Digital Temperature Controllers/Digital Controllers E5@N/E5@N-H Upgraded 1/16, 1/8, and 1/4 DIN Controllers, the Best-selling E5@N Series. Basic Type (Renewal E5@N) and Advanced Type (New E5@N-H). • Improved indication accuracy and preventive maintenance (Basic Type E5@N). • New high-performance Controllers (Advanced Type E5@N-H). • Easy-to-use one-touch operation with PF Key (Only for 1/8 and 1/4 DIN). • Logic operations. E5@N Series Basic Type (Renewal E5@N) Advanced Type (New E5@N-H) E5CN E5EN E5AN E5CN-H E5EN-H E5AN-H 1/16 DIN 1/8 DIN 1/4 DIN 1/16 DIN 1/8 DIN 1/4 DIN 1 Contents Digital Temperature Controllers E5CN/E5CN-U ............................................. 3 E5AN/E5EN ................................................. 17 Digital Controllers E5CN-H........................................................ 31 E5AN-H/E5EN-H.......................................... 43 Operation Procedure 2 • Operation ..................................................... Common to All Controllers 58 • Safety Precautions ....................................... CX-Thermo Support Software 66 • EST2-2C-MV4.............................................. 70 (48 x 48 mm) • Indication Accuracy Thermocouple input: ±0.3% of PV (previous models: ±0.5%) Pt input: ±0.2% of PV (previous models: ±0.5%) Analog input: ±0.2% FS (previous models: ±0.5%) • New E5CN-U Models (Plug-in Models) with analog inputs and current outputs. • A PV/SV-status display function can be set to automatically alternate between displaying the status of the Temperature Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV. • Preventive maintenance for relays in the Temperature Controller using a Control Output ON/OFF Counter. E5AN (96 x 96 mm) E5EN (48 x 96 mm) New 48 x 48-mm Basic Temperature Controller with Enhanced Functions and Performance. Improved Indication Accuracy and Preventive Maintenance Function. 48 × 48-mm E5CN 48 × 48-mm E5CN-U E5CN-H (48 x 48 mm) E5CN/E5CN-U E5CN E5CN-U (48 x 48 mm) Basic-type Digital Temperature Controller Refer to Safety Precautions on page 66. Indication Accuracy • Thermocouple input: ±0.3% of PV • Pt input: ±0.2% of PV • Analog input: ±0.2% FS Sampling Period • 250 ms 2-level Display: PV and SV Control Output 2 • None • Voltage output (for driving SSR) Auxiliary Outputs • None • One • Two 4-digit Display • Auto/manual switching • Temperature Controller status display • Simple program function • Control output ON/OFF count alarm • PV change rate alarm • Models also available with RS-485 communications Operation Sensor Inputs • Universal thermocouple/Pt inputs (Models with temperature inputs) • Analog current/voltage inputs (Models with analog inputs) E5CN Control Output 1 • Relay output • Voltage output (for driving SSR) • Current output • Long-life relay output (hybrid) Safety Precautions Event Inputs • None • Two E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Main I/O Functions This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) E5CN/E5AN/E5EN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158) 3 E5CN E5CN-U (48 x 48 mm) E5CN/E5CN-U Lineup 1 control output Temperature input 2 control outputs 2 auxiliary outputs 1 control output 0 or 2 auxiliary outputs Terminal block Analog input E5CN 2 control outputs 2 auxiliary outputs Temperature input 1 control output 0, 1, or 2 auxiliary outputs Analog input 1 control output 0, 1, or 2 auxiliary outputs Basic Type E5AN (96 x 96 mm) E5EN (48 x 96 mm) 0 or 2 auxiliary outputs Plug-in Note: Models with one control output and one or two auxiliary outputs and models with two control outputs can be used for heating/cooling control. Model Number Structure Model Number Legend E5CN-H (48 x 48 mm) Controllers Option Units E5CN-@@M@@-@-500 E53-CN@@@ 1 2 3 4 5 1 6 7 E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) 1. Control Output 1 R: Relay output Q: Voltage output (for driving SSR) C: Current output Y: Long-life relay output (hybrid) ✽1 2. Auxiliary Outputs ✽2 Blank: None 2: Two outputs 3. Option M: Option Unit can be mounted. 4. Input Type T: Universal thermocouple/platinum resistance thermometer L: Analog current/voltage input 5. Power Supply Voltage Blank: 100 to 240 VAC D: 24 VAC/VDC Operation 6. Case Color Blank: Black W: Silver 7. Terminal Cover -500: With terminal cover 2 3 4 1. Applicable Controller CN: E5CN or E5CN-H 2. Function 1 Blank: None Q: Control output 2 (voltage for driving SSR) P: Power supply for sensor 3. Function 2 Blank: None H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection (CT2) B: Two event inputs 03: RS-485 communications H03: Heater burnout/SSR failure/Heater overcurrent detection (CT1) + RS-485 communications HB: Heater burnout/SSR failure/Heater overcurrent detection (CT1) + Two event inputs HH03: Heater burnout/SSR failure/Heater overcurrent detection (CT2) + RS-485 communications 4. Version N2: Applicable only to models released after January 2008 Safety Precautions Note: Not all combinations of function 1 and function 2 specifications are possible for Option Units (E53-@@@@). ✽1. Always connect an AC load to a long-life relay output. The output will not turn OFF if a DC load is connected because a triac is used for switching the circuit. For details, check the conditions in Ratings. ✽2. Auxiliary outputs are contact outputs that can be used to output alarms or results of logic operations. 4 Input type Auxiliary outputs Control output 1 Relay output None 100 to 240 VAC Thermocouple or Resistance thermometer 2 None 24 VAC/VDC Thermocouple or Resistance thermometer Black 2 None 1/16 DIN 48 × 48 × 78 (W × H × D) 100 to 240 VAC Analog (current/voltage) 2 24 VAC/VDC Analog (current/voltage) 2 None 100 to 240 VAC Thermocouple or Resistance thermometer Silver 24 VAC/VDC 2 2 Model E5CN-RMT-500 Voltage output (for driving SSR) E5CN-QMT-500 Current output E5CN-CMT-500 Relay output E5CN-R2MT-500 Voltage output (for driving SSR) E5CN-Q2MT-500 Current output E5CN-C2MT-500 Long-life relay output (hybrid) E5CN-Y2MT-500 Relay output E5CN-RMTD-500 Voltage output (for driving SSR) E5CN-QMTD-500 Current output E5CN-CMTD-500 Relay output E5CN-R2MTD-500 Voltage output (for driving SSR) E5CN-Q2MTD-500 Current output E5CN-C2MTD-500 Relay output E5CN-RML-500 Voltage output (for driving SSR) E5CN-QML-500 Current output E5CN-CML-500 Relay output E5CN-R2ML-500 Voltage output (for driving SSR) E5CN-Q2ML-500 Current output E5CN-C2ML-500 Long-life relay output (hybrid) E5CN-Y2ML-500 Relay output E5CN-R2MLD-500 Voltage output (for driving SSR) E5CN-Q2MLD-500 Current output E5CN-C2MLD-500 Relay output E5CN-RMT-W-500 Voltage output (for driving SSR) E5CN-QMT-W-500 Current output E5CN-CMT-W-500 Relay output E5CN-R2MT-W-500 Voltage output (for driving SSR) E5CN-Q2MT-W-500 Current output E5CN-C2MT-W-500 Long-life relay output (hybrid) E5CN-Y2MT-W-500 Relay output E5CN-R2MTD-W-500 Voltage output (for driving SSR) E5CN-Q2MTD-W-500 Current output E5CN-C2MTD-W-500 Option Units One of the following Option Units can be mounted to provide the E5CN with additional functions. Functions Communications RS-485 Model 3-phase heater burnout/SSR failure/ Heater overcurrent detection Heater burnout/SSR failure/Heater overcurrent detection E53-CNHH03N2 Event inputs Communications RS-485 E53-CNHBN2 Control output 2 (Voltage for driving SSR) Event inputs Heater burnout/SSR failure/Heater overcurrent detection Communications RS-485 Communications RS-485 E5AN (96 x 96 mm) E5EN (48 x 96 mm) Power supply voltage Heater burnout/SSR failure/Heater overcurrent detection Operation Case color E53-CNQ03N2 External power supply for ES1B E53-CNPBN2 External power supply for ES1B E53-CNPHN2 External power supply for ES1B E53-CNP03N2 E53-CNH03N2 Communications RS-485 Safety Precautions Size E5CN-H (48 x 48 mm) Controllers with Terminal Blocks E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Ordering Information E5CN E5CN-U (48 x 48 mm) E5CN/E5CN-U E53-CN03N2 Event inputs E53-CNBN2 Heater burnout/SSR failure/Heater overcurrent detection Control output 2 (Voltage for driving SSR) E53-CNQHN2 3-phase heater burnout/SSR failure/ Heater overcurrent detection Control output 2 (Voltage for driving SSR) E53-CNQHHN2 Control output 2 (Voltage for driving SSR) E53-CNQBN2 Event inputs Note: Option Units cannot be used for plug-in models. These Option Units are applicable only to models released after January 2008. 5 E5AN (96 x 96 mm) E5EN (48 x 96 mm) E5CN E5CN-U (48 x 48 mm) E5CN/E5CN-U Model Number Structure Model Number Legend (Plug-in-type Controllers) E5CN-@@@U 1 2 3 4 3. Input Type T: Universal thermocouple/platinum resistance thermometer L: Analog Input 4. Plug-in type U: Plug-in type 1. Output Type R: Relay output Q: Voltage output (for driving SSR) C: Current output 2. Number of Alarms Blank: No alarm 1: One alarm 2: Two alarms Ordering Information Plug-in-type Controllers Size Case color Power supply voltage Input type Auxiliary outputs Control output 1 Relay output E5CN-H (48 x 48 mm) None Thermocouple or resistance thermometer 1 2 100 to 240 VAC E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) 1 1/16 DIN Analog (current/voltage) Black 2 None 24 VAC/VDC Thermocouple or resistance thermometer 1 Operation 2 Voltage output (for driving SSR) E5CN-QTU Current output E5CN-CTU Relay output E5CN-R1TU Voltage output (for driving SSR) E5CN-Q1TU Current output E5CN-C1TU Relay output E5CN-R2TU Voltage output (for driving SSR) E5CN-Q2TU Current output E5CN-C2TU Relay output E5CN-R1LU Voltage output (for driving SSR) E5CN-Q1LU Current output E5CN-C1LU Relay output E5CN-R2LU Voltage output (for driving SSR) E5CN-Q2LU Current output E5CN-C2LU Relay output E5CN-RTDU Voltage output (for driving SSR) E5CN-QTDU Current output E5CN-CTDU Relay output E5CN-R1TDU Voltage output (for driving SSR) E5CN-Q1TDU Current output E5CN-C1TDU Relay output E5CN-R2TDU Voltage output (for driving SSR) E5CN-Q2TDU Safety Precautions Current output 6 Model E5CN-RTU E5CN-C2TDU E5CN/E5CN-U Note: Use this Adapter when the panel has been previously prepared for the E5B@. Terminal Cover Connectable models Terminal block models Model E53-COV17 Sockets (for Plug-in Models) Type Note: The Terminal Cover comes with the E5CN-@@@-500 models. Waterproof Packing Model Y92S-29 Note: The Waterproof Packing is included with the Controller only for models with terminal blocks. Current Transformers (CTs) Model Front-connecting Socket P2CF-11 Front-connecting Socket with Finger Protection P2CF-11-E Back-connecting Socket P3GA-11 Terminal Cover for Back-connecting socket with Finger Protection Y92A-48G CX-Thermo Support Software Model Hole diameter Model 5.8 dia. E54-CT1 12.0 dia. E54-CT3 EST2-2C-MV4 E5AN (96 x 96 mm) E5EN (48 x 96 mm) Model Y92F-45 E5CN-H (48 x 48 mm) Connectable models Terminal block models E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Model E58-CIFQ1 Operation Adapter Safety Precautions USB-Serial Conversion Cable E5CN E5CN-U (48 x 48 mm) Accessories (Order Separately) 7 E5AN (96 x 96 mm) E5EN (48 x 96 mm) E5CN E5CN-U (48 x 48 mm) E5CN/E5CN-U Specifications Ratings Power supply voltage No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power consumption E5CN 100 to 240 VAC: 7.5 VA (max.) (E5CN-R2T at 100 VAC: 3.0 VA) 24 VAC/VDC: 5 VA/3 W (max.) (E5CN-R2TD at 24 VAC: 2.7 VA) E5CN-U 100 to 240 VAC: 6 VA (max.) 24 VAC/VDC: 3 VA/2 W (max.) (models with current output: 4 VA/2 W) Sensor input Models with temperature inputs Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Voltage input: 0 to 50 mV Models with analog inputs Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.) Control method ON/OFF control or 2-PID control (with auto-tuning) E5CN SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA E5CN-U SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Voltage output (for driving SSR) E5CN E5CN-U Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection circuit Current output E5CN 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000 Long-life relay output E5CN SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply voltage: 75 to 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA, leakage current: 5 mA max. (250 VAC, 60 Hz) E5CN-H (48 x 48 mm) Relay output Control outputs Operation E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Auxiliary outputs Event inputs Number of outputs 1 or 2 max. (Depends on the model.) Output specifications Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Number of inputs 2 External contact input specifications Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. Current flow: Approx. 7 mA per contact External power supply for ES1B 12 VDC ±10%, 20 mA, short-circuit protection circuit provided Setting method Digital setting using front panel keys Indication method 11-segment digital display and individual indicators (7-segment display also possible) Character height: PV: 11 mm, SV: 6.5 mm Multi SP Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial communications. Bank switching Not supported Other functions Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic operations, PV/SV status display, simple program, automatic cooling coefficient adjustment Safety Precautions Ambient operating temperature −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C 8 Ambient operating humidity 25% to 85% Storage temperature −25 to 65°C (with no condensation or icing) Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal Inputs) Input Type Platinum resistance thermometer Name Pt100 Infrared temperature sensor Thermocouple JPt100 K J T E L U N R S B W PL II 10 to 70°C 60 to 120 °C 115 to 165 °C 140 to 260 °C Analog input 0 to 50 mV 2300 2300 E5CN E5CN-U (48 x 48 mm) E5CN/E5CN-U 1800 1800 1700 1700 1700 1600 1300 1300 1300 1300 Usable in the following ranges by scaling: −1999 to 9999 or −199.9 to 999.9 1200 1100 900 850 850 850 800 700 600 600 500.0 500 500.0 500.0 400.0 400 400 400.0 400 400.0 260 300 200 100.0 100 0.0 −100.0 Setting number 165 90 100 0 −200.0 100.0 120 E5CN-H (48 x 48 mm) 1000 0.0 −20.0 −100 −20.0 −200 −199.9 0 1 −199.9 2 3 −200 4 5 −200 −199.9 −200 6 7 8 9 10 11 12 13 14 15 Current 4 to 20mA Voltage 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V Setting range Usable in the following ranges by scaling: −1999 to 9999, −199.9 to 999.9, −19.99 to 99.99 or −1.999 to 9.999 Setting number 0 1 2 16 17 0 0 0 0 0 0 18 24 25 19 20 21 22 23 JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) Models with Analog Inputs Input Type 0 −200 −199.9 −200 Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990 Input specification 0 −100 3 4 E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Temperature range (°C) 1400 E5AN (96 x 96 mm) E5EN (48 x 96 mm) 1500 Safety Precautions Operation Shaded settings are the default settings. 9 E5CN E5CN-U (48 x 48 mm) E5CN/E5CN-U Alarm Outputs Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function). E5AN (96 x 96 mm) E5EN (48 x 96 mm) Set value 0 1 ✽1 2 3 4 Safety Precautions Operation E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) ✽1 10 5 ✽1 Alarm output operation Alarm type Alarm function OFF When X is positive ON OFF Upper limit ON OFF Upper- and lowerlimit range Upper- and lowerlimit with standby sequence Absolute-value upper-limit ON OFF 9 Absolute-value lower-limit ON OFF 10 Absolute-value upper-limit with standby sequence ON OFF Absolute-value lower-limit with standby sequence ON OFF 11 12 LBA (for alarm 1 only) --- 13 PV change rate alarm --- H ✽2 ON OFF H SP H < 0, L > 0 H < L X H SP L H H > 0, L < 0 H > L H SP L H < 0, L > 0 H ≥ L L SP SP H SP L ✽3. Set value: 4, Upper- and lower-limit range X Case 1 SP L Case 3 (Always OFF) Case 2 H SP H < 0, L > 0 H < L H SP L H H H > 0, L < 0 H > L H SP L L SP ✽4 SP SP H L X SP X SP X 0 X 0 X 0 X 0 H > 0, L < 0 H ≤ L H < 0, L < 0 ✽3 SP L Case 3 (Always ON) H < 0, L < 0 L ON OFF SP L ✽5 ON OFF 8 X ON OFF Lower-limit with standby sequence 7 X SP ON OFF ON OFF H SP ON OFF Upper-limit with standby sequence 6 L Case 2 Case 1 Output OFF Upper- and lowerlimit Lower limit When X is negative ✽1. With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” ✽2. Set value: 1, Upper- and lower-limit alarm ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF H < 0, L > 0 H ≥ L H > 0, L < 0 H ≤ L ✽4. Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above X SP X SP X 0 X 0 X 0 X 0 • Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. • Case 3: Always OFF ✽5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. E5CN E5CN-U (48 x 48 mm) E5CN/E5CN-U Characteristics E5AN (96 x 96 mm) E5EN (48 x 96 mm) Influence of voltage ✽2 Input sampling period 250 ms Hysteresis Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) ✽4 Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS) Proportional band (P) Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) ✽4 Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS) Integral time (I) 0 to 3999 s (in units of 1 s) Derivative time (D) 0 to 3999 s (in units of 1 s) ✽5 Control period 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range −1999 to 9999 (decimal point position depends on input type) Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) Vibration resistance Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions Shock resistance Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Destruction 300 m/s2, 3 times each in X, Y, and Z directions E5CN Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g E5CN-U Controller: Approx. 110 g, Mounting Bracket: Approx. 10 g E5CN Front panel: IP66, Rear case: IP20, Terminals: IP00 Degree of protection E5CN-U Front panel: IP50, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.0 or higher Setup Tool port Provided on the bottom of the E5CN. Use this port to connect a computer to the E5CN when using the Setup Tool. An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN. ✽6 Standards EMC Approved standards ✽7 UL 61010-1, CSA C22.2 No. 1010-1 Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II EMI: Radiated Interference Electromagnetic Field Strength: Noise Terminal Voltage: EMS: ESD Immunity: Electromagnetic Field Immunity: Burst Noise Immunity: Conducted Disturbance Immunity: Surge Immunity: Power Frequency Magnetic Field Immunity: Voltage Dip/Interrupting Immunity: Operation Weight E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Affect of signal source resis- Thermocouple: 0.1°C/Ω max. (100 Ω max.) tance Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) E5CN-H (48 x 48 mm) Influence of temperature ✽2 Thermocouple input (R, S, B, W, PL II): Terminal block models (E5CN): (±1% of PV or ±10°C, whichever is greater) ±1 digit max. Plug-in models (E5CN-U): (±2% of PV or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: ✽3 Terminal block models (E5CN): (±1% of PV or ±4°C, whichever is greater) ±1 digit max. Plug-in models (E5CN-U): (±2% of PV or ±4°C, whichever is greater) ±1 digit max. Platinum resistance thermometer input: Terminal block models (E5CN) and plug-in models (E5CN-U): (±1% of PV or ±2°C, whichever is greater) ±1 digit max. Analog input: Terminal block models (E5CN) and plug-in models (E5CN-U): (±1%FS) ±1 digit max. EN 61326 EN 55011 Group 1, class A EN 55011 Group 1, class A EN 61326 EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-6 EN 61000-4-5 EN 61000-4-8 EN 61000-4-11 ✽1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C, whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max. ✽2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage ✽3. K thermocouple at −100°C max.: ±10° max. ✽4. “EU” stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is °C or °F. ✽5. