
18
DO NOT
USE
9
19
10
20
Control output 2
Relay outputs
250 VAC, 3 A
13
EV2
EV
CT1/CT2
+
-
DO NOT
USE
A
B
External power supply
12 VDC, 20 mA
DO NOT
USE
DO NOT
USE
B
TC/Pt multi-input
Auxiliary output
1, 2, 3
DO NOT USE
12
External Power Supply
-
CT2
Auxiliary output 1
13
11
EV1
5
Auxiliary output 2
12 VDC, 21 mA
Long-life relay output
250 VAC, 3 A
(resistive load)
EV2
CT1
Auxiliary output 3
Control output 2
Voltage output
(for driving SSR)
Event Inputs
E53-AKB
Event inputs
V
mA
DO NOT
USE
Analog input
A heater burnout alarm, heater short alarm,
heater overcurrent alarm, or input alarm is
sent to the output to which the alarm 1
function is assigned.
E5CN-H (48 x 48 mm)
1
E53-EN03
RS-485
B (+)
11
12
A (−)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Communications
E53-EN01
RS-232C
11
SD
12
RD
13
SG
Control output 1
Relay output
250 VAC, 5A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 40 mA
Current output
0 to 20 mA DC
4 to 20 mA DC
Load: 600 Ω max.
E5CN
E5CN-U (48 x 48 mm)
External Connections
Safety Precautions
Operation
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
(resistive load)
27
E5AN/E5EN
E5CN
E5CN-U (48 x 48 mm)
Nomenclature
E5AN
E5EN
Temperature unit
Operation indicators
SUB1
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Programmable
Function Key/
Auto/Manual Key
MV
OUT1
STOP
OUT2
CMW MANU
SUB3
PV
Temperature unit
HA
SV
No.1 display
SV
No. 2 display
No. 3 display
OUT1 STOP
Operation indicators
MV
OUT2 CMW MANU
Up Key
A/M
PF
Level Key
No.3 display
A/M
Programmable
Function Key/
Auto/Manual Key
E5EN
Down Key
E5AN
No.2 display
Up Key
Mode Key
PF
Level Key
Down Key
Mode Key
✽ A 2-level display when shipped from the factory. A 3-level display is activated if parameters are initialized. For details on the third display level,
refer to the User’s Manual, Basic Type (Cat. No. H156).
Dimensions
(Unit: mm)
E5AN
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
HA
No.1 display
SUB3
Operation indicators
SUB1 SUB2
PV
SUB2
Mounted Separately
92
6
Group Mounted
+1.0
0
+0.8
0
(96 × number of units − 3.5)
79.2
2
+0.8
0
92
Safety Precautions
Operation
96 × 96
28
112
91
Group mounting does not allow waterproofing.
120 min.
+0.8
0
92
Waterproof
Packing
(Accessory)
Mounting Bracket
(Accessory)
Terminal Cover
(E53-COV16)
(Accessory)
Crimp terminal size: M3.5
• Recommended panel thickness is 1 to
8 mm.
• Group mounting is not possible in the
vertical direction. (Maintain the specified
mounting space between Controllers.)
• To mount the Controller so that it is
waterproof, insert the waterproof packing
onto the Controller.
• When two or more Controllers are
mounted, make sure that the surrounding
temperature does not exceed the
allowable operating temperature specified
in the specifications.
E5EN
Mounted Separately
6
+0.6
0
+1.0
0
2
+0.8
0
92
112
91
Group mounting does not
allow waterproofing.
120 min.
+0.8
0
92
Waterproof
Packing
(Accessory)
Terminal Cover
(E53-COV16)
(Accessory)
Mounting Bracket
(Accessory)
Crimp terminal size: M3.5
• Recommended panel thickness is 1 to 8 mm.
• Group mounting is not possible in the vertical direction.
(Maintain the specified mounting space between
Controllers.)
• To mount the Controller so that it is waterproof, insert the
waterproof packing onto the Controller.
• When two or more Controllers are mounted, make sure that
the surrounding temperature does not exceed the allowable
operating temperature specified in the specifications.
Accessories (Order Separately)
USB-Serial Conversion Cable
E58-CIFQ1
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
96
E5CN-H (48 x 48 mm)
48
45
79.2
Group Mounted
(48 × number of units − 2.5)
E5CN
E5CN-U (48 x 48 mm)
E5AN/E5EN
(2,100)
1,765
LED (SD)
USB connector (type A plug)
LED (RD)
Terminal Covers
1.2
E53-COV16 (Six Covers provided.)
Serial connector
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
250
3.2
Safety Precautions
44.8
Operation
10
29
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
E5CN
E5CN-U (48 x 48 mm)
E5AN/E5EN
Waterproof Packing
Y92S-P4 (for DIN 96 × 96)
Y92S-P5 (for DIN 48 × 96)
Order the Waterproof Packing separately if it becomes lost or
damaged.
The Waterproof Packing can be used to achieve an IP66 degree of
protection.
(Deterioration, shrinking, or hardening of the waterproof packing may
occur depending on the operating environment. Therefore, periodic
replacement is recommended to ensure the level of waterproofing
specified in IP66. The time for periodic replacement depends on the
operating environment. Be sure to confirm this point at your site.
Consider one year a rough standard. OMRON shall not be liable for
the level of water resistance if the customer does not perform periodic
replacement.)
The Waterproof Packing does not need to be attached if a waterproof
structure is not required.
Current Transformers
E54-CT1
21
E5CN-H (48 x 48 mm)
15
E54-CT1
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
2.8
5.8 dia.
7.5
3
Output voltage (Eo) V (r.m.s.)
25
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
Winding resistance: 18±2 Ω
10.5
40
Two, 3.5 dia.
10
30
100 V
50 Hz
∞
10
Distortion
factor 10%
1 kΩ
1
3%
1%
100 mV
100 Ω
E54-CT3
12 dia.
10
1
10
100 mA
1
40 × 40
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for an OMRON
Temperature Controller is 50 A.)
Number of windings: 400±2
Winding resistance: 8±0.8 Ω
E54-CT3 Accessory
Connection Example
Armature
Plug
Approx. 3 dia.
Lead
18
100 V
50 Hz
Distortion
factor
10%
3%
1%
∞
10
1 kΩ
500 Ω
1
100 mV
100 Ω
50 Ω
10
RL = 10 Ω
• Plug
1
100 µV
Approx. 6 dia.
30
100 1,000 A
E54-CT3
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
30
• Armature
10
Thru-current (Io) A (r.m.s.)
15
Operation
100 µV
9
Two, M3 (depth: 4)
Safety Precautions
RL = 10 Ω
1
2.36 dia.
30
Output voltage (Eo) V (r.m.s.)
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
10
(22)
10
1
10
100 mA
1
10
100 1,000 A
Thru-current (Io) A (r.m.s.)
48 × 48 mm
E5CN-H
Refer to Safety Precautions on page 66.
Main I/O Functions
Event Inputs
• None
• Two
E5CN-H
2-level Display: PV and SV
Universal Sensor Inputs
• Universal thermocouple/Pt/analog
(current/voltage) inputs.
Indication Accuracy
• Thermocouple/Pt input: ±0.1% of PV
• Analog input: ±0.1% FS
Sampling Period
• 60 ms
Auxiliary Outputs
• Two
Control Output 2
• None
• Voltage output
(for driving SSR)
5-digit Display with high resolution of 0.01°C
• Auto/manual switching
• Temperature Controller status display
• Simple program function
• Logic operations
• Control output ON/OFF count alarm
• PV change rate alarm
• Models also available with RS-485 or
RS-232C communications
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157)
E5CN
E5CN-U (48 x 48 mm)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
• High-resolution display with 5 digits/0.01°C display in a compact
Controller (48 x 48 mm).
• High-speed sampling cycle of 60 ms.
• High Accuracy
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
• Universal inputs on all models (thermocouple, PT, or analog input)
to handle various sensors with one Controller.
• A PV/SV-status display function can be set to automatically alternate
between displaying the status of the Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV.
• Flexible contact outputs with logic operations (AND, OR, and delays)
set from the Support Software (CX-Thermo Ver. 4.0)
• Preventive maintenance for relays in the Temperature Controller
using a Control Output ON/OFF Counter.
E5CN-H (48 x 48 mm)
A New High-performance Controller: High Resolution, High Speed, and
High Input Accuracy.
Logic Operations and Preventive
Maintenance Function.
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
(48 x 48 mm)
Operation
E5CN-H
Safety Precautions
Advanced Digital Temperature Controller
E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)
31
E5CN-H
E5CN
E5CN-U (48 x 48 mm)
Lineup
E5CN-H
Terminal block
Advanced Type
1 control output
2 auxiliary outputs
2 control outputs
2 auxiliary outputs
Fully universal input
Note: Models with one control output and models with two control outputs can be used for heating/cooling control.
Model Number Structure
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Model Number Legend
Controllers
Option Units
E5CN-@@@M@-@-500
1 2 3 4 5
6
7
E53-@@@@
1 2 3 4
1. Type
H: Advanced
1. Applicable Controller
CN: E5CN-H or E5CN
2. Control Output 1
R: Relay output
Q: Voltage output (for driving SSR)
C: Current output
V: Linear voltage output
2. Function 1
Blank: None
Q: Control output 2 (voltage output for driving SSR)
P: Power supply for sensor
C: Current output
3. Auxiliary Outputs
2: Two outputs
3. Function 2
Blank: None
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(CT2)
B: Two event inputs
03: RS-485 communications
H03: Heater burnout/SSR failure/Heater overcurrent detection
(CT1) + RS-485 communications
HB: Heater burnout/SSR failure/Heater overcurrent detection
(CT1) + Two event inputs
HH03: Heater burnout/SSR failure/Heater overcurrent detection
(CT2) + RS-485 communications
H01: Heater burnout/SSR failure/Heater overcurrent detection
(CT1)/RS-232C communications
F: Transfer output
BF: Two event inputs/Transfer output
4. Option 1
M: Option Unit can be mounted.
5. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
6. Case Color
Blank: Black
W: Silver
7. Terminal Cover
-500: With terminal cover
4. Version
N2: Available only to models released after January 2008
Safety Precautions
Operation
Note: Not all combinations of function 1 and function 2 specifications are possible for Option Units (E53-@@@@).
32
E5CN-H
Size
Case Color
Power supply voltage
100 to 240 VAC
Auxiliary output
2
Black
24 VAC/VDC
1/16 DIN
48 × 48 × 78
(W × H × D)
2
100 to 240 VAC
2
Silver
24 VAC/VDC
2
Control output 1
Model
Relay output
E5CN-HR2M-500
Voltage output (for driving SSR)
E5CN-HQ2M-500
Current output
E5CN-HC2M-500
Linear voltage output
E5CN-HV2M-500
Relay output
E5CN-HR2MD-500
Voltage output (for driving SSR)
E5CN-HQ2MD-500
Current output
E5CN-HC2MD-500
Linear voltage output
E5CN-HV2MD-500
Relay output
E5CN-HR2M-W-500
Voltage output (for driving SSR)
E5CN-HQ2M-W-500
Current output
E5CN-HC2M-W-500
Relay output
E5CN-HR2MD-W-500
Voltage output (for driving SSR)
E5CN-HQ2MD-W-500
Current output
E5CN-HC2MD-W-500
Option Units
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Controllers
E5CN
E5CN-U (48 x 48 mm)
Ordering Information
One of the following Option Units can be mounted to provide the E5CN with additional functions.
Heater burnout/SSR failure/
Heater overcurrent detection
E53-CNHH03N2
Event inputs
Communications
RS-485
E53-CNHBN2
Control output 2
(Voltage for driving SSR)
Communications
RS-485
E53-CNQ03N2
Heater burnout/SSR failure/
Heater overcurrent detection
E53-CNH03N2
Communications
RS-485
E53-CN03N2
Event inputs
E53-CNBN2
Heater burnout/SSR failure/
Heater overcurrent detection
Control output 2
(Voltage for driving SSR)
E53-CNQHN2
3-phase heater burnout/SSR failure/
Heater overcurrent detection
Control output 2
(Voltage for driving SSR)
E53-CNQHHN2
Control output 2
Event inputs (Voltage for driving SSR)
Control output 2
(Voltage for driving SSR) Transfer Output
E53-CNQFN2
Transfer Output
E53-CNBFN2
Event inputs
Communications
RS-232C
E53-CNQBN2
Control output 2
(Voltage for driving SSR)
E53-CNQ01N2
Communications
RS-232C
Communications
RS-232C
E53-CN01N2
Heater burnout/SSR failure/
Heater overcurrent detection
E5CN-H (48 x 48 mm)
Model
3-phase heater burnout/SSR failure/
Heater overcurrent detection
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Functions
Communications
RS-485
E53-CNH01N2
Accessories (Order Separately)
USB-Serial Conversion Cable
Adapter
Model
Connectable models
E58-CIFQ1
Model
Terminal type
Y92F-45
Note: Use this Adapter when the panel has been previously prepared for the
E5B@.
Terminal Cover
Operation
Note: These Option Units are applicable only to models released after January 2008.
CX-Thermo Support Software
Model
E53-COV17
Waterproof Packing
Model
Y92S-29
Note: Waterproof Packing is included with the controller only for models with
terminal blocks.
Current Transformers (CTs)
Hole diameter
Model
5.8 dia.
E54-CT1
12.0 dia.
E54-CT3
EST2-2C-MV4
Safety Precautions
Model
Note: 1. The Terminal Cover comes with the E5CN-@@@-500 models.
2. The E53-COV10 cannot be used.
33
E5CN-H
Ratings
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
E5CN
E5CN-U (48 x 48 mm)
Specifications
Power supply voltage
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
100 to 240 VAC: 8.5 VA (max.) (E5CN-HR2 at 100 VAC: 3.0 VA)
24 VAC/VDC: 5.5 VA (24 VAC)/3.5 W (24 VDC) (max.) (E5CN-HR2D at 24 VAC: 2.7 VA)
Sensor input
Any of the following can be selected (i.e., fully universal input).
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Input impedance
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
Control method
Control
output
ON/OFF control or 2-PID control (with auto-tuning)
Relay output
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA
Voltage output
(for driving SSR)
Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection circuit
Current output
4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000 ✽
Linear voltage out0 to 10 VDC (load: 1 kΩ min.), Resolution: Approx. 10,000
put
E5CN-H (48 x 48 mm)
Auxiliary
output
Output specifications
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable
load: 5 V, 10 mA
Number of outputs 2
Event
input
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Logic
operations
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
External contact
input specifications
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Number of operations
8 max. (Combinations can be made using work bits.)
Operations
• Logic operation: Any of the following four patterns can be selected. The input status may be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B,
C, and D are four inputs.)
• Delay:
ON delay or OFF delay for the results of the logic operation given above.
Setting time: 0 to 9999 s or 0 to 9999 min
• Output inversion: Possible
Outputs
One work bit per operation
Work bit assignments
Any of the following can be assigned to up to eight work bits (logic operation results): Event input operations,
auxiliary outputs, or control outputs.
Current flow: Approx. 7 mA per contact
Number of outputs 1 max.
Transfer
outputs Output
Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000
specifications
Operation
Safety Precautions
Number of outputs 2 max.
RSP input
Not supported
Setting method
Digital setting using front panel keys
Indication method
11-segment digital display and individual indicators (7-segments displays also possible)
Character height: PV: 11 mm, SV: 6.5 mm
Bank switching
Supported (number of banks: 8)
Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.)
