Download

Datasheet
picoPak Optocoupler Modules
picoPak optocoupler modules are ideal for
applications where DIN rail space is limited.
Requiring just 6mm of either 32mm or
35mm DIN rail, they easily fit in the space
normally occupied by a single terminal
block.
Two versions are available:
NEW
MC5O-Input: Dual 24Vdc and 120Vac
input with a 5-30Vdc @100mA output.
120Vac input includes leakage immunity up
to 5mA.
MC5O-Output: Designed as a solenoid
driver, this module has a 24Vdc input and
an output rated 5-34Vdc @ 10A maximum resistive or 6A - inductive.
CSA Class 1 Div 2 approved
Other features include:
• status LED
• input polarity protection
• back-EMF diode protection on outputs
• high input-output isolation
• CSA approved
United States
Canada
Mexico
Weidmuller Inc.
Weidmuller Ltd.
Weidmuller, S.A. de C.V.
821 Southlake Blvd.
10 Spy Court
5 Sur No. 4311
Richmond, Virginia 23236
Markham, Ontario L3R 5H6
Col. Huexotitla
Telephone: (800) 849-9343
Telephone: (800) 268-4080
72534 Puebla, Pue. Mexico
Facsimile: (804) 379-2593
Facsimile: (905) 475-2798
Telephone: (22) 37 2549
Email: [email protected]
Email: [email protected]
Facsimile: (22) 43 1981
Website: www.weidmuller.com
Website: www.weidmuller.ca
Email: [email protected]
3/9
picoPak Optocoupler Modules
Rated data
Input
voltage
min. turn-on
current
protection
Output
Isolation
General
voltage
current
picoPak MC5O Input
24Vdc ±10%
120Vac/dc±10%
15Vdc, 90Vac
4mA @ 24Vdc
19mA @ 120Vac
polarity diode on 24Vdc input
MOV on 120Vac/dc input
120Vac input protected against
up to 5mA of leakage current
5-30Vdc
100mA1)
volt. drop @ max. load
turn-on/off time, 24Vdc input
120Vac input
125Vdc input
protection
input-output
operating temperature
wire size
width on 32/35mm rail
Approvals
2Vdc
1ms
150ms typ.
100ms typ.
back-EMF diode
2500V
picoPak
optional endplate3)
9915700000
C9039986
0° to + 50°C
22-12 AWG (0.5-4.0mm2)
6mm
CSA
picoPak MC5O Output
24Vdc nom.
12.5Vdc
5.0mA @ 24Vdc
polarity diode
5-34Vdc
10A resistive
6A inductive
0.1Vdc @ 10A
1ms
back-EMF diode
4000V
-40 to +60°C
22-12 AWG (0.5-4.0mm2)
6mm
CE, CSA
Class 1 Division 2
Ordering data
7901690001
C9039986
1) derate by 0.8mA per °C above 25°C ambient
2) 5 to 20mm spacing between terminals recommended when operating in environments with ambient temperatures over 30°C
3) required on last terminal in a group, 1.5mm wide.
2
Subject to technical changes ·Printed in Canada ·99990257 ·12/01