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s). ✽6. External communications (RS-485) and cable communications for the Setup Tool can be used at the same time. ✽7. The E5CN-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11 is not certified for UL listing. Safety Precautions Indication accuracy Thermocouple: ✽1 Terminal block models (E5CN): (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max. Plug-in models (E5CN-U): (±1% of indicated value or ±2°C, whichever is greater) ±1 digit max. Platinum resistance thermometer input: Terminal block models (E5CN) and plug-in models (E5CN-U): (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit max. Analog input: Terminal block models (E5CN) and plug-in models (E5CN-U): ±0.2% FS ±1 digit max. CT input: Terminal block models (E5CN): ±5% FS ±1 digit max. 11 USB-Serial Conversion Cable Applicable OS Windows 2000, XP, or Vista Applicable software Thermo Mini, CX-Thermo version 4.0 or higher Applicable models E5AN/E5EN/E5CN/E5CN-U/E5AN-H/ E5EN-H/E5CN-H E5CN-H (48 x 48 mm) E5AN (96 x 96 mm) E5EN (48 x 96 mm) USB interface standard Conforms to USB Specification 1.1. DTE speed 38400 bps Connector specifications Computer: USB (type A plug) Temperature Controller: Setup Tool port (on bottom of Controller) Power supply Bus power (Supplied from USB host controller.) Power supply voltage 5 VDC Current consumption 70 mA Ambient operating temperature 0 to 55°C (with no condensation or icing) Ambient operating humidity 10% to 80% Storage temperature −20 to 60°C (with no condensation or icing) Storage humidity 10% to 80% Altitude 2,000 m max. Weight Approx. 100 g Note: A driver must be installed in the personal computer. Refer to installation information in the operation manual for the Conversion Cable. Communications Specifications E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Transmission line RS-485: Multipoint connection method RS-485 (two-wire, half duplex) Synchronization method Start-stop synchronization Protocol CompoWay/F, SYSWAY, or Modbus Baud rate 1200, 2400, 4800, 9600, 19200, 38400, or 57600 bps Transmission code ASCII Operation Safety Precautions Communications Data bit length ✽ 7 or 8 bits Stop bit length ✽ 1 or 2 bits Error detection Vertical parity (none, even, odd) Frame check sequence (FCS) with SYSWAY Block check character (BCC) with CompoWay/F or CRC-16 Modbus Dielectric strength 1,000 VAC for 1 min Vibration resistance 50 Hz, 98 m/s2 Weight E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Accessories (E54-CT3 only) Armatures (2) Plugs (2) Heater Burnout Alarms, SSR Failure Alarms, and Heater Overcurrent Alarms Models with detection for single-phase heaters: One input Models with detection for single-phase or three-phase heaters: Two inputs CT input (for heater current detection) Maximum heater current 50 A AC Input current indication accuracy ±5% FS ±1 digit max. Heater burnout alarm setting range ✽1 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms SSR failure alarm setting range ✽2 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms Heater overcurrent alarm setting range ✽3 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms ✽1. For heater burnout alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). ✽2. For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). ✽3. For heater overcurrent alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value). Electrical Life Expectancy Curve for Relays (Reference Values) 500 300 100 50 30 Flow control None Interface RS-485 Retry function None Communications buffer 217 bytes 3 Communications response wait time 0 to 99 ms Default: 20 ms 1 10 5 ✽ The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level. 12 Current Transformer (Order Separately) Ratings Life (× 104 operations) E5CN E5CN-U (48 x 48 mm) E5CN/E5CN-U E5CN 250 VAC, 30 VDC (resistive load) cosφ = 1 0 1 2 3 4 5 6 Switching current (A) Note: Do not connect a DC load to a Controller with a Long-life Relay Output. External Connections • A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to ground. (If the control output terminals are connected to ground, errors will occur in the measured temperature values as a result of leakage current.) • Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose. E5CN Auxiliary outputs (relay outputs) − + DO NOT DO NOT USE mA − USE − − Auxiliary output 1 B V DO NOT USE Auxiliary output 2 A + Analog input A heater burnout alarm, heater short alarm, heater overcurrent alarm, or input alarm is sent to the output to which the alarm 1 function is assigned. Input power supply B + TC/Pt universalinput • 100 to 240 VAC • 24 VAC/VDC (no polarity) Option Units E53-CNHH03N2 Communications (RS-485) and CT2 B(+) E53-CNHBN2 Event inputs and CT 11 11 B(+) 12 RS-485 RS-485 A(−) 12 13 CT2 EV1 13 EV2 14 CT1 A(−) 15 Control output 2 − E53-CN03N2 Communications (RS-485) E53-CNH03N2 Communications (RS-485) and CT B(+) B(+) 11 RS-485 A(−) DO NOT USE 12 DO NOT USE + 13 14 15 E53-CNBN2 Event inputs 11 13 14 CT1 15 A(−) EV1 12 − 13 EV2 + 14 12 VDC, External power supply 20 mA − 15 11 Control output 2 12 DO NOT USE DO NOT USE 13 DO NOT USE 15 14 EV1 EV2 DO NOT USE DO NOT USE 12 − 12 13 DO NOT USE 13 14 DO NOT USE 12 A(−) DO NOT USE 13 14 11 12 13 + 14 External 12 VDC, power supply 20 mA 14 CT1 − + 15 E53-CNQBN2 Event Inputs and Control Output 2 E53-CNQHHN2 Control Output 2 and CT2 11 11 Control output 2 − 12 EV1 13 CT2 EV2 + 14 CT1 CT1 15 B(+) RS-485 15 E53-CNQHN2 Control Output 2 and CT + E53-CNP03N2 Communications (RS-485) and External Power Supply E53-CNPHN2 External Power Supply and CT External + 11 12 VDC, power supply 20 mA 11 11 RS-485 12 E53-CNPBN2 Event Inputs and External Power Supply 11 14 CT1 15 E53-CNQ03N2 Communications (RS-485) and Control Output 2 13 14 Control output 2 15 15 12 − 15 E5CN-U Auxiliary output 250 VAC, 3 A (resistive load) (Relay outputs) Control output 1 Relay output (three terminals used) SPDT, 250 VAC, 3 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Current output 4 to 20 mA DC 0 to 20 mA DC Load: 600 W max. Control output 1 DO NOT USE mA DO NOT USE A Auxiliary output 1 Auxiliary output 2 (Control output (cooling side)) An input error is sent to the output to which the alarm 1 function is assigned. B V DO NOT USE Analog input B TC/Pt universal input Note: For the Wiring Socket, purchase the P2CF-11 or PG3A-11 separately. E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Control output 2 Voltage output (for driving SSR) 12 VDC, 21 mA Input power supply • 100 to 240 VAC • 24 VAC/VDC (no polarity) Operation + Control output 1 E5CN-H (48 x 48 mm) Auxiliary outputs (relay outputs) 250 VAC, 3 A (resistive load) Safety Precautions Control output 1 Long-life relay output 250 VAC, 3 A (resistive load) Relay output 250 VAC, 3 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Current output 0 to 20 mA DC 4 to 20 mA DC Load: 600 Ω max. E5AN (96 x 96 mm) E5EN (48 x 96 mm) Controllers E5CN E5CN-U (48 x 48 mm) E5CN/E5CN-U 13 E5CN E5CN-U (48 x 48 mm) E5CN/E5CN-U Nomenclature E5CN E5CN-U Temperature unit The front panel is the same for the E5CN and E5CN-U. No.1 display Operation indicators No. 2 display Up Key E5AN (96 x 96 mm) E5EN (48 x 96 mm) Level Key Mode Key Down Key Dimensions (Unit: mm) E5CN Terminal Models E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) 6 48 × 48 Panel Cutout Mounted Separately Group Mounted 91 (48 × number of units − 2.5) 78 +1.0 0 1.5 +0.6 0 45 44.8 × 44.8 48.8 58 Group mounting does not allow waterproofing. 60 min. +0.6 0 45 Waterproof Mounting Adapter Packing (Accessory) (Accessory) Terminal Cover (E53-COV17) (Accessory) +0.6 0 45 Note: The terminal block cannot be removed. E5CN-U Plug-in Models (84.7) 70.5 6 48 × 48 • Recommended panel thickness is 1 to 5 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. Panel Cutout Mounted Separately Group Mounted 14.2 +1.0 0 (48 × number of units − 2.5) +0.6 0 45 44.8 × 44.8 58 Operation 60 min. +0.6 0 45 Mounting Adapter (Accessory) 45 +0.6 0 • Recommended panel thickness is 1 to 5 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. Accessories (Order Separately) USB-Serial Conversion Cable Safety Precautions E58-CIFQ1 14 250 USB connector (type A plug) (2,100) LED indicator (SD) LED indicator (RD) 1,765 Serial connector Waterproof Packing E53-COV17 Y92S-29 (for DIN 48 × 48) Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Waterproof Packing does not need to be attached if a waterproof structure is not required. Note: The E53-COV10 cannot be used. 48 48.8 22 E5AN (96 x 96 mm) E5EN (48 x 96 mm) Terminal Cover E5CN E5CN-U (48 x 48 mm) E5CN/E5CN-U Current Transformers E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) 21 15 2.8 5.8 dia. 7.5 Output voltage (Eo) V (r.m.s.) 3 10.5 40 Two, 3.5 dia. 10 30 100 V 50 Hz ∞ 10 Distortion factor 10% 1 kΩ 1 3% 1% 100 mV 100 Ω 10 E54-CT3 RL = 10 Ω 1 2.36 dia. 30 12 dia. 100 µV 9 10 1 10 100 mA 1 E54-CT3 Accessory Connection Example Armature Plug Lead • Plug Output voltage (Eo) V (r.m.s.) 30 18 E54-CT3 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for the Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω 15 Approx. 3 dia. 100 1,000 A 100 V 50 Hz Distortion factor 10% 3% 1% ∞ 10 1 kΩ 500 Ω 1 100 mV 100 Ω 50 Ω 10 RL = 10 Ω 1 100 µV Approx. 6 dia. (22) 10 1 10 100 mA 1 10 100 1,000 A Operation Two, M3 (depth: 4) • Armature 10 Thru-current (Io) A (r.m.s.) 40 × 40 Safety Precautions 25 Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E54-CT1 E5CN-H (48 x 48 mm) 9.1 Thru-current (Io) A (r.m.s.) 15 E5CN E5CN-U (48 x 48 mm) E5CN/E5CN-U Adapter Y92F-45 Note: Use this Adapter when the panel has already been prepared for the E5B@. Fixture (Accessory) 76 4.7 69.6 to 77.6 72 × 72 Mounted to E5CN Panel (1 to 8 mm) 72 × 72 E5CN-H (48 x 48 mm) E5AN (96 x 96 mm) E5EN (48 x 96 mm) 67 × 67 87 48 × 48 2.2 4.7 77.3 (to back of E5CN) E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-U Wiring Socket Front-connecting Socket Eleven, M3.5 × 7.5 sems screws P2CF-11 3 Terminal Layout/Internal Connections (Top View) 4.5 7.8 8 7 6 5 Mounting Holes 4 Two, 4.5 dia. mounting holes 35.4 70 max. Two, 4.5-dia. holes 4 9 3 10 11 1 2 40±0.2 Note: Can also be mounted to a DIN track. 50 max. 31.2 max. Operation Note: A model with finger protection (P2CF-11-E) is also available. Back-connecting Socket P3GA-11 27 dia. 4 7 3 Terminal Layout/Internal Connections (Bottom View) 5 6 7 8 4 45 25.6 Safety Precautions 3 9 2 1 11 10 45 4.5 16.3 6.2 6 8.7 Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets. 2. A Protective Cover for finger protection (Y92A-48G) is also available. 16 • Indication Accuracy Thermocouple input: ±0.3% of PV (previous models: ±0.5%) Pt input: ±0.2% of PV (previous models: ±0.5%) Analog input: ±0.2% FS (previous models: ±0.5%) • A PV/SV-status display function can be set to automatically alternate between displaying the status of the Temperature Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV. 96 × 96 mm 48 × 96 mm • Preventive maintenance for relays in the Temperature Controller E5AN E5EN using a Control Output ON/OFF Counter. • Three-level display that simultaneously displays the PV, SV, and MV. • One-touch operation with PF Key that can be assigned to auto/manual, RUN/ Refer to Safety Precautions on page 66. STOP, or other functions. Main I/O Functions E5AN E5EN 3-level Display ✽ Simultaneously displays set items, such as the PV, SV, and MV. Event Inputs • None • Two ✽ A 2-level display when shipped from the factory. A 3-level display is activated if parameters are initialized. For details on the third display level, refer to the User’s Manual, Basic Type (Cat. No. H156). Sensor Inputs • Universal thermocouple/Pt inputs (Models with temperature inputs) • Analog current/voltage inputs (Models with analog inputs) Sampling Period • 250 ms PF Key (Programmable function key) Auxiliary Outputs • Three Control Output 2 • Voltage output (for driving SSR) • Long-life relay output (hybrid) • Auto/manual switching • Temperature Controller status display • Simple program function • Control output ON/OFF count alarm • PV change rate alarm • Models also available with RS-485 or RS-232C communications Control Output 1 • Relay output • Voltage output (for driving SSR) • Current output This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) Operation 4-digit Display Safety Precautions Indication Accuracy • Thermocouple input: ±0.3% of PV • Pt input: ±0.2% of PV • Analog input: ±0.2% FS E5CN E5CN-U (48 x 48 mm) New 96 x 96-mm and 48 x 96-mm Basic Temperature Controllers with Enhanced Functions and Performance. Improved Indication Accuracy and Preventive Maintenance Function. E5AN (96 x 96 mm) E5EN (48 x 96 mm) (96 x 96 mm and 48 x 96 mm) E5CN-H (48 x 48 mm) E5AN/E5EN E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Basic-type Digital Temperature Controller E5CN/E5AN/E5EN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158) 17 E5AN/E5EN E5CN E5CN-U (48 x 48 mm) Lineup 1 control output 3 auxiliary outputs 2 control outputs 3 auxiliary outputs 1 control output 3 auxiliary outputs 2 control outputs 3 auxiliary outputs Temperature input E5AN/E5EN Basic Type Terminal block E5AN (96 x 96 mm) E5EN (48 x 96 mm) Analog input Note: Models with one control output or two control outputs can be used for heating/cooling control. Model Number Structure Model Number Legend Controllers Option Units E5AN/E5EN-@3@M@@-@-500-N Operation E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) 1 2 3 4 5 6 7 8 9 1. Control Output 1 R: Relay output Q: Voltage output (for driving SSR) C: Current output 2. Auxiliary Outputs 3: Three outputs 3. Heater Burnout/SSR Failure, Control Output 2, or External Power Supply for ES1B Blank: None Q: Control output 2 (voltage output for driving SSR) Y: Long-life relay output (hybrid) H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection (CT2) P: Power supply for sensor 4. Option M: Option Unit can be mounted. 5. Input Type T: Universal thermocouple/platinum resistance thermometer input L: Analog current/voltage input 6. Power Supply Voltage Blank: 100 to 240 VAC D: 24 VAC/VDC 7. Case Color Blank: Black W: Silver Safety Precautions 8. Terminal Cover -500: With terminal cover 9. Version N: Available only to models released after January 2008. 18 E53-@ 1 1. Function EN01: RS-232C communications EN03: RS-485 communications AKB: Event input E5AN/E5EN E5AN Controllers with Terminal Blocks Control output 1 Functions Heater Power supply Control burnout for Sensor output 2 Relay output E5AN-R3MT-500-N Voltage output (for driving SSR) E5AN-Q3MT-500-N Current output Thermocouple or Resistance thermometer 3 100 to 240 VAC E5AN-C3MT-500-N Relay output 1 E5AN-R3HMT-500-N Voltage output for driving SSR) 1 E5AN-Q3HMT-500-N Relay output 2 E5AN-R3HHMT-500-N Voltage output for driving SSR) 2 E5AN-Q3HHMT-500-N Relay output Voltage output E5AN-R3QMT-500-N Voltage output (for driving SSR) Voltage output E5AN-Q3QMT-500-N Current output Voltage output E5AN-C3QMT-500-N E5AN-R3YMT-500-N Long-life E5AN-Q3YMT-500-N relay output E5AN-C3YMT-500-N Relay output Voltage output (for driving SSR) Current output Black 1/4 DIN 96 × 96 × 78 (W × H × D) Analog (current/voltage) 3 Relay output Sensor Power E5AN-R3PMT-500-N Voltage output (for driving SSR) Sensor Power E5AN-Q3PMT-500-N Relay output E5AN-R3ML-500-N Voltage output (for driving SSR) E5AN-Q3ML-500-N Current output E5AN-C3ML-500-N Relay output 1 E5AN-R3HML-500-N Voltage output 1 (for driving SSR) E5AN-Q3HML-500-N Long-life relay E5AN-Q3YML-500-N output Voltage output (for driving SSR) 24 VAC/ VDC Thermocouple or Resistance thermometer 100 to 240 VAC 24 VAC/ VDC E5AN-R3MTD-500-N Voltage output (for driving SSR) E5AN-Q3MTD-500-N Relay output E5AN-C3MTD-500-N 1 E5AN-R3HMTD-500-N Voltage output 1 (for driving SSR) E5AN-Q3HMTD-500-N Relay output 2 E5AN-R3HHMTD-500-N Voltage output 2 (for driving SSR) E5AN-Q3HHMTD-500-N Relay output E5AN-R3MT-W-500-N Voltage output (for driving SSR) E5AN-Q3MT-W-500-N Current output Thermocouple or Resistance 3 thermometer Silver Relay output Current output 3 Model Relay output E5AN-C3MT-W-500-N 1 E5AN-R3HMT-W-500-N Voltage output 1 (for driving SSR) E5AN-Q3HMT-W-500-N Relay output E5AN-R3MTD-W-500-N Voltage output (for driving SSR) E5AN-Q3MTD-W-500-N Current output E5AN-C3MTD-W-500-N E5AN (96 x 96 mm) E5EN (48 x 96 mm) Auxiliary outputs E5CN-H (48 x 48 mm) Input type E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Power supply voltage Operation Case color Safety Precautions Size E5CN E5CN-U (48 x 48 mm) Ordering Information 19 E5CN E5CN-U (48 x 48 mm) E5AN/E5EN E5EN Controllers with Terminal Blocks Size Case color Power supply voltage Input type Auxiliary outputs Control output 1 Functions Heater Power supply burnout for Sensor Control output 2 Relay output E5EN-R3MT-500-N Voltage output (for driving SSR) E5EN-Q3MT-500-N E5AN (96 x 96 mm) E5EN (48 x 96 mm) Current output Relay output E5CN-H (48 x 48 mm) Thermocouple or 3 Resistance thermometer 100 to 240 VAC 1/8 DIN 48 × 96 × 78 (W × H × D) Analog (current/voltage) Safety Precautions 20 3 24 VAC/ VDC Thermocouple or 3 Resistance thermometer 100 to 240 VAC E5EN-R3HMT-500-N Voltage output 1 (for driving SSR) E5EN-Q3HMT-500-N Relay output 2 E5EN-R3HHMT-500-N Voltage output 2 (for driving SSR) E5EN-Q3HHMT-500-N Relay output Voltage output E5EN-R3QMT-500-N Voltage output (for driving SSR) Voltage output E5EN-Q3QMT-500-N Current output Voltage output E5EN-C3QMT-500-N Relay output Long-life E5EN-R3YMT-500-N relay output Voltage output (for driving SSR) Long-life E5EN-Q3YMT-500-N relay output Current output Long-life E5EN-C3YMT-500-N relay output Relay output Sensor Power E5EN-R3PMT-500-N Voltage output (for driving SSR) Sensor Power E5EN-Q3PMT-500-N Relay output E5EN-R3ML-500-N Voltage output (for driving SSR) E5EN-Q3ML-500-N Current output Relay output 24 VAC/ VDC E5EN-C3ML-500-N 1 1 E5EN-Q3HML-500-N Relay output E5EN-R3MTD-500-N Voltage output (for driving SSR) E5EN-Q3MTD-500-N Current output Relay output E5EN-C3MTD-500-N 1 E5EN-R3HMTD-500-N Voltage output 1 (for driving SSR) E5EN-Q3HMTD-500-N Relay output 2 E5EN-R3HHMTD-500-N Voltage output 2 (for driving SSR) E5EN-Q3HHMTD-500-N Relay output E5EN-R3MT-W-500-N Voltage output (for driving SSR) E5EN-Q3MT-W-500-N Relay output 3 E5EN-R3HML-500-N Long-life E5EN-Q3YML-500-N relay output Current output Thrmocouple or Resistance thermometer Silver E5EN-C3MT-500-N 1 Voltage output (for driving SSR) Operation E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Black Model E5EN-C3MT-W-500-N 1 E5EN-R3HMT-W-500-N Voltage output 1 (for driving SSR) E5EN-Q3HMT-W-500-N Relay output E5EN-R3MTD-W-500-N Voltage output (for driving SSR) E5EN-Q3MTD-W-500-N Current output E5EN-C3MTD-W-500-N Option Units Name Function Event Input Unit E53-EN01 RS-485 communications E53-EN03 Event inputs E53-AKB Accessories (Order Separately) USB-Serial Conversion Cable Current Transformers (CTs) Model Hole diameter Model E58-CIFQ1 5.8 dia. E54-CT1 12.0 dia. E54-CT3 Terminal Cover Connectable models E5AN E5EN Model E53-COV16 CX-Thermo Support Software Model EST2-2C-MV4 E5AN (96 x 96 mm) E5EN (48 x 96 mm) Communications Unit Model RS-232C communications E5CN E5CN-U (48 x 48 mm) E5AN/E5EN Note: The Terminal Cover comes with the E5CN-@@@-500 models. E5EN Y92S-P5 Note: The Waterproof Packing is included with the Controller. E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Y92S-P4 Operation Model E5AN Safety Precautions Connectable models E5CN-H (48 x 48 mm) Waterproof Packing 21 E5AN/E5EN Ratings No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power 100 to 240 VAC: 10 VA consumption 24 VAC/VDC: 5.5 VA (24 VAC)/4 W (24 VDC) Models with temperature inputs Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Sensor input Voltage input: 0 to 50 mV Models with analog inputs Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.) Control method ON/OFF control or 2-PID control (with auto-tuning) SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, Relay output 10 mA Voltage output Output voltage: 12 VDC ±15% (PNP), max. load current: 40 mA, With short-circuit protection circuit: Max. load current of 21 mA for control output 2 Control (for driving SSR) output Current output 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000 SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply voltage: 75 Long-life relay outto 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA, leakage current: 5 mA put max. (250 VAC, 60 Hz) Number of outputs 3 Auxiliary Output specificaRelay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable output tions load: 5 V, 10 mA Number of inputs 2 Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. Event External contact ininput Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. put specifications Current flow: Approx. 