Other functions
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout
detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop,
protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV
status display, logic operations, automatic cooling coefficient adjustment
Ambient operating temperature
−10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C
Ambient operating humidity
25% to 85%
Storage temperature
−25 to 65°C (with no condensation or icing)
✽ For models with current outputs, control output 1 can be used as a transfer output.
34
Input Ranges
Thermocouple/Platinum Resistance Thermometer/Analog Input (Fully Universal Inputs)
Platinum resistance
thermometer
Input type
Name
Pt100
Analog
input
Thermocouple
JPt100
K
J
T
E
L
U
N
R
S
B
W PL II
4 to
0 to
20 mA 20 mA
1 to
5V
0 to 0 to
5 V 10 V
2300.0
2300
1800.0
1800
E5CN
E5CN-U (48 x 48 mm)
E5CN-H
1700.01700.0
1700
1600
1500
1300.0
1300.0
1200
1100
850.0
850.0
Usable in the following
ranges by scaling:
−19999 to 32400,
−1999.9 to 3240.0,
−199.99 to 324.00, or
−19.999 to 32.400
850.0
800
700
600.0
600
500.0
500
500.0
500.0
400.0
400
300
200.00
200
100
0.0
0.0
200.00
200.00
−50.00
−200.0−199.9
0
1
−20.0 −50.00−100.0 −20.0 −50.00
−199.9
2
24
3
−200.0
4
5
−50.00
−200.0−199.9
6
21
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
7
8
22
9
10
0.0
16
17
0.0
0.0
19
20
−100.0
−200.0
23
0.0
11
−200.0−199.9−200.0
12
13
14
15
18
25
26
27
28
29
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously
Engelhard)
E5CN-H (48 x 48 mm)
−200
100.0
400.0 400.0
100.0
0
−100
Setting
number
200.00
100.0
400.0 400.0
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
900
Operation
1000
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
1300.0
1300
Safety Precautions
Temperature range (°C)
1400
35
E5CN
E5CN-U (48 x 48 mm)
E5CN-H
Alarm Outputs
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Set
value
0
1
✽1
2
3
4
Safety Precautions
Operation
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
✽1
36
5
✽1
Alarm output operation
Alarm type
Alarm function
OFF
When X is
positive
Output OFF
Upper- and lowerlimit
ON
OFF
Upper limit
ON
OFF
Lower limit
Upper- and lowerlimit range
Upper- and lowerlimit with standby
sequence
X
✽2
L
ON
OFF
ON
OFF
SP
H
X
Absolute-value
upper-limit
ON
OFF
9
Absolute-value
lower-limit
ON
OFF
10
Absolute-value
upper-limit with
standby sequence
ON
OFF
Absolute-value
lower-limit with
standby sequence
ON
OFF
12
LBA (for alarm 1
only)
---
13
PV change rate
alarm
---
H
SP L H
H > 0, L < 0
H > L
H
SP
L
H < 0, L > 0
H ≥ L
L SP
SP H
SP
L
Case 1
Case 3 (Always OFF)
Case 2
H < 0, L < 0
✽3
L
H SP
H < 0, L > 0
H < L
✽4
SP L
H
H
H > 0, L < 0
H > L
H
SP
L
L SP
SP H L
X
SP
X
SP
X
0
X
0
X
0
X
0
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
H > 0, L < 0
H ≤ L
✽3. Set value: 4, Upper- and lower-limit range
X
SP
H
SP
H SP
H < 0, L > 0
H < L
SP
L
Case 3 (Always ON)
H < 0, L < 0
L
✽5
ON
OFF
11
X
SP
ON
OFF
Lower-limit with
standby sequence
8
H
Case 2
Case 1
SP
ON
OFF
ON
OFF
7
L
ON
OFF
Upper-limit with
standby sequence
6
When X is
negative
✽1. With set values 1, 4 and 5, the upper and lower limit values can
be set independently for each alarm type, and are expressed as
“L” and “H.”
✽2. Set value: 1, Upper- and lower-limit alarm
X
H < 0, L > 0
H ≥ L
H > 0, L < 0
H ≤ L
✽4. Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above
SP
X
SP
X
0
X
0
X
0
X
0
• Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
• Case 3: Always OFF
✽5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
E5CN
E5CN-U (48 x 48 mm)
E5CN-H
Characteristics
Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1
Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max.
Analog input: ±0.1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Input sampling period
60 ms
Hysteresis
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1 °C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0.0 to 3240.0 s (in units of 0.1 s)
Derivative time (D)
0.0 to 3240.0 s (in units of 0.1 s)
Control period
0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
−19999 to 32400 (decimal point position depends on input type)
Affect of signal source
resistance
Thermocouple: 0.1°C/Ω max. (100 Ω max.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Vibration
resistance
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Shock
resistance
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g
Degree of protection
Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool
CX-Thermo version 4.0 or higher
Setup Tool port
Provided on the bottom of the E5CN-H. Use this port to connect a computer to the E5CN-H.
An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN-H. ✽4
UL 61010-1, CSA C22.2 No. 1010-1
Conformed
standards
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMI:
Radiated Interference Electromagnetic Field Strength:
Noise Terminal Voltage:
EMS:
ESD Immunity:
Electromagnetic Field Immunity:
Burst Noise Immunity:
Conducted Disturbance Immunity:
Surge Immunity:
Power Frequency Magnetic Field Immunity:
Voltage Dip/Interrupting Immunity:
EN 61326
EN 55011 Group 1, class A
EN 55011 Group 1, class A
EN 61326
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
EN 61000-4-5
EN 61000-4-8
EN 61000-4-11
Operation
EMC
Approved
standards
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Destruction 300 m/s2, 3 times each in X, Y, and Z directions
Weight
Standards
E5CN-H (48 x 48 mm)
Influence of voltage ✽2
Thermocouple input (R, S, B, W, PLII): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. ✽3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: (±1%FS) ±1 digit max.
Influence of temperature
✽2
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Transfer output accuracy ±0.3% FS max.
✽1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U
and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S
thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C,
whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max.
✽2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
✽3. K thermocouple at −100°C max.: ±10°C max.
✽4. External communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the same time.
Safety Precautions
Indication accuracy
37
USB-Serial Conversion Cable
Windows 2000, XP, or Vista
Applicable software
Thermo Mini, CX-Thermo version
4.0 or higher
Applicable models
E5AN/E5EN/E5CN/E5CN-U/
E5AN-H/E5EN-H/E5CN-H
USB interface standard
Conforms to USB Specification 1.1.
DTE speed
38400 bps
Connector specifications
Computer: USB (type A plug)
Temperature Controller: Setup Tool
port (on bottom of Controller)
Power supply
Bus power (Supplied from USB
host controller.)
Power supply voltage
5 VDC
Current consumption
70 mA
Dielectric strength
1,000 VAC for 1 min
Vibration resistance
50 Hz, 98 m/s2
Weight
E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Accessories (E54-CT3 only)
Armatures (2)
Plugs (2)
Heater Burnout Alarms, SSR Failure
Alarms, and Heater Overcurrent Alarms
Ambient operating tempera- 0 to 55°C (with no condensation or
ture
icing)
Models with detection for singlephase heaters: One input
Models with detection for singlephase or three-phase heaters: Two
inputs
Maximum heater current
50 A AC
Ambient operating humidity 10% to 80%
Input current indication
accuracy
±5% FS ±1 digit max.
Heater burnout alarm setting range ✽1
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
SSR failure alarm setting
range ✽2
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms
Heater overcurrent alarm
setting range ✽3
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 100 g
Communications
RS-485 (two-wire, half duplex)/RS-232C
Synchronization
method
Start-stop synchronization
Protocol
CompoWay/F, SYSWAY, or Modbus
Baud rate
1200, 2400, 4800, 9600, 19200, 38400, or
57600 bps
Transmission code
ASCII (CompoWay/F, SYSWAY)
RTU (Modbus)
Data bit length ✽
7 or 8 bits
Stop bit length ✽
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Frame check sequence (FCS) with SYSWAY
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
Flow control
None
Interface
RS-485, RS-232C
Retry function
None
Communications
buffer
217 bytes
Communications
response wait time
0 to 99 ms
Default: 20 ms
✽ The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
✽1. For heater burnout alarms, the heater current will be measured
when the control output is ON, and the output assigned to the
alarm 1 function will turn ON if the heater current is lower than the
set value (i.e., heater burnout detection current value).
✽2. For SSR failure alarms, the heater current will be measured when
the control output is OFF, and the output assigned to the alarm 1
function will turn ON if the heater current is higher than the set
value (i.e., SSR failure detection current value).
✽3. For heater overcurrent alarms, the heater current will be
measured when the control output is ON, and the output assigned
to the alarm 1 function will turn ON if the heater current is higher
than the set value (i.e., heater overcurrent detection current
value).
Electrical Life Expectancy Curve for
Relays (Reference Values)
Life (× 104 operations)
Storage temperature
−20 to 60°C (with no condensation
or icing)
Transmission line
RS-485: Multipoint
connection method RS-232C: Point-to-point
38
Current Transformer (Order Separately)
Ratings
CT input (for heater current detection)
Communications Specifications
Operation
Safety Precautions
Applicable OS
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
E5CN
E5CN-U (48 x 48 mm)
E5CN-H
500
300
100
50
30
10
5
E5CN-H
250 VAC, 30 VDC
(resistive load)
cosφ = 1
3
1
0
1
2
3
4
5
6
Switching current (A)
E5CN-H
• A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.
Controllers
Control output 1
6
2
12
7
Auxiliary output 2
DO NOT DO NOT A
USE
USE
mA
B
V
B
DO NOT
USE
A heater burnout alarm, SSR
failure, heater overcurrent alarm,
or input alarm is sent to the
output to which the alarm 1
function is assigned.
Auxiliary output 1
3
13
8
4
14
9
5
15
10
?
Input power supply
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
E53-CNBN2
Event Inputs
E53-CNQBN2
Event Inputs and
Control Output 2
11
EV1
EV2
DO NOT
USE
DO NOT
USE
11
12
13
14
15
E53-CNQHHN2
Control Output 2
and CT2
EV1
13
EV2
Control output 2
12 VDC 21 mA
12 VDC 21 mA
CT2
15
4 to 20 mA DC
(Load 600 Ω
15 max.)
EV1
12
13
EV2
14
Transfer output
15
E53-CN01N2
Communications
(RS-232)
RS-232C
SD
RD
12
14
Transfer output
11
14
SG
DO NOT
13
USE
14
CT1
13
EV2
15
12 VDC 21 mA
Event Inputs and
Transfer Output
12
CT1
11
Control output 2
13
EV1
14
E53-CNQFN2
Control Output 2 and
Transfer Output
E53-CNBFN2
11
12
11
Control output 2
12
E53-CNHBN2
Event Inputs
and CT
11
15
4 to 20 mA DC
(Load 600 Ω max.)
E53-CNH01N2
Communications
(RS-232) and CT
RS-232C
SD
RD
12
SG
13
DO NOT
14
USE
DO NOT
15
USE
E5CN-H (48 x 48 mm)
Option Units
E53-CNQ01N2
Communications (RS-232)
and Control Output 2
RS-232C
SD
11
RD
12
SG
13
14
CT1
15
Control output 2
12 VDC 21 mA
11
12
13
14
15
E53-CN03N2
E53-CNQ03N2
E53-CNH03N2
E53-CNHH03N2
E53-CNQHN2
Communications
(RS-485)
Communications (RS-485)
and Control Output 2
Communications
(RS-485) and CT
Communications
(RS-485) and CT2
Control Output 2
and CT
B (+)
11
RS-485
B (+)
12
A (−)
DO NOT
13
USE
DO NOT
14
USE
DO NOT 15
USE
12
11
RS-485
12
A (−)
DO NOT
13
USE
14
14
A (−)
12
Control output 2
12 VDC 21 mA
13
CT2
15
11
12
DO NOT
13
USE
14
14
CT1
CT1
CT1
15
B (+)
11
RS-485
A (−)
DO NOT
13
USE
Control output 2
12 VDC 21 mA
B (+)
11
RS-485
15
Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly.
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
11
Operation
1
Control output 1
Auxiliary outputs (relay outputs)
250 VAC, 3 A
(resistive load)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Auxiliary outputs
(relay outputs)
15
Safety Precautions
Relay output
250 VAC, 3 A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 21 mA
Linear voltage output
0 to 10 VAC
Load 1 kΩ max.
Current output
0 to 20 mA DC
4 to 20 mA DC
Load 600 Ω max.
E5CN
E5CN-U (48 x 48 mm)
External Connections
39
E5CN-H
E5CN
E5CN-U (48 x 48 mm)
Nomenclature
E5CN-H
Temperature unit
SUB1
SUB2
SUB3
HA
Operation indicators
No. 1 display
OUT1 STOP
No. 2 display
OUT2 CWM MANU
Up Key
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Level Key
E5CN-H
Mode Key
Down Key
Dimensions
(Unit: mm)
E5CN-H
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
6
48 × 48
Panel Cutout
Mounted Separately
Group Mounted
91
(48 × number of units − 2.5)
78
+1.0
0
1.5
+0.6
0
45
44.8 × 44.8 48.8
58
Group mounting does not
allow waterproofing.
60 min.
45
Waterproof
Packing
(Accessory)
Mounting Adapter
(Accessory)
Terminal Cover
(E53-COV17)
(Accessory)
45
+0.6
0
+0.6
0
Note: The terminal block cannot be removed.
• Recommended panel thickness is 1 to
5 mm.
• Group mounting is not possible in the
vertical direction. (Maintain the specified
mounting space between Controllers.)
• To mount the Controller so that it is
waterproof, insert the waterproof packing
onto the Controller.
• When two or more Controllers are mounted,
make sure that the surrounding
temperature does not exceed the allowable
operating temperature specified in the
specifications.
Accessories (Order Separately)
USB-Serial Conversion Cable
E58-CIFQ1
(2,100)
Safety Precautions
Operation
250
40
USB connector (type A plug)
LED indicator
(SD)
1,765
LED indicator (RD)
Serial connector
Waterproof Packing
E53-COV17
Y92S-29 (for DIN 48 × 48)
Order the Waterproof Packing separately if it becomes lost or
damaged.
The Waterproof Packing can be used to achieve an IP66 degree of
protection.
(Deterioration, shrinking, or hardening of the waterproof packing may
occur depending on the operating environment. Therefore, periodic
replacement is recommended to ensure the level of waterproofing
specified in IP66. The time for periodic replacement depends on the
operating environment. Be sure to confirm this point at your site.
Consider one year a rough standard. OMRON shall not be liable for
the level of water resistance if the customer does not perform periodic
replacement.)
The Waterproof Packing does not need to be attached if a waterproof
structure is not required.
Note: The E53-COV10
can not be used.
48
48.8
22
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Terminal Cover
E5CN
E5CN-U (48 x 48 mm)
E5CN-H
9.1
E54-CT1
15
E54-CT1
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
2.8
5.8 dia.
7.5
Output voltage (Eo) V (r.m.s.)
3
10.5
40
Two, 3.5 dia.
10
30
100 V
50 Hz
∞
10
Distortion
factor 10%
1 kΩ
1
3%
1%
100 mV
100 Ω
10
E54-CT3
RL = 10 Ω
1
2.36 dia.
