Power Relays
MK-S(X)
MK-S-series Relays with DC-switching
Models That Can Switch 220 VDC, 10 A
(Resistive Load).
• Switch a DC load of 220 VDC, 10 A (resistive load).
• Models for AC Loads can switch 250 VAC, 15 A (resistive load).
• Lineup includes models with SPST-NO and SPST-NO/SPSTNC contact forms.
• Using a SPST-NO/SPST-NC contact form enables detecting
contact welding. (When the NO contacts become welded, the
NC contacts will maintain a minimum distance of 0.5 mm.)
• Models available with operation indicators and built-in test
buttons.
• RoHS compliant.
• Standards: UL, IEC (TÜV certification)
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Ordering Information
When your order, specify the rated voltage.
General-purpose Relays
Models for DC Loads
Contact form
SPST-NO
Type
Model
Standard Models
MKS1XT-10
Models with Built-in
Operation Indicators
MKS1XTN-10
Models with Test Button
MKS1XTI-10
Models with Test Button and
Built-in Operation Indicators
MKS1XTIN-10
SPST-NO/SPST-NC
Rated voltage (V)
Model
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
MKS2XT-11
MKS2XTN-11
MKS2XTI-11
MKS2XTIN-11
Rated voltage (V)
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
Models for AC Loads
Contact form
SPST-NO
Type
Model
Standard Models
MKS1T-10
Models with Built-in
Operation Indicators
MKS1TN-10
Models with Test Button
Models with Test Button and
Built-in Operation Indicators
MKS1TI-10
MKS1TIN-10
SPST-NO/SPST-NC
Rated voltage (V)
Model
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
MKS2T-11
MKS2TN-11
MKS2TI-11
MKS2TIN-11
Rated voltage (V)
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
AC: 24, 100, 110, 120, 200, 220, 230, 240
DC: 12, 24, 48, 110, 220
Accessory (Order Separately)
Connecting Socket
Built-in diode
Model
Back-connecting Socket
Classifications
PCB Terminals
No
P7M-06P
Front-connecting Socket
Mounts to DIN Track or via
screws
No
P7MF-06
Yes
P7MF-06-D
1
MK-S(X)
Specifications
Ratings
Operating Coil
Item
Rated voltage (V)
24
AC
50 Hz
60 Hz
110
96.3
Coil
resistance
(Ω)
26.6
23.1
110
24.2
21.0
932
120
22.2
19.3
1,130
200
13.3
11.6
3,160
220
12.1
10.5
3,550
230
11.5
10.0
4,250
240
11.0
9.6
4,480
24
126
63.2
Must
operate
voltage (V)
Must
release
voltage (V)
Maximum
voltage
allowable (V)
Percentage of rated voltage
Power
consumption
(VA, W)
48.4
100
12
DC
Rated current (mA)
760
30% min. at
60 Hz
25% min. at
50 Hz
80% max.
Approx. 2.3 VA
at 60 Hz
Approx. 2.7 VA
at 50 Hz
110%
95
380
48
32.0
1,500
110
13.6
8,060
220
6.8
32,200
15% min.
Approx. 1.5 W
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/−20% for AC rated current and
±15% for DC coil resistance.
2. Performance characteristic data are measured at a coil temperature of 23°C.
3. The maximum allowable voltage is the maximum value of the allowable voltage range for the operating power supply for the relay coil.
There is no continuous allowance.
4. The rated current is approximately 5 mA higher for Models with Built-in Operation Indicators (DC operating coils).
2
MK-S(X)
Contact Ratings for Models for DC Loads
Contact form
Model
Load
Item
Contact configuration
Resistive load
NO
SPST-NO
SPST-NO/SPST-NC
MKS1XT(I)(N)-10
MKS2XT(I)(N)-11
Inductive load
L/R = 7 ms
DC13 class
Resistive load
Double-break
Double-break
---
Single-break
NC
AgSnIn
Contact material
NO
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Max. switching capacity
(reference value)
10 A, 220 VDC
Inductive load
L/R = 7 ms
5 A, 220 VDC
AgSnIn
0.4 A, 220 VDC
5 A, 220 VDC
3 A, 220 VDC
0.2 A, 220 VDC
2 A, 220 VDC
0.3 A, 220 VDC
0.1 A, 220 VDC
NC
---
NO
10 A
5A
NC
---
2A
NO
220 VDC
NC
---
NO
10 A
5A
NO
220 VDC
0.4 A
---
NC
2,200 W
-----
NC
DC13 class
---
5A
3A
0.2 A
2A
0.3 A
0.1 A
1,100 W
---
---
440 W
---
---
Note: If the L/R of an inductive load exceeds 7 ms with a Model for a DC Load, the arc interruption time must be less than approximately 50 ms
to use the Relay. Design the circuit so that the arc interruption time is 50 ms or less.