7 mA per contact External power supply for ES1B 12 VDC ±10%, 20 mA, short-circuit protection circuit provided Setting method Digital setting using front panel keys 11-segment digital display and individual indicators (7-segments displays also possible) Character height: E5AN: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN: PV: 11.8 mm, SV: 8.1 mm, Indication method MV: 5.8 mm Content of 3-level display: PV/SV/MV, PV/SV/multi-SP, or soak time remain ✽ Number of digits: 4 for PV, SV, and MV Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial Multi SP communications. Bank switching Not supported. Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, Other functions protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic operations, PV/SV status display, simple program, automatic cooling coefficient adjustment Ambient operating temperature −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C Ambient operating humidity 25% to 85% Storage temperature −25 to 65°C (with no condensation or icing) Power supply voltage ✽ A 2-level display when shipped from the factory. A 3-level display is activated if parameters are initialized. For details on the third display level, refer to the User’s Manual, Basic Type (Cat. No. H156). Safety Precautions Operation E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) E5AN (96 x 96 mm) E5EN (48 x 96 mm) E5CN E5CN-U (48 x 48 mm) Specifications 22 Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal inputs) Input type Platinum resistance thermometer Name Pt100 Infrared temperature sensor Thermocouple JPt100 K J T E L U N R S B W PL II 10 to 70°C 60 to 120 °C 115 to 165 °C 140 to 260 °C Analog input 0 to 50 mV 2300 2300 E5CN E5CN-U (48 x 48 mm) E5AN/E5EN 1800 1800 1700 1700 1700 1600 1300 1300 1300 1300 Usable in the following ranges by scaling: −1999 to 9999 or −199.9 to 999.9 1200 1100 900 850 850 850 800 700 600 600 500.0 500 500.0 500.0 400.0 400 400 400.0 400 400.0 260 300 200 100.0 100 0.0 −100.0 Setting number 165 90 100 0 −200.0 100.0 120 0.0 −20.0 −100 −20.0 −200 −199.9 0 1 −199.9 2 3 −200 4 5 −200 −199.9 −200 6 7 8 9 10 11 12 13 14 15 Current 4 to 20mA Voltage 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V Setting range Usable in the following ranges by scaling: −1999 to 9999, −199.9 to 999.9, −19.99 to 99.99 or −1.999 to 9.999 Setting number 0 1 2 16 17 0 0 0 0 0 0 18 24 25 19 20 21 22 23 JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) Models with Analog Inputs Input type 0 −200 −199.9 −200 Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990 Input specification 0 −100 3 4 E5CN-H (48 x 48 mm) 1000 E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Temperature range (°C) 1400 E5AN (96 x 96 mm) E5EN (48 x 96 mm) 1500 Safety Precautions Operation Shaded settings are the default settings. 23 E5CN E5CN-U (48 x 48 mm) E5AN/E5EN Alarm Outputs Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function). E5AN (96 x 96 mm) E5EN (48 x 96 mm) Set value 1 ✽1 Upper- and lower-limit ON OFF 2 Upper limit ON OFF 3 E5CN-H (48 x 48 mm) 5 ✽1 6 7 E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) 8 Operation When X is positive Alarm function OFF ✽1 Safety Precautions Alarm type 0 4 24 Alarm output operation 9 10 11 Lower limit Upper- and lower-limit range Upper- and lower-limit with standby sequence When X is negative X SP X L ✽2 L ON OFF ON OFF SP ON OFF H L ON OFF Lower-limit with standby sequence ON OFF Absolute-value upper-limit ON OFF Absolute-value lower-limit ON OFF Absolute-value upper-limit with standby sequence ON OFF Absolute-value lower-limit with standby sequence ON OFF 12 LBA (for alarm 1 --only) 13 PV change rate alarm --- X 0 X 0 X 0 X 0 L H < 0, L > 0 H ≥ L L SP SP H L Case 1 Case 3 (Always OFF) Case 2 H < 0, L < 0 ✽3 L H SP H < 0, L > 0 H < L ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF H > 0, L < 0 H ≤ L ✽3. Set value: 4, Upper- and lower-limit range X SP SP L H H H > 0, L < 0 H > L H SP L L SP SP H L X SP H SP ✽4 SP X H > 0, L < 0 H > L SP H SP H SP L H X ✽5 Upper-limit with standby sequence H SP H < 0, L > 0 H < L SP ON OFF Case 3 (Always ON) H < 0, L < 0 H SP ON OFF Case 2 Case 1 Output OFF L ✽1. With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” ✽2. Set value: 1, Upper- and lower-limit alarm H < 0, L > 0 H ≥ L H > 0, L < 0 H ≤ L ✽4. Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above X SP X SP X 0 X 0 X 0 X 0 • Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. • Case 3: Always OFF ✽5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. E5CN E5CN-U (48 x 48 mm) E5AN/E5EN Characteristics Thermocouple: (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1 Platinum resistance thermometer: (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit max. Analog input: ±0.2% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Transfer output accuracy ±0.3% FS max. Influence of temperature Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max. ✽2 Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. ✽3 Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. Influence of voltage ✽2 Analog input: (±1%FS) ±1 digit max. Input sampling period 250 ms Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 Hysteresis EU) ✽4 Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS) Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 Proportional band (P) EU) ✽4 Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS) Integral time (I) 0 to 3999 s (in units of 1 s) Derivative time (D) 0 to 3999 s (in units of 1 s) ✽5 Control period 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range −1999 to 9999 (decimal point position depends on input type) Affect of signal source Thermocouple: 0.1°C/Ω max. (100 Ω max.) Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) resistance Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Vibration resistance Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Shock resistance Destruction 300 m/s2, 3 times each in X, Y, and Z directions EMC E5CN-H (48 x 48 mm) E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Approved standards Standards Conformed standards UL 61010-1, CSA C22.2 No. 1010-1 EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II EMI: EN 61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Power Frequency Magnetic Field Immunity: EN 61000-4-8 Voltage Dip/Interrupting Immunity: EN 61000-4-11 ✽1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C, whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max. ✽2. Ambient temperature: −10°C to 23°C to 55°, Voltage range: −15% to 10% of rated voltage ✽3. K thermocouple at −100°C max.: ±10°C max. ✽4. “EU” stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is °C or °F. ✽5. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s). ✽6. External communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the same time. Operation Setup Tool port Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g Front panel: IP66, Rear case: IP20, Terminals: IP00 Non-volatile memory (number of writes: 1,000,000 times) CX-Thermo version 4.0 or higher Provided on the bottom of the E5AN and E5EN. An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN and E5EN ✽6 Safety Precautions E5AN E5EN Degree of protection Memory protection Setup Tool Weight E5AN (96 x 96 mm) E5EN (48 x 96 mm) Indication accuracy 25 Applicable OS Windows 2000, XP, or Vista Applicable software Thermo Mini, CX-Thermo version 4.0 or higher Applicable models E5AN/E5EN/E5CN/E5CN-U/E5ANH/E5EN-H/E5CN-H USB interface standard Conforms to USB Specification 1.1. DTE speed 38400 bps Connector specifications Computer: USB (type A plug) Temperature Controller: Setup Tool port (on bottom of Controller) Power supply Bus power (Supplied from USB host controller.) Power supply voltage 5 VDC Current consumption 70 mA Ambient operating temperature 0 to 55°C (with no condensation or icing) Storage humidity 10% to 80% Altitude 2,000 m max. Weight Approx. 100 g Communications Specifications Transmission line connection method RS-485: Multipoint RS-232C: Point-to-point Communications RS-485 (two-wire, half duplex) or RS232C Synchronization method Start-stop synchronization Operation Safety Precautions Storage temperature −20 to 60°C (with no condensation or icing) Note: A driver must be installed in the personal computer. Refer to installation information in the operation manual for the Conversion Cable. E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) Ambient operating humidity 10% to 80% Protocol CompoWay/F, SYSWAY, or Modbus Baud rate 1200, 2400, 4800, 9600, 19200, 38400, or 57600 bps Transmission code ASCII Data bit length ✽ 7 or 8 bits Stop bit length ✽ 1 or 2 bits Error detection Vertical parity (none, even, odd) Frame check sequence (FCS) with SYSWAY Block check character (BCC) with CompoWay/F or CRC-16 Modbus Flow control None Interface RS-485, RS-232C Retry function None Communications buffer 217 bytes Communications response wait time 0 to 99 ms Default: 20 ms ✽ The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level. 26 Current Transformer (Order Separately) Ratings Dielectric strength 1,000 VAC for 1 min Vibration resistance 50 Hz, 98 m/s2 Weight E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Accessories (E54-CT3 only) Armatures (2) Plugs (2) Heater Burnout Alarms, SSR Failure Alarms, and Heater Overcurrent Alarms CT input (for heater current detection) Models with detection for singlephase heaters: One input Models with detection for singlephase or three-phase heaters: Two inputs Maximum heater current 50 A AC Input current indication accuracy ±5% FS ±1 digit max. Heater burnout alarm setting range ✽1 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms SSR failure alarm setting range ✽2 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms Heater overcurrent alarm setting range ✽3 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms ✽1. For heater burnout alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). ✽2. For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). ✽3. For heater overcurrent alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value). Electrical Life Expectancy Curve for Relays (Reference Values) Life (× 104 operations) USB-Serial Conversion Cable E5AN (96 x 96 mm) E5EN (48 x 96 mm) E5CN E5CN-U (48 x 48 mm) E5AN/E5EN 500 300 E5AN/E5EN 250 VAC, 30 VDC (resistive load) cosφ = 1 100 50 30 10 5 3 1 0 1 2 3 4 5 6 Switching current (A) Note: Do not connect a DC load to a Controller with a Long-life Relay Output. E5AN/E5EN • A voltage output (control output 1, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the measured temperature values as a result of leakage current. The voltage output (control output 2, for driving SSR) has basic insulation provided for the internal circuit. • Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose. Controllers Option Units • 100 to 240 VAC • 24 VAC/VDC (no polarity) 11 Input power supply 2 12 3 13 4 14 Control output 1 CT1/CT2 Control Output 2 + 15 6 16 7 17 DO NOT USE 8 18 DO NOT USE 9 19 10 20 Control output 2 Relay outputs 250 VAC, 3 A 13 EV2 EV CT1/CT2 + - DO NOT USE A B External power supply 12 VDC, 20 mA DO NOT USE DO NOT USE B TC/Pt multi-input Auxiliary output 1, 2, 3 DO NOT USE 12 External Power Supply - CT2 Auxiliary output 1 13 11 EV1 5 Auxiliary output 2 12 VDC, 21 mA Long-life relay output 250 VAC, 3 A (resistive load) EV2 CT1 Auxiliary output 3 Control output 2 Voltage output (for driving SSR) Event Inputs E53-AKB Event inputs V mA DO NOT USE Analog input A heater burnout alarm, heater short alarm, heater overcurrent alarm, or input alarm is sent to the output to which the alarm 1 function is assigned. E5CN-H (48 x 48 mm) 1 E53-EN03 RS-485 B (+) 11 12 A (−) E5AN (96 x 96 mm) E5EN (48 x 96 mm) Communications E53-EN01 RS-232C 11 SD 12 RD 13 SG Control output 1 Relay output 250 VAC, 5A (resistive load) Voltage output (for driving SSR) 12 VDC, 40 mA Current output 0 to 20 mA DC 4 to 20 mA DC Load: 600 Ω max. E5CN E5CN-U (48 x 48 mm) External Connections Safety Precautions Operation E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) (resistive load) 27 E5AN/E5EN E5CN E5CN-U (48 x 48 mm) Nomenclature E5AN E5EN Temperature unit Operation indicators SUB1 E5AN (96 x 96 mm) E5EN (48 x 96 mm) Programmable Function Key/ Auto/Manual Key MV OUT1 STOP OUT2 CMW MANU SUB3 PV Temperature unit HA SV No.1 display SV No. 2 display No. 3 display OUT1 STOP Operation indicators MV OUT2 CMW MANU Up Key A/M PF Level Key No.3 display A/M Programmable Function Key/ Auto/Manual Key E5EN Down Key E5AN No.2 display Up Key Mode Key PF Level Key Down Key Mode Key ✽ A 2-level display when shipped from the factory. A 3-level display is activated if parameters are initialized. For details on the third display level, refer to the User’s Manual, Basic Type (Cat. No. H156). Dimensions (Unit: mm) E5AN E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) HA No.1 display SUB3 Operation indicators SUB1 SUB2 PV SUB2 Mounted Separately 92 6 Group Mounted +1.0 0 +0.8 0 (96 × number of units − 3.5) 79.2 2 +0.8 0 92 Safety Precautions Operation 96 × 96 28 112 91 Group mounting does not allow waterproofing. 120 min. +0.8 0 92 Waterproof Packing (Accessory) Mounting Bracket (Accessory) Terminal Cover (E53-COV16) (Accessory) Crimp terminal size: M3.5 • Recommended panel thickness is 1 to 8 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. E5EN Mounted Separately 6 +0.6 0 +1.0 0 2 +0.8 0 92 112 91 Group mounting does not allow waterproofing. 120 min. +0.8 0 92 Waterproof Packing (Accessory) Terminal Cover (E53-COV16) (Accessory) Mounting Bracket (Accessory) Crimp terminal size: M3.5 • Recommended panel thickness is 1 to 8 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ1 E5AN (96 x 96 mm) E5EN (48 x 96 mm) 96 E5CN-H (48 x 48 mm) 48 45 79.2 Group Mounted (48 × number of units − 2.5) E5CN E5CN-U (48 x 48 mm) E5AN/E5EN (2,100) 1,765 LED (SD) USB connector (type A plug) LED (RD) Terminal Covers 1.2 E53-COV16 (Six Covers provided.) Serial connector E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) 250 3.2 Safety Precautions 44.8 Operation 10 29 E5AN (96 x 96 mm) E5EN (48 x 96 mm) E5CN E5CN-U (48 x 48 mm) E5AN/E5EN Waterproof Packing Y92S-P4 (for DIN 96 × 96) Y92S-P5 (for DIN 48 × 96) Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Waterproof Packing does not need to be attached if a waterproof structure is not required. Current Transformers E54-CT1 21 E5CN-H (48 x 48 mm) 15 E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) 2.8 5.8 dia. 7.5 3 Output voltage (Eo) V (r.m.s.) 25 Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω 10.5 40 Two, 3.5 dia. 10 30 100 V 50 Hz ∞ 10 Distortion factor 10% 1 kΩ 1 3% 1% 100 mV 100 Ω E54-CT3 12 dia. 10 1 10 100 mA 1 40 × 40 Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω E54-CT3 Accessory Connection Example Armature Plug Approx. 3 dia. Lead 18 100 V 50 Hz Distortion factor 10% 3% 1% ∞ 10 1 kΩ 500 Ω 1 100 mV 100 Ω 50 Ω 10 RL = 10 Ω • Plug 1 100 µV Approx. 6 dia. 30 100 1,000 A E54-CT3 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) 30 • Armature 10 Thru-current (Io) A (r.m.s.) 15 Operation 100 µV 9 Two, M3 (depth: 4) Safety Precautions RL = 10 Ω 1 2.36 dia. 30 Output voltage (Eo) V (r.m.s.) E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) 10 (22) 10 1 10 100 mA 1 10 100 1,000 A Thru-current (Io) A (r.m.s.) 48 × 48 mm E5CN-H Refer to Safety Precautions on page 66. Main I/O Functions Event Inputs • None • Two E5CN-H 2-level Display: PV and SV Universal Sensor Inputs • Universal thermocouple/Pt/analog (current/voltage) inputs. Indication Accuracy • Thermocouple/Pt input: ±0.1% of PV • Analog input: ±0.1% FS Sampling Period • 60 ms Auxiliary Outputs • Two Control Output 2 • None • Voltage output (for driving SSR) 5-digit Display with high resolution of 0.01°C • Auto/manual switching • Temperature Controller status display • Simple program function • Logic operations • Control output ON/OFF count alarm • PV change rate alarm • Models also available with RS-485 or RS-232C communications Control Output 1 • Relay output • Voltage output (for driving SSR) • Current output • Linear voltage output This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157) E5CN E5CN-U (48 x 48 mm) E5AN (96 x 96 mm) E5EN (48 x 96 mm) • High-resolution display with 5 digits/0.01°C display in a compact Controller (48 x 48 mm). • High-speed sampling cycle of 60 ms. • High Accuracy Thermocouple/Pt input: ±0.1% of PV Analog input: ±0.1% FS • Universal inputs on all models (thermocouple, PT, or analog input) to handle various sensors with one Controller. • A PV/SV-status display function can be set to automatically alternate between displaying the status of the Temperature Controller (auto/ manual, RUN/STOP, and alarms) and the PV or SV. • Flexible contact outputs with logic operations (AND, OR, and delays) set from the Support Software (CX-Thermo Ver. 4.0) • Preventive maintenance for relays in the Temperature Controller using a Control Output ON/OFF Counter. E5CN-H (48 x 48 mm) A New High-performance Controller: High Resolution, High Speed, and High Input Accuracy. Logic Operations and Preventive Maintenance Function. E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) (48 x 48 mm) Operation E5CN-H Safety Precautions Advanced Digital Temperature Controller E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159) 31 E5CN-H E5CN E5CN-U (48 x 48 mm) Lineup E5CN-H Terminal block Advanced Type 1 control output 2 auxiliary outputs 2 control outputs 2 auxiliary outputs Fully universal input Note: Models with one control output and models with two control outputs can be used for heating/cooling control. Model Number Structure E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) E5AN (96 x 96 mm) E5EN (48 x 96 mm) Model Number Legend Controllers Option Units E5CN-@@@M@-@-500 1 2 3 4 5 6 7 E53-@@@@ 1 2 3 4 1. Type H: Advanced 1. Applicable Controller CN: E5CN-H or E5CN 2. Control Output 1 R: Relay output Q: Voltage output (for driving SSR) C: Current output V: Linear voltage output 2. Function 1 Blank: None Q: Control output 2 (voltage output for driving SSR) P: Power supply for sensor C: Current output 3. Auxiliary Outputs 2: Two outputs 3. Function 2 Blank: None H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection (CT2) B: Two event inputs 03: RS-485 communications H03: Heater burnout/SSR failure/Heater overcurrent detection (CT1) + RS-485 communications HB: Heater burnout/SSR failure/Heater overcurrent detection (CT1) + Two event inputs HH03: Heater burnout/SSR failure/Heater overcurrent detection (CT2) + RS-485 communications H01: Heater burnout/SSR failure/Heater overcurrent detection (CT1)/RS-232C communications F: Transfer output BF: Two event inputs/Transfer output 4. Option 1 M: Option Unit can be mounted. 