30
12 dia.
100 µV
9
10
1
10
100 mA
1
40 × 40
E54-CT3 Accessory
Connection Example
Armature
Plug
Lead
Output voltage (Eo) V (r.m.s.)
30
18
E54-CT3
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for an OMRON
Temperature Controller is 50 A.)
Number of windings: 400±2
Winding resistance: 8±0.8 Ω
15
Approx. 3 dia.
100 1,000 A
100 V
50 Hz
Distortion
factor
10%
3%
1%
∞
10
1 kΩ
500 Ω
1
100 mV
100 Ω
50 Ω
10
RL = 10 Ω
• Plug
1
100 µV
Approx. 6 dia.
(22)
10
1
10
100 mA
1
10
100 1,000 A
Operation
Two, M3 (depth: 4)
• Armature
10
Thru-current (Io) A (r.m.s.)
Safety Precautions
25
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
Winding resistance: 18±2 Ω
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
21
E5CN-H (48 x 48 mm)
Current Transformers
Thru-current (Io) A (r.m.s.)
41
E5CN
E5CN-U (48 x 48 mm)
E5CN-H
Adapter
Y92F-45
Note: Use this Adapter when the panel has already been prepared for the E5B@.
Fixture (Accessory)
4.7
76
69.6 to 77.6
72 × 72
Mounted to E5CN-H
Safety Precautions
Operation
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
67 × 67 87
42
Panel (1 to 8 mm)
72 × 72
48 × 48
2.2
4.7
77.3 (to back of E5CN-H)
A New High-performance Controller: High Resolution, High Speed, and
High Input Accuracy.
Logic Operations and Preventive Maintenance Function. Plus Infrared
Port on Front Panel.
96 × 96 mm
E5AN-H
48 × 96 mm
E5EN-H
Refer to Safety Precautions on page 66.
Main I/O Functions
E5AN-H
E5EN-H
3-level Display
Simultaneously displays set items, such as the
PV, SV, and MV.
Event Inputs
• None
• Two
• Four
Indication Accuracy
• Thermocouple/Pt input:
±0.1% of PV
• Analog input:
±0.1% FS
Sampling Period
• 60 ms
PF Key
(Programmable
key function)
Infrared port
USB
Auxiliary Outputs
• Two
• Three
Computer Support Software
CX-Thermo
Control Output 2
(built-in)
Output Unit
• SSR outputs
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
Control Output 1
(built-in)
Output Unit
• SSR outputs
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
• Auto/manual switching
• Temperature Controller
status display
• Simple program
function
• Logic operations
• Control output ON/OFF
count alarm
• PV change rate alarm
• Models available with
RS-485, RS-422, or
RS-232C
communications
Operation
Universal Sensor Inputs
• Universal thermocouple/
Pt/analog
(current/voltage) inputs.
5-digit Display with high resolution of 0.01°C
Safety Precautions
Remote SP Input
• One
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
• High-resolution display with 5 digits/0.01×C display.
• High-speed sampling cycle of 60 ms.
• High Accuracy
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
• Universal inputs on all models (thermocouple, PT, or analog input)
to handle various sensors with one Controller. Models also
available with Remote SP.
• A PV/SV-status display function can be set to automatically
alternate between displaying the status of the Temperature
Controller (auto/manual, RUN/STOP, and alarms) and the PV or
SV.
• Flexible contact outputs with logic operations (AND, OR, and
delays) set from the Support Software (CX-Thermo Ver. 4.0)
• Preventive maintenance for relays in the Temperature Controller
using a Control Output ON/OFF Counter.
• Model available with position-proportional control
E5CN
E5CN-U (48 x 48 mm)
(96 x 96 mm and 48 x 96 mm)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
E5AN-H/E5EN-H
E5CN-H (48 x 48 mm)
Advanced Digital Temperature Controller
43
E5AN-H/E5EN-H
E5CN
E5CN-U (48 x 48 mm)
Lineup
E5AN-H/E5EN-H
Advanced Type
Terminal block
1 control output
2 auxiliary outputs
2 control outputs
2 auxiliary outputs
Fully universal input
Note: The Controller can be used for heating/cooling control even if only 1 control output is used.
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Model Number Structure
Model Number Legend
Controllers
Option Units
E5AN/E5EN-@@@@@@@M@-@-500
1 2 3 4 5 6 7 8 9 10
11
1. Type
H: Advanced
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
2. Control Mode
Blank: Standard or heating/cooling control
P: Position-proportional control
E53-@
1
1. Function
EN01: RS-232C communications
EN02: RS-422 communications
EN03: RS-485 communications
AKB: Event input
3. Control Output 1
A: Control Output Unit
R: Relay output
S: SSR output
Output Units
4. Control Output 2
A: Control Output Unit
R: Relay output
S: SSR output
1. Control Output
R: Relay output
Q: Voltage output (for driving SSR)
Q3: Voltage output (for driving SSR) + 24 VDC (NPN)
Q4: Voltage output (for driving SSR) + 24 VDC (PNP)
C3: Current output + 4 to 20 mA DC
C3D: Current output + 0 to 20 mA DC
V34: Linear voltage output + 0 to 10 VDC
V35: Linear voltage output + 0 to 5 VDC
2. Version
Blank: Available for E5AN-H/E5EN-H and E5AK/E5EK.
N: Available only for E5AN-H/E5EN-H.
5. Auxiliary Outputs
2: Two outputs
3: Three outputs
6. Option 1
Blank: None
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(CT2)
E53-@@
1 2
7. Option 2
B: Two event inputs
BF: Event input + Transfer output
Safety Precautions
Operation
8. Option 3
M: Option Unit can be mounted.
9. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
10.Case Color
Blank: Black
W: Silver
11.Terminal Cover
-500: With Terminal Cover
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157)
E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)
44
E5AN-H/E5EN-H
Control output 1/2
Heater
burnout
Optional functions
Event
inputs
2
4 to 20-mA
E5AN-HAA2HBM-500
input
SSR outputs × 2
1
2
4 to 20-mA
E5AN-HSS2HBM-500
input
Control Output Unit × 2
2
2
4 to 20-mA 4 to 20-mA
E5AN-HAA2HHBFM-500
output
input
SSR outputs × 2
2
2
4 to 20-mA 4 to 20-mA
E5AN-HSS2HHBFM-500
output
input
Control Output Unit × 2
2
4 to 20-mA 4 to 20-mA
E5AN-HAA3BFM-500
output
input
SSR outputs × 2
2
4 to 20-mA 4 to 20-mA
E5AN-HSS3BFM-500
output
input
Relay outputs × 2
2
4 to 20-mA
E5AN-HPRR2BM-500
input
Relay outputs × 2
2
4 to 20-mA 4 to 20-mA E5AN-HPRR2BFM-500
output
input
3
2
Black
1/4 DIN
96 × 96 × 78
(W × H × D)
Control Output Unit × 2
1
2
4 to 20-mA E5AN-HAA2HBMD-500
input
SSR outputs × 2
1
2
4 to 20-mA
E5AN-HSS2HBMD-500
input
Control Output Unit × 2
2
2
4 to 20-mA 4 to 20-mA E5AN-HAA2HHBFMD-500
output
input
SSR outputs × 2
2
2
4 to 20-mA 4 to 20-mA E5AN-HSS2HHBFMD-500
output
input
Control Output Unit × 2
2
4 to 20-mA 4 to 20-mA
E5AN-HAA3BFMD-500
output
input
SSR outputs × 2
2
4 to 20-mA 4 to 20-mA E5AN-HSS3BFMD-500
output
input
Relay outputs × 2
2
4 to 20-mA E5AN-HPRR2BMD-500
input
Relay outputs × 2
2
4 to 20-mA 4 to 20-mA
E5AN-HPRR2BFMD-500
output
input
4 to 20-mA E5AN-HAA2HBM-W-500
input
2
Basic
24 VAC/
VDC
3
Valve
Silver
100 to
240 VAC
24 VAC/
VDC
Basic
2
2
Model
1
Basic
Valve
RSP
Control Output Unit × 2
2
100 to
240 VAC
Transfer
output
Control Output Unit × 2
1
2
Control Output Unit × 2
2
2
Control Output Unit × 2
1
2
4 to 20-mA 4 to 20-mA E5AN-HAA2HHBFM-W-500
output
input
4 to 20-mA
E5AN-HAA2HBMD-W-500
input
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Control Auxiliary
method
output
E5CN-H (48 x 48 mm)
Power
supply
voltage
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Case
color
Operation
Size
Safety Precautions
E5AN-H
E5CN
E5CN-U (48 x 48 mm)
Ordering Information
45
E5CN
E5CN-U (48 x 48 mm)
E5AN-H/E5EN-H
E5EN-H
Size
Case
color
Power
supply
voltage
Control
method
Auxiliary
output
Optional Functions
Heater
burnout
Event
inputs
Control Output Unit × 2
1
2
4 to 20-mA
input
E5EN-HAA2HBM-500
SSR outputs × 2
1
2
4 to 20-mA
input
E5EN-HSS2HBM-500
Control Output Unit × 2
2
2
4 to 20-mA
output
4 to 20-mA
input
E5EN-HAA2HHBFM-500
SSR outputs × 2
2
2
4 to 20-mA
output
4 to 20-mA
input
E5EN-HSS2HHBFM-500
Control Output Unit × 2
2
4 to 20-mA
output
4 to 20-mA
input
E5EN-HAA3BFM-500
SSR outputs × 2
2
4 to 20-mA
output
4 to 20-mA
input
E5EN-HSS3BFM-500
Relay outputs × 2
2
4 to 20-mA
input
E5EN-HPRR2BM-500
Relay outputs × 2
2
4 to 20-mA
input
E5EN-HPRR2BFM-500
Control output 1/2
2
Basic
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
100 to
240 VAC
3
Valve
2
Black
E5CN-H (48 x 48 mm)
1/8 DIN
48 × 96 × 78
(W × H × D)
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Silver
Basic
24 VAC/
VDC
4 to 20-mA
input
E5EN-HAA2HBMD-500
SSR outputs × 2
1
2
4 to 20-mA
input
E5EN-HSS2HBMD-500
Control Output Unit × 2
2
2
4 to 20-mA
output
4 to 20-mA
input
E5EN-HAA2HHBFMD-500
SSR outputs × 2
2
2
4 to 20-mA
output
4 to 20-mA
input
E5EN-HSS2HHBFMD-500
Control Output Unit × 2
2
4 to 20-mA
output
4 to 20-mA
input
E5EN-HAA3BFMD-500
SSR outputs × 2
2
4 to 20-mA
output
4 to 20-mA
input
E5EN-HSS3BFMD-500
Relay outputs × 2
2
4 to 20-mA
input
E5EN-HPRR2BMD-500
Relay outputs × 2
2
4 to 20-mA
input
E5EN-HPRR2BFMD-500
4 to 20-mA
input
E5EN-HAA2HBM-W-500
4 to 20-mA
input
E5EN-HAA2HHBFM-W-500
4 to 20-mA
input
E5EN-HAA2HBMD-W-500
2
2
Control Output Unit × 2
1
2
Control Output Unit × 2
2
2
Control Output Unit × 2
1
2
4 to 20-mA
output
4 to 20-mA
output
Accessories (Order Separately)
Output Units
Output unit
Operation
Relay
output
Voltage
output
(for driving
SSR)
Current
output
Safety Precautions
2
3
100 to
240 VAC
4 to 20-mA
output
1
Basic
Valve
Model
RSP
Control Output Unit × 2
2
24 VAC/
VDC
Transfer
output
Linear
voltage
output
USB-Serial Conversion Cable
Model
Specifications
Model
E53-RN
SPST-NO, 250 VAC, 5 A (resistive load),
electrical life: 100,000 operations
E58-CIFQ1
E53-QN
12 VDC (PNP), max. load current:
40-mA, with short-circuit protection
E53-Q3
24 VDC (NPN), max. load current:
20-mA, with short-circuit protection
E53-Q4
24 VDC (PNP), max. load current:
20-mA, with short-circuit protection
E53-C3N
4 to 20-mA DC, load: 600 Ω max.,
resolution: approx. 10,000
E53-C3DN
0 to 20-mA DC, load: 600 Ω max.,
resolution: approx. 10,000
E53-V34N
0 to 10 VDC, load: 1 kΩ min., resolution:
approx. 10,000
E53-V35N
0 to 5 VDC, load: 1 kΩ min., resolution:
approx. 10,000
USB-infrared Conversion Cable
Model
E58-CIFIR
Terminal Cover
Connectable models
Model
E5AN-H
E53-COV16
E5EN-H
Note: The Terminal Cover comes with the E5CN-@@@-500 models.
Waterproof Packing
Connectable models
Model
E5AN-H
Y92S-P4
E5EN-H
Y92S-P5
Note: The Waterproof Packing is included with the Controller.
Current Transformers (CTs)
Hole diameter
Model
5.8 dia.
E54-CT1
12.0 dia.
E54-CT3
CX-Thermo Support Software
Model
EST2-2C-MV4
46
E5AN-H/E5EN-H
E5CN
E5CN-U (48 x 48 mm)
Specifications
Power supply voltage
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
100 to 240 VAC: 12 VA
24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC)
Sensor input
Any of the following can be selected.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Input impedance
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
Control method
ON/OFF control or 2-PID control (with auto-tuning)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Ratings
Relay output
Voltage output
(for driving SSR)
Control
output
Output Unit (Install the Output Unit (sold separately).)
Current output
Linear voltage output
Built-in SSR output
75 to 250 VAC, 1 A (resistive load)
Auxiliary
output
Event
input
Number of outputs
2 or 3 max.
Output specifications
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load:
5 V, 10 mA
Number of outputs
2 or 4 (with an E53-AKB)
E5CN-H (48 x 48 mm)
Relay output for posi- Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations
tion-proportional con- min.
trol
Potentiometer input: Must be between 100 Ω and 2.5 kΩ for maximum open position.
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
External contact input
specifications
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
Number of operations 8 max.
Transfer
outputs
RSP
input
Operations
Output
One work bit per operation
Work bit
assignment
Any of The following can be assigned to up to eight work bits (logic operation results): Event input operations,
auxiliary outputs, or control outputs.
Number of outputs
1 max. (Depends on model. Models with transfer output (F in model number)
Output specifications
Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000
Number of inputs
1
Signal type
Current input: 4 to 20 mA (input impedance: 150 Ω ±10%)
Analog input scaling
Scaling of signal to engineering units (EU)
−19,999 to 30,000 (display: 30,000 max.)
Accuracy
(±0.2% of FS) ±1 digit max.
Input sampling period 60 ms
Set digitally using keys on the front panel or by using the RSP input.
Indication method
11-segment digital display and individual indicators (7-segments displays also possible)
Character height: E5AN-H: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-H: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm
Content of 3-level display: PV/SV/MV, PV/SV/Bank No., or soak time remain
Number of digits: 5 for PV and SV, 4 for MV
Bank switching
Supported (number of banks: 8)
Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.)
Other functions
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection,
40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions,
control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic
operations, automatic cooling coefficient adjustment
Ambient operating temperature
−10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C
Ambient operating humidity
25% to 85%
Storage temperature
−25 to 65°C (with no condensation or icing)
Safety Precautions
Setting method
Operation
Logic
operations
Any of the following four patterns can be selected. The input status may be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C,
and D are four inputs.)