* These values apply to a switching frequency of 30 times per minute.
Contact Ratings for Models for AC Loads
Contact form
SPST-NO
SPST-NO/SPST-NC
MKS1T(I)(N)-10
MKS2T(I)(N)-11
Resistive load
Resistive load
NO
Double-break
Double-break
NC
---
Single-break
Model
Load
Item
Contact configuration
AgSnIn
AgSnIn
15 A, 250 VAC
15 A, 250 VAC
NC
---
5 A, 250 VAC
NO
15 A
15 A
NC
---
5A
NO
250 VAC
NC
---
NO
15 A
NC
---
5A
NO
3,750 VA
3,750 VA
NC
---
1,250 VA
Contact material
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Max. switching capacity
(reference value)
NO
250 VAC
15 A
* These values apply to a switching frequency of 20 times per minute.
3
MK-S(X)
Characteristics
Contact resistance *1
100 mΩ max.
Operate time *2
AC: 20 ms max.
DC: 30 ms max.
Release time *2
Max. operating
frequency
20 ms max.
Mechanical
18,000 operations/h
Rated load
Models for DC loads: 1,800 times/hour
Models for AC loads: 1,200 times/hour
Insulation resistance *3
100 MΩ min.
2,500 VAC 50/60 Hz for 1 min between
Between coil and contacts
Dielectric
strength
Between contacts of different polarity 2,500 VAC 50/60 Hz for 1 min between
Between contacts of same polarity
1,000 VAC 50/60 Hz for 1 min
Vibration
resistance
Destruction
10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Malfunction
10 to 55 to 10 Hz, 0.50-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction
Back-connecting Socket (P7M-06P) mounting: 1,000 m/s2
Front-connecting Socket (P7MF-06(-D)) mounting:500m/s2
Malfunction
100 m/s2
Endurance
Mechanical
1,000,000 operations min. (at 18,000 operations/hr)
Electrical *4
100,000 operations min. (at rated load and maximum switching frequency)
Failure rate P level (reference value)
10 mA at 24 VDC
Ambient operating temperature
−40°C to 60°C (with no icing or condensation)
Note: The range is −25°C to 60°C for models with built-in operation indicators.
Ambient operating humidity
5% to 85%
Weight
SPST-NO: Approx. 73 g, SPST-NO/SPST-NC: Approx. 82 g
Note: The values given above are initial values.
*1. The contact resistance was measured for 1 A at 5 VDC using the voltage drop method.
*2. The operate time was measured with the rated voltage imposed and any contact bounce ignored at an ambient temperature of 23°C.
*3. The insulation resistance was measured with a 500-VDC insulation resistance tester at the same places as those used for checking the
dielectric strength.
*4. The electrical endurance was measured at an ambient temperature of 23°C.