5. Power Supply Voltage Blank: 100 to 240 VAC D: 24 VAC/VDC 6. Case Color Blank: Black W: Silver 7. Terminal Cover -500: With terminal cover 4. Version N2: Available only to models released after January 2008 Safety Precautions Operation Note: Not all combinations of function 1 and function 2 specifications are possible for Option Units (E53-@@@@). 32 E5CN-H Size Case Color Power supply voltage 100 to 240 VAC Auxiliary output 2 Black 24 VAC/VDC 1/16 DIN 48 × 48 × 78 (W × H × D) 2 100 to 240 VAC 2 Silver 24 VAC/VDC 2 Control output 1 Model Relay output E5CN-HR2M-500 Voltage output (for driving SSR) E5CN-HQ2M-500 Current output E5CN-HC2M-500 Linear voltage output E5CN-HV2M-500 Relay output E5CN-HR2MD-500 Voltage output (for driving SSR) E5CN-HQ2MD-500 Current output E5CN-HC2MD-500 Linear voltage output E5CN-HV2MD-500 Relay output E5CN-HR2M-W-500 Voltage output (for driving SSR) E5CN-HQ2M-W-500 Current output E5CN-HC2M-W-500 Relay output E5CN-HR2MD-W-500 Voltage output (for driving SSR) E5CN-HQ2MD-W-500 Current output E5CN-HC2MD-W-500 Option Units E5AN (96 x 96 mm) E5EN (48 x 96 mm) Controllers E5CN E5CN-U (48 x 48 mm) Ordering Information One of the following Option Units can be mounted to provide the E5CN with additional functions. Heater burnout/SSR failure/ Heater overcurrent detection E53-CNHH03N2 Event inputs Communications RS-485 E53-CNHBN2 Control output 2 (Voltage for driving SSR) Communications RS-485 E53-CNQ03N2 Heater burnout/SSR failure/ Heater overcurrent detection E53-CNH03N2 Communications RS-485 E53-CN03N2 Event inputs E53-CNBN2 Heater burnout/SSR failure/ Heater overcurrent detection Control output 2 (Voltage for driving SSR) E53-CNQHN2 3-phase heater burnout/SSR failure/ Heater overcurrent detection Control output 2 (Voltage for driving SSR) E53-CNQHHN2 Control output 2 Event inputs (Voltage for driving SSR) Control output 2 (Voltage for driving SSR) Transfer Output E53-CNQFN2 Transfer Output E53-CNBFN2 Event inputs Communications RS-232C E53-CNQBN2 Control output 2 (Voltage for driving SSR) E53-CNQ01N2 Communications RS-232C Communications RS-232C E53-CN01N2 Heater burnout/SSR failure/ Heater overcurrent detection E5CN-H (48 x 48 mm) Model 3-phase heater burnout/SSR failure/ Heater overcurrent detection E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Functions Communications RS-485 E53-CNH01N2 Accessories (Order Separately) USB-Serial Conversion Cable Adapter Model Connectable models E58-CIFQ1 Model Terminal type Y92F-45 Note: Use this Adapter when the panel has been previously prepared for the E5B@. Terminal Cover Operation Note: These Option Units are applicable only to models released after January 2008. CX-Thermo Support Software Model E53-COV17 Waterproof Packing Model Y92S-29 Note: Waterproof Packing is included with the controller only for models with terminal blocks. Current Transformers (CTs) Hole diameter Model 5.8 dia. E54-CT1 12.0 dia. E54-CT3 EST2-2C-MV4 Safety Precautions Model Note: 1. The Terminal Cover comes with the E5CN-@@@-500 models. 2. The E53-COV10 cannot be used. 33 E5CN-H Ratings E5AN (96 x 96 mm) E5EN (48 x 96 mm) E5CN E5CN-U (48 x 48 mm) Specifications Power supply voltage No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power consumption 100 to 240 VAC: 8.5 VA (max.) (E5CN-HR2 at 100 VAC: 3.0 VA) 24 VAC/VDC: 5.5 VA (24 VAC)/3.5 W (24 VDC) (max.) (E5CN-HR2D at 24 VAC: 2.7 VA) Sensor input Any of the following can be selected (i.e., fully universal input). Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.) Control method Control output ON/OFF control or 2-PID control (with auto-tuning) Relay output SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Voltage output (for driving SSR) Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection circuit Current output 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000 ✽ Linear voltage out0 to 10 VDC (load: 1 kΩ min.), Resolution: Approx. 10,000 put E5CN-H (48 x 48 mm) Auxiliary output Output specifications Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Number of outputs 2 Event input E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Logic operations Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. External contact input specifications Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Number of operations 8 max. (Combinations can be made using work bits.) Operations • Logic operation: Any of the following four patterns can be selected. The input status may be inverted. (A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C, and D are four inputs.) • Delay: ON delay or OFF delay for the results of the logic operation given above. Setting time: 0 to 9999 s or 0 to 9999 min • Output inversion: Possible Outputs One work bit per operation Work bit assignments Any of the following can be assigned to up to eight work bits (logic operation results): Event input operations, auxiliary outputs, or control outputs. Current flow: Approx. 7 mA per contact Number of outputs 1 max. Transfer outputs Output Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000 specifications Operation Safety Precautions Number of outputs 2 max. RSP input Not supported Setting method Digital setting using front panel keys Indication method 11-segment digital display and individual indicators (7-segments displays also possible) Character height: PV: 11 mm, SV: 6.5 mm Bank switching Supported (number of banks: 8) Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.) Other functions Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic operations, automatic cooling coefficient adjustment Ambient operating temperature −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C Ambient operating humidity 25% to 85% Storage temperature −25 to 65°C (with no condensation or icing) ✽ For models with current outputs, control output 1 can be used as a transfer output. 34 Input Ranges Thermocouple/Platinum Resistance Thermometer/Analog Input (Fully Universal Inputs) Platinum resistance thermometer Input type Name Pt100 Analog input Thermocouple JPt100 K J T E L U N R S B W PL II 4 to 0 to 20 mA 20 mA 1 to 5V 0 to 0 to 5 V 10 V 2300.0 2300 1800.0 1800 E5CN E5CN-U (48 x 48 mm) E5CN-H 1700.01700.0 1700 1600 1500 1300.0 1300.0 1200 1100 850.0 850.0 Usable in the following ranges by scaling: −19999 to 32400, −1999.9 to 3240.0, −199.99 to 324.00, or −19.999 to 32.400 850.0 800 700 600.0 600 500.0 500 500.0 500.0 400.0 400 300 200.00 200 100 0.0 0.0 200.00 200.00 −50.00 −200.0−199.9 0 1 −20.0 −50.00−100.0 −20.0 −50.00 −199.9 2 24 3 −200.0 4 5 −50.00 −200.0−199.9 6 21 Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990 7 8 22 9 10 0.0 16 17 0.0 0.0 19 20 −100.0 −200.0 23 0.0 11 −200.0−199.9−200.0 12 13 14 15 18 25 26 27 28 29 JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) E5CN-H (48 x 48 mm) −200 100.0 400.0 400.0 100.0 0 −100 Setting number 200.00 100.0 400.0 400.0 E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) 900 Operation 1000 E5AN (96 x 96 mm) E5EN (48 x 96 mm) 1300.0 1300 Safety Precautions Temperature range (°C) 1400 35 E5CN E5CN-U (48 x 48 mm) E5CN-H Alarm Outputs Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function). E5AN (96 x 96 mm) E5EN (48 x 96 mm) Set value 0 1 ✽1 2 3 4 Safety Precautions Operation E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) ✽1 36 5 ✽1 Alarm output operation Alarm type Alarm function OFF When X is positive Output OFF Upper- and lowerlimit ON OFF Upper limit ON OFF Lower limit Upper- and lowerlimit range Upper- and lowerlimit with standby sequence X ✽2 L ON OFF ON OFF SP H X Absolute-value upper-limit ON OFF 9 Absolute-value lower-limit ON OFF 10 Absolute-value upper-limit with standby sequence ON OFF Absolute-value lower-limit with standby sequence ON OFF 12 LBA (for alarm 1 only) --- 13 PV change rate alarm --- H SP L H H > 0, L < 0 H > L H SP L H < 0, L > 0 H ≥ L L SP SP H SP L Case 1 Case 3 (Always OFF) Case 2 H < 0, L < 0 ✽3 L H SP H < 0, L > 0 H < L ✽4 SP L H H H > 0, L < 0 H > L H SP L L SP SP H L X SP X SP X 0 X 0 X 0 X 0 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF H > 0, L < 0 H ≤ L ✽3. Set value: 4, Upper- and lower-limit range X SP H SP H SP H < 0, L > 0 H < L SP L Case 3 (Always ON) H < 0, L < 0 L ✽5 ON OFF 11 X SP ON OFF Lower-limit with standby sequence 8 H Case 2 Case 1 SP ON OFF ON OFF 7 L ON OFF Upper-limit with standby sequence 6 When X is negative ✽1. With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” ✽2. Set value: 1, Upper- and lower-limit alarm X H < 0, L > 0 H ≥ L H > 0, L < 0 H ≤ L ✽4. Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above SP X SP X 0 X 0 X 0 X 0 • Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. • Case 3: Always OFF ✽5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. E5CN E5CN-U (48 x 48 mm) E5CN-H Characteristics Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1 Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max. Analog input: ±0.1% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Input sampling period 60 ms Hysteresis Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F) Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Proportional band (P) Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1 °C or °F) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) 0.0 to 3240.0 s (in units of 0.1 s) Derivative time (D) 0.0 to 3240.0 s (in units of 0.1 s) Control period 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range −19999 to 32400 (decimal point position depends on input type) Affect of signal source resistance Thermocouple: 0.1°C/Ω max. (100 Ω max.) Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) Vibration resistance Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Shock resistance Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.0 or higher Setup Tool port Provided on the bottom of the E5CN-H. Use this port to connect a computer to the E5CN-H. An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN-H. ✽4 UL 61010-1, CSA C22.2 No. 1010-1 Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II EMI: Radiated Interference Electromagnetic Field Strength: Noise Terminal Voltage: EMS: ESD Immunity: Electromagnetic Field Immunity: Burst Noise Immunity: Conducted Disturbance Immunity: Surge Immunity: Power Frequency Magnetic Field Immunity: Voltage Dip/Interrupting Immunity: EN 61326 EN 55011 Group 1, class A EN 55011 Group 1, class A EN 61326 EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-6 EN 61000-4-5 EN 61000-4-8 EN 61000-4-11 Operation EMC Approved standards E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Destruction 300 m/s2, 3 times each in X, Y, and Z directions Weight Standards E5CN-H (48 x 48 mm) Influence of voltage ✽2 Thermocouple input (R, S, B, W, PLII): (±1% of PV or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. ✽3 Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. Analog input: (±1%FS) ±1 digit max. Influence of temperature ✽2 E5AN (96 x 96 mm) E5EN (48 x 96 mm) Transfer output accuracy ±0.3% FS max. ✽1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C, whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max. ✽2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage ✽3. K thermocouple at −100°C max.: ±10°C max. ✽4. External communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the same time. Safety Precautions Indication accuracy 37 USB-Serial Conversion Cable Windows 2000, XP, or Vista Applicable software Thermo Mini, CX-Thermo version 4.0 or higher Applicable models E5AN/E5EN/E5CN/E5CN-U/ E5AN-H/E5EN-H/E5CN-H USB interface standard Conforms to USB Specification 1.1. DTE speed 38400 bps Connector specifications Computer: USB (type A plug) Temperature Controller: Setup Tool port (on bottom of Controller) Power supply Bus power (Supplied from USB host controller.) Power supply voltage 5 VDC Current consumption 70 mA Dielectric strength 1,000 VAC for 1 min Vibration resistance 50 Hz, 98 m/s2 Weight E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Accessories (E54-CT3 only) Armatures (2) Plugs (2) Heater Burnout Alarms, SSR Failure Alarms, and Heater Overcurrent Alarms Ambient operating tempera- 0 to 55°C (with no condensation or ture icing) Models with detection for singlephase heaters: One input Models with detection for singlephase or three-phase heaters: Two inputs Maximum heater current 50 A AC Ambient operating humidity 10% to 80% Input current indication accuracy ±5% FS ±1 digit max. Heater burnout alarm setting range ✽1 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms SSR failure alarm setting range ✽2 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms Heater overcurrent alarm setting range ✽3 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms Storage humidity 10% to 80% Altitude 2,000 m max. Weight Approx. 100 g Communications RS-485 (two-wire, half duplex)/RS-232C Synchronization method Start-stop synchronization Protocol CompoWay/F, SYSWAY, or Modbus Baud rate 1200, 2400, 4800, 9600, 19200, 38400, or 57600 bps Transmission code ASCII (CompoWay/F, SYSWAY) RTU (Modbus) Data bit length ✽ 7 or 8 bits Stop bit length ✽ 1 or 2 bits Error detection Vertical parity (none, even, odd) Frame check sequence (FCS) with SYSWAY Block check character (BCC) with CompoWay/F or CRC-16 Modbus Flow control None Interface RS-485, RS-232C Retry function None Communications buffer 217 bytes Communications response wait time 0 to 99 ms Default: 20 ms ✽ The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level. ✽1. For heater burnout alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). ✽2. For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). ✽3. For heater overcurrent alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value). Electrical Life Expectancy Curve for Relays (Reference Values) Life (× 104 operations) Storage temperature −20 to 60°C (with no condensation or icing) Transmission line RS-485: Multipoint connection method RS-232C: Point-to-point 38 Current Transformer (Order Separately) Ratings CT input (for heater current detection) Communications Specifications Operation Safety Precautions Applicable OS Note: A driver must be installed in the personal computer. Refer to installation information in the operation manual for the Conversion Cable. E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) E5AN (96 x 96 mm) E5EN (48 x 96 mm) E5CN E5CN-U (48 x 48 mm) E5CN-H 500 300 100 50 30 10 5 E5CN-H 250 VAC, 30 VDC (resistive load) cosφ = 1 3 1 0 1 2 3 4 5 6 Switching current (A) E5CN-H • A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the measured temperature values as a result of leakage current. Controllers Control output 1 6 2 12 7 Auxiliary output 2 DO NOT DO NOT A USE USE mA B V B DO NOT USE A heater burnout alarm, SSR failure, heater overcurrent alarm, or input alarm is sent to the output to which the alarm 1 function is assigned. Auxiliary output 1 3 13 8 4 14 9 5 15 10 ? Input power supply • 100 to 240 VAC • 24 VAC/VDC (no polarity) E53-CNBN2 Event Inputs E53-CNQBN2 Event Inputs and Control Output 2 11 EV1 EV2 DO NOT USE DO NOT USE 11 12 13 14 15 E53-CNQHHN2 Control Output 2 and CT2 EV1 13 EV2 Control output 2 12 VDC 21 mA 12 VDC 21 mA CT2 15 4 to 20 mA DC (Load 600 Ω 15 max.) EV1 12 13 EV2 14 Transfer output 15 E53-CN01N2 Communications (RS-232) RS-232C SD RD 12 14 Transfer output 11 14 SG DO NOT 13 USE 14 CT1 13 EV2 15 12 VDC 21 mA Event Inputs and Transfer Output 12 CT1 11 Control output 2 13 EV1 14 E53-CNQFN2 Control Output 2 and Transfer Output E53-CNBFN2 11 12 11 Control output 2 12 E53-CNHBN2 Event Inputs and CT 11 15 4 to 20 mA DC (Load 600 Ω max.) E53-CNH01N2 Communications (RS-232) and CT RS-232C SD RD 12 SG 13 DO NOT 14 USE DO NOT 15 USE E5CN-H (48 x 48 mm) Option Units E53-CNQ01N2 Communications (RS-232) and Control Output 2 RS-232C SD 11 RD 12 SG 13 14 CT1 15 Control output 2 12 VDC 21 mA 11 12 13 14 15 E53-CN03N2 E53-CNQ03N2 E53-CNH03N2 E53-CNHH03N2 E53-CNQHN2 Communications (RS-485) Communications (RS-485) and Control Output 2 Communications (RS-485) and CT Communications (RS-485) and CT2 Control Output 2 and CT B (+) 11 RS-485 B (+) 12 A (−) DO NOT 13 USE DO NOT 14 USE DO NOT 15 USE 12 11 RS-485 12 A (−) DO NOT 13 USE 14 14 A (−) 12 Control output 2 12 VDC 21 mA 13 CT2 15 11 12 DO NOT 13 USE 14 14 CT1 CT1 CT1 15 B (+) 11 RS-485 A (−) DO NOT 13 USE Control output 2 12 VDC 21 mA B (+) 11 RS-485 15 Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly. E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) 11 Operation 1 Control output 1 Auxiliary outputs (relay outputs) 250 VAC, 3 A (resistive load) E5AN (96 x 96 mm) E5EN (48 x 96 mm) Auxiliary outputs (relay outputs) 15 Safety Precautions Relay output 250 VAC, 3 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Linear voltage output 0 to 10 VAC Load 1 kΩ max. Current output 0 to 20 mA DC 4 to 20 mA DC Load 600 Ω max. E5CN E5CN-U (48 x 48 mm) External Connections 39 E5CN-H E5CN E5CN-U (48 x 48 mm) Nomenclature E5CN-H Temperature unit SUB1 SUB2 SUB3 HA Operation indicators No. 1 display OUT1 STOP No. 2 display OUT2 CWM MANU Up Key E5AN (96 x 96 mm) E5EN (48 x 96 mm) Level Key E5CN-H Mode Key Down Key Dimensions (Unit: mm) E5CN-H E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) 6 48 × 48 Panel Cutout Mounted Separately Group Mounted 91 (48 × number of units − 2.5) 78 +1.0 0 1.5 +0.6 0 45 44.8 × 44.8 48.8 58 Group mounting does not allow waterproofing. 60 min. 45 Waterproof Packing (Accessory) Mounting Adapter (Accessory) Terminal Cover (E53-COV17) (Accessory) 45 +0.6 0 +0.6 0 Note: The terminal block cannot be removed. • Recommended panel thickness is 1 to 5 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ1 (2,100) Safety Precautions Operation 250 40 USB connector (type A plug) LED indicator (SD) 1,765 LED indicator (RD) Serial connector Waterproof Packing E53-COV17 Y92S-29 (for DIN 48 × 48) Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Waterproof Packing does not need to be attached if a waterproof structure is not required. Note: The E53-COV10 can not be used. 48 48.8 22 E5AN (96 x 96 mm) E5EN (48 x 96 mm) Terminal Cover E5CN E5CN-U (48 x 48 mm) E5CN-H 9.1 E54-CT1 15 E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) 2.8 5.8 dia. 7.5 Output voltage (Eo) V (r.m.s.) 3 10.5 40 Two, 3.5 dia. 10 30 100 V 50 Hz ∞ 10 Distortion factor 10% 1 kΩ 1 3% 1% 100 mV 100 Ω 10 E54-CT3 RL = 10 Ω 1 2.36 dia. 30 12 dia. 100 µV 9 10 1 10 100 mA 1 40 × 40 E54-CT3 Accessory Connection Example Armature Plug Lead Output voltage (Eo) V (r.m.s.) 30 18 E54-CT3 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω 15 Approx. 3 dia. 100 1,000 A 100 V 50 Hz Distortion factor 10% 3% 1% ∞ 10 1 kΩ 500 Ω 1 100 mV 100 Ω 50 Ω 10 RL = 10 Ω • Plug 1 100 µV Approx. 