• Delay:
ON delay or OFF delay for the results of the logic operation given above.
Setting time: 0 to 9999 s or 0 to 9999 min
• Output inversion: Possible
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
• Logic operation:
47
E5CN
E5CN-U (48 x 48 mm)
E5AN-H/E5EN-H
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Fully Universal Inputs)
Input
type
Platinum resistance
thermometer
Name
Pt100
Thermocouple
JPt100
K
J
T
E
Analog input
L
U
N
R
S
B
W
PL
II
4 to
20 m
A
0 to
20 m
A
1 to
5V
0 to
5V
0 to
10 V
2300.0
2300
1800.0
1800
1700.01700.0
1700
1600
1400
Temperature range (°C)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
1500
1300.0
1300
1000
900
850.0
850.0
700
600.0
600
500.0
500
500.0
500.0
400.0
400
200.00
100
−200.0
Setting
number
200.00
100.0
100.0
0.0
0.0
200.00
−50.00
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
400.0 400.0
200.00
−200.0−199.9
0
1
−20.0 −50.00−100.0 −20.0 −50.00
−199.9
2
24
3
−200.0
4
5
−50.00
−200.0−199.9
6
21
7
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
Operation
400.0 400.0
100.0
0
−100.0
Safety Precautions
Usable in the following
ranges by scaling:
−19999 to 32400,
−1999.9 to 3240.0,
−199.99 to 324.00, or
−19.999 to 32.400
850.0
800
200
48
1300.0
1100
300
E5CN-H (48 x 48 mm)
1300.0
1200
8
22
9
10
0.0
16
17
0.0
0.0
19
20
−100.0
−200.0
23
0.0
11
−200.0−199.9−200.0
12
13
14
15
18
25
26
27
28
29
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously
Engelhard)
Alarm Outputs
Each alarm can be independently set to one of the following 15 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).
Upper- and lowerlimit
✽1
2
3
4
✽1
5
✽1
6
7
Upper limit
Lower limit
Upper- and lowerlimit range
X
SP
X
ON
OFF
L
9
Absolute-value
lower-limit
ON
OFF
10
Absolute-value
upper-limit with
standby
sequence
ON
OFF
Absolute-value
lower-limit with
standby
sequence
ON
OFF
12
LBA (for alarm 1
only)
---
13
PV change rate
alarm
---
14
RSP absolute
value upper limit
15
RSP absolute
value lower limit
✽6
✽6
ON
OFF
ON
OFF
ON
OFF
H
L
H
SP L H
H > 0, L < 0
H > L
H
SP
Case 2
Case 1
X
SP
X
0
X
0
X
0
X
0
X
0
X
0
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
H > 0, L < 0
H ≤ L
Case 3 (Always ON)
H < 0, L < 0
✽3
ON
OFF
L
✽3. Set value: 4, Upper- and lower-limit range
X
SP
L
H SP
H < 0, L > 0
H < L
✽4
X
H < 0, L > 0
H ≥ L
SP H
H
SP L H
H > 0, L < 0
H > L
H
SP
L
H < 0, L > 0
H ≥ L
L SP
SP H
SP
L
L SP
SP
H
SP
H SP
H < 0, L > 0
H < L
X
SP
ON
OFF
ON
OFF
L
✽2
ON
OFF
SP
ON
OFF
Absolute-value
upper-limit
H
SP
ON
OFF
8
11
Case 3 (Always ON)
H < 0, L < 0
L
ON
OFF
Upper- and lower- ON
OFF
limit with standby
sequence
✽5
Upper-limit with
ON
standby
OFF
sequence
Lower-limit with
standby
sequence
Case 2
Case 1
L
H > 0, L < 0
H ≤ L
✽4. Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above
X
SP
X
SP
X
0
X
0
X
0
X
0
X
0
X
0
• Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
• Case 3: Always OFF
✽5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
✽6. Displayed when there is a remote SP input.
E5CN-H (48 x 48 mm)
1
Output OFF
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Alarm function
OFF
When X is
negative
Operation
0
When X is
positive
Safety Precautions
Alarm type
✽1.With set values 1, 4 and 5, the upper and lower limit values can be
set independently for each alarm type, and are expressed as “L”
and “H.”
✽2. Set value: 1, Upper- and lower-limit alarm
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Alarm output operation
Set
value
E5CN
E5CN-U (48 x 48 mm)
E5AN-H/E5EN-H
49
E5CN
E5CN-U (48 x 48 mm)
E5AN-H/E5EN-H
Characteristics
Indication accuracy
Transfer output accuracy ±0.3% FS max.
Influence of voltage ✽2
Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. ✽3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: (±1%FS) ±1 digit max.
Input sampling period
60 ms
Hysteresis
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0.0 to 3240.0 s (in units of 0.1 s)
Derivative time (D)
0.0 to 3240.0 s (in units of 0.1 s)
Control period
0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
−19999 to 32400 (decimal point position depends on input type)
Affect of signal source
resistance
Thermocouple: 0.1°C/Ω max. (100 Ω max.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
E5CN-H (48 x 48 mm)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Influence of temperature
✽2
Vibration
resistance
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Shock
resistance
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Weight
Operation
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
Destruction 300 m/s2, 3 times each in X, Y, and Z directions
E5AN-H
E5EN-H
Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g
Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g
Degree of protection
Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool
CX-Thermo version 4.0 or higher
Setup Tool port
Provided on the bottom of the E5AN-H and E5EN-H.
An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN-H and E5EN-H.
Provided on the front of the E5AN-H and E5EN-H. An E58-CIFIR USB-infrared Conversion Cable is required to
connect the computer to the E5AN-H or E5EN-H. ✽4
Standards
Safety Precautions
Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1
Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max.
Analog input: ±0.1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Potentiometer input: ±5% FS ±1 digit max.
EMC
Approved
standards
UL 61010-1, CSA C22.2 No. 1010-1
Conformed
standards
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMI:
EN 61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EN 55011 Group 1, class A
EMS:
EN 61326
ESD Immunity:
EN 61000-4-2
Electromagnetic Field Immunity:
EN 61000-4-3
Burst Noise Immunity:
EN 61000-4-4
Conducted Disturbance Immunity:
EN 61000-4-6
Surge Immunity:
EN 61000-4-5
Power Frequency Magnetic Field Immunity:
EN 61000-4-8
Voltage Dip/Interrupting Immunity:
EN 61000-4-11
✽1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of
−100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a
temperature of 400°C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication
accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is
±0.3% of PV or ±3°C, whichever is greater, ±1 digit max.
The indication accuracy of PL II thermocouples is ±0.3% of PV or ±2°C, whichever is greater, ±1 digit max.
✽2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
✽3. K thermocouple at −100°C max.: ±10°C max.
✽4. External communications (RS-232C, RS-485, or RS-422) and cable communications for the Setup Tool can be used at the same time.
50
Current Transformer (Order Separately)
Ratings
Applicable OS
Windows 2000, XP, or Vista
Applicable software
Thermo Mini, CX-Thermo version
4.0 or higher
Dielectric strength
1,000 VAC for 1 min
Vibration resistance
50 Hz, 98 m/s2
Applicable models
E5AN/E5EN/E5CN/E5CN-U/
E5AN-H/E5EN-H/E5CN-H
Weight
E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
USB interface standard
Conforms to USB Specification 1.1.
DTE speed
38400 bps
Accessories (E54-CT3 only) Armatures (2)
Plugs (2)
Connector specifications
Computer: USB (type A plug)
Temperature Controller: Setup
Tool port (on bottom of Controller)
Power supply
Bus power (Supplied from USB
host controller.)
Power supply voltage
5 VDC
Current consumption
70 mA
Thermo Mini, CX-Thermo version
4.0 or higher
Applicable models
E5AN-H/E5EN-H
USB interface standard
Conforms to USB Specification 1.1.
DTE speed
38400 bps
Connector specifications
Computer: USB (type A plug)
Temperature Controller: Infrared
port (on front of Controller)
Storage temperature
−20 to 60°C (with no condensation
or icing)
Storage humidity
10% to 80%
Power supply
Bus power (Supplied from USB
host controller.)
Altitude
2,000 m max.
Power supply voltage
5 VDC
Weight
Approx. 100 g
Current consumption
80 mA
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
Communications Specifications
Transmission line RS-485, RS-422: Multipoint
connection method RS-232C: Point-to-point
Communications
RS-485 (two-wire, half duplex)
RS-422 (four-wire, half duplex) or RS-232C
Synchronization
method
Start-stop synchronization
Protocol
CompoWay/F, SYSWAY, or Modbus
Baud rate
1200, 2400, 4800, 9600, 19200, 38400, or
57600 bps
ASCII (CompoWay/F, SYSWAY)
Transmission code
RTU (Modbus)
Data bit length ✽
7 or 8 bits
Stop bit length ✽
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Frame check sequence (FCS) with SYSWAY
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
Ambient operating tempera- 0 to 55°C (with no condensation or
ture
icing)
Ambient operating humidity 10% to 80%
Storage temperature
−20 to 60°C (with no condensation
or icing)
Storage humidity
10% to 80%
Altitude
2,000 m max.
Weight
Approx. 130 g (with mounting
adaptor)
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
Heater Burnout Alarms, SSR Failure
Alarms, and Heater Overcurrent Alarms
Models with detection for single-phase
CT input
heaters: One input
(for heater current detecModels with detection for single-phase
tion)
or three-phase heaters: Two inputs
Maximum heater current
50 A AC
Input current indication
accuracy
±5% FS ±1 digit max.
Flow control
None
Interface
RS-485, RS-422, or RS-232C
Retry function
None
Communications
buffer
SSR failure alarm setting
range ✽2
217 bytes
Heater overcurrent alarm 0.1 to 49.9 A (in units of 0.1 A)
setting range ✽3
Minimum detection ON time: 100 ms
Communications
0 to 99 ms
response wait time Default: 20 ms
Note: The baud rate, data bit length, stop bit length, and vertical parity
can be individually set using the Communications Setting
Level.
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Applicable software
E5CN-H (48 x 48 mm)
Windows 2000, XP, or Vista
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Ambient operating humidity 10% to 80%
Applicable OS
Operation
Ambient operating tempera- 0 to 55°C (with no condensation or
ture
icing)
USB-Infrared Conversion Cable
Heater burnout alarm set- 0.1 to 49.9 A (in units of 0.1 A)
ting range ✽1
Minimum detection ON time: 100 ms
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms
✽1. For heater burnout alarms, the heater current will be measured when
the control output is ON, and the output assigned to the alarm 1
function will turn ON if the heater current is lower than the set value
(i.e., heater burnout detection current value).
✽2. For SSR failure alarms, the heater current will be measured when the
control output is OFF, and the output assigned to the alarm 1 function
will turn ON if the heater current is higher than the set value (i.e., SSR
failure detection current value).
✽3. For heater overcurrent alarms, the heater current will be measured
when the control output is ON, and the output assigned to the alarm 1
function will turn ON if the heater current is higher than the set value
(i.e., heater overcurrent detection current value).
Safety Precautions
USB-Serial Conversion Cable
E5CN
E5CN-U (48 x 48 mm)
E5AN-H/E5EN-H
51
Electrical Life Expectancy Curve for
Relays (Reference Values)
500
• Rated load voltage: 75 to 250 VAC
• Rated load current: 1 A (resistive load)
Note: 1. The load current must be within the derating curve.
2. There is no zero-cross function.
300
Derating Curve for SSR Outputs (Reference Values)
E5AN-H/E5EN-H
250 VAC, 30 VDC
(resistive load)
cosφ = 1
100
50
30
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
SSR Outputs (OUT1/OUT2) Ratings
Load current I (A) OUT1/OUT2
Life (× 104 operations)
E5CN
E5CN-U (48 x 48 mm)
E5AN-H/E5EN-H
10
5
3
1
0
1
2
3
4
5
6
1.5
1.25
Condition B
1
0.75
0.5
Condition A
Switching current (A)
0.25
Safety Precautions
Operation
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
E5CN-H (48 x 48 mm)
0
−10
52
0
10
20
30
40 45 50 55 60
Ambient temperature (°C)
Condition A: SSR outputs 100% ON
Condition B: SSR outputs 50% ON with 2-s control cycle
E5AN-H/E5EN-H
• A voltage output (control output 1, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.
The voltage output (control output 2, for driving SSR) has basic insulation provided for the internal circuit
Option Units
Communications
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
Output Unit
Control outputs 1, 2
Relay Outputs
250 VAC, 5 A
(resistive load)
SSR Outputs
75 to 250 VAC, 1A
(resistive load)
Models with Positionproportional Control
250 VAC, 1 A
(including inrush
current)
Input power
supply
21
11
2
22
12
3
23
13
Control output 1
11
SD
11
RDB
11
B (+)
11
12
RD
12
RDA
12
A (−)
12
13
SG
13
SG
13
DO NOT USE
13
21
DO NOT USE
21
SDB
21
B (+)
21
22
DO NOT USE
22
SDA
22
A (−)
22
24
15
6
26
16
7
27
17
8
28
18
9
29
19
10
30
20
Control output 2
Potentiometer
CT2
Auxiliary output 2
EV1
EV1
CT1
25
EV2
EV2
14
5
Event Inputs
Event Inputs
CT2
4
Auxiliary outputs 1, 2
Relay output
SPST-NO,
250 VAC, 3 A
(resistive load)
1
E53-AKB
E53-EN03
RS-485
O
W
C
14
Auxiliary output 3
15 Auxiliary output 3
16
DO NOT DO NOT
USE
USE
A
DO NOT
DO NOT V
USE
USE
B
Auxiliary output 1
B
DO NOT
USE
DO NOT
USE
mA
Relay output
SPDT, 250 VAC, 3 A
(resistive load)
A heater burnout alarm, SSR
failure, heater overcurrent
alarm, or input alarm is sent
to the output to which the
alarm 1 function is assigned.
DO NOT
USE
21
E5CN-H (48 x 48 mm)
Control outputs 1, 2
E53-EN02
RS-422
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
E53-EN01
RS-232C
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Controllers
E5CN
E5CN-U (48 x 48 mm)
External Connections
22
EV3
23
25
DO NOT USE
Transfer output
26
27 4 to 20 mA DC
(Load: 600 Ω max.)
28
Operation
24
EV4
29
30
Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly.
Safety Precautions
4 to 20 mA DC
Remote SP input
53
E5AN-H/E5EN-H
E5CN
E5CN-U (48 x 48 mm)
Nomenclature
E5AN-H
E5EN-H
Temperature unit
Operation indicators
SUB1 SUB2
SUB1
PV
SUB2
Operation indicators
HA SUB3
No.1 display
SUB3
PV
Temperature unit
No.1 display
HA
SV
No.2 display
SV
No.2 display
MV
No.3 display
RSP
MV
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
OUT1 RSP STOP
OUT2
CMW MANU
OUT1 STOP
Operation indicators
OUT2 CMW MANU
Up Key
Mode Key
Programmable
Function Key/
Auto/Manual Key
PF
Up Key
A/M
PF
Level Key
A/M
Ir
Ir
E5AN-H
E5EN-H
Down Key
Level Key
E5CN-H (48 x 48 mm)
No.3 display
Programmable
Function Key/
Auto/Manual Key
Down Key
Mode Key
Dimensions
(Unit: mm)
E5AN-H
Mounted Separately
92
Group Mounted✽
+1.0
0
+0.8
0
(96 × number of units − 3.5)
+0.8
0
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
92
Group mounting does not
allow waterproofing.
