Download

Installation & Configuration Guide
WI-I/O-9-U2-TC - Thermocouple Adapter for WI-I/O-9-U2
Configuration
Dip Switches
On the “I/O Configuration” web page select:
·
·
·
·
Select Thermocouple type from the drop down list. Options
are Type T, Type J, Type K.
Select the Polarity from the drop down list (Normal or
Reversed)
Set Thermocouple Error Value to a value the integer
registers (30003 and/or 30004) will go to during fail *
Press “Save and Activate Changes” button.
*
*
Error Value is set in register 30003
when the thermocouple is open
circuit.
Error Value is set in register 30003
and 30004 when the thermocouple
adaptor is not fitted
RF
Thermocouple Range @ Tamb (+10- +40) Thermocouple Range @ Tamb (-40- +60)
Type
Normal
Reverse
PWR
Type
Normal
Reverse
- 25°C to + 365°C - 200°C to + 70°C
Type T
0°C to + 330°C
- 200°C to + 5°C
Type K
- 25°C to + 455°C
- 200°C to + 70°C
Type K
0°C to + 410°C
- 200°C to + 5°C
Type J
- 10°C to + 345°C
- 210°C to + 60°C
Type J
15°C to + 300°C
- 210°C to + 10°C
485
D1
Type T
232
D2
Caution:
D5
D7
·
·
·
For normal Polarity setting Zero and Span to 0 and 100 respectively
will scale the register to read the temperature as an integer value,
e.g. 148.25 °C will read 14825 or 26.51 °C will read 2651
For normal Polarity, setting Zero and Span to 15019 and 682.6667
respectively will scale the register so that a temperature of -10 to
50°C will give a scaled range of 8192 to 49152
For Reverse Polarity, setting Zero and Span to 30948 and 455.106
respectively will scale the register so that a temperature of -50 to
40°C will give a scaled range of 8192 to 49152
Revision 1.6 - Oct 2011
-Ve
+Ve
If ‘Thermocouple
Polarity’ selection is
reversed
Thermocouple wires
must be swapped,
e.g. (red) to TC+ &
(blue) to TC-
N/C
N/C
COM
(+24V)
TC-
Constantan
(red)
TC+
Copper (blue)
Normal Type “T”
Thermocouple
ON
Analog Input Scale Examples
5 6
Thermocouple Adapter
3 4
38005 = 32 bit Floating Point temperature value
38007 = 32 bit Floating Point Cold Junction value
30003 = Scaled 16 bit Analog value
30004 = Scaled 16 bit Cold Junction value
AI 1 AI 1 AI2 AI2
AO1 AO2
+
- AI3 AI4 +
D8 GND +24V +
+ GND +24V
Thermocouple input terminals must
be within +/- 5V of the WI-I/O-9-U2
‘GND’ terminal
1 2
ESD Sensitive pins. Use ESD
handling precautions.
D6
Address locations
D4
The WI-I/O-9-U2-TC adaptor board plugs into the
bottom 6 terminals on the WI-I/O-9-U2 terminal strip.
A separate 14 way terminal strip is provided to allow
connection to the remaining terminals.
Connections
D3
Installation
All Dip Switches
must be set to
the OFF position.
WI-I/O 9-U2
6720005011
Inst_WI-I/O-9-U2 _TC_Adaptor_V1.6.vsd