6 dia. (22) 10 1 10 100 mA 1 10 100 1,000 A Operation Two, M3 (depth: 4) • Armature 10 Thru-current (Io) A (r.m.s.) Safety Precautions 25 Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) 21 E5CN-H (48 x 48 mm) Current Transformers Thru-current (Io) A (r.m.s.) 41 E5CN E5CN-U (48 x 48 mm) E5CN-H Adapter Y92F-45 Note: Use this Adapter when the panel has already been prepared for the E5B@. Fixture (Accessory) 4.7 76 69.6 to 77.6 72 × 72 Mounted to E5CN-H Safety Precautions Operation E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) E5AN (96 x 96 mm) E5EN (48 x 96 mm) 67 × 67 87 42 Panel (1 to 8 mm) 72 × 72 48 × 48 2.2 4.7 77.3 (to back of E5CN-H) A New High-performance Controller: High Resolution, High Speed, and High Input Accuracy. Logic Operations and Preventive Maintenance Function. Plus Infrared Port on Front Panel. 96 × 96 mm E5AN-H 48 × 96 mm E5EN-H Refer to Safety Precautions on page 66. Main I/O Functions E5AN-H E5EN-H 3-level Display Simultaneously displays set items, such as the PV, SV, and MV. Event Inputs • None • Two • Four Indication Accuracy • Thermocouple/Pt input: ±0.1% of PV • Analog input: ±0.1% FS Sampling Period • 60 ms PF Key (Programmable key function) Infrared port USB Auxiliary Outputs • Two • Three Computer Support Software CX-Thermo Control Output 2 (built-in) Output Unit • SSR outputs • Relay output • Voltage output (for driving SSR) • Current output • Linear voltage output Control Output 1 (built-in) Output Unit • SSR outputs • Relay output • Voltage output (for driving SSR) • Current output • Linear voltage output • Auto/manual switching • Temperature Controller status display • Simple program function • Logic operations • Control output ON/OFF count alarm • PV change rate alarm • Models available with RS-485, RS-422, or RS-232C communications Operation Universal Sensor Inputs • Universal thermocouple/ Pt/analog (current/voltage) inputs. 5-digit Display with high resolution of 0.01°C Safety Precautions Remote SP Input • One E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) • High-resolution display with 5 digits/0.01×C display. • High-speed sampling cycle of 60 ms. • High Accuracy Thermocouple/Pt input: ±0.1% of PV Analog input: ±0.1% FS • Universal inputs on all models (thermocouple, PT, or analog input) to handle various sensors with one Controller. Models also available with Remote SP. • A PV/SV-status display function can be set to automatically alternate between displaying the status of the Temperature Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV. • Flexible contact outputs with logic operations (AND, OR, and delays) set from the Support Software (CX-Thermo Ver. 4.0) • Preventive maintenance for relays in the Temperature Controller using a Control Output ON/OFF Counter. • Model available with position-proportional control E5CN E5CN-U (48 x 48 mm) (96 x 96 mm and 48 x 96 mm) E5AN (96 x 96 mm) E5EN (48 x 96 mm) E5AN-H/E5EN-H E5CN-H (48 x 48 mm) Advanced Digital Temperature Controller 43 E5AN-H/E5EN-H E5CN E5CN-U (48 x 48 mm) Lineup E5AN-H/E5EN-H Advanced Type Terminal block 1 control output 2 auxiliary outputs 2 control outputs 2 auxiliary outputs Fully universal input Note: The Controller can be used for heating/cooling control even if only 1 control output is used. E5AN (96 x 96 mm) E5EN (48 x 96 mm) Model Number Structure Model Number Legend Controllers Option Units E5AN/E5EN-@@@@@@@M@-@-500 1 2 3 4 5 6 7 8 9 10 11 1. Type H: Advanced E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) 2. Control Mode Blank: Standard or heating/cooling control P: Position-proportional control E53-@ 1 1. Function EN01: RS-232C communications EN02: RS-422 communications EN03: RS-485 communications AKB: Event input 3. Control Output 1 A: Control Output Unit R: Relay output S: SSR output Output Units 4. Control Output 2 A: Control Output Unit R: Relay output S: SSR output 1. Control Output R: Relay output Q: Voltage output (for driving SSR) Q3: Voltage output (for driving SSR) + 24 VDC (NPN) Q4: Voltage output (for driving SSR) + 24 VDC (PNP) C3: Current output + 4 to 20 mA DC C3D: Current output + 0 to 20 mA DC V34: Linear voltage output + 0 to 10 VDC V35: Linear voltage output + 0 to 5 VDC 2. Version Blank: Available for E5AN-H/E5EN-H and E5AK/E5EK. N: Available only for E5AN-H/E5EN-H. 5. Auxiliary Outputs 2: Two outputs 3: Three outputs 6. Option 1 Blank: None H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection (CT2) E53-@@ 1 2 7. Option 2 B: Two event inputs BF: Event input + Transfer output Safety Precautions Operation 8. Option 3 M: Option Unit can be mounted. 9. Power Supply Voltage Blank: 100 to 240 VAC D: 24 VAC/VDC 10.Case Color Blank: Black W: Silver 11.Terminal Cover -500: With Terminal Cover This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157) E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159) 44 E5AN-H/E5EN-H Control output 1/2 Heater burnout Optional functions Event inputs 2 4 to 20-mA E5AN-HAA2HBM-500 input SSR outputs × 2 1 2 4 to 20-mA E5AN-HSS2HBM-500 input Control Output Unit × 2 2 2 4 to 20-mA 4 to 20-mA E5AN-HAA2HHBFM-500 output input SSR outputs × 2 2 2 4 to 20-mA 4 to 20-mA E5AN-HSS2HHBFM-500 output input Control Output Unit × 2 2 4 to 20-mA 4 to 20-mA E5AN-HAA3BFM-500 output input SSR outputs × 2 2 4 to 20-mA 4 to 20-mA E5AN-HSS3BFM-500 output input Relay outputs × 2 2 4 to 20-mA E5AN-HPRR2BM-500 input Relay outputs × 2 2 4 to 20-mA 4 to 20-mA E5AN-HPRR2BFM-500 output input 3 2 Black 1/4 DIN 96 × 96 × 78 (W × H × D) Control Output Unit × 2 1 2 4 to 20-mA E5AN-HAA2HBMD-500 input SSR outputs × 2 1 2 4 to 20-mA E5AN-HSS2HBMD-500 input Control Output Unit × 2 2 2 4 to 20-mA 4 to 20-mA E5AN-HAA2HHBFMD-500 output input SSR outputs × 2 2 2 4 to 20-mA 4 to 20-mA E5AN-HSS2HHBFMD-500 output input Control Output Unit × 2 2 4 to 20-mA 4 to 20-mA E5AN-HAA3BFMD-500 output input SSR outputs × 2 2 4 to 20-mA 4 to 20-mA E5AN-HSS3BFMD-500 output input Relay outputs × 2 2 4 to 20-mA E5AN-HPRR2BMD-500 input Relay outputs × 2 2 4 to 20-mA 4 to 20-mA E5AN-HPRR2BFMD-500 output input 4 to 20-mA E5AN-HAA2HBM-W-500 input 2 Basic 24 VAC/ VDC 3 Valve Silver 100 to 240 VAC 24 VAC/ VDC Basic 2 2 Model 1 Basic Valve RSP Control Output Unit × 2 2 100 to 240 VAC Transfer output Control Output Unit × 2 1 2 Control Output Unit × 2 2 2 Control Output Unit × 2 1 2 4 to 20-mA 4 to 20-mA E5AN-HAA2HHBFM-W-500 output input 4 to 20-mA E5AN-HAA2HBMD-W-500 input E5AN (96 x 96 mm) E5EN (48 x 96 mm) Control Auxiliary method output E5CN-H (48 x 48 mm) Power supply voltage E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Case color Operation Size Safety Precautions E5AN-H E5CN E5CN-U (48 x 48 mm) Ordering Information 45 E5CN E5CN-U (48 x 48 mm) E5AN-H/E5EN-H E5EN-H Size Case color Power supply voltage Control method Auxiliary output Optional Functions Heater burnout Event inputs Control Output Unit × 2 1 2 4 to 20-mA input E5EN-HAA2HBM-500 SSR outputs × 2 1 2 4 to 20-mA input E5EN-HSS2HBM-500 Control Output Unit × 2 2 2 4 to 20-mA output 4 to 20-mA input E5EN-HAA2HHBFM-500 SSR outputs × 2 2 2 4 to 20-mA output 4 to 20-mA input E5EN-HSS2HHBFM-500 Control Output Unit × 2 2 4 to 20-mA output 4 to 20-mA input E5EN-HAA3BFM-500 SSR outputs × 2 2 4 to 20-mA output 4 to 20-mA input E5EN-HSS3BFM-500 Relay outputs × 2 2 4 to 20-mA input E5EN-HPRR2BM-500 Relay outputs × 2 2 4 to 20-mA input E5EN-HPRR2BFM-500 Control output 1/2 2 Basic E5AN (96 x 96 mm) E5EN (48 x 96 mm) 100 to 240 VAC 3 Valve 2 Black E5CN-H (48 x 48 mm) 1/8 DIN 48 × 96 × 78 (W × H × D) E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Silver Basic 24 VAC/ VDC 4 to 20-mA input E5EN-HAA2HBMD-500 SSR outputs × 2 1 2 4 to 20-mA input E5EN-HSS2HBMD-500 Control Output Unit × 2 2 2 4 to 20-mA output 4 to 20-mA input E5EN-HAA2HHBFMD-500 SSR outputs × 2 2 2 4 to 20-mA output 4 to 20-mA input E5EN-HSS2HHBFMD-500 Control Output Unit × 2 2 4 to 20-mA output 4 to 20-mA input E5EN-HAA3BFMD-500 SSR outputs × 2 2 4 to 20-mA output 4 to 20-mA input E5EN-HSS3BFMD-500 Relay outputs × 2 2 4 to 20-mA input E5EN-HPRR2BMD-500 Relay outputs × 2 2 4 to 20-mA input E5EN-HPRR2BFMD-500 4 to 20-mA input E5EN-HAA2HBM-W-500 4 to 20-mA input E5EN-HAA2HHBFM-W-500 4 to 20-mA input E5EN-HAA2HBMD-W-500 2 2 Control Output Unit × 2 1 2 Control Output Unit × 2 2 2 Control Output Unit × 2 1 2 4 to 20-mA output 4 to 20-mA output Accessories (Order Separately) Output Units Output unit Operation Relay output Voltage output (for driving SSR) Current output Safety Precautions 2 3 100 to 240 VAC 4 to 20-mA output 1 Basic Valve Model RSP Control Output Unit × 2 2 24 VAC/ VDC Transfer output Linear voltage output USB-Serial Conversion Cable Model Specifications Model E53-RN SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations E58-CIFQ1 E53-QN 12 VDC (PNP), max. load current: 40-mA, with short-circuit protection E53-Q3 24 VDC (NPN), max. load current: 20-mA, with short-circuit protection E53-Q4 24 VDC (PNP), max. load current: 20-mA, with short-circuit protection E53-C3N 4 to 20-mA DC, load: 600 Ω max., resolution: approx. 10,000 E53-C3DN 0 to 20-mA DC, load: 600 Ω max., resolution: approx. 10,000 E53-V34N 0 to 10 VDC, load: 1 kΩ min., resolution: approx. 10,000 E53-V35N 0 to 5 VDC, load: 1 kΩ min., resolution: approx. 10,000 USB-infrared Conversion Cable Model E58-CIFIR Terminal Cover Connectable models Model E5AN-H E53-COV16 E5EN-H Note: The Terminal Cover comes with the E5CN-@@@-500 models. Waterproof Packing Connectable models Model E5AN-H Y92S-P4 E5EN-H Y92S-P5 Note: The Waterproof Packing is included with the Controller. Current Transformers (CTs) Hole diameter Model 5.8 dia. E54-CT1 12.0 dia. E54-CT3 CX-Thermo Support Software Model EST2-2C-MV4 46 E5AN-H/E5EN-H E5CN E5CN-U (48 x 48 mm) Specifications Power supply voltage No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power consumption 100 to 240 VAC: 12 VA 24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC) Sensor input Any of the following can be selected. Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.) Control method ON/OFF control or 2-PID control (with auto-tuning) E5AN (96 x 96 mm) E5EN (48 x 96 mm) Ratings Relay output Voltage output (for driving SSR) Control output Output Unit (Install the Output Unit (sold separately).) Current output Linear voltage output Built-in SSR output 75 to 250 VAC, 1 A (resistive load) Auxiliary output Event input Number of outputs 2 or 3 max. Output specifications Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Number of outputs 2 or 4 (with an E53-AKB) E5CN-H (48 x 48 mm) Relay output for posi- Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations tion-proportional con- min. trol Potentiometer input: Must be between 100 Ω and 2.5 kΩ for maximum open position. Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. External contact input specifications Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Current flow: Approx. 7 mA per contact Number of operations 8 max. Transfer outputs RSP input Operations Output One work bit per operation Work bit assignment Any of The following can be assigned to up to eight work bits (logic operation results): Event input operations, auxiliary outputs, or control outputs. Number of outputs 1 max. (Depends on model. Models with transfer output (F in model number) Output specifications Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000 Number of inputs 1 Signal type Current input: 4 to 20 mA (input impedance: 150 Ω ±10%) Analog input scaling Scaling of signal to engineering units (EU) −19,999 to 30,000 (display: 30,000 max.) Accuracy (±0.2% of FS) ±1 digit max. Input sampling period 60 ms Set digitally using keys on the front panel or by using the RSP input. Indication method 11-segment digital display and individual indicators (7-segments displays also possible) Character height: E5AN-H: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-H: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm Content of 3-level display: PV/SV/MV, PV/SV/Bank No., or soak time remain Number of digits: 5 for PV and SV, 4 for MV Bank switching Supported (number of banks: 8) Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.) Other functions Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic operations, automatic cooling coefficient adjustment Ambient operating temperature −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C Ambient operating humidity 25% to 85% Storage temperature −25 to 65°C (with no condensation or icing) Safety Precautions Setting method Operation Logic operations Any of the following four patterns can be selected. The input status may be inverted. (A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C, and D are four inputs.) • Delay: ON delay or OFF delay for the results of the logic operation given above. Setting time: 0 to 9999 s or 0 to 9999 min • Output inversion: Possible E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) • Logic operation: 47 E5CN E5CN-U (48 x 48 mm) E5AN-H/E5EN-H Input Ranges Thermocouple/Platinum Resistance Thermometer (Fully Universal Inputs) Input type Platinum resistance thermometer Name Pt100 Thermocouple JPt100 K J T E Analog input L U N R S B W PL II 4 to 20 m A 0 to 20 m A 1 to 5V 0 to 5V 0 to 10 V 2300.0 2300 1800.0 1800 1700.01700.0 1700 1600 1400 Temperature range (°C) E5AN (96 x 96 mm) E5EN (48 x 96 mm) 1500 1300.0 1300 1000 900 850.0 850.0 700 600.0 600 500.0 500 500.0 500.0 400.0 400 200.00 100 −200.0 Setting number 200.00 100.0 100.0 0.0 0.0 200.00 −50.00 E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) 400.0 400.0 200.00 −200.0−199.9 0 1 −20.0 −50.00−100.0 −20.0 −50.00 −199.9 2 24 3 −200.0 4 5 −50.00 −200.0−199.9 6 21 7 Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990 Operation 400.0 400.0 100.0 0 −100.0 Safety Precautions Usable in the following ranges by scaling: −19999 to 32400, −1999.9 to 3240.0, −199.99 to 324.00, or −19.999 to 32.400 850.0 800 200 48 1300.0 1100 300 E5CN-H (48 x 48 mm) 1300.0 1200 8 22 9 10 0.0 16 17 0.0 0.0 19 20 −100.0 −200.0 23 0.0 11 −200.0−199.9−200.0 12 13 14 15 18 25 26 27 28 29 JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) Alarm Outputs Each alarm can be independently set to one of the following 15 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function). Upper- and lowerlimit ✽1 2 3 4 ✽1 5 ✽1 6 7 Upper limit Lower limit Upper- and lowerlimit range X SP X ON OFF L 9 Absolute-value lower-limit ON OFF 10 Absolute-value upper-limit with standby sequence ON OFF Absolute-value lower-limit with standby sequence ON OFF 12 LBA (for alarm 1 only) --- 13 PV change rate alarm --- 14 RSP absolute value upper limit 15 RSP absolute value lower limit ✽6 ✽6 ON OFF ON OFF ON OFF H L H SP L H H > 0, L < 0 H > L H SP Case 2 Case 1 X SP X 0 X 0 X 0 X 0 X 0 X 0 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF H > 0, L < 0 H ≤ L Case 3 (Always ON) H < 0, L < 0 ✽3 ON OFF L ✽3. Set value: 4, Upper- and lower-limit range X SP L H SP H < 0, L > 0 H < L ✽4 X H < 0, L > 0 H ≥ L SP H H SP L H H > 0, L < 0 H > L H SP L H < 0, L > 0 H ≥ L L SP SP H SP L L SP SP H SP H SP H < 0, L > 0 H < L X SP ON OFF ON OFF L ✽2 ON OFF SP ON OFF Absolute-value upper-limit H SP ON OFF 8 11 Case 3 (Always ON) H < 0, L < 0 L ON OFF Upper- and lower- ON OFF limit with standby sequence ✽5 Upper-limit with ON standby OFF sequence Lower-limit with standby sequence Case 2 Case 1 L H > 0, L < 0 H ≤ L ✽4. Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above X SP X SP X 0 X 0 X 0 X 0 X 0 X 0 • Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. • Case 3: Always OFF ✽5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. ✽6. Displayed when there is a remote SP input. E5CN-H (48 x 48 mm) 1 Output OFF E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Alarm function OFF When X is negative Operation 0 When X is positive Safety Precautions Alarm type ✽1.With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” ✽2. Set value: 1, Upper- and lower-limit alarm E5AN (96 x 96 mm) E5EN (48 x 96 mm) Alarm output operation Set value E5CN E5CN-U (48 x 48 mm) E5AN-H/E5EN-H 49 E5CN E5CN-U (48 x 48 mm) E5AN-H/E5EN-H Characteristics Indication accuracy Transfer output accuracy ±0.3% FS max. Influence of voltage ✽2 Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. ✽3 Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. Analog input: (±1%FS) ±1 digit max. Input sampling period 60 ms Hysteresis Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F) Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Proportional band (P) Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) 0.0 to 3240.0 s (in units of 0.1 s) Derivative time (D) 0.0 to 3240.0 s (in units of 0.1 s) Control period 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range −19999 to 32400 (decimal point position depends on input type) Affect of signal source resistance Thermocouple: 0.1°C/Ω max. (100 Ω max.) Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) E5CN-H (48 x 48 mm) E5AN (96 x 96 mm) E5EN (48 x 96 mm) Influence of temperature ✽2 Vibration resistance Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Shock resistance Malfunction 100 m/s2, 3 times each in X, Y, and Z directions E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Weight Operation Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions Destruction 300 m/s2, 3 times each in X, Y, and Z directions E5AN-H E5EN-H Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.0 or higher Setup Tool port Provided on the bottom of the E5AN-H and E5EN-H. An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN-H and E5EN-H. Provided on the front of the E5AN-H and E5EN-H. An E58-CIFIR USB-infrared Conversion Cable is required to connect the computer to the E5AN-H or E5EN-H. ✽4 Standards Safety Precautions Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1 Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max. Analog input: ±0.1% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Potentiometer input: ±5% FS ±1 digit max. EMC Approved standards UL 61010-1, CSA C22.2 No. 1010-1 Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II EMI: EN 61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Power Frequency Magnetic Field Immunity: EN 61000-4-8 Voltage Dip/Interrupting Immunity: EN 61000-4-11 ✽1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3% of PV or ±3°C, whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3% of PV or ±2°C, whichever is greater, ±1 digit max. ✽2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage ✽3. K thermocouple at −100°C max.: ±10°C max. ✽4. External communications (RS-232C, RS-485, or RS-422) and cable communications for the Setup Tool can be used at the same time. 50 Current Transformer (Order Separately) Ratings Applicable OS Windows 2000, XP, or Vista Applicable software Thermo Mini, CX-Thermo version 4.0 or higher Dielectric strength 1,000 VAC for 1 min Vibration resistance 50 Hz, 98 m/s2 Applicable models E5AN/E5EN/E5CN/E5CN-U/ E5AN-H/E5EN-H/E5CN-H Weight E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g USB interface standard Conforms to USB Specification 1.1. DTE speed 38400 bps Accessories (E54-CT3 only) Armatures (2) Plugs (2) Connector specifications Computer: USB (type A plug) Temperature Controller: Setup Tool port (on bottom of Controller) Power supply Bus power (Supplied from USB host controller.) Power supply voltage 5 VDC Current consumption 70 mA Thermo Mini, CX-Thermo version 4.0 or higher Applicable models E5AN-H/E5EN-H USB interface standard Conforms to USB Specification 1.1. DTE speed 38400 bps Connector specifications Computer: USB (type A plug) Temperature Controller: Infrared port (on front of Controller) Storage temperature −20 to 60°C (with no condensation or icing) Storage humidity 10% to 80% Power supply Bus power (Supplied from USB host controller.) Altitude 2,000 m max. Power supply voltage 5 VDC Weight Approx. 