120 min.
6
79.2
2
+0.8
0
92
Operation
96 × 96
112
91
• Recommended panel thickness is 1 to
8 mm.
• Group mounting is not possible in the
vertical direction. (Maintain the specified
mounting space between Controllers.)
• To mount the Controller so that it is
waterproof, insert the waterproof packing
onto the Controller.
• When two or more Controllers are
mounted, make sure that the surrounding
temperature does not exceed the
allowable operating temperature specified
in the specifications.
✽ Group mounting is not possible if an SSR output is used for
control output 1 or 2 and the E53-C3N or E53-C3DN Output Unit
is used. For these combinations, maintain the following mounting
space between Controllers.
Waterproof
Packing
(Accessory)
Mounting Bracket
(Accessory)
110 min.
Terminal Cover
(E53-COV16)
(Accessory)
+0.8
0
92
Crimp terminal size: M3.5
Safety Precautions
92
54
120 min.
+0.8
0
E5CN
E5CN-U (48 x 48 mm)
E5AN-H/E5EN-H
E5EN-H
Mounted Separately
Group Mounted✽
(48 × number of units − 2.5)
+0.6
45 0
+1.0
0
+0.8
0
92
+0.8
92 0
6
48
79.2
2
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Group mounting does not
allow waterproofing.
120 min.
• Recommended panel thickness is 1 to 8 mm.
• Group mounting is not possible in the vertical direction.
(Maintain the specified mounting space between
Controllers.)
• When two or more Controllers are mounted, make sure
that the surrounding temperature does not exceed the
allowable operating temperature specified in the
specifications.
60 min.
91
45
+0.6
0
92
Mounting Bracket
(Accessory)
Terminal Cover
(E53-COV16)
(Accessory)
Crimp terminal size: M3.5
120 min.
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
Waterproof
Packing
(Accessory)
+0.8
0
Operation
112
Safety Precautions
96
E5CN-H (48 x 48 mm)
✽ Group mounting is not possible if an SSR output is used for control
output 1 or 2 and the E53-C3N or E53-C3DN Output Unit is used.
For these combinations, maintain the following mounting space
between Controllers.
55
E5AN-H/E5EN-H
E5CN
E5CN-U (48 x 48 mm)
Accessories (Order Separately)
USB-Infrared Conversion Cable
E58-CIFIR
USB-Infrared Conversion Cable
54
(2,000)
35.8
4.6 dia.
USB connector (type A plug)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
LED indicator: RD
LED indicator: SD
17.8
With Mounting Adapter Connected
Mounting Adapter
39
16
E5CN-H (48 x 48 mm)
18.5
Mounting Adapter
(Accessory)
99.2
23.1
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
21.8
(75)
USB-Serial Conversion Cable
E58-CIFQ1
(2,100)
LED indicator: SD
250
Operation
USB connector (type A plug)
LED indicator: RD
Terminal Covers
1.2
E53-COV16 (Six Covers provided.)
Safety Precautions
10
56
44.8
1,765
3.2
Serial connector
E5CN
E5CN-U (48 x 48 mm)
E5AN-H/E5EN-H
Waterproof Packing
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Order the Waterproof Packing separately if it becomes lost or
damaged.
The Waterproof Packing can be used to achieve an IP66 degree of
protection.
(Deterioration, shrinking, or hardening of the waterproof packing may
occur depending on the operating environment. Therefore, periodic
replacement is recommended to ensure the level of waterproofing
specified in IP66. The time for periodic replacement depends on the
operating environment. Be sure to confirm this point at your site.
Consider one year a rough standard. OMRON shall not be liable for
the level of water resistance if the customer does not perform periodic
replacement.)
The Waterproof Packing does not need to be attached if a waterproof
structure is not required.
Current Transformers
5.8 dia.
7.5
25
Output voltage (Eo) V (r.m.s.)
3
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
Winding resistance: 18±2 Ω
10.5
40
Two, 3.5 dia.
10
30
100 V
50 Hz
∞
10
Distortion
factor 10%
1 kΩ
1
3%
1%
100 mV
100 Ω
10
E54-CT3
RL = 10 Ω
1
2.36 dia.
E5CN-H (48 x 48 mm)
15
E54-CT1
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
2.8
30
12 dia.
100 µV
9
10
1
10
100 mA
1
40 × 40
Two, M3 (depth 4)
E54-CT3 Accessory
Connection Example
Armature
Plug
Lead
18
E54-CT3
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Output voltage (Eo) V (r.m.s.)
30
Approx. 3 dia.
100 1,000 A
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for an OMRON
Temperature Controller is 50 A.)
Number of windings: 400±2
Winding resistance: 8±0.8 Ω
15
• Armature
10
Thru-current (Io) A (r.m.s.)
100 V
50 Hz
Distortion
factor
10%
3%
1%
∞
10
1 kΩ
500 Ω
1
100 mV
100 Ω
50 Ω
10
RL = 10 Ω
• Plug
1
100 µV
Approx. 6 dia.
(22)
E5AN-H (96 x 96 mm)
E5EN-H (48 x 96 mm)
21
Operation
E54-CT1
10
1
10
100 mA
1
10
100 1,000 A
Thru-current (Io) A (r.m.s.)
Safety Precautions
Y92S-P5 (for DIN 48 × 96)
Y92S-P4 (for DIN 96 × 96)
57
E5@N/E5@N-H
E5CN
E5CN-U (48 x 48 mm)
Operation
Setting Levels Diagram
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.
Basic Type
Power ON
Start in manual mode.
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Start in automatic mode.
Press the O Key or the
PF Key for at least 1 s. ✽4
Operation
Level
Adjustment
Level
Press the
O Key less than 1 s.
a-m
Manual
mode
PF Key
Press the O Key
for at least 3 s while
a-m is displayed.
(a-m will flash after
1st second.)
✽3
PF Key
E5CN-H (48 x 48 mm)
✽4
Press the
O Key for
at least 1 s.
Control stops.
25
c
100
c
Press the O Key for at
least 3 s. (Display will flash
after 1st second.)
25
100
Protect Level
*1
Note: The time taken to
move to the protect
level can be adjusted
by changing the
“Move to protect level
time” setting.
Communications Setting
Level
Initial Setting
Level
Press the
O Key for less than 1 s.
Input password while
amoV is displayed. (Set
value −169)
Press the O Key
for at least 1 s.
E5AN-H (96 x 96 mm)
E5EN-H(48 x 96 mm)
Press the
O+ M
Keys for at
least 1 s.
✽5
Press the PF Key
for at least 1 s.
Manual
Control Level
✽5
Monitor/Setting
Item Level
Press the
O+ M
Keys for at
least 3 s.
(Display
will flash
after 1st
second.)
Advanced Function
Setting Level
Input password.
Control in progress
Control stopped
Calibration Level
✽2
Not displayed for some models
Operation
Level change
✽1. You can return to the operation level by executing a software reset.
✽2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel.
It can be done only by first turning OFF the power.
✽3. From the manual control level, key operations can be used to move to the operation level only.
✽4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/E5EN).
✽5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/E5EN)
Error Displays (Troubleshooting)
Safety Precautions
When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
No.1 display
Meaning
s.err (S. Err)
Input error
✽
Action
Status at error
Control output
Alarm output
Check the wiring of inputs for miswiring, disconnections, and short-circuits and check the
input type.
OFF
Operates as above
the upper limit.
e333 (E333)
A/D
converter
error
Turn the power OFF then back ON again. If the display remains the same, the controller must
be repaired. If the display is restored to normal, then a probable cause can be external noise
affecting the control system. Check for external noise.
OFF
OFF
e111 (E111)
Memory
error
Turn the power OFF then back ON again. If the display remains the same, the controller must
be repaired. If the display is restored to normal, then a probable cause can be external noise
affecting the control system. Check for external noise.
OFF
OFF
Note: If the input value exceeds the display limit (−1999 to 9999), though it is within the control range,
will be displayed under −1999 and
above 9999. Under these conditions, control output and alarm output will operate normally.
For details on the control range, refer to the E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156).
✽ These errors are displayed only when the PV/SP is displayed. Errors are not displayed for other displays.
58
E5CN
E5CN-U (48 x 48 mm)
E5@N/E5@N-H
Advanced Type
Power ON
Start in automatic mode.
a-m
Manual
mode
✽3
Press the O Key
for at least 3 s while
a-m is displayed.
(a-m will flash after
1st second.)
Adjustment
Level
Press the
O Key less than 1 s.
Press the
O Key less than 1 s.
PID Setting
Level
Press the
O Key less
than 1 s.
Bank Setting
Level
Press the PF Key
for at least 1 s. ✽4
Manual
Control Level
PF Key
Press the
O Key less
than 1 s.
Press
the O +
M Keys
for at
least 3 s.
(Display
will flash
after 1st
second.)
c
25.0
100.0
Protect Level
Press the O Key for at
least 3 s. (Display will flash
after 1st second.)
25.0
c
PF Key ✽5
Monitor/Setting
Item Level
✽5
Press the O Key
for at least 1 s.
Press the O+
M Keys for at
least 1 s.
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Operation
Level
Note: The time taken to
move to the protect
level can be adjusted
by changing the
“Move to protect level
time” setting.
E5CN-H (48 x 48 mm)
Press the O Key or the
PF Key for at least 1 s. ✽4
100.0
✽1
Control stops.
Communications Setting
Level
Initial Setting
Level
Press the
O Key for less than 1 s.
Press the O Key
for at least 1 s.
E5AN-H (96 x 96 mm)
E5EN-H(48 x 96 mm)
Input password while
amov is displayed.
(Set value −169)
Advanced Function
Setting Level
Input password.
Control in progress
Control stopped
✽2
Calibration Level
Not displayed for some models
Level change
Operation
✽1. You can return to the operation level by executing a software reset.
✽2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel.
It can be done only by first turning OFF the power.
✽3. From the manual control level, key operations can be used to move to the operation level only.
✽4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H).
✽5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H)
Error Displays (Troubleshooting)
When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
No.1 display
Meaning
s.err (S. Err)
Input error
✽
Action
Status at error
Control output
Alarm output
Check the wiring of inputs for miswiring, disconnections, and short-circuits and check the
input type.
OFF
Operates as above
the upper limit.
e333 (E333)
A/D
converter
error
Turn the power OFF then back ON again. If the display remains the same, the controller must
be repaired. If the display is restored to normal, then a probable cause can be external noise
affecting the control system. Check for external noise.
OFF
OFF
e111 (E111)
Memory
error
Turn the power OFF then back ON again. If the display remains the same, the controller must
be repaired. If the display is restored to normal, then a probable cause can be external noise
affecting the control system. Check for external noise.
OFF
OFF
Note: If the input value exceeds the display limit (−19999 to 32400), though it is within the control range,
will be displayed under −19999
and
above 32400. Under these conditions, control output and alarm output will operate normally.
For details on the control range, refer to the E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157).
✽ These errors are displayed only when the PV/SP is displayed. Errors are not displayed for other displays.
Safety Precautions
Start in manual mode.
59
Parameters
Basic Type
Some parameters are not displayed depending on
the model of the Controller and parameter settings.
For details, refer to the E5CN/E5AN/E5EN Digital
Temperature Controllers User's Manual Basic Type
(Cat. No. H156).
PF Key ✽2
Power ON
Starting in manual mode.
Press the PF Key for
at least 1 s. ✽1
Adjustment
Level
5
M
in-h
25
off
C
0.0 Input Shift Value parameters.
2-point shift
M
Limit
insl Lower
Temperature
C
0.0 Input Shift Value
off
C
0.0
M
Burnout
hb1 Heater
Detection 1
M
i
M
d
0.0
M
hb2
0.0
M
oc2
50.0
M
lcr1
0.0
0.0
M
hs1
Heater Burnout
Detection 2
0.0
M
hs2
0.0
M
of-r
M
sp-0
M
hys Hysteresis (Heating)
1.0
M
soak Soak Time
Leakage Current 2
Monitor
HS Alarm 2
1
M
wt-b
C
M
sp-1
SP 0
M
sp-2
0
C
M
mv-e
SP 1
M
Current 2
lcr2 Leakage
Monitor
MV at PV Error
SP used by
multi-SP
SP 2
C
M
sprt SP Ramp Set Value
off
M
ol-h
M
M
ol-l
MV Upper Limit
MV Lower Limit
-5.0
M
orl MV Change Rate Limit
0.0
M
sqrp
0.0
M
C
Extraction of Square Root
Low-cut Point
Alarm Value
Upper Limit 2
M
Value
al2l Alarm
Lower Limit 2
C
M
al-3 Alarm Value 3
0
M
Value
al3h Alarm
Upper Limit 3
0
M
prst Program Start
C
rset
M
sktr Soak Time Remain
0
M
Value
al3l Alarm
Lower Limit 3
M
d-u
c
C
M
Operation/Adjustment Protect:
oapt Restricts displaying and
modifying menus in operation,
0 adjustment, and manual control
levels.
M
s-hc
stnd
on
M
ptrn
M
20
M
c-cp
20
M
alt1
Press the O Key
less than 1 s.
Alarm 1 Type
2
C
M
alh1
0.2
Alarm 1
Hysteresis
M
Setting:
psel Protocol
Switches between
cwf CompoWay/F (SYSWAY)
and Modbus.
M
u-no Communications Unit No.
1
9.6
CompoWay/F
(SYSWAY) only
7
M
sbit Communications
Stop Bits
M
Mask Enable:
pmsk Parameter
Displayed only when a
M
prty Communications Parity
M
to Move to Protect Level:
prlp Password
Password setting
M
sdwt
M
Set the ON/OFF
output cycle.
Control Period (Cooling)
M
orev Direct/Reverse Operation
M
Key Protect
pfpt PF
Restricts PF key operation
0
control output to ON/OFF
output
cp Control Period (Heating)
Note: Displayed only for models with communications.
Changes are effective after cycling power or
after a software reset.
M
len Communications
Data Length
on parameter mask is set.
Program Pattern
off When assigning PID or
Communications
Setting Level
M levels.
Change Protect:
wtpt Setting
Protects changes to setups by
off (E5AN/E5EN only)
For input type of
temperature, standard
control, or PID
or-r
M
Communications
bps Baud Rate
off operating the front panel keys.
Standard or
Heating/Cooling
M
st ST (Self-tuning)
M
o MV Monitor (Heating)
M Initial Setting/
Protect:
icpt Communications
This protect level restricts movement
1 to the initial setting, communications
Limit the set point
SP Lower Limit
onof
0
Press the O and M Keys for at least 1 s.
Move to Protect Level:
Displayed only when a password
0 is set. Restricts moving to protect
level.
M
sl-l
M
cntl PID ON/OFF
M
Protect Level
SP Upper Limit
-200
M
c-o MV Monitor (Cooling)
Note: The time taken to move to the protect
level can be adjusted by changing the
"Move to protect level time" setting.
Temperature Unit
°C, °F
For input type of
temperature
1300
0.0
Press the O and M Keys for
at least 3 s.
