EXPLOSION HAZARD
DO NOT DISCONNECT
WHILE CIRCUIT IS LIVE
UNLESS AREA IS
KNOWN TO BE NON –
HAZARDOUS
This device complies with Part 15.247 of the FCC Rules.
Operation is subject to the following two conditions:
1) This device may not cause harmful interference and
2) This device must accept any interference received, including
interference that may cause undesired operation
+ DC Load
1m minimum
WEATHERPROOF
CONNECTORS WITH
“3M 23” TAPE
COAXIAL CABLE
ANT
+24V
DOT
All I/O must be SELV.
CAUTION!
For continued
protection against
risk of fire, replace
the module fuse only
with the same type
and rating
MAST
PROVIDE GOOD
GROUND
CONNECTION TO
MAST, MODULE
AND SURGE
ARRESTOR
RADIO TELEMETRY MODULE
INPUTS
-
+AI 2
+AI 1
+24V
DI 4
4
COM
DI 1
SOL
GND
SUP1
SUP2
SOL
GND
IF GROUND CONDITION IS POOR
INSTALL MORE THAN 1 STAKE
SUP1
EARTH STAKE
SUP2
INSTALL AERIAL ABOVE
LOCAL OBSTRUCTIONS
3
-
2
1
DI 3
WI-I/O
GND
STRESS RELIEF LOOP
WI-I/O 9-2
NOTES
DI 2
SURGE
ARRESTOR
(OPTIONAL)
AI 6+
OUTPUT
1.
COLINEAR
ANTENNA
AI 5+
AI 4+
BAT+
2A
THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1 DIVISION 2
GROUPS ABC AND D OR NON HAZARDOUS LOCATIONS ONLY
Aerial Installation
Digital Output
Max 30VDC, 500mA
DC Relay Supply
+ -
COM
FCC Notice
AI 3+
Installation Guide
11-15VDC Supply or
Optional 12V Backup
Battery
to 12 Amphour for AC/DC
to 100 Amphour for Solar
COM
WARNING!
GND
WI-I/O 9-2
ANTENNA INSTALLATION
Antennas should be installed by experienced contractors.
+
-
WI-I/O 9-2 Installation
Power supply:
(A) 12-24VAC 1.5 Amp CSA Certified Class 2
(B) 15-30VDC 1.5 Amp CSA Certified Class 2
(C) Supply battery or 11-15VDC
(D) Solar panel with solar battery
Choose option and wire as shown
AC Supply
12-24VAC
min 15VAC
for Battery
Charging.
Do not earth
SUP1 or
SUP2
connections
12V Solar
Panel Supply
max 20VDC
max 30W
panel
+ -
DC Supply
15-30VDC
min 17VDC
for Battery
Charging
Digital Input
Voltage Free
Contact
OR
Transistor
Device
Loop
Powered
Analog
Transducer
+ Ext. Powered
AnalogTransducer
To Earth
Connection
Weidmuller Inc., v1.4