32310371 OE spec MTUContainer Enclosures 1 16

Sound Proof Enclosure
MTU 16V2000 DS: 800 - 1,250 kVA
Optional equipment and finishing shown. Standard may vary.
Product Highlights
// Benefits
- Plug & play, ready-to-use unit
- Wide standard scope of supply
- Shipping optimized
- Modular design - wide range of options
- Serviceability access - double door access gives ease
of serviceability to all components
// MTU
Onsite Energy is a single-source supplier
// Global
product support
// Performance
Assurance Certification (PAC)
- Engine-generator set tested to ISO 8528-5 for transient
response
- Verified product design, quality and performance integrity
- Prototype and factory tested
// Certifications
- CE certification option
- German WHG option
2
/ // / Sound Proof Enclosure / MTU 16V2000 DS
Application data➀
// Engine
Manufacturer
Model
// MTU 16V2000 DS1000 MTU
16V2000 MTU 16V2000 DS1100 MTU 16V2000 DS1250
MTU
MTU
16V2000 16V2000
Ratings➁
Standby Power: kVA
Standby Power with Overload: kVA
Data Center Continuous Power: kVA
Mission Critical Power: kVA
–
900
–
–
1,090
1,000
1,000
1,000
1,230
1,110
–
–
Prime Power: kVA
Grid Stability Power: kVA
900
–
1,000
1,000
1,110
–
Continuous Power: kVA
–
–
790
≤ 92
≤ 83
≤ 92
≤ 83
92
83
50
50
50
Marathon
H
± 0.25%
Marathon
H
± 0.25%
Marathon
H
± 0.25%
// Sound Data
Sound Pressure @1m: dB(A)
Sound Pressure @7m: dB(A)
// Cooling System
Radiator design temperature: °C
// Generator
Manufacturer
Insulation Class
Voltage regulation
For further technical data please refer to the MTU Diesel Generator set data sheet.
➀ All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
➁Rated power refers to ISO standard conditions, 25°C ambient temperature and 100m above sea level – 400V.
Full rated power available up to 27°C ambient temperature and 300m above sea level.
3
/ // / Sound Proof Enclosure / MTU 16V2000 DS
Application data➀
1
2 3
4 5
6
7
6 8
Description of individual components
1
2
3
4
5
6
7
8
STANDARD AND OPTIONAL FEATURES
// Radiator
■ Mechanical driven fan
(50°C ambient temperature)
// Batterys
■ Starterbattery (ready for operation)
// Coolant preheating
2kW/230V incl. thermostat
// 6kW/400V incl. thermostat
Control Panel
■Island operation (V2 - V6)
with Deif mounted on front side
■Represents standard features
 Represents optional features
Fuel filling
Control system
Emergency stop
Circuit Breaker
Access for load cables
2 air inlets on both enclosure sides
Air outlet
Exhaust outlet
4
/ // / Sound Proof Enclosure / MTU 16V2000 DS
STANDARD AND OPTIONAL FEATURES
// Circuit Breaker
■ Circuit breaker mounted on
front side
// Exhaust System
■ Exhaust silencer
// Enclosure
■ Sound insulated canopy
■Lifting eyes at base frame
■ Base frame with integrated fuel tank
// ■ Exhaust outlet via roof and flap
■ Air outlet via enclosure roof
■ Air inlet via alternator side
■Control & Load distribution pane
at front side
Forklift pockets
WHG option
Welded bund
Access Door
■Double wings doors at each side
// Paintwork
■Canopy RAL7001 (silver grey)
// Fuel Tank
■ 900L single walled fuel tank
// Single water separator
Automatic Tank Refilling
Control of external fuel transfer pump
via dry contacts
// ■ Base frame painted black
Incl. design approved overfill
protection (electrical level sensor)
Leakage Sensor
Leakage sensor mounted at
container bund
■Represents standard features
 Represents optional features
Double water separator
5
/ // / Sound Proof Enclosure / MTU 16V2000 DS
Weights and dimensions
Outline drawing above is for reference only. Do not use for installation design. For unit-specific template drawings, please see our website.
MTU Onsite
Energy Genset Type
MTU 16V 2000 DS1000
MTU 16V 2000 DS1100
MTU 16V 2000 DS1250
Dimensions
Size
Length (mm) Width (mm)
Height (mm)
Enclosure
7,125
2,220
2,494
Enclosure
7,125
2,220
2,494
Enclosure
7,125
2,220
2,494
Emissions data
// Consult your local MTU Onsite Energy distributor for emissions data.
Weight
kg
approx. 10,500
approx. 10,500
approx. 10,500
6
/ // / Sound Proof Enclosure / MTU 16V2000 DS
Rating Definitions and conditions
Standby Power ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads
for the duration of a power outage. No overload capability for this rating. Ratings are in accordance with ISO 8528-1,
ISO-3046-1, BS 5514 and AS 2789. Average load factor: ≤ 85%. Operating hours/year: max. 500.
// Standby Power with Overload ratings apply to installations served by a reliable utility source. The standby rating is applicable
to varying loads for the duration of a power outage. A 10% overload capabicity is available for one hour in twelve. Ratings are in
accordance with ISO 8528-1, ISO-3046-1, BS 5514 and AS 2789. Average load factor: ≤ 85%. Operating hours/year: max. 500.
// Data Center Continuous Power ratings apply to Data Center installations where a reliable utility power is available and comply
with Uptime Institute Tier III and IV requirements. At constant or varying load, the number of generator set operating hours is
unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO 8528-1, ISO 3046-1,
BS 5514 and AS 2789. Average load factor: ≤ 100%.
// Mission Critical Power ratings apply to installations served by a reliable utility source. The rating is applicable to varying loads
for the duration of a power outage. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with
ISO 8528-1, ISO-3046-1, BS 5514 and AS 2789. Average Load Factor: ≤ 85%. Operating hours/year: max. 1,000.
// Prime Power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number
of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in
accordance with ISO 8528-1, ISO 3046-1, BS 5514 and AS 2789. Average load factor: ≤ 75%. Operating hours/year: unlimited.
// Grid Stability Power ratings apply to installations serving electric utility programs. At constant or varying load, the number of
generator set operating hours is limited to 1,000 hours per year with no more than 500 hours per year at 100% load without
interruption. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO 8528-1,
ISO-3046-1, BS 5514 and AS 2789. Average Load Factor: ≤ 100.
// // Continuous Power ratings apply to installations where the generator set serves as utility. At constant load, the number of
generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in
accordance with ISO 8528-1, ISO 3046-1, BS 5514 and AS 2789. Average load factor: ≤ 100%. Operating hours/year: unlimited.
Deration factor:
Altitude: Consult your local MTU Onsite Energy Power Generation distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power Generation distributor for temperature derations.
// Subject to change. | 32310371 | Edition 01/16 | ENC 2016-05.
Rated power refers to ISO standard conditions 25°C ambient temperature and 100m above sea level.
C/F = Consult Factory/MTU Onsite Energy Distributor
Materials and specifications subject to change without notice.
MTU Onsite Energy
Part of the Rolls-Royce Group