M
sl-h
C
0.0
M
Decimal Point
0 For input type of analog
0
C
setting, and advanced function setting
105.0
M
al2h
0
0.0
pmov
0.0
M
sp-3 SP 3
0
MV at Stop
0.0
0
C
Heater Current 2 Value
Monitor
M
Current 1
lcr1 Leakage
Monitor
Wait Band
off
M
mv-s
C
0.0
M Hysteresis settings
chys Hysteresis (Cooling)
C
0
C
Manual Reset Value
Clear the offset during
M
al-2 Alarm Value 2
0
0.0
50.0 stabilization of P or PD
C
C
M
Current 1 Value
ct1 Heater
Monitor
0.0
M
Value
al1l Alarm
Lower Limit 1
0
M
dp
0
M
Point During
sp-m Set
SP Ramp
M
ct2
M
Value
al1h Alarm
Upper Limit 1
0
C
Multi-SP
Set Point Setting
1.0
50.0
C
C
PID settings
Heating/cooling
M
c-db Dead Band
50.0
M
lcr2
0
Derivative Time
control.
HS Alarm 1
m-sp
Integral Time
1.00
C
C
0
M
c-sc Cooling Coefficient
Heater Overcurrent
Detection 2
Leakage Current 1
Monitor
Press the
O Key
for at
least 3 s.
M
al-1 Alarm Value 1
0
Added when
auto/manual select
M addition is ON.
40
Heater Current 2
Value Monitor
C
M
Switch
a-m Auto/Manual
PID control only.
233
0.0
M
ct2
M
p Proportional Band
8.0
run
0
1-point shift
M
Set either
Limit
insh Upper
of these
Temperature
C
M
Current 1
ct1 Heater
Value Monitor
M
Value/
25 Process
Set Point
C
0.0
AT Execute/Cancel
M
cmwt Communications
Writing
ins Temperature Input Shift
M
in-l Scaling Lower Limit
r-s RUN/STOP
Process Value
Added when Additional
PV display is ON.
Set either of these parameters.
M
at
Adjustment Level
Display
Displayed only
once when
entering
adjustment level.
Scaling Upper Limit
100
C
E5CN-H (48 x 48 mm)
E5AN-H (96 x 96 mm)
E5EN-H(48 x 96 mm)
in-t Input Type
Operation Level
50.0
Operation
Press the O Key less than 1 s.
Press the O Key less than 1 s.
M
Overcurrent
oc1 Heater
Detection 1
60
Initial Setting Level
Press the
O Key for
at least 1 s.
C
Press the O Key less than 1 s.
l.adj
Safety Precautions
Press the O
PID
Key or the PF
25 Control Key for at least
only
1 s.
✽1
PV/MV
PF Key ✽2
Press the O Key for at least 3 s.
Other than the Auto/Manual Switch display
Starting in
automatic
mode.
Set either of these parameters.
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Manual Control Level
Set either of these parameters.
E5CN
E5CN-U (48 x 48 mm)
E5@N/E5@N-H
2
even
20
M
Send Data Wait Time
✽1. When the PF Setting
parameter is set to A-M for a
Controller with a PF Key
(E5AN/E5EN).
✽2. When the PF Setting
parameter is set to PFDP for a
Controller with a PF Key
(E5AN/E5EN).
Monitor/Setting Item Level
25
C
0
Monitor/Setting
Item Display 1
PF
(E5AN/E5EN only)
Monitor/Setting
Item Display 2
Monitor/Setting
Item Display 3
PF
Monitor/Setting
Item Display 4
PF
Monitor/Setting
Item Display 5
PF
E5CN
E5CN-U (48 x 48 mm)
E5@N/E5@N-H
M
mspu Multi-SP Uses
M
a2lt Alarm 2 Latch
M
hsl HS Alarm Latch
M
spru
M
a3lt Alarm 3 Latch
M
hsh HS Alarm Hysteresis
(E5AN/E5EN only)
M
pfd2 Monitor/Setting Item 2
M
Sequence
rest Standby
Reset
M
to Protect Level
prlt Move
Time
M
lba LBA Detection Time
M
pfd3 Monitor/Setting Item 3
M
sb1n
M
sero Input Error Output
0.2
Alarm 3
Hysteresis
off
M
tr-h
100.0
Linear output
n-o
Transfer Output
Upper Limit
M
Output
tr-l Transfer
Lower Limit
0.0
M
o1-t Linear Current Output
4-20
Auxiliary Output 2
Open in Alarm
M
sb3n
Auxiliary Output 3
Open in Alarm
n-o
M
hbu
Linear output
M
of Multi-SP Uses
ev-m Number
Two SPs: 1
none
M
ev-2
stop
setting/communications
C
Control Output 2
Assignment
M
odsl MV Display Selection
Auxiliary Output 1
Assignment
M
Decimal Point
pvdp PV
Display
none
M
st-b ST Stable Range
M
a2on Alarm 2 ON Delay
M
sub3
M
alfa α
M
a3on Alarm 3 ON Delay
M
csel Character Select
M
at-g AT Calculated Gain
M
a1of Alarm 1 OFF Delay
M
t-u Soak Time Unit
M
at-h AT Hysteresis
M
a2of Alarm 2 OFF Delay
M
alsp Alarm SP Selection
M
a3of Alarm 3 OFF Delay
0.8
Move by setting password (−169).
M
out2
o
M
sub2
0.65
M protect is set to 0.
M
colr PV Change Color
off
3.0
M
a1on Alarm 1 ON Delay
15.0
0 Displayed when initial
M
spdp
C
M
Burnout
hbh Heater
Hysteresis
C
M
to Advanced
amov Move
Function Setting Level:
M
Output 1
out1 Control
Assignment
8.0
M
sub1
0.1
off
M
Command
rlrv MB
Logic Switching
C
M
pv-b PV Stable Band
Event Input
Assignment 2
0.8
20.0
M
inf Input Digital Filter
0.0
M
pvad Additional PV Display
off
M
o-dp
MV Display
M
Display
ret Automatic
Return Time
M
0
0
0
0
0
M
istp Input Shift Type
ins1
M
at Stop and Error
mvse MV
Addition
off
off
off
5.0
0
M
Cycle MV
lcma Limit
Amplitude
0
M
pfd5
on Method
C
0
M
lbab LBA Band
red
off
1
M
pfd4 Monitor/Setting Item 4
M
Junction
cjc Cold
Compensation
on
Event Input
Assignment 1
M
of Square
sqr Extraction
Root Enable
0
M
pfd1 Monitor/Setting Item 1
M
lbal LBA Level
off
HB ON/OFF
M
hbl Heater Burnout Latch
1 Four SPs: 2
M
ev-1
0.1
3
Auxiliary Output 1
Open in Alarm
M
sb2n
n-o
off
off
a
tr-t Transfer Output Type
a-m
M
Select
amad Auto/Manual
Addition
off
alm1
Auxiliary Output 2
Assignment
alm2
alm3
Auxiliary Output 3
Assignment
(E5AN/E5EN only)
on
m
Monitor/Setting Item 5
0
4
"PV/SP" Display
Screen Selection
o
on
M
PV Status Display
pvst Function
off
M
Status Display
svst SV
Function
off
M
Refresh
d.ref Display
Period
0.25
M
Output 1
ra1m Control
ON/OFF Count
0 Monitor
M
ra2m
Control Output 2
ON/OFF Count
M
MV
manl Manual
Limit Enable
M
ra1
Control Output 1
ON/OFF Count
M
Rate of Change
pvrp PV
Calculation Period
M
Output 2
ra2 Control
ON/OFF Count
sp-m
off
4
M
csca
off
Automatic Cooling
Coefficient Adjustment
M
Overcurrent
ocu Heater
Use
on
M
rt RT
M
Overcurrent
ocl Heater
Latch
M
M
och
off
0
off
0.1
M
Heater Overcurrent
Hysteresis
E5CN-H (48 x 48 mm)
C
SP Ramp Time Unit
m
HS Alarm Use
on
off
off
2
hsu
off
E5AN-H (96 x 96 mm)
E5EN-H(48 x 96 mm)
0.2
M
alt3 Alarm 3 Type
M
alh3
PF Setting
(E5AN/E5EN only)
a1lt Alarm 1 Latch
off
M
2
alh2 Alarm
Hysteresis
C
pf
init Parameter Initialization
Alarm 2 Type
2
0 Monitor
0 Alarm Set Value
Operation
alt2
Advanced Function Setting Level
0 Alarm Set Value
M
Counter
rac ON/OFF
Reset
0
M
to Calibration
cmov Move
Level
0
M
Safety Precautions
Press the O Key for at least 1 s.
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
61
E5CN
E5CN-U (48 x 48 mm)
E5@N/E5@N-H
Advanced Type
Some parameters are not displayed
depending on the model of the Controller and
parameter settings.
For details, refer to the E5CN-H/E5AN-H/
E5EN-H Digital Controllers User's Manual
Advanced Type (Cat. No. H157).
Power ON
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Manual Control
Level
Protect Level
Operation
Level
Adjustment
Level
Initial Setting
Level
Communications Setting
Level
E5CN-H (48 x 48 mm)
Press the O Key less than 1 s.
Bank Setting Level
PID Setting Level
Press the O Key less than 1 s.
Display Bank Selection
d.bnk Bank0
0
2 PID2
d.bnk
d.bnk
3 PID3
22 Bank2
d.bnk Bank7
PID8
7
M
1.p
8.0
M
8.d
M
1.olh
M
8.olh
M
1.oll
-5.0
M
1.lba
0
M
off
PID 8 MV Upper Limit
c
c
c
c
PID 8 Cooling Coefficient
1.00
0
M
c
0.0
PID 8 LBA Detection Time
M
0.a2l
7.pid
1
0.a-3
c
M
0.a3h
c
M
c
0.a3l
c
0.0
M
0.sok
0.a1l
0.a-2
M
0.0
M
c
M
0.0
0.0
M
M
8.lba
c
1
M
c
7.lsp
0.wtb
Bank 7 SP
0.0
M
M
PID 8 Automatic Selection
1320.0 Range Upper Limit
c
0.0
M
0.a1h
0.0
M
8.aut
8.csc
0.a-1
0.0
PID 8 MV Lower Limit
c
M
-5.0
1.aut
M
c
M
0.spr
0.a 2h
0.0
0.pid
1
PID 8 Derivative Time
M
c
M
105.0
M
8.oll
0.lsp
0.0
40.0
105.0
1.00
c
233.0
40.0
M
1.csc
PID 8 Proportional Band
M
8.i PID 8 Integral Time
M
1320.0
8.p
8.0
M
1.i
c
M
M
c
c
M
7.a1h
Bank 7
Alarm Value
0.0 Upper Limit 1
Bank 7
Alarm Value
0.0 Lower Limit 1
7.a1l
7.a 2h
Bank 7
Alarm Value
0.0 Upper Limit 2
M
Bank 7 SP
off Ramp Set Value
M
c
c
M
7.spr
Bank 7
0.0 Alarm Value 1
Bank 7
0.0 Alarm Value 2
M
Bank 7 PID
Set No.
M
7.a-1
7.a-2
c
c
Bank 7
Alarm Value
0.0 Lower Limit 2
7.a2l
M
7.a-3 Bank 7
0.0 Alarm Value 3
c
c
M
M
7.a3h
Bank 7
Alarm Value
0.0 Upper Limit 3
M
7.a3l
Bank 7
Alarm Value
0.0 Lower Limit 3
M
7.sok
off
M
Set either of these parameters
8
Set either of these parameters
d.pid
c
d.bnk Bank1
1
d.pid
1.d
Operation
Press the O Key less than 1 s.
Set either of these parameters
E5AN-H (96 x 96 mm)
E5EN-H(48 x 96 mm)
d.pid PID1
1
d.pid
233.0
Safety Precautions
Monitor/Setting
Item Level
Advanced
Function Setting
Level
Display PID Selection
62
PID Setting
Level
Bank Setting
Level
Bank 7 Soak Time
1
c
M
7.wtb
off
M
Bank 7 Wait Band
E5CN
E5CN-U (48 x 48 mm)
E5@N/E5@N-H
Power ON
Starting in manual mode.
PID
Press the O
25.0 Control Key or the PF
100.0 only
Key for at least
1 s. ✽1
PV/MV
Press the PF Key
for at least 1 s.
Starting in
automatic
mode.
✽1
Press the O
and M Keys for
at least 3 s.
Press the O Key less than 1 s.
Operation Level
AT Execute/Cancel
M
M
d
Communications
off Writing
M
irda
40.0
Infrared Communications Use
SP Mode
0.0
lsp
of-r
Heater Current 1
0.0 Value Monitor
M
hb1
M
hys
Heater Burnout
1.0
M
chys
M
oc1
Heater Overcurrent
50.0 Detection 1
1.0
M
soak
M
0.0
M
hb2
0.0
M
oc2
50.0
Heater Current 2
Value Monitor
M
wt-b
Heater Burnout
Detection 2
off
50.0
M
lcr2
0.0
M
hs2
50.0
mv-s
Heater Overcurrent
Detection 2
ins
0.00
M
c
insh
mv-e
0.0
M
sprt
M
insl
0.00
M
rsp
c
Remote SP Monitor
Hysteresis (Heating)
Hysteresis (Cooling)
c
Set Point During
c
Heater Current 1 Value
c
Heater Current 2 Value
lcr1
Leakage Current 1
Leakage Current 2
M
al3l Alarm Value
0.0 Upper Limit 3
M
lcr2
M
M
o
prst Program Start
0.0
rset
M
ol-h
Leakage Current 2
Monitor
105.0
MV Monitor (Heating)
M
M
MV at PV Error
Press the O
and M Keys for
at least 1 s.
0.0 Lower Limit 3
0.0 Monitor
MV at Stop
Alarm Value 3
M
al3h Alarm Value
0.0 Monitor
Wait Band
Alarm Value
M
al-3
0.0
0.0 Monitor
M
Soak Time
Alarm Value
M
al2l
0.0 Lower Limit 2
M
ct2
al2h
0.0 Upper Limit 2
0.0 Monitor
Hysteresis settings
Alarm Value 2
0.0
M
ct1
al-2
M
0.0 SP Ramp
control.
M
al1l Alarm Value
0.0 Lower Limit 1
0.0
sp-m
Alarm Value
M
c-o
sktr Soak Time Remain
0.0
0
MV Monitor (Cooling)
M
M
v-m
SP Ramp Set Value
off
HS Alarm 1
Valve Opening
Monitor
0.0
M
MV Upper Limit
M
ol-l
-5.0
HS Alarm 2
M
orl
Temperature Input Shift
Upper Limit
Temperature
2-point shift
Lower Limit
Temperature
Input Shift Value
0.0
MV Lower Limit
PF Key ✽2
MV Change Rate Limit
Monitor/Setting Item Level
(E5AN-H/E5EN-H only)
M
1-point shift
0.00 Input Shift Value
c
Manual Reset Value
Clear the offset during
M
Leakage Current 1
c
Bank No.
M
0.0
M
c
c
al1h
0.0 Upper Limit 1
0
Dead Band
Alarm Value 1
M
c
Auto/Manual Switch
PID control only.
Added when
auto/manual select
addition is ON.
M
M
0.0 Monitor
M
hs1
M
bank
Heating/cooling
1
M
lcr1
Press
the O
Key for
at least
3 s.
50.0 stabilization of P or PD
0.0 Detection 1
ct2
Derivative Time
a-m
al-1
0.0
M
PID settings
M
M
ct1
c
Process Value/
0.0 Set Point
Integral Time
M
c-sc Cooling Coefficient
M
c-db
M
M
25.0
1.00
off
spmd
c
233.0
cmwt
run
M
E5CN-H (48 x 48 mm)
M
i
r-s RUN/STOP
Process Value
Added when Additional
PV display is ON.