100 g Current consumption 80 mA Note: A driver must be installed in the personal computer. Refer to installation information in the operation manual for the Conversion Cable. Communications Specifications Transmission line RS-485, RS-422: Multipoint connection method RS-232C: Point-to-point Communications RS-485 (two-wire, half duplex) RS-422 (four-wire, half duplex) or RS-232C Synchronization method Start-stop synchronization Protocol CompoWay/F, SYSWAY, or Modbus Baud rate 1200, 2400, 4800, 9600, 19200, 38400, or 57600 bps ASCII (CompoWay/F, SYSWAY) Transmission code RTU (Modbus) Data bit length ✽ 7 or 8 bits Stop bit length ✽ 1 or 2 bits Error detection Vertical parity (none, even, odd) Frame check sequence (FCS) with SYSWAY Block check character (BCC) with CompoWay/F or CRC-16 Modbus Ambient operating tempera- 0 to 55°C (with no condensation or ture icing) Ambient operating humidity 10% to 80% Storage temperature −20 to 60°C (with no condensation or icing) Storage humidity 10% to 80% Altitude 2,000 m max. Weight Approx. 130 g (with mounting adaptor) Note: A driver must be installed in the personal computer. Refer to installation information in the operation manual for the Conversion Cable. Heater Burnout Alarms, SSR Failure Alarms, and Heater Overcurrent Alarms Models with detection for single-phase CT input heaters: One input (for heater current detecModels with detection for single-phase tion) or three-phase heaters: Two inputs Maximum heater current 50 A AC Input current indication accuracy ±5% FS ±1 digit max. Flow control None Interface RS-485, RS-422, or RS-232C Retry function None Communications buffer SSR failure alarm setting range ✽2 217 bytes Heater overcurrent alarm 0.1 to 49.9 A (in units of 0.1 A) setting range ✽3 Minimum detection ON time: 100 ms Communications 0 to 99 ms response wait time Default: 20 ms Note: The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level. E5AN (96 x 96 mm) E5EN (48 x 96 mm) Applicable software E5CN-H (48 x 48 mm) Windows 2000, XP, or Vista E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Ambient operating humidity 10% to 80% Applicable OS Operation Ambient operating tempera- 0 to 55°C (with no condensation or ture icing) USB-Infrared Conversion Cable Heater burnout alarm set- 0.1 to 49.9 A (in units of 0.1 A) ting range ✽1 Minimum detection ON time: 100 ms 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms ✽1. For heater burnout alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). ✽2. For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). ✽3. For heater overcurrent alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value). Safety Precautions USB-Serial Conversion Cable E5CN E5CN-U (48 x 48 mm) E5AN-H/E5EN-H 51 Electrical Life Expectancy Curve for Relays (Reference Values) 500 • Rated load voltage: 75 to 250 VAC • Rated load current: 1 A (resistive load) Note: 1. The load current must be within the derating curve. 2. There is no zero-cross function. 300 Derating Curve for SSR Outputs (Reference Values) E5AN-H/E5EN-H 250 VAC, 30 VDC (resistive load) cosφ = 1 100 50 30 E5AN (96 x 96 mm) E5EN (48 x 96 mm) SSR Outputs (OUT1/OUT2) Ratings Load current I (A) OUT1/OUT2 Life (× 104 operations) E5CN E5CN-U (48 x 48 mm) E5AN-H/E5EN-H 10 5 3 1 0 1 2 3 4 5 6 1.5 1.25 Condition B 1 0.75 0.5 Condition A Switching current (A) 0.25 Safety Precautions Operation E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) E5CN-H (48 x 48 mm) 0 −10 52 0 10 20 30 40 45 50 55 60 Ambient temperature (°C) Condition A: SSR outputs 100% ON Condition B: SSR outputs 50% ON with 2-s control cycle E5AN-H/E5EN-H • A voltage output (control output 1, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the measured temperature values as a result of leakage current. The voltage output (control output 2, for driving SSR) has basic insulation provided for the internal circuit Option Units Communications • 100 to 240 VAC • 24 VAC/VDC (no polarity) Output Unit Control outputs 1, 2 Relay Outputs 250 VAC, 5 A (resistive load) SSR Outputs 75 to 250 VAC, 1A (resistive load) Models with Positionproportional Control 250 VAC, 1 A (including inrush current) Input power supply 21 11 2 22 12 3 23 13 Control output 1 11 SD 11 RDB 11 B (+) 11 12 RD 12 RDA 12 A (−) 12 13 SG 13 SG 13 DO NOT USE 13 21 DO NOT USE 21 SDB 21 B (+) 21 22 DO NOT USE 22 SDA 22 A (−) 22 24 15 6 26 16 7 27 17 8 28 18 9 29 19 10 30 20 Control output 2 Potentiometer CT2 Auxiliary output 2 EV1 EV1 CT1 25 EV2 EV2 14 5 Event Inputs Event Inputs CT2 4 Auxiliary outputs 1, 2 Relay output SPST-NO, 250 VAC, 3 A (resistive load) 1 E53-AKB E53-EN03 RS-485 O W C 14 Auxiliary output 3 15 Auxiliary output 3 16 DO NOT DO NOT USE USE A DO NOT DO NOT V USE USE B Auxiliary output 1 B DO NOT USE DO NOT USE mA Relay output SPDT, 250 VAC, 3 A (resistive load) A heater burnout alarm, SSR failure, heater overcurrent alarm, or input alarm is sent to the output to which the alarm 1 function is assigned. DO NOT USE 21 E5CN-H (48 x 48 mm) Control outputs 1, 2 E53-EN02 RS-422 E5AN (96 x 96 mm) E5EN (48 x 96 mm) E53-EN01 RS-232C E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Controllers E5CN E5CN-U (48 x 48 mm) External Connections 22 EV3 23 25 DO NOT USE Transfer output 26 27 4 to 20 mA DC (Load: 600 Ω max.) 28 Operation 24 EV4 29 30 Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly. Safety Precautions 4 to 20 mA DC Remote SP input 53 E5AN-H/E5EN-H E5CN E5CN-U (48 x 48 mm) Nomenclature E5AN-H E5EN-H Temperature unit Operation indicators SUB1 SUB2 SUB1 PV SUB2 Operation indicators HA SUB3 No.1 display SUB3 PV Temperature unit No.1 display HA SV No.2 display SV No.2 display MV No.3 display RSP MV E5AN (96 x 96 mm) E5EN (48 x 96 mm) OUT1 RSP STOP OUT2 CMW MANU OUT1 STOP Operation indicators OUT2 CMW MANU Up Key Mode Key Programmable Function Key/ Auto/Manual Key PF Up Key A/M PF Level Key A/M Ir Ir E5AN-H E5EN-H Down Key Level Key E5CN-H (48 x 48 mm) No.3 display Programmable Function Key/ Auto/Manual Key Down Key Mode Key Dimensions (Unit: mm) E5AN-H Mounted Separately 92 Group Mounted✽ +1.0 0 +0.8 0 (96 × number of units − 3.5) +0.8 0 E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) 92 Group mounting does not allow waterproofing. 120 min. 6 79.2 2 +0.8 0 92 Operation 96 × 96 112 91 • Recommended panel thickness is 1 to 8 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. ✽ Group mounting is not possible if an SSR output is used for control output 1 or 2 and the E53-C3N or E53-C3DN Output Unit is used. For these combinations, maintain the following mounting space between Controllers. Waterproof Packing (Accessory) Mounting Bracket (Accessory) 110 min. Terminal Cover (E53-COV16) (Accessory) +0.8 0 92 Crimp terminal size: M3.5 Safety Precautions 92 54 120 min. +0.8 0 E5CN E5CN-U (48 x 48 mm) E5AN-H/E5EN-H E5EN-H Mounted Separately Group Mounted✽ (48 × number of units − 2.5) +0.6 45 0 +1.0 0 +0.8 0 92 +0.8 92 0 6 48 79.2 2 E5AN (96 x 96 mm) E5EN (48 x 96 mm) Group mounting does not allow waterproofing. 120 min. • Recommended panel thickness is 1 to 8 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. 60 min. 91 45 +0.6 0 92 Mounting Bracket (Accessory) Terminal Cover (E53-COV16) (Accessory) Crimp terminal size: M3.5 120 min. E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) Waterproof Packing (Accessory) +0.8 0 Operation 112 Safety Precautions 96 E5CN-H (48 x 48 mm) ✽ Group mounting is not possible if an SSR output is used for control output 1 or 2 and the E53-C3N or E53-C3DN Output Unit is used. For these combinations, maintain the following mounting space between Controllers. 55 E5AN-H/E5EN-H E5CN E5CN-U (48 x 48 mm) Accessories (Order Separately) USB-Infrared Conversion Cable E58-CIFIR USB-Infrared Conversion Cable 54 (2,000) 35.8 4.6 dia. USB connector (type A plug) E5AN (96 x 96 mm) E5EN (48 x 96 mm) LED indicator: RD LED indicator: SD 17.8 With Mounting Adapter Connected Mounting Adapter 39 16 E5CN-H (48 x 48 mm) 18.5 Mounting Adapter (Accessory) 99.2 23.1 E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) 21.8 (75) USB-Serial Conversion Cable E58-CIFQ1 (2,100) LED indicator: SD 250 Operation USB connector (type A plug) LED indicator: RD Terminal Covers 1.2 E53-COV16 (Six Covers provided.) Safety Precautions 10 56 44.8 1,765 3.2 Serial connector E5CN E5CN-U (48 x 48 mm) E5AN-H/E5EN-H Waterproof Packing E5AN (96 x 96 mm) E5EN (48 x 96 mm) Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Waterproof Packing does not need to be attached if a waterproof structure is not required. Current Transformers 5.8 dia. 7.5 25 Output voltage (Eo) V (r.m.s.) 3 Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω 10.5 40 Two, 3.5 dia. 10 30 100 V 50 Hz ∞ 10 Distortion factor 10% 1 kΩ 1 3% 1% 100 mV 100 Ω 10 E54-CT3 RL = 10 Ω 1 2.36 dia. E5CN-H (48 x 48 mm) 15 E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) 2.8 30 12 dia. 100 µV 9 10 1 10 100 mA 1 40 × 40 Two, M3 (depth 4) E54-CT3 Accessory Connection Example Armature Plug Lead 18 E54-CT3 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Output voltage (Eo) V (r.m.s.) 30 Approx. 3 dia. 100 1,000 A Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for an OMRON Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω 15 • Armature 10 Thru-current (Io) A (r.m.s.) 100 V 50 Hz Distortion factor 10% 3% 1% ∞ 10 1 kΩ 500 Ω 1 100 mV 100 Ω 50 Ω 10 RL = 10 Ω • Plug 1 100 µV Approx. 6 dia. (22) E5AN-H (96 x 96 mm) E5EN-H (48 x 96 mm) 21 Operation E54-CT1 10 1 10 100 mA 1 10 100 1,000 A Thru-current (Io) A (r.m.s.) Safety Precautions Y92S-P5 (for DIN 48 × 96) Y92S-P4 (for DIN 96 × 96) 57 E5@N/E5@N-H E5CN E5CN-U (48 x 48 mm) Operation Setting Levels Diagram This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Control stops when you move from the operation level to the initial setting level. Basic Type Power ON Start in manual mode. E5AN (96 x 96 mm) E5EN (48 x 96 mm) Start in automatic mode. Press the O Key or the PF Key for at least 1 s. ✽4 Operation Level Adjustment Level Press the O Key less than 1 s. a-m Manual mode PF Key Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.) ✽3 PF Key E5CN-H (48 x 48 mm) ✽4 Press the O Key for at least 1 s. Control stops. 25 c 100 c Press the O Key for at least 3 s. (Display will flash after 1st second.) 25 100 Protect Level *1 Note: The time taken to move to the protect level can be adjusted by changing the “Move to protect level time” setting. Communications Setting Level Initial Setting Level Press the O Key for less than 1 s. Input password while amoV is displayed. (Set value −169) Press the O Key for at least 1 s. E5AN-H (96 x 96 mm) E5EN-H(48 x 96 mm) Press the O+ M Keys for at least 1 s. ✽5 Press the PF Key for at least 1 s. Manual Control Level ✽5 Monitor/Setting Item Level Press the O+ M Keys for at least 3 s. (Display will flash after 1st second.) Advanced Function Setting Level Input password. Control in progress Control stopped Calibration Level ✽2 Not displayed for some models Operation Level change ✽1. You can return to the operation level by executing a software reset. ✽2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning OFF the power. ✽3. From the manual control level, key operations can be used to move to the operation level only. ✽4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/E5EN). ✽5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/E5EN) Error Displays (Troubleshooting) Safety Precautions When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below. No.1 display Meaning s.err (S. Err) Input error ✽ Action Status at error Control output Alarm output Check the wiring of inputs for miswiring, disconnections, and short-circuits and check the input type. OFF Operates as above the upper limit. e333 (E333) A/D converter error Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. OFF OFF e111 (E111) Memory error Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. OFF OFF Note: If the input value exceeds the display limit (−1999 to 9999), though it is within the control range, will be displayed under −1999 and above 9999. Under these conditions, control output and alarm output will operate normally. For details on the control range, refer to the E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156). ✽ These errors are displayed only when the PV/SP is displayed. Errors are not displayed for other displays. 58 E5CN E5CN-U (48 x 48 mm) E5@N/E5@N-H Advanced Type Power ON Start in automatic mode. a-m Manual mode ✽3 Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.) Adjustment Level Press the O Key less than 1 s. Press the O Key less than 1 s. PID Setting Level Press the O Key less than 1 s. Bank Setting Level Press the PF Key for at least 1 s. ✽4 Manual Control Level PF Key Press the O Key less than 1 s. Press the O + M Keys for at least 3 s. (Display will flash after 1st second.) c 25.0 100.0 Protect Level Press the O Key for at least 3 s. (Display will flash after 1st second.) 25.0 c PF Key ✽5 Monitor/Setting Item Level ✽5 Press the O Key for at least 1 s. Press the O+ M Keys for at least 1 s. E5AN (96 x 96 mm) E5EN (48 x 96 mm) Operation Level Note: The time taken to move to the protect level can be adjusted by changing the “Move to protect level time” setting. E5CN-H (48 x 48 mm) Press the O Key or the PF Key for at least 1 s. ✽4 100.0 ✽1 Control stops. Communications Setting Level Initial Setting Level Press the O Key for less than 1 s. Press the O Key for at least 1 s. E5AN-H (96 x 96 mm) E5EN-H(48 x 96 mm) Input password while amov is displayed. (Set value −169) Advanced Function Setting Level Input password. Control in progress Control stopped ✽2 Calibration Level Not displayed for some models Level change Operation ✽1. You can return to the operation level by executing a software reset. ✽2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning OFF the power. ✽3. From the manual control level, key operations can be used to move to the operation level only. ✽4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H). ✽5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H) Error Displays (Troubleshooting) When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below. No.1 display Meaning s.err (S. Err) Input error ✽ Action Status at error Control output Alarm output Check the wiring of inputs for miswiring, disconnections, and short-circuits and check the input type. OFF Operates as above the upper limit. e333 (E333) A/D converter error Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. OFF OFF e111 (E111) Memory error Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. OFF OFF Note: If the input value exceeds the display limit (−19999 to 32400), though it is within the control range, will be displayed under −19999 and above 32400. Under these conditions, control output and alarm output will operate normally. For details on the control range, refer to the E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157). ✽ These errors are displayed only when the PV/SP is displayed. Errors are not displayed for other displays. Safety Precautions Start in manual mode. 59 Parameters Basic Type Some parameters are not displayed depending on the model of the Controller and parameter settings. For details, refer to the E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156). PF Key ✽2 Power ON Starting in manual mode. Press the PF Key for at least 1 s. ✽1 Adjustment Level 5 M in-h 25 off C 0.0 Input Shift Value parameters. 2-point shift M Limit insl Lower Temperature C 0.0 Input Shift Value off C 0.0 M Burnout hb1 Heater Detection 1 M i M d 0.0 M hb2 0.0 M oc2 50.0 M lcr1 0.0 0.0 M hs1 Heater Burnout Detection 2 0.0 M hs2 0.0 M of-r M sp-0 M hys Hysteresis (Heating) 1.0 M soak Soak Time Leakage Current 2 Monitor HS Alarm 2 1 M wt-b C M sp-1 SP 0 M sp-2 0 C M mv-e SP 1 M Current 2 lcr2 Leakage Monitor MV at PV Error SP used by multi-SP SP 2 C M sprt SP Ramp Set Value off M ol-h M M ol-l MV Upper Limit MV Lower Limit -5.0 M orl MV Change Rate Limit 0.0 M sqrp 0.0 M C Extraction of Square Root Low-cut Point Alarm Value Upper Limit 2 M Value al2l Alarm Lower Limit 2 C M al-3 Alarm Value 3 0 M Value al3h Alarm Upper Limit 3 0 M prst Program Start C rset M sktr Soak Time Remain 0 M Value al3l Alarm Lower Limit 3 M d-u c C M Operation/Adjustment Protect: oapt Restricts displaying and modifying menus in operation, 0 adjustment, and manual control levels. M s-hc stnd on M ptrn M 20 M c-cp 20 M alt1 Press the O Key less than 1 s. Alarm 1 Type 2 C M alh1 0.2 Alarm 1 Hysteresis M Setting: psel Protocol Switches between cwf CompoWay/F (SYSWAY) and Modbus. M u-no Communications Unit No. 1 9.6 CompoWay/F (SYSWAY) only 7 M sbit Communications Stop Bits M Mask Enable: pmsk Parameter Displayed only when a M prty Communications Parity M to Move to Protect Level: prlp Password Password setting M sdwt M Set the ON/OFF output cycle. Control Period (Cooling) M orev Direct/Reverse Operation M Key Protect pfpt PF Restricts PF key operation 0 control output to ON/OFF output cp Control Period (Heating) Note: Displayed only for models with communications. Changes are effective after cycling power or after a software reset. M len Communications Data Length on parameter mask is set. Program Pattern off When assigning PID or Communications Setting Level M levels. Change Protect: wtpt Setting Protects changes to setups by off (E5AN/E5EN only) For input type of temperature, standard control, or PID or-r M Communications bps Baud Rate off operating the front panel keys. Standard or Heating/Cooling M st ST (Self-tuning) M o MV Monitor (Heating) M Initial Setting/ Protect: icpt Communications This protect level restricts movement 1 to the initial setting, communications Limit the set point SP Lower Limit onof 0 Press the O and M Keys for at least 1 s. Move to Protect Level: Displayed only when a password 0 is set. Restricts moving to protect level. M sl-l M cntl PID ON/OFF M Protect Level SP Upper Limit -200 M c-o MV Monitor (Cooling) Note: The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting. Temperature Unit °C, °F For input type of temperature 1300 0.0 Press the O and M Keys for at least 3 s. M sl-h C 0.0 M Decimal Point 0 For input type of analog 0 C setting, and advanced function setting 105.0 M al2h 0 0.0 pmov 0.0 M sp-3 SP 3 0 MV at Stop 0.0 0 C Heater Current 2 Value Monitor M Current 1 lcr1 Leakage Monitor Wait Band off M mv-s C 0.0 M Hysteresis settings chys Hysteresis (Cooling) C 0 C Manual Reset Value Clear the offset during M al-2 Alarm Value 2 0 0.0 50.0 stabilization of P or PD C C M Current 1 Value ct1 Heater Monitor 0.0 M Value al1l Alarm Lower Limit 1 0 M dp 0 M Point During sp-m Set SP Ramp M ct2 M Value al1h Alarm Upper Limit 1 0 C Multi-SP Set Point Setting 1.0 50.0 C C PID settings Heating/cooling M c-db Dead Band 50.0 M lcr2 0 Derivative Time control. HS Alarm 1 m-sp Integral Time 1.00 C C 0 M c-sc Cooling Coefficient Heater Overcurrent Detection 2 Leakage Current 1 Monitor Press the O Key for at least 3 s. M al-1 Alarm Value 1 0 Added when auto/manual select M addition is ON. 40 Heater Current 2 Value Monitor C M Switch a-m Auto/Manual PID control only. 233 0.0 M ct2 M p Proportional Band 8.0 run 0 1-point shift M Set either Limit insh Upper of these Temperature C M Current 1 ct1 Heater Value Monitor M Value/ 25 Process Set Point C 0.0 AT Execute/Cancel M cmwt Communications Writing ins Temperature Input Shift M in-l Scaling Lower Limit r-s RUN/STOP Process Value Added when Additional PV display is ON. Set either of these parameters. M at Adjustment Level Display Displayed only once when entering adjustment level. Scaling