Approved Standards
UL508 (File No. E41515)
*
Model
Coil ratings
MKS1XT@-@
MKS2XT@-@
12 to 220 VDC
24 to 240 VAC
MKS1T@-@
MKS2T@-@
Contact ratings
NO contacts
10 A, 220 VDC (Resistive)
5 A, 220 VDC L/R (T0.632) = 7 ms
0.4 A, 220 VDC L/R (T0.95) = 300 ms
NO contacts
5 A, 220 VDC (Resistive)
3 A, 220 VDC L/R (T0.632) = 7 ms
0.2 A, 220 VDC L/R (T0.95) = 300 ms
NC contacts
2 A, 220 VDC (Resistive)
0.3 A, 220 VDC L/R (T0.632) = 7 ms
0.1 A, 220 VDC L/R (T0.95) = 300 ms
NO contacts
15 A, 250 VAC (Resistive)
NO contacts
15 A, 250 VAC (Resistive)
NC contacts
5 A, 250 VAC (Resistive)
CSA Standard: CSA Certification by
Operations
6,000
: CSA C22.2 No.14
IEC Standard/TÜV Certification: IEC61810-1 (Certification No. R50104853)
Model
Coil ratings
MKS1XT@-@
MKS2XT@-@
MKS1T@-@
MKS2T@-@
4
12, 24, 48, 110,
220 VDC
24, 100, 110, 120,
200, 220, 230,
240 VAC
Contact ratings
NO contacts
DC-1: 10 A, 220 VDC
5 A, 220 VDC L/R (T0.632) = 7 ms
DC-13: 0.4 A, 220 VDC
NO contacts
DC-1: 5 A, 220 VDC
3 A, 220 VDC L/R (T0.632) = 7 ms
DC-13: 0.2 A, 220 VDC
NC contacts
DC-1: 2 A, 220 VDC
0.3 A, 220 VDC L/R (T0.632) = 7 ms
DC-13: 0.1 A, 220 VDC
NO contacts
AC-1: 15 A, 250 VAC 50/60 Hz
NO contacts
AC-1: 15 A, 250 VAC 50/60 Hz
NC contacts
AC-1: 5 A, 250 VAC 50/60 Hz
Operations
100,000
MK-S(X)
Engineering Data
100
DC resistive load
10
5
DC inductive load
L/R = 7 ms
1
MKS2XT-11, MKS2XTN-11
MKS2XTI-11, MKS2XTIN-11
Switching current (A)
Switching current (A)
Maximum Switching Power
MKS1XT-10, MKS1XTN-10
MKS1XTI-10, MKS1XTIN-10
100
1
10
100
1.000
0.01
Switching voltage (V)
DC resistive load
NC
15
10
AC resistive load
0.1
1.000
100
1.000
Switching voltage (V)
AC resistive load
NO
5
0.1
100
10
15
10
1
10
1
100
1
1
DC inductive load
DC inductive load
DC13 class
DC13 class
NO
NC
MKS2T-11, MKS2TN-11
MKS2TI-11, MKS2TIN-11
Switching current (A)
100
0.01
DC inductive load
L/R = 7 ms
NC
0.1
DC inductive load
DC13 class
MKS1T-10, MKS1TN-10
MKS1TI-10, MKS1TIN-10
Switching current (A)
5
3
2
0.3
0.2
0.1
0.01
10
1
0.4
DC inductive load
L/R = 7 ms
NO
DC resistive load
NO
0.01
Switching voltage (V)
AC resistive load
NC
1
10
100
1.000
Switching voltage (V)
Ambient Temperature vs. Must Operate Voltage and Must Release Voltage
MKS2XT-11
MKS2XT-11
Number of Relays: 5
DC Specification
Must operate
voltage
Must release
voltage
80
60
40
Must operate/release voltage (%)
Must operate/release voltage (%)
AC Specification (60 Hz)
100
100
Must operate
voltage
Must release
voltage
Number of Relays: 5
80
60
40
20
20
-40
23
60
-40
Ambient temperature (°C)
23
60
Ambient temperature (°C)
100
220 VDC
10
1
Switching current (A)
Switching current (A)
Inductive Load Switching Power (Models for DC Loads)
MKS1XT-10, MKS1XTN-10
MKS2XT-11, MKS2XTN-11
MKS1XTI-10, MKS1XTIN-10
MKS2XTI-11, MKS2XTIN-11
10
220 VDC
NO
1
0.1
NC
0.1
0 7 10
50
100
Load time constant (ms)
0.01
0 7 10
50
100
Load time constant (ms)
5
MK-S(X)
Test Button
The circuit can be checked using either of two modes.
Test Button
DC specification: Blue
AC specification: Red
Test Button Applications
Example: Checking operation of Relays and sequence circuits.
6
Normal
Mode 1
(momentary)
Mode 2
(locked)
Press the button
for operation.
(No tool is required.)
Lock the contacts by
pressing down on the
button and turning it.
MK-S(X)
Dimensions
(Unit: mm)
General-purpose Relays
Models for DC Loads
Standard Models
MKS1XT-10
MKS2XT-11
Models with Built-in Operation Indicators
MKS1XTN-10
MKS2XTN-11
34.5 max.
34.5 max.
Models for AC Loads
0.8
Standard Models
MKS1T-10
MKS2T-11
Models with Built-in Operation Indicators
MKS1TN-10
MKS2TN-11
44 max.
7.3
3.5
Models for DC Loads
Models with Test Button
MKS1XTI-10
MKS2XTI-11
Models with Test Button and Built-in
Operation Indicators
MKS1XTIN-10
MKS2XTIN-11
34.5 max.
34.5 max.