E5AN-H (96 x 96 mm)
E5EN-H(48 x 96 mm)
8.0
25.0
Proportional Band
Operation
off
p
Set either
of these
parameters.
db
2.0
Position Proportional
Dead Band
Monitor/Setting
Item Display 2
PF
0.0
M
oc-h
25.0 Monitor/Setting
Item Display 1
PF
Monitor/Setting
Item Display 3
PF
Open/Close Hysteresis
0.8
M
sqrp
Extraction of Square
Root
0.0 Low-cut Point
M
Monitor/Setting
Item Display 4
PF
Monitor/Setting
Item Display 5
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to
5 parameters (advanced function setting level).
PF Key ✽2
Safety Precautions
at
c
c
Set either of these parameters.
M
Adjustment Level
Display
Displayed only
once when
entering
adjustment level.
Set either of these parameters.
l.adj
Set either of these parameters.
Adjustment Level
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Manual Control Level
c
✽1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H).
✽2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).
63
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
E5CN
E5CN-U (48 x 48 mm)
E5@N/E5@N-H
Press the O Key for at least 1 s.
Press the O Key for at least 3 s.
Other than the Auto/Manual Switch display
Initial Setting Level
E5CN-H (48 x 48 mm)
Press the O Key less than 1 s.
Press the O Key less than 1 s.
Protect Level
The time taken to move to the protect level
can be adjusted by changing the "Move to
protect level time" setting.
to Protect Level:
pmov Move
Displayed only when a password
M
0 is set. Restricts moving to protect
level.
Operation/Adjustment
Protect:
oapt Restricts displaying and
modifying menus in
0 operation, adjustment, and
manual control levels.
M
icpt
0
E5AN-H (96 x 96 mm)
E5EN-H(48 x 96 mm)
M
Initial Setting/
Communications Protect:
This protect level restricts
movement to the initial setting,
communications setting, and
advanced function setting levels.
wtpt
Setting Change Protect:
Protects changes to setups
off by operating the front panel
keys.
M
pfpt
PF Key Protect
Restricts PF key operation
off (E5AN-H/E5EN-H only)
M
Mask Enable:
pmsk Parameter
Displayed only when a
on parameter mask is set.
M
prlp
Password to Move to
Protect Level:
0 Password setting
M
in-t
Communications
Setting Level
5
Input Type
Displayed only for models with communications. Changes
are effective after cycling power or after a software reset.
in-h
M
in-l
M
Scaling Upper Limit
1
dp
7
d-u
c
M
Communications
Data Length
c
M
sbit
2
sl-h
c
Decimal Point
Temperature Unit
°C, °F
For input type of
temperature
Limit the set point
M
sl-l SP Lower Limit
pid
M
s-hc
Send Data Wait Time
20
M
stnd
M
st
on
Operation
M
ptrn
Standard or
Heating/Cooling
7
cp
ST (Self-tuning)
For input type of
temperature,
standard control, or
PID
Program Pattern
c-cp
When assigning PID or
control output to ON/OFF
output
Control Period (Heating)
Set the ON/OFF
output cycle.
Control Period (Cooling)
Safety Precautions
M
orev Direct/Reverse Operation
or-r
Alarm 1 Type
M
Transfer Output
Upper Limit
M
tr-l
0.0
M
o1-t
Transfer Output
Lower Limit
Linear Current Output
Linear output
M
ev-b
Bank Numbers Used
M
ev-1
none
Event Input
Assignment 1
M
M
ev-3
none
Event Input
Assignment 3
M
ev-4
none
Event Input
Assignment 4
M
clfl
Closed/Floating
flot
M
Motor Calibration
M
mot
Travel Time
30
Alarm 1
0.2 Hysteresis
M
100.0
off
2
alh1
tr-h
calb
M
c
Linear output
M
stop
Valid Program Bank
20
alt1
M
tr-t Transfer Output Type
Input
ev-2 Event
Assignment 2
20
M
Alarm 3
Hysteresis
1
M
M
Alarm 3 Type
4-20
off
pbnk
M
alh3
off
SP Upper Limit
M
cntl PID ON/OFF
M
c
0.2
-200.0
even
Hysteresis
2
1300.0
Communications
Stop Bits
M
prty Communications Parity
sdwt
alt3
M
M
Alarm 2
M
Scaling Lower Limit
0 For input type of analog
Communications
Baud Rate
9.6
CompoWay/F
(SYSWAY) only
M
alh2
0.2
0
M
bps
len
c
M
Communications Unit No.
Alarm 2 Type
2
100
Protocol Setting:
psel Switches between
cwf CompoWay/F (SYSWAY)
and Modbus.
u-no
alt2
M
M
sqr
off
Extraction of Square
Root Enable
M
Move to Advanced Function
Level:
amov Setting
Displayed when initial
0 setting/ communications
M
protect is set to 0.
Move by setting password (−169).
64
E5CN
E5CN-U (48 x 48 mm)
E5@N/E5@N-H
Power ON
Manual Control
Level
Operation
Level
Adjustment
Level
Initial Setting
Level
Communications Setting
Level
PID Setting
Level
Bank Setting
Level
Monitor/Setting
Item Level
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Protect Level
Advanced
Function Setting
Level
Advanced Function Setting Level
M
rest
a
M
Standby Sequence
Reset
a1lt Alarm 1 Latch
Auxiliary Output 1
a2lt
M
sb1n
n-o Open in Alarm
Open in Alarm
3
rlrv
ST Stable Range
colr
off
M
st-b
0.65
AT Calculated Gain
AT Hysteresis
Limit Cycle MV
Amplitude
Input Digital Filter
M
Additional PV Display
alm1
alm2
a1of Alarm 1 OFF Delay
0
M
Alarm 3 OFF Delay
Auxiliary Output 2
Assignment
m
M
manl
off
pmvd
PID Set Automatic
Selection Hysteresis
pvdp
PV Dead Band
pvst
off
on
ocl
0.1
pf
a-m
M
SV Status Display
Function
d.ref
0.25
Display Refresh
Period
M
PV Rate of Change
ra1m
Control Output 1
ON/OFF Count
0 Monitor
M
Automatic Cooling
ra2m
Control Output 2
ON/OFF Count
0 Monitor
M
Heater Overcurrent
Use
ra1
Control Output 1
ON/OFF Count
0 Alarm Set Value
M
Heater Overcurrent
Heater Overcurrent
Hysteresis
ra2
Control Output 2
ON/OFF Count
0 Alarm Set Value
M
Counter
rac ON/OFF
Reset
0
M
Soak Time Unit
PV Status Display
Function
M
Direct Setting of
off Latch
och
svst
off
M
Character Select
PV Decimal Point
Display
M
Manual MV
Limit Enable
off Coefficient Adjustment
ocu
on
M
17 Calculation Period
csca
o
M
off Position Proportional MV
pvrp
"PV/SP" Display
4 Screen Selection
M
M
Auxiliary Output 3
Assignment
(E5AN/E5EN-H only)
M
t-u
odsl MV Display Selection
M
on
M
PID Set Automatic
Selection Data
M
Auxiliary Output 1
Assignment
M
csel
spdp
M
Control Output 2
Assignment
M
sub3
alm3
a2of Alarm 2 OFF Delay
0
sub2
M
Remote SP Input
Error Output
M
Control Output 1
Assignment
M
Alarm 3 ON Delay
0
a3of
sub1
p-db
Monitor/Setting Item 5
0
M
LBA Band
M
Alarm 2 ON Delay
M
M
out2
none
00
0.0
off
a3on
out1
c
Monitor/Setting Item 4
0
M
0.0
M
Alarm 1 ON Delay
M
M
pvad
a2on
lbab
pfd5
M
LBA Level
8.0
o
M
M
inf
5.0
a1on
lbal
M
PV Stable Band
0
0.8
20.0
pv-b
0.50
3.0
M
M
lcma
c
pidh
LBA Detection Time
M
0
1.0
at-h
c
M
M
c
PV Change Color
M
M
at-g
c
red
alfa α
pv
M
M
MB Command
Logic Switching
M
15.0
0.1
0
M
Heater Burnout
Hysteresis
SP Tracking
M
pidi
HS Alarm Hysteresis
M
lba
Cold Junction
on Compensation
Method
M
off
M
hsh
M
M
off
Monitor/Setting Item 3
0
pfd4
off
rseo
pfd3
Remote SP
Lower Limit
M
sptr
HS Alarm Use
M
Input Error Output
rspl
-200.0
hsl HS Alarm Latch
M
cjc
c
Monitor/Setting Item 2
M
Remote SP
Upper Limit
M
RT
on
Time
rsph
1300.0
M
hsu
Alarm 3 Latch
off
off
c
pfd2
0
M
Auto/Manual Select
Addition
off
M
sero
HB ON/OFF
Burnout
hbl Heater
Latch
c
Alarm 2 Latch
M
on
0.1
rt
prlt Move to Protect Level
Auxiliary Output 3
M
hbh
M
off
M
hbu
M
M
M
n-o
on
a3lt
Auxiliary Output 2
n-o Open in Alarm
sb3n
off
M
Remote SP Enable
off
M
amad
off
M
sb2n
off
off
Monitor/Setting Item 1
1
M
rspu
MV at Stop and Error
Addition
pfd1
E5AN-H (96 x 96 mm)
E5EN-H(48 x 96 mm)
m
Alarm SP Selection
sp-m
M
mvse
Display
ret Automatic
Return Time
SP Ramp Time Unit
alsp
Input Shift Type
ins1
M
M
spru
istp
MV Display
off
Operation
o-dp
Parameter Initialization
off
M
PF Setting
cmov
0
M
Move to Calibration
Level
Safety Precautions
init
E5CN-H (48 x 48 mm)
Press the O Key for at least 1 s.
65
E5@N/E5@N-H
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
E5CN
E5CN-U (48 x 48 mm)
Safety Precautions
!CAUTION
Do not touch the terminals while power is being supplied.
Doing so may occasionally result in minor injury due to
electric shock.
Do not allow pieces of metal, wire clippings, or fine
metallic shavings or filings from installation to enter the
product. Doing so may occasionally result in electric
shock, fire, or malfunction.
Do not use the product where subject to flammable or
explosive gas. Otherwise, minor injury from explosion
may occasionally occur.
Do not leave the cable for the Support Software
connected to the product. Malfunction may occur due to
noise in the cable.
Do not use the Temperature Controller or Conversion
Cable if it is damaged. Doing so may occasionally result
in minor electric shock or fire.
E5AN-H (96 x 96 mm)
E5EN-H(48 x 96 mm)
E5CN-H (48 x 48 mm)
Never disassemble, modify, or repair the product or touch
any of the internal parts. Minor electric shock, fire, or
malfunction may occasionally occur.
CAUTION - Risk of Fire and Electric Shock
a) This product is UL listed as Open Type Process
Control Equipment. It must be mounted in an
enclosure that does not allow fire to escape externally.
b) More than one disconnect switch may be required to
de-energize the equipment before servicing the
product.
c) Signal inputs are SELV, limited energy. ✽1
d) Caution: To reduce the risk of fire or electric shock, do
not interconnect the outputs of different Class 2
circuits. ✽2
If the output relays are used past their life expectancy,
contact fusing or burning may occasionally occur.
Always consider the application conditions and use the
output relays within their rated load and electrical life
expectancy. The life expectancy of output relays varies
considerably with the output load and switching
conditions.
Tighten the terminal screws to between 0.74 and
0.90 N·m. ✽3 Loose screws may occasionally result in
fire.
Safety Precautions
Operation
Set the parameters of the product so that they are
suitable for the system being controlled. If they are not
suitable, unexpected operation may occasionally result in
property damage or accidents.
A malfunction in the product may occasionally make
control operations impossible or prevent alarm outputs,
resulting in property damage. To maintain safety in the
event of malfunction of the product, take appropriate
safety measures, such as installing a monitoring device
on a separate line.
A semiconductor is used in the output section of long-life
relays. If excessive noise or surge is impressed on the
output terminals, a short-circuit failure is likely to occur. If
the output remains shorted, fire will occur due to
overheating of the heater or other cause. Take measures
in the overall system to prevent excessive temperature
increase and to prevent fire from spreading.
Do not allow pieces of metal or wire cuttings to get inside
the cable connector for the Support Software. Failure to
do so may occasionally result in minor electric shock, fire,
or damage to equipment.
Do not allow dust and dirt to collect between the pins in
the connector on the Conversion Cable. Failure to do so
may occasionally result in fire.
66
When inserting the body of the Temperature Controller
into the case, confirm that the hooks on the top and
bottom are securely engaged with the case. If the body of
the Temperature Controller is not inserted properly, faulty
contact in the terminal section or reduced water
resistance may occasionally result in fire or malfunction.
When connecting the Control Output Unit to the socket,
press it in until there is no gap between the Control Output
Unit and the socket. Otherwise contact faults in the
connector pins may occasionally result in fire or
malfunction.
✽1. An SELV circuit is one separated from the power supply with
double insulation or reinforced insulation, that does not exceed
30 V r.m.s. and 42.4 V peak or 60 VDC.
✽2. A class 2 power supply is one tested and certified by UL as having
the current and voltage of the secondary output restricted to
specific levels.
✽3. The tightening torque for E5CN-U is 0.5 N·m.
Precautions for Safe Use
Be sure to observe the following precautions to prevent malfunction
or adverse affects on the performance or functionality of the product.
Not doing so may occasionally result in faulty operation.
1. This product is specifically designed for indoor use only.
Do not use this product in the following places:
• Places directly subject to heat radiated from heating equipment.
• Places subject to splashing liquid or oil atmosphere.
• Places subject to direct sunlight.
• Places subject to dust or corrosive gas (in particular, sulfide gas
and ammonia gas).
• Places subject to intense temperature change.
• Places subject to icing and condensation.
• Places subject to vibration and large shocks.
2. Use and store the product within the rated ambient temperature
and humidity.
Gang-mounting two or more Temperature Controllers, or mounting
Temperature Controllers above each other may cause heat to build
up inside the Temperature Controllers, which will shorten their
service life. In such a case, use forced cooling by fans or other
means of air ventilation to cool down the Temperature Controllers.
3. To allow heat to escape, do not block the area around the product.
Do not block the ventilation holes on the product.
4. Be sure to wire properly with correct polarity of terminals.
5. Use the specified size (M3.5, width 7.2 mm or less) crimped
terminals for wiring. To connect bare wires to the terminal block,
use stranded or solid copper wires with a gage of AWG24 to
AWG14 (equal to a cross-sectional area of 0.205 to 2.081 mm2).
(The stripping length is 5 to 6 mm.) Up to two wires of the same
size and type or two crimp terminals can be inserted into a single
terminal.
6. Do not wire the terminals that are not used.
7. To avoid inductive noise, keep the wiring for the product’s terminal
block away from power cables carry high voltages or large
currents. Also, do not wire power lines together with or parallel to
product wiring. Using shielded cables and using separate conduits
or ducts is recommended.
Attach a surge suppressor or noise filter to peripheral devices that
generate noise (in particular, motors, transformers, solenoids,
magnetic coils, or other equipment that have an inductance
component).