Upper Limit 100 C E5CN-H (48 x 48 mm) E5AN-H (96 x 96 mm) E5EN-H(48 x 96 mm) in-t Input Type Operation Level 50.0 Operation Press the O Key less than 1 s. Press the O Key less than 1 s. M Overcurrent oc1 Heater Detection 1 60 Initial Setting Level Press the O Key for at least 1 s. C Press the O Key less than 1 s. l.adj Safety Precautions Press the O PID Key or the PF 25 Control Key for at least only 1 s. ✽1 PV/MV PF Key ✽2 Press the O Key for at least 3 s. Other than the Auto/Manual Switch display Starting in automatic mode. Set either of these parameters. E5AN (96 x 96 mm) E5EN (48 x 96 mm) Manual Control Level Set either of these parameters. E5CN E5CN-U (48 x 48 mm) E5@N/E5@N-H 2 even 20 M Send Data Wait Time ✽1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/E5EN). ✽2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/E5EN). Monitor/Setting Item Level 25 C 0 Monitor/Setting Item Display 1 PF (E5AN/E5EN only) Monitor/Setting Item Display 2 Monitor/Setting Item Display 3 PF Monitor/Setting Item Display 4 PF Monitor/Setting Item Display 5 PF E5CN E5CN-U (48 x 48 mm) E5@N/E5@N-H M mspu Multi-SP Uses M a2lt Alarm 2 Latch M hsl HS Alarm Latch M spru M a3lt Alarm 3 Latch M hsh HS Alarm Hysteresis (E5AN/E5EN only) M pfd2 Monitor/Setting Item 2 M Sequence rest Standby Reset M to Protect Level prlt Move Time M lba LBA Detection Time M pfd3 Monitor/Setting Item 3 M sb1n M sero Input Error Output 0.2 Alarm 3 Hysteresis off M tr-h 100.0 Linear output n-o Transfer Output Upper Limit M Output tr-l Transfer Lower Limit 0.0 M o1-t Linear Current Output 4-20 Auxiliary Output 2 Open in Alarm M sb3n Auxiliary Output 3 Open in Alarm n-o M hbu Linear output M of Multi-SP Uses ev-m Number Two SPs: 1 none M ev-2 stop setting/communications C Control Output 2 Assignment M odsl MV Display Selection Auxiliary Output 1 Assignment M Decimal Point pvdp PV Display none M st-b ST Stable Range M a2on Alarm 2 ON Delay M sub3 M alfa α M a3on Alarm 3 ON Delay M csel Character Select M at-g AT Calculated Gain M a1of Alarm 1 OFF Delay M t-u Soak Time Unit M at-h AT Hysteresis M a2of Alarm 2 OFF Delay M alsp Alarm SP Selection M a3of Alarm 3 OFF Delay 0.8 Move by setting password (−169). M out2 o M sub2 0.65 M protect is set to 0. M colr PV Change Color off 3.0 M a1on Alarm 1 ON Delay 15.0 0 Displayed when initial M spdp C M Burnout hbh Heater Hysteresis C M to Advanced amov Move Function Setting Level: M Output 1 out1 Control Assignment 8.0 M sub1 0.1 off M Command rlrv MB Logic Switching C M pv-b PV Stable Band Event Input Assignment 2 0.8 20.0 M inf Input Digital Filter 0.0 M pvad Additional PV Display off M o-dp MV Display M Display ret Automatic Return Time M 0 0 0 0 0 M istp Input Shift Type ins1 M at Stop and Error mvse MV Addition off off off 5.0 0 M Cycle MV lcma Limit Amplitude 0 M pfd5 on Method C 0 M lbab LBA Band red off 1 M pfd4 Monitor/Setting Item 4 M Junction cjc Cold Compensation on Event Input Assignment 1 M of Square sqr Extraction Root Enable 0 M pfd1 Monitor/Setting Item 1 M lbal LBA Level off HB ON/OFF M hbl Heater Burnout Latch 1 Four SPs: 2 M ev-1 0.1 3 Auxiliary Output 1 Open in Alarm M sb2n n-o off off a tr-t Transfer Output Type a-m M Select amad Auto/Manual Addition off alm1 Auxiliary Output 2 Assignment alm2 alm3 Auxiliary Output 3 Assignment (E5AN/E5EN only) on m Monitor/Setting Item 5 0 4 "PV/SP" Display Screen Selection o on M PV Status Display pvst Function off M Status Display svst SV Function off M Refresh d.ref Display Period 0.25 M Output 1 ra1m Control ON/OFF Count 0 Monitor M ra2m Control Output 2 ON/OFF Count M MV manl Manual Limit Enable M ra1 Control Output 1 ON/OFF Count M Rate of Change pvrp PV Calculation Period M Output 2 ra2 Control ON/OFF Count sp-m off 4 M csca off Automatic Cooling Coefficient Adjustment M Overcurrent ocu Heater Use on M rt RT M Overcurrent ocl Heater Latch M M och off 0 off 0.1 M Heater Overcurrent Hysteresis E5CN-H (48 x 48 mm) C SP Ramp Time Unit m HS Alarm Use on off off 2 hsu off E5AN-H (96 x 96 mm) E5EN-H(48 x 96 mm) 0.2 M alt3 Alarm 3 Type M alh3 PF Setting (E5AN/E5EN only) a1lt Alarm 1 Latch off M 2 alh2 Alarm Hysteresis C pf init Parameter Initialization Alarm 2 Type 2 0 Monitor 0 Alarm Set Value Operation alt2 Advanced Function Setting Level 0 Alarm Set Value M Counter rac ON/OFF Reset 0 M to Calibration cmov Move Level 0 M Safety Precautions Press the O Key for at least 1 s. E5AN (96 x 96 mm) E5EN (48 x 96 mm) Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level). 61 E5CN E5CN-U (48 x 48 mm) E5@N/E5@N-H Advanced Type Some parameters are not displayed depending on the model of the Controller and parameter settings. For details, refer to the E5CN-H/E5AN-H/ E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157). Power ON E5AN (96 x 96 mm) E5EN (48 x 96 mm) Manual Control Level Protect Level Operation Level Adjustment Level Initial Setting Level Communications Setting Level E5CN-H (48 x 48 mm) Press the O Key less than 1 s. Bank Setting Level PID Setting Level Press the O Key less than 1 s. Display Bank Selection d.bnk Bank0 0 2 PID2 d.bnk d.bnk 3 PID3 22 Bank2 d.bnk Bank7 PID8 7 M 1.p 8.0 M 8.d M 1.olh M 8.olh M 1.oll -5.0 M 1.lba 0 M off PID 8 MV Upper Limit c c c c PID 8 Cooling Coefficient 1.00 0 M c 0.0 PID 8 LBA Detection Time M 0.a2l 7.pid 1 0.a-3 c M 0.a3h c M c 0.a3l c 0.0 M 0.sok 0.a1l 0.a-2 M 0.0 M c M 0.0 0.0 M M 8.lba c 1 M c 7.lsp 0.wtb Bank 7 SP 0.0 M M PID 8 Automatic Selection 1320.0 Range Upper Limit c 0.0 M 0.a1h 0.0 M 8.aut 8.csc 0.a-1 0.0 PID 8 MV Lower Limit c M -5.0 1.aut M c M 0.spr 0.a 2h 0.0 0.pid 1 PID 8 Derivative Time M c M 105.0 M 8.oll 0.lsp 0.0 40.0 105.0 1.00 c 233.0 40.0 M 1.csc PID 8 Proportional Band M 8.i PID 8 Integral Time M 1320.0 8.p 8.0 M 1.i c M M c c M 7.a1h Bank 7 Alarm Value 0.0 Upper Limit 1 Bank 7 Alarm Value 0.0 Lower Limit 1 7.a1l 7.a 2h Bank 7 Alarm Value 0.0 Upper Limit 2 M Bank 7 SP off Ramp Set Value M c c M 7.spr Bank 7 0.0 Alarm Value 1 Bank 7 0.0 Alarm Value 2 M Bank 7 PID Set No. M 7.a-1 7.a-2 c c Bank 7 Alarm Value 0.0 Lower Limit 2 7.a2l M 7.a-3 Bank 7 0.0 Alarm Value 3 c c M M 7.a3h Bank 7 Alarm Value 0.0 Upper Limit 3 M 7.a3l Bank 7 Alarm Value 0.0 Lower Limit 3 M 7.sok off M Set either of these parameters 8 Set either of these parameters d.pid c d.bnk Bank1 1 d.pid 1.d Operation Press the O Key less than 1 s. Set either of these parameters E5AN-H (96 x 96 mm) E5EN-H(48 x 96 mm) d.pid PID1 1 d.pid 233.0 Safety Precautions Monitor/Setting Item Level Advanced Function Setting Level Display PID Selection 62 PID Setting Level Bank Setting Level Bank 7 Soak Time 1 c M 7.wtb off M Bank 7 Wait Band E5CN E5CN-U (48 x 48 mm) E5@N/E5@N-H Power ON Starting in manual mode. PID Press the O 25.0 Control Key or the PF 100.0 only Key for at least 1 s. ✽1 PV/MV Press the PF Key for at least 1 s. Starting in automatic mode. ✽1 Press the O and M Keys for at least 3 s. Press the O Key less than 1 s. Operation Level AT Execute/Cancel M M d Communications off Writing M irda 40.0 Infrared Communications Use SP Mode 0.0 lsp of-r Heater Current 1 0.0 Value Monitor M hb1 M hys Heater Burnout 1.0 M chys M oc1 Heater Overcurrent 50.0 Detection 1 1.0 M soak M 0.0 M hb2 0.0 M oc2 50.0 Heater Current 2 Value Monitor M wt-b Heater Burnout Detection 2 off 50.0 M lcr2 0.0 M hs2 50.0 mv-s Heater Overcurrent Detection 2 ins 0.00 M c insh mv-e 0.0 M sprt M insl 0.00 M rsp c Remote SP Monitor Hysteresis (Heating) Hysteresis (Cooling) c Set Point During c Heater Current 1 Value c Heater Current 2 Value lcr1 Leakage Current 1 Leakage Current 2 M al3l Alarm Value 0.0 Upper Limit 3 M lcr2 M M o prst Program Start 0.0 rset M ol-h Leakage Current 2 Monitor 105.0 MV Monitor (Heating) M M MV at PV Error Press the O and M Keys for at least 1 s. 0.0 Lower Limit 3 0.0 Monitor MV at Stop Alarm Value 3 M al3h Alarm Value 0.0 Monitor Wait Band Alarm Value M al-3 0.0 0.0 Monitor M Soak Time Alarm Value M al2l 0.0 Lower Limit 2 M ct2 al2h 0.0 Upper Limit 2 0.0 Monitor Hysteresis settings Alarm Value 2 0.0 M ct1 al-2 M 0.0 SP Ramp control. M al1l Alarm Value 0.0 Lower Limit 1 0.0 sp-m Alarm Value M c-o sktr Soak Time Remain 0.0 0 MV Monitor (Cooling) M M v-m SP Ramp Set Value off HS Alarm 1 Valve Opening Monitor 0.0 M MV Upper Limit M ol-l -5.0 HS Alarm 2 M orl Temperature Input Shift Upper Limit Temperature 2-point shift Lower Limit Temperature Input Shift Value 0.0 MV Lower Limit PF Key ✽2 MV Change Rate Limit Monitor/Setting Item Level (E5AN-H/E5EN-H only) M 1-point shift 0.00 Input Shift Value c Manual Reset Value Clear the offset during M Leakage Current 1 c Bank No. M 0.0 M c c al1h 0.0 Upper Limit 1 0 Dead Band Alarm Value 1 M c Auto/Manual Switch PID control only. Added when auto/manual select addition is ON. M M 0.0 Monitor M hs1 M bank Heating/cooling 1 M lcr1 Press the O Key for at least 3 s. 50.0 stabilization of P or PD 0.0 Detection 1 ct2 Derivative Time a-m al-1 0.0 M PID settings M M ct1 c Process Value/ 0.0 Set Point Integral Time M c-sc Cooling Coefficient M c-db M M 25.0 1.00 off spmd c 233.0 cmwt run M E5CN-H (48 x 48 mm) M i r-s RUN/STOP Process Value Added when Additional PV display is ON. E5AN-H (96 x 96 mm) E5EN-H(48 x 96 mm) 8.0 25.0 Proportional Band Operation off p Set either of these parameters. db 2.0 Position Proportional Dead Band Monitor/Setting Item Display 2 PF 0.0 M oc-h 25.0 Monitor/Setting Item Display 1 PF Monitor/Setting Item Display 3 PF Open/Close Hysteresis 0.8 M sqrp Extraction of Square Root 0.0 Low-cut Point M Monitor/Setting Item Display 4 PF Monitor/Setting Item Display 5 Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level). PF Key ✽2 Safety Precautions at c c Set either of these parameters. M Adjustment Level Display Displayed only once when entering adjustment level. Set either of these parameters. l.adj Set either of these parameters. Adjustment Level E5AN (96 x 96 mm) E5EN (48 x 96 mm) Manual Control Level c ✽1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H). ✽2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H). 63 E5AN (96 x 96 mm) E5EN (48 x 96 mm) E5CN E5CN-U (48 x 48 mm) E5@N/E5@N-H Press the O Key for at least 1 s. Press the O Key for at least 3 s. Other than the Auto/Manual Switch display Initial Setting Level E5CN-H (48 x 48 mm) Press the O Key less than 1 s. Press the O Key less than 1 s. Protect Level The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting. to Protect Level: pmov Move Displayed only when a password M 0 is set. Restricts moving to protect level. Operation/Adjustment Protect: oapt Restricts displaying and modifying menus in 0 operation, adjustment, and manual control levels. M icpt 0 E5AN-H (96 x 96 mm) E5EN-H(48 x 96 mm) M Initial Setting/ Communications Protect: This protect level restricts movement to the initial setting, communications setting, and advanced function setting levels. wtpt Setting Change Protect: Protects changes to setups off by operating the front panel keys. M pfpt PF Key Protect Restricts PF key operation off (E5AN-H/E5EN-H only) M Mask Enable: pmsk Parameter Displayed only when a on parameter mask is set. M prlp Password to Move to Protect Level: 0 Password setting M in-t Communications Setting Level 5 Input Type Displayed only for models with communications. Changes are effective after cycling power or after a software reset. in-h M in-l M Scaling Upper Limit 1 dp 7 d-u c M Communications Data Length c M sbit 2 sl-h c Decimal Point Temperature Unit °C, °F For input type of temperature Limit the set point M sl-l SP Lower Limit pid M s-hc Send Data Wait Time 20 M stnd M st on Operation M ptrn Standard or Heating/Cooling 7 cp ST (Self-tuning) For input type of temperature, standard control, or PID Program Pattern c-cp When assigning PID or control output to ON/OFF output Control Period (Heating) Set the ON/OFF output cycle. Control Period (Cooling) Safety Precautions M orev Direct/Reverse Operation or-r Alarm 1 Type M Transfer Output Upper Limit M tr-l 0.0 M o1-t Transfer Output Lower Limit Linear Current Output Linear output M ev-b Bank Numbers Used M ev-1 none Event Input Assignment 1 M M ev-3 none Event Input Assignment 3 M ev-4 none Event Input Assignment 4 M clfl Closed/Floating flot M Motor Calibration M mot Travel Time 30 Alarm 1 0.2 Hysteresis M 100.0 off 2 alh1 tr-h calb M c Linear output M stop Valid Program Bank 20 alt1 M tr-t Transfer Output Type Input ev-2 Event Assignment 2 20 M Alarm 3 Hysteresis 1 M M Alarm 3 Type 4-20 off pbnk M alh3 off SP Upper Limit M cntl PID ON/OFF M c 0.2 -200.0 even Hysteresis 2 1300.0 Communications Stop Bits M prty Communications Parity sdwt alt3 M M Alarm 2 M Scaling Lower Limit 0 For input type of analog Communications Baud Rate 9.6 CompoWay/F (SYSWAY) only M alh2 0.2 0 M bps len c M Communications Unit No. Alarm 2 Type 2 100 Protocol Setting: psel Switches between cwf CompoWay/F (SYSWAY) and Modbus. u-no alt2 M M sqr off Extraction of Square Root Enable M Move to Advanced Function Level: amov Setting Displayed when initial 0 setting/ communications M protect is set to 0. Move by setting password (−169). 64 E5CN E5CN-U (48 x 48 mm) E5@N/E5@N-H Power ON Manual Control Level Operation Level Adjustment Level Initial Setting Level Communications Setting Level PID Setting Level Bank Setting Level Monitor/Setting Item Level E5AN (96 x 96 mm) E5EN (48 x 96 mm) Protect Level Advanced Function Setting Level Advanced Function Setting Level M rest a M Standby Sequence Reset a1lt Alarm 1 Latch Auxiliary Output 1 a2lt M sb1n n-o Open in Alarm Open in Alarm 3 rlrv ST Stable Range colr off M st-b 0.65 AT Calculated Gain AT Hysteresis Limit Cycle MV Amplitude Input Digital Filter M Additional PV Display alm1 alm2 a1of Alarm 1 OFF Delay 0 M Alarm 3 OFF Delay Auxiliary Output 2 Assignment m M manl off pmvd PID Set Automatic Selection Hysteresis pvdp PV Dead Band pvst off on ocl 0.1 pf a-m M SV Status Display Function d.ref 0.25 Display Refresh Period M PV Rate of Change ra1m Control Output 1 ON/OFF Count 0 Monitor M Automatic Cooling ra2m Control Output 2 ON/OFF Count 0 Monitor M Heater Overcurrent Use ra1 Control Output 1 ON/OFF Count 0 Alarm Set Value M Heater Overcurrent Heater Overcurrent Hysteresis ra2 Control Output 2 ON/OFF Count 0 Alarm Set Value M Counter rac ON/OFF Reset 0 M Soak Time Unit PV Status Display Function M Direct Setting of off Latch och svst off M Character Select PV Decimal Point Display M Manual MV Limit Enable off Coefficient Adjustment ocu on M 17 Calculation Period csca o M off Position Proportional MV pvrp "PV/SP" Display 4 Screen Selection M M Auxiliary Output 3 Assignment (E5AN/E5EN-H only) M t-u odsl MV Display Selection M on M PID Set Automatic Selection Data M Auxiliary Output 1 Assignment M csel spdp M Control Output 2 Assignment M sub3 alm3 a2of Alarm 2 OFF Delay 0 sub2 M Remote SP Input Error Output M Control Output 1 Assignment M Alarm 3 ON Delay 0 a3of sub1 p-db Monitor/Setting Item 5 0 M LBA Band M Alarm 2 ON Delay M M out2 none 00 0.0 off a3on out1 c Monitor/Setting Item 4 0 M 0.0 M Alarm 1 ON Delay M M pvad a2on lbab pfd5 M LBA Level 8.0 o M M inf 5.0 a1on lbal M PV Stable Band 0 0.8 20.0 pv-b 0.50 3.0 M M lcma c pidh LBA Detection Time M 0 1.0 at-h c M M c PV Change Color M M at-g c red alfa α pv M M MB Command Logic Switching M 15.0 0.1 0 M Heater Burnout Hysteresis SP Tracking M pidi HS Alarm Hysteresis M lba Cold Junction on Compensation Method M off M hsh M M off Monitor/Setting Item 3 0 pfd4 off rseo pfd3 Remote SP Lower Limit M sptr HS Alarm Use M Input Error Output rspl -200.0 hsl HS Alarm Latch M cjc c Monitor/Setting Item 2 M Remote SP Upper Limit M RT on Time rsph 1300.0 M hsu Alarm 3 Latch off off c pfd2 0 M Auto/Manual Select Addition off M sero HB ON/OFF Burnout hbl Heater Latch c Alarm 2 Latch M on 0.1 rt prlt Move to Protect Level Auxiliary Output 3 M hbh M off M hbu M M M n-o on a3lt Auxiliary Output 2 n-o Open in Alarm sb3n off M Remote SP Enable off M amad off M sb2n off off Monitor/Setting Item 1 1 M rspu MV at Stop and Error Addition pfd1 E5AN-H (96 x 96 mm) E5EN-H(48 x 96 mm) m Alarm SP Selection sp-m M mvse Display ret Automatic Return Time SP Ramp Time Unit alsp Input Shift Type ins1 M M spru istp MV Display off Operation o-dp Parameter Initialization off M PF Setting cmov 0 M Move to Calibration Level Safety Precautions init E5CN-H (48 x 48 mm) Press the O Key for at least 1 s. 65 E5@N/E5@N-H E5AN (96 x 96 mm) E5EN (48 x 96 mm) E5CN E5CN-U (48 x 48 mm) Safety Precautions !CAUTION Do not touch the terminals while power is being supplied. Doing so may occasionally result in minor injury due to electric shock. Do not allow pieces of metal, wire clippings, or fine metallic shavings or filings from installation to enter the product. Doing so may occasionally result in electric shock, fire, or malfunction. Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury from explosion may occasionally occur. Do not leave the cable for the Support Software connected to the product. Malfunction may occur due to noise in the cable. Do not use the Temperature Controller or Conversion Cable if it is damaged. Doing so may occasionally result in minor electric shock or fire. E5AN-H (96 x 96 mm) E5EN-H(48 x 96 mm) E5CN-H (48 x 48 mm) Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric shock, fire, or malfunction may occasionally occur. CAUTION - Risk of Fire and Electric Shock a) This product is UL listed as Open Type Process Control Equipment. It must be mounted in an enclosure that does not allow fire to escape externally. b) More than one disconnect switch may be required to de-energize the equipment before servicing the product. c) Signal inputs are SELV, limited energy. ✽1 d) Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits. ✽2 If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur. Always consider the application conditions and use the output relays within their rated load and electrical life expectancy. The life expectancy of output relays varies considerably with the output load and switching conditions. Tighten the terminal screws to between 0.74 and 0.90 N·m. ✽3 Loose screws may occasionally result in fire. Safety Precautions Operation Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable, unexpected operation may occasionally result in property damage or accidents. A malfunction in the product may occasionally make control operations impossible or prevent alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the product, take appropriate safety measures, such as installing a monitoring device on a separate line. A semiconductor is used in the output section of long-life relays. If excessive noise or surge is impressed on the output terminals, a short-circuit failure is likely to occur. If the output remains shorted, fire will occur due to overheating of the heater or other cause. Take measures in the overall system to prevent excessive temperature increase and to prevent fire from spreading. Do not allow pieces of metal or wire cuttings to get inside the cable connector for the Support Software. Failure to do so may occasionally result in minor electric shock, fire, or damage to equipment. Do not allow dust and dirt to collect between the pins in the connector on the Conversion Cable. Failure to do so may occasionally result in fire. 66 When inserting the body of the Temperature Controller into the case, confirm that the hooks on the top and bottom are securely engaged with the case. If the body of the Temperature Controller is not inserted properly, faulty contact in the terminal section or reduced water resistance may occasionally result in fire or malfunction. When connecting the Control Output Unit to the socket, press it in until there is no gap between the Control Output Unit and the socket. Otherwise contact faults in the connector pins may occasionally result in fire or malfunction. ✽1. An SELV circuit is one separated from the power supply with double insulation or reinforced insulation, that does not exceed 30 V r.m.s. and 42.4 V peak or 60 VDC. ✽2. A class 2 power supply is one tested and certified by UL as having the current and voltage of the secondary output restricted to specific levels. ✽3. The tightening torque for E5CN-U is 0.5 N·m. Precautions for Safe Use Be sure to observe the following precautions to prevent malfunction or adverse affects on the performance or functionality of the product. Not doing so may occasionally result in faulty operation. 