WI-GTWY-9 Host Protocol Connection WARNING ! Installation Guide EXPLOSION HAZARD FCC Notice This device complies with Part 15.247 of the FCC Rules. Operation is subject to the following two conditions: 1) This device may not cause harmful interference and 2) This device must accept any interference received, including interference that may cause undesired operation Aerial Installation 1m minimum COLINEAR ANTENNA WEATHERPROOF CONNECTORS WITH “3M 23” TAPE COAXIAL CABLE ANT 1. DIO channels can be wired as either inputs or outputs. 2. All I/O must be SELV. CAUTION! For continued protection against risk of fire, replace the module fuse only with the same type and rating MAST INSTALL AERIAL ABOVE LOCAL OBSTRUCTIONS 2A - + - + WI-GTWY-9 Installation DC Supply 9-30VDC 16VA (A) 12-24VAC 16VA CSA Certified Class 2 (B) 9-30VDC 16VA CSA Certified Class 2 BAT+ GND SUP1 SUP2 GND DIO8 DIO7 DIO6 DIO5 DIO4 DIO3 DIO2 GND SUP1 SUP2 EARTH STAKE IF GROUND CONDITIONS ARE POOR, INSTALL MORE THAN ONE EARTH STAKE ANTENNA INSTALLATION Antennas should be installed by experienced contractors. Power supply: DIO1 WI-GTWY-9-xx PROVIDE GOOD GROUND CONNECTION TO MAST, MODULE AND SURGE ARRESTOR GND GND NOTES SUP2 WIGTWY STRESS RELIEF LOOP WIRELESS GATEWAY SUP1 SURGE ARRESTOR (OPTIONAL) DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON HAZARDOUS To Earth Connection (C) 13.8V Lead Acid Battery or Gel-cell Choose option and wire as shown Weidmuller Inc., v1.2 AC Supply 12-24VAC Do not earth SUP1 or SUP2 connections Digital Input Voltage Free Contact OR Transistor Device Optional 12V Backup Battery up to 100 Amphour To Earth Connection + - Digital Output Max 30VDC, 500mA DC Relay Supply