When a noise filter is used at the power supply, first check the
voltage or current, and attach the noise filter as close as possible
to the product.
Allow as much space as possible between the product and devices
that generate powerful high frequencies (high-frequency welders,
high-frequency sewing machines, etc.) or surge.
8. Use this product within the rated load and power supply.
9. Make sure that the rated voltage is attained within two seconds of
turning ON the power using a switch or relay contact. If the voltage
is applied gradually, the power may not be reset or output
malfunctions may occur.
10.Make sure that the Temperature Controller has 30 minutes or
more to warm up after turning ON the power before starting actual
control operations to ensure the correct temperature display.
Precautions for Correct Use
Service Life
1. Use the product within the following temperature and humidity
ranges:
Temperature: −10 to 55°C (with no icing or condensation)
Humidity: 25% to 85%
If the product is installed inside a control board, the ambient
temperature must be kept to under 55°C, including the temperature
around the product.
2. The service life of electronic devices like Temperature Controllers
is determined not only by the number of times the relay is switched
but also by the service life of internal electronic components.
Component service life is affected by the ambient temperature: the
higher the temperature, the shorter the service life and, the lower
the temperature, the longer the service life. Therefore, the service
life can be extended by lowering the temperature of the
Temperature Controller.
3. When two or more Temperature Controllers are mounted
horizontally close to each other or vertically next to one another,
the internal temperature will increase due to heat radiated by the
Temperature Controllers and the service life will decrease. In such
a case, use forced cooling by fans or other means of air ventilation
to cool down the Temperature Controllers. When providing forced
cooling, however, be careful not to cool down the terminals
sections alone to avoid measurement errors.
1. When extending or connecting the thermocouple lead wire, be sure
to use compensating wires that match the thermocouple types.
2. When extending or connecting the lead wire of the platinum
resistance thermometer, be sure to use wires that have low
resistance and keep the resistance of the three lead wires the
same.
3. Mount the product so that it is horizontally level.
4. If the measurement accuracy is low, check to see if input shift has
been set correctly.
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Measurement Accuracy
Operating Precautions
1. It takes approximately two seconds for the outputs to turn ON from
after the power supply is turned ON. Due consideration must be
given to this time when incorporating Temperature Controllers in a
sequence circuit.
2. When using self-tuning, turn ON power for the load (e.g., heater)
at the same time as or before supplying power to the Temperature
Controller. If power is turned ON for the Temperature Controller
before turning ON power for the load, self-tuning will not be
performed properly and optimum control will not be achieved.
3. When starting operation after the Temperature Controller has
warmed up, turn OFF the power and then turn it ON again at the
same time as turning ON power for the load. (Instead of turning
the Temperature Controller OFF and ON again, switching from
STOP mode to RUN mode can also be used.)
4. Avoid using the Controller in places near a radio, television set, or
wireless installing. These devices can cause radio disturbances
which adversely affect the performance of the Controller.
E5AN-H (96 x 96 mm)
E5EN-H(48 x 96 mm)
The degree of protection is as shown below. Sections without any
specification on their degree of protection or those with IP@0 are not
waterproof.
Front panel: IP66
Rear case: IP20, Terminal section: IP00
(E5CN-U: Front panel: IP50, rear case: IP20, terminals: IP00)
E5CN-H (48 x 48 mm)
Waterproofing
1. The disk that is included with the Conversion Cable is designed for
a computer CD-ROM driver. Never attempt to play the disk in a
general-purpose audio player.
2. Do not connect or disconnect the Conversion Cable connector
repeatedly over a short period of time. The computer may
malfunction.
3. After connecting the Conversion Cable to the computer, check the
COM port number before starting communications. The computer
requires time to recognize the cable connection. This delay does
not indicate failure.
4. Do not connect the Conversion Cable through a USB hub. Doing
so may damage the Conversion Cable.
5. Do not use an extension cable to extend the Conversion Cable
length when connecting to the computer. Doing so may damage
the Conversion Cable.
6. The E5AN-H/E5EN-H use the same port for communications
through the infrared port and the Support Software port. Do not
attempt to use communications through the Support Software port
when the infrared port is being used.
Operation
Others
Safety Precautions
11.When executing self-tuning, turn ON power to the load (e.g.,
heater) at the same time as or before supplying power to the
product. If power is turned ON to the product before turning ON
power to the load, self-tuning will not be performed properly and
optimum control will not be achieved.
12.A switch or circuit breaker must be provided close to the product.
The switch or circuit breaker must be within easy reach of the
operator, and must be marked as a disconnecting means for this
unit.
13.Always turn OFF the power supply before pulling out the interior of
the product, and never touch nor apply shock to the terminals or
electronic components. When inserting the interior of the product,
do not allow the electronic components to touch the case.
14.Do not use paint thinner or similar chemical to clean with. Use
standard grade alcohol.
15.Design the system (e.g., control panel) considering the 2 seconds
of delay that the product's output to be set after power ON.
16.The output may turn OFF when shifting to certain levels. Take this
into consideration when performing control.
17.The number of EEPROM write operations is limited. Therefore,
use RAM write mode when frequently overwriting data during
communications or other operations.
18.Always touch a grounded piece of metal before touching the
Temperature Controller to discharge static electricity from your
body.
19.Do not remove the terminal block. Doing so may result in failure or
malfunction.
20.Control outputs (for driving SSR) that are voltage outputs are not
isolated from the internal circuits. When using a grounded
thermocouple, do not connect any of the control output terminals
to ground. (Doing so may result in an unwanted circuit path,
causing error in the measured temperature.)
21.When replacing the body of the Temperature Controller, check the
condition of the terminals. If corroded terminals are used, contact
failure in the terminals may cause the temperature inside the
Temperature Controller to increase, possibly resulting in fire. If the
terminals are corroded, replace the case as well.
22.Use suitable tools when taking the Temperature Controller apart
for disposal. Sharp parts inside the Temperature Controller may
cause injury.
23.Before connecting an Output Unit, confirm the specifications and
thoroughly read relevant information in the datasheet and manual
for the Temperature Controller.
24.Check the orientation of the connectors on the Conversion Cable
before connecting the Conversion Cable. Do not force a
connector if it does not connect smoothly. Using excessive force
may damage the connector.
25.Do not place heavy object on the Conversion Cable, bend the
cable past its natural bending radius, or pull on the cable with
undue force.
26.Do not connect or disconnect the Conversion Cable while
communications are in progress. Product faults or malfunction
may occur.
27.Make sure that the Conversion Cable's metal components are not
touching the external power terminals.
28.Do not touch the connectors on the Conversion Cable with wet
hands. Electrical shock may result.
29.Before using infrared communications, correctly attach the
enclosed Mounting Adapter to the cable for the Support Software.
When connecting the infrared port on the cable to the Support
Software into the Adapter, insert the connector to the specified
line. Communications may not be possible if the connector is not
connected properly.
E5CN
E5CN-U (48 x 48 mm)
E5@N/E5@N-H
67
E5CN
E5CN-U (48 x 48 mm)
E5@N/E5@N-H
Mounting
Mounting the Terminal Cover
Mounting to a Panel
E5CN
For waterproof mounting, waterproof packing must be installed on the
Controller. Waterproofing is not possible when group mounting
several Controllers. Waterproof packing is not necessary when there
is no need for the waterproofing function.
Make sure that the “UP” mark is facing up, and then attach the E53COV17 Terminal Cover to the holes on the top and bottom of the
Temperature Controller.
E5AN/E5EN
E5CN
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
Order the P2CF-11 or
P3GA-11 Socket separately.
E53-COV17
Terminal Cover
(Accessory)
Slightly bend the E53-COV16 Terminal Cover to attach it to the
terminal block as shown in the following diagram. The Terminal Cover
cannot be attached in the opposite direction.
Adapter
(Accessory)
Slightly bend the
E53-COV16
Terminal Cover in
the direction shown
by the arrows to
attach it to the
terminal block.
E5CN-U
E5CN-H (48 x 48 mm)
Waterproof packing
(Accessory)
Panel
E5CN
1. The Panel Mounting Adapter is also included with the E5CN-U.
There is no waterproof packing included with the E5CN-U.
2. Insert the E5CN/E5CN-U into the mounting hole in the panel.
3. Push the adapter from the terminals up to the panel, and
temporarily fasten the E5CN/E5CN-U.
4. Tighten the two fastening screws on the adapter. Alternately
tighten the two screws little by little to maintain a balance. Tighten
the screws to a torque of 0.29 to 0.39 N·m.
E5EN/E5AN
E5AN-H (96 x 96 mm)
E5EN-H(48 x 96 mm)
Mounting Bracket
(Accessory)
Panel
E53-COV16
Terminal Cover
(Accessory)
Removing the Temperature Controller from the
Case
The Temperature Controller can be removed from the case to perform
maintenance without removing the terminal leads. This is possible for
only the E5CN, E5AN, and E5EN, and not for the E5CN-U. Check the
specifications of the case and Temperature Controller before
removing the Temperature Controller from the case.
E5CN
Tool insertion hole
Flat-blade screwdriver
(Unit: mm)
(1)
(2)
E53-COV16
Terminal Cover
(Accessory)
(3)
Waterproof
packing
(Accessory)
Waterproof
packing
(Accessory)
E5EN
1. Insert the E5AN/E5EN into the square mounting hole in the panel
(thickness: 1 to 8 mm). Attach the Mounting Brackets provided with
the product to the mounting grooves on the top and bottom
surfaces of the rear case.
2. Use a ratchet to alternately tighten the screws on the top and
bottom Mounting Brackets little by little to maintain balance, until
the ratchet turns freely.
68
2.0
(1)
Panel
E53-COV16
Terminal Cover
(Accessory)
0.4
E5AN
Mounting Bracket
(Accessory)
Operation
Safety Precautions
For Front-mounting Socket
(Panel mounting is also possible.)
1. Insert a flat-blade screwdriver into the two tool insertion holes (one
on the top and one on the bottom) to release the hooks.
2. Insert the flat-blade screwdriver in the gap between the front panel
and rear case, and pull out the front panel slightly. Hold the top and
bottom of the front panel and carefully pull it out toward you,
without applying unnecessary force.
3. When inserting the body of the Temperature Controller into the
case, make sure the PCBs are parallel to each other, make sure
that the sealing rubber is in place, and press the E5CN toward the
rear case into position. While pushing the E5CN into place, push
down on the hooks on the top and bottom surfaces of the rear case
so that the hooks are securely locked in place. Be sure that
electronic components do not come into contact with the case.
E5AN/E5EN
Tool insertion
hole
Tool insertion
hole
(1)
E5CN
E5CN-U (48 x 48 mm)
E5@N/E5@N-H
(1)
E5EN
(1)
(1)
1. Insert a flat-blade screwdriver into the two tool insertion holes (one
on the top and one on the bottom) to release the hooks.
2. Insert the flat-blade screwdriver in the gap between the front panel
and rear case (two on the top and two on the bottom), and use it to
pry and pull out the front panel slightly. Then, pull out on the front
panel gripping both sides. Be sure not to impose excessive force
on the panel.
3. When inserting the body of the Temperature Controller into the
case, make sure the PCBs are parallel to each other, make sure
that the sealing rubber is in place, and press the E5AN/E5EN
toward the rear case until it snaps into position. While pressing the
E5AN/E5EN into place, press down on the hooks on the top and
bottom surfaces of the rear case so that the hooks securely lock in
place. Make sure that electronic components do not come into
contact with the case.
Precautions when Wiring
• Separate input leads and power lines in order to prevent external
noise.
• Use wires with a gage of AWG24 (cross-sectional area:
0.205 mm2) to AWG14 (cross-sectional area: 2.081 mm2) twistedpair cable (stripping length: 5 to 6 mm).
• Use crimp terminals when wiring the terminals.
• Tighten the terminal screws to a torque of 0.74 to 0.90 N·m,
however the terminal screws on the E5CN-U must be tightened to
a torque of 0.5 N·m.
• Use the following types of crimp terminals for M3.5 screws.
E5CN-H (48 x 48 mm)
E5AN
E5AN-H (96 x 96 mm)
E5EN-H(48 x 96 mm)
(3)
(3)
E5AN (96 x 96 mm)
E5EN (48 x 96 mm)
(2)
(2)
7.2 mm max.
Safety Precautions
Operation
7.2 mm max.
• Do not remove the terminal block. Doing so will result in
malfunction or failure.
69
CX-Thermo Support Software Ver. 4.0
EST2-2C-MV4
Monitoring/Setting Support Software for E5CN/CN-H, E5AN/AN-H,
E5EN/EN-H, E5ZN, E5@R/@R-T, and EJ1 Temperature Controllers
Enabling Faster Parameter Setup, Device Adjustment, and
Maintenance
• Enables editing and batch-downloading parameters from a
personal computer, reducing the work required to set parameters.
Usability is improved with table-formatted parameter editing from
version. 4.0.
• Supports Trend Monitoring:
Monitor data (PV,SP,MV,PID parameter, Alarm ON/OFF, etc.) for
up to 31 E5@N/@N-H Temperature Controllers.
Connect up to 64 EJ1N, 17 EJ1G, or 16 E5ZN Temperature
Controllers. (The Temperature Controllers must be from the same
series.)
• Supports parameter masks to hide parameters unnecessary to
display. (Supported only by the E5@N/@N-H and E5@R/@R-T).
• Logic operations enable setting inputs from external inputs (event
inputs) or temperature status, outputs to external outputs (control or
auxiliary outputs), and changing operating status with ON/OFF
delays.
(Supported only by the E5@N/@N-H).
• Easy adjustment of control performance by fine-tuning.
✽ Fine-tuning instructs the CX-Thermo to calculate a PID parameters by
directly inputting commands to improve response.
Ordering Information
List of Models
Name
Model
CX-Thermo Support Software
EST2-2C-MV4
Specifications
Compatible
devices
Temperature
Controllers
E5CN (available from April 2004)
E5AN, E5EN (available from Feb 2005),
E5CN-H, E5AN-H, E5EN-H
E5AR, E5ER
E5AR-T, E5ER-T
E5ZN
EJ1N-TC4, EJ1N-TC2, EJ1N-HFU
EJ1G-TC4, EJ1G-TC2, EJ1G-HFU
G3ZA (only when connected to EJ1N-TC4, EJ1N-TC2, EJ1G-TC4, EJ1G-TC2)
Note: Models with DeviceNet communications are not supported.
Personal
computer
system
requirements
OS
Windows 2000 (service pack 3 or higher), XP, or Vista (Japanese or English version)
CPU
300 MHz min.
Memory
128 MB min.
Harddisk
300 MB min. available space
CD-ROM
One CD-ROM drive min.
Monitor
SVGA (800 × 600) min.
Communications
ports
Connection method
70
• RS-232C port, or USB port, 1 port min.
• An E58-CIFQ1 USB-Serial Conversion Cable is required to connect a computer to the setup tool port the
E5@N, E5@N-H, or EJ1.
• A K3SC Interface Converter is used to connect a computer to models with RS-422/RS-485
communications.
• An E58-CIFIR USB-Infrared Conversion Cable is required to wirelessly connect a computer to models with
infrared communications (E5AN-H or E5EN-H).
71
Warranty and Application Considerations
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or
other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. H160-E1-01A In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
Control Devices Division H.Q.
Analog Controller Division
Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
Tel: (81)75-344-7080/Fax: (81)75-344-7149