1. This product is specifically designed for indoor use only. Do not use this product in the following places: • Places directly subject to heat radiated from heating equipment. • Places subject to splashing liquid or oil atmosphere. • Places subject to direct sunlight. • Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas). • Places subject to intense temperature change. • Places subject to icing and condensation. • Places subject to vibration and large shocks. 2. Use and store the product within the rated ambient temperature and humidity. Gang-mounting two or more Temperature Controllers, or mounting Temperature Controllers above each other may cause heat to build up inside the Temperature Controllers, which will shorten their service life. In such a case, use forced cooling by fans or other means of air ventilation to cool down the Temperature Controllers. 3. To allow heat to escape, do not block the area around the product. Do not block the ventilation holes on the product. 4. Be sure to wire properly with correct polarity of terminals. 5. Use the specified size (M3.5, width 7.2 mm or less) crimped terminals for wiring. To connect bare wires to the terminal block, use stranded or solid copper wires with a gage of AWG24 to AWG14 (equal to a cross-sectional area of 0.205 to 2.081 mm2). (The stripping length is 5 to 6 mm.) Up to two wires of the same size and type or two crimp terminals can be inserted into a single terminal. 6. Do not wire the terminals that are not used. 7. To avoid inductive noise, keep the wiring for the product’s terminal block away from power cables carry high voltages or large currents. Also, do not wire power lines together with or parallel to product wiring. Using shielded cables and using separate conduits or ducts is recommended. Attach a surge suppressor or noise filter to peripheral devices that generate noise (in particular, motors, transformers, solenoids, magnetic coils, or other equipment that have an inductance component). When a noise filter is used at the power supply, first check the voltage or current, and attach the noise filter as close as possible to the product. Allow as much space as possible between the product and devices that generate powerful high frequencies (high-frequency welders, high-frequency sewing machines, etc.) or surge. 8. Use this product within the rated load and power supply. 9. Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or relay contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur. 10.Make sure that the Temperature Controller has 30 minutes or more to warm up after turning ON the power before starting actual control operations to ensure the correct temperature display. Precautions for Correct Use Service Life 1. Use the product within the following temperature and humidity ranges: Temperature: −10 to 55°C (with no icing or condensation) Humidity: 25% to 85% If the product is installed inside a control board, the ambient temperature must be kept to under 55°C, including the temperature around the product. 2. The service life of electronic devices like Temperature Controllers is determined not only by the number of times the relay is switched but also by the service life of internal electronic components. Component service life is affected by the ambient temperature: the higher the temperature, the shorter the service life and, the lower the temperature, the longer the service life. Therefore, the service life can be extended by lowering the temperature of the Temperature Controller. 3. When two or more Temperature Controllers are mounted horizontally close to each other or vertically next to one another, the internal temperature will increase due to heat radiated by the Temperature Controllers and the service life will decrease. In such a case, use forced cooling by fans or other means of air ventilation to cool down the Temperature Controllers. When providing forced cooling, however, be careful not to cool down the terminals sections alone to avoid measurement errors. 1. When extending or connecting the thermocouple lead wire, be sure to use compensating wires that match the thermocouple types. 2. When extending or connecting the lead wire of the platinum resistance thermometer, be sure to use wires that have low resistance and keep the resistance of the three lead wires the same. 3. Mount the product so that it is horizontally level. 4. If the measurement accuracy is low, check to see if input shift has been set correctly. E5AN (96 x 96 mm) E5EN (48 x 96 mm) Measurement Accuracy Operating Precautions 1. It takes approximately two seconds for the outputs to turn ON from after the power supply is turned ON. Due consideration must be given to this time when incorporating Temperature Controllers in a sequence circuit. 2. When using self-tuning, turn ON power for the load (e.g., heater) at the same time as or before supplying power to the Temperature Controller. If power is turned ON for the Temperature Controller before turning ON power for the load, self-tuning will not be performed properly and optimum control will not be achieved. 3. When starting operation after the Temperature Controller has warmed up, turn OFF the power and then turn it ON again at the same time as turning ON power for the load. (Instead of turning the Temperature Controller OFF and ON again, switching from STOP mode to RUN mode can also be used.) 4. Avoid using the Controller in places near a radio, television set, or wireless installing. These devices can cause radio disturbances which adversely affect the performance of the Controller. E5AN-H (96 x 96 mm) E5EN-H(48 x 96 mm) The degree of protection is as shown below. Sections without any specification on their degree of protection or those with IP@0 are not waterproof. Front panel: IP66 Rear case: IP20, Terminal section: IP00 (E5CN-U: Front panel: IP50, rear case: IP20, terminals: IP00) E5CN-H (48 x 48 mm) Waterproofing 1. The disk that is included with the Conversion Cable is designed for a computer CD-ROM driver. Never attempt to play the disk in a general-purpose audio player. 2. Do not connect or disconnect the Conversion Cable connector repeatedly over a short period of time. The computer may malfunction. 3. After connecting the Conversion Cable to the computer, check the COM port number before starting communications. The computer requires time to recognize the cable connection. This delay does not indicate failure. 4. Do not connect the Conversion Cable through a USB hub. Doing so may damage the Conversion Cable. 5. Do not use an extension cable to extend the Conversion Cable length when connecting to the computer. Doing so may damage the Conversion Cable. 6. The E5AN-H/E5EN-H use the same port for communications through the infrared port and the Support Software port. Do not attempt to use communications through the Support Software port when the infrared port is being used. Operation Others Safety Precautions 11.When executing self-tuning, turn ON power to the load (e.g., heater) at the same time as or before supplying power to the product. If power is turned ON to the product before turning ON power to the load, self-tuning will not be performed properly and optimum control will not be achieved. 12.A switch or circuit breaker must be provided close to the product. The switch or circuit breaker must be within easy reach of the operator, and must be marked as a disconnecting means for this unit. 13.Always turn OFF the power supply before pulling out the interior of the product, and never touch nor apply shock to the terminals or electronic components. When inserting the interior of the product, do not allow the electronic components to touch the case. 14.Do not use paint thinner or similar chemical to clean with. Use standard grade alcohol. 15.Design the system (e.g., control panel) considering the 2 seconds of delay that the product's output to be set after power ON. 16.The output may turn OFF when shifting to certain levels. Take this into consideration when performing control. 17.The number of EEPROM write operations is limited. Therefore, use RAM write mode when frequently overwriting data during communications or other operations. 18.Always touch a grounded piece of metal before touching the Temperature Controller to discharge static electricity from your body. 19.Do not remove the terminal block. Doing so may result in failure or malfunction. 20.Control outputs (for driving SSR) that are voltage outputs are not isolated from the internal circuits. When using a grounded thermocouple, do not connect any of the control output terminals to ground. (Doing so may result in an unwanted circuit path, causing error in the measured temperature.) 21.When replacing the body of the Temperature Controller, check the condition of the terminals. If corroded terminals are used, contact failure in the terminals may cause the temperature inside the Temperature Controller to increase, possibly resulting in fire. If the terminals are corroded, replace the case as well. 22.Use suitable tools when taking the Temperature Controller apart for disposal. Sharp parts inside the Temperature Controller may cause injury. 23.Before connecting an Output Unit, confirm the specifications and thoroughly read relevant information in the datasheet and manual for the Temperature Controller. 24.Check the orientation of the connectors on the Conversion Cable before connecting the Conversion Cable. Do not force a connector if it does not connect smoothly. Using excessive force may damage the connector. 25.Do not place heavy object on the Conversion Cable, bend the cable past its natural bending radius, or pull on the cable with undue force. 26.Do not connect or disconnect the Conversion Cable while communications are in progress. Product faults or malfunction may occur. 27.Make sure that the Conversion Cable's metal components are not touching the external power terminals. 28.Do not touch the connectors on the Conversion Cable with wet hands. Electrical shock may result. 29.Before using infrared communications, correctly attach the enclosed Mounting Adapter to the cable for the Support Software. When connecting the infrared port on the cable to the Support Software into the Adapter, insert the connector to the specified line. Communications may not be possible if the connector is not connected properly. E5CN E5CN-U (48 x 48 mm) E5@N/E5@N-H 67 E5CN E5CN-U (48 x 48 mm) E5@N/E5@N-H Mounting Mounting the Terminal Cover Mounting to a Panel E5CN For waterproof mounting, waterproof packing must be installed on the Controller. Waterproofing is not possible when group mounting several Controllers. Waterproof packing is not necessary when there is no need for the waterproofing function. Make sure that the “UP” mark is facing up, and then attach the E53COV17 Terminal Cover to the holes on the top and bottom of the Temperature Controller. E5AN/E5EN E5CN E5AN (96 x 96 mm) E5EN (48 x 96 mm) Order the P2CF-11 or P3GA-11 Socket separately. E53-COV17 Terminal Cover (Accessory) Slightly bend the E53-COV16 Terminal Cover to attach it to the terminal block as shown in the following diagram. The Terminal Cover cannot be attached in the opposite direction. Adapter (Accessory) Slightly bend the E53-COV16 Terminal Cover in the direction shown by the arrows to attach it to the terminal block. E5CN-U E5CN-H (48 x 48 mm) Waterproof packing (Accessory) Panel E5CN 1. The Panel Mounting Adapter is also included with the E5CN-U. There is no waterproof packing included with the E5CN-U. 2. Insert the E5CN/E5CN-U into the mounting hole in the panel. 3. Push the adapter from the terminals up to the panel, and temporarily fasten the E5CN/E5CN-U. 4. Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m. E5EN/E5AN E5AN-H (96 x 96 mm) E5EN-H(48 x 96 mm) Mounting Bracket (Accessory) Panel E53-COV16 Terminal Cover (Accessory) Removing the Temperature Controller from the Case The Temperature Controller can be removed from the case to perform maintenance without removing the terminal leads. This is possible for only the E5CN, E5AN, and E5EN, and not for the E5CN-U. Check the specifications of the case and Temperature Controller before removing the Temperature Controller from the case. E5CN Tool insertion hole Flat-blade screwdriver (Unit: mm) (1) (2) E53-COV16 Terminal Cover (Accessory) (3) Waterproof packing (Accessory) Waterproof packing (Accessory) E5EN 1. Insert the E5AN/E5EN into the square mounting hole in the panel (thickness: 1 to 8 mm). Attach the Mounting Brackets provided with the product to the mounting grooves on the top and bottom surfaces of the rear case. 2. Use a ratchet to alternately tighten the screws on the top and bottom Mounting Brackets little by little to maintain balance, until the ratchet turns freely. 68 2.0 (1) Panel E53-COV16 Terminal Cover (Accessory) 0.4 E5AN Mounting Bracket (Accessory) Operation Safety Precautions For Front-mounting Socket (Panel mounting is also possible.) 1. Insert a flat-blade screwdriver into the two tool insertion holes (one on the top and one on the bottom) to release the hooks. 2. Insert the flat-blade screwdriver in the gap between the front panel and rear case, and pull out the front panel slightly. Hold the top and bottom of the front panel and carefully pull it out toward you, without applying unnecessary force. 3. When inserting the body of the Temperature Controller into the case, make sure the PCBs are parallel to each other, make sure that the sealing rubber is in place, and press the E5CN toward the rear case into position. While pushing the E5CN into place, push down on the hooks on the top and bottom surfaces of the rear case so that the hooks are securely locked in place. Be sure that electronic components do not come into contact with the case. E5AN/E5EN Tool insertion hole Tool insertion hole (1) E5CN E5CN-U (48 x 48 mm) E5@N/E5@N-H (1) E5EN (1) (1) 1. Insert a flat-blade screwdriver into the two tool insertion holes (one on the top and one on the bottom) to release the hooks. 2. Insert the flat-blade screwdriver in the gap between the front panel and rear case (two on the top and two on the bottom), and use it to pry and pull out the front panel slightly. Then, pull out on the front panel gripping both sides. Be sure not to impose excessive force on the panel. 3. When inserting the body of the Temperature Controller into the case, make sure the PCBs are parallel to each other, make sure that the sealing rubber is in place, and press the E5AN/E5EN toward the rear case until it snaps into position. While pressing the E5AN/E5EN into place, press down on the hooks on the top and bottom surfaces of the rear case so that the hooks securely lock in place. Make sure that electronic components do not come into contact with the case. Precautions when Wiring • Separate input leads and power lines in order to prevent external noise. • Use wires with a gage of AWG24 (cross-sectional area: 0.205 mm2) to AWG14 (cross-sectional area: 2.081 mm2) twistedpair cable (stripping length: 5 to 6 mm). • Use crimp terminals when wiring the terminals. • Tighten the terminal screws to a torque of 0.74 to 0.90 N·m, however the terminal screws on the E5CN-U must be tightened to a torque of 0.5 N·m. • Use the following types of crimp terminals for M3.5 screws. E5CN-H (48 x 48 mm) E5AN E5AN-H (96 x 96 mm) E5EN-H(48 x 96 mm) (3) (3) E5AN (96 x 96 mm) E5EN (48 x 96 mm) (2) (2) 7.2 mm max. Safety Precautions Operation 7.2 mm max. • Do not remove the terminal block. Doing so will result in malfunction or failure. 69 CX-Thermo Support Software Ver. 4.0 EST2-2C-MV4 Monitoring/Setting Support Software for E5CN/CN-H, E5AN/AN-H, E5EN/EN-H, E5ZN, E5@R/@R-T, and EJ1 Temperature Controllers Enabling Faster Parameter Setup, Device Adjustment, and Maintenance • Enables editing and batch-downloading parameters from a personal computer, reducing the work required to set parameters. Usability is improved with table-formatted parameter editing from version. 4.0. • Supports Trend Monitoring: Monitor data (PV,SP,MV,PID parameter, Alarm ON/OFF, etc.) for up to 31 E5@N/@N-H Temperature Controllers. Connect up to 64 EJ1N, 17 EJ1G, or 16 E5ZN Temperature Controllers. (The Temperature Controllers must be from the same series.) • Supports parameter masks to hide parameters unnecessary to display. (Supported only by the E5@N/@N-H and E5@R/@R-T). • Logic operations enable setting inputs from external inputs (event inputs) or temperature status, outputs to external outputs (control or auxiliary outputs), and changing operating status with ON/OFF delays. (Supported only by the E5@N/@N-H). • Easy adjustment of control performance by fine-tuning. ✽ Fine-tuning instructs the CX-Thermo to calculate a PID parameters by directly inputting commands to improve response. Ordering Information List of Models Name Model CX-Thermo Support Software EST2-2C-MV4 Specifications Compatible devices Temperature Controllers E5CN (available from April 2004) E5AN, E5EN (available from Feb 2005), E5CN-H, E5AN-H, E5EN-H E5AR, E5ER E5AR-T, E5ER-T E5ZN EJ1N-TC4, EJ1N-TC2, EJ1N-HFU EJ1G-TC4, EJ1G-TC2, EJ1G-HFU G3ZA (only when connected to EJ1N-TC4, EJ1N-TC2, EJ1G-TC4, EJ1G-TC2) Note: Models with DeviceNet communications are not supported. Personal computer system requirements OS Windows 2000 (service pack 3 or higher), XP, or Vista (Japanese or English version) CPU 300 MHz min. Memory 128 MB min. Harddisk 300 MB min. available space CD-ROM One CD-ROM drive min. Monitor SVGA (800 × 600) min. Communications ports Connection method 70 • RS-232C port, or USB port, 1 port min. • An E58-CIFQ1 USB-Serial Conversion Cable is required to connect a computer to the setup tool port the E5@N, E5@N-H, or EJ1. • A K3SC Interface Converter is used to connect a computer to models with RS-422/RS-485 communications. • An E58-CIFIR USB-Infrared Conversion Cable is required to wirelessly connect a computer to models with infrared communications (E5AN-H or E5EN-H). 71 Warranty and Application Considerations Read and Understand This Catalog Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will be used. Know and observe all prohibitions of use applicable to this product. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Disclaimers PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with your OMRON representative at any time to confirm actual specifications of purchased product. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. H160-E1-01A In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company Control Devices Division H.Q. Analog Controller Division Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 Japan Tel: (81)75-344-7080/Fax: (81)75-344-7149 0208 (1207)