Models for AC Loads
0.5
0.8
Models with Test Button
MKS1TI-10
MKS2TI-11
Models with Test Button and Built-in
Operation Indicators
MKS1TIN-10
MKS2TIN-11
44 max.
29.7
7.3
Terminal Arrangement/Internal Connection (Bottom View)
MKS1XT-10
MKS1XTI-10
MKS1XTN-10
MKS1XTIN-10
DC specification
MKS2XT-11
MKS2XTI-11
MKS2XTN-11
MKS2XTIN-11
AC specification
DC specification
2
4
6 (+)
4
8
A
6 (+)
4
8
B
A (+)
4
A
B
MKS1TN-10
MKS1TIN-10
DC specification
6 (+)
A
4
6
4
B
A (+)
A
6
4
B
A (+)
6
4
B (−)
A
A
A
B
AC specification
2
6
4
2
6
4
8
8
B
6 (+)
MKS2TN-11
MKS2TIN-11
DC specification
8
4
8 (+)
B (−)
MKS2T-11
MKS2TI-11
AC specification
8
8
6 (+)
8 (+)
2
4
2
2
8 (+)
8
B (−)
MKS1T-10
MKS1TI-10
6 (+)
AC specification
B
A (+)
6
8
B (−)
A
B
Note: 1. Wire properly using the correct coil polarity.
2. The contact terminals on Models for DC Loads have polarity. Wire properly using the correct polarity.
7
MK-S(X)
Connecting Socket
Back-connecting Socket
P7M-06P
Dimensions
39 max.
Terminal Arrangement/Internal Connections PCB Mounting Holes
(Bottom View)
(Bottom View)
4
43 max.
2
5.5
6
0.9
8
39 max.
A
8.3
7.7
B
21.9
4.35
22.1
7.7
0.9
8.3
5.5
Front-connecting Socket
P7MF-06
P7MF-06-D
Terminal Arrangement/Internal Connections
(TOP View)
Dimensions
7
P7MF-06
34 max.
78 max.
39 max.
Six, M3 x 8
8
P7MF-06-D
Mounting Holes
(TOP View)
Two, M4 or
two 3.5-dia. hole
66±0.3
35.5
6
4
24.3
Note: 1. The internal connections diagram is for the MKS2(X)T@@-11.
2. The P7MF-06-D has polarity. Be careful to wire with the
correct polarity.
31±0.2
MK-S(X)
Accessory (Order Separately)
Connecting Socket
Socket
Back-connecting Socket
Front-connecting Socket
PCB terminals
Mounts to DIN Track or via screws
P7M-06P
P7MF-06
P7MF-06-D
Number of poles
2
Note: 1. The P7M-06P, P7MF-06, and P7MF-06-D can be used with models for DC loads with an SPST-NO or SPST-NO/SPST-NC contact form
or with models for AC loads with an SPST-NO or SPST-NO/SPST-NC contact form.
2. The P7MF-06-D has a built-in diode and can thus be used only with Relays with DC operating coils. Do not use it with a Relay with an
AC operating coil.
3. Refer to Gang Mounting on page 10 for the conditions required for gang mounting.
Relay Hold-down Clips
Use the Clips to securely mount the Relay and prevent it from falling due to vibration or shock.
Applicable Relay models
MKS1XT-10
MKS1XTI-10
MKS1XTIN-10
MKS1XTN-10
MKS1T-10
MKS1TI-10
MKS1TIN-10
MKS1TN-10
Socket
Back-connecting Socket
PCB terminals
P7M-06P
Mounts to DIN
Track or via
screws
P7MF-06
Front-connecting Socket
PYC-A2
One Set (Two Clips)
MKS2XT-11
MKS2XTI-11
MKS2XTIN-11
MKS2XTN-11
MKS2T-11
MKS2TI-11
MKS2TIN-11
MKS2TN-11
5 max.
42.8
PYC-A2
P7MF-06-D
4.5
1.2
4.5
Note: The minimum order for the
PYC-A2 is ten clips.
Socket Mounting Height
P7M-06P
64
MK-S(X)
61
P7MF-06
P7MF-06-D
MK-S(X)
74
70
75
79
9
MK-S(X)
Safety Precautions
Refer also to Precautions for All Relays.
Precautions for Correct Use
Installation
Test Button
• Models for DC loads (i.e., models with “X” in the model number)
have permanent magnets built into the insulating block. If a
permanent magnet or other magnetic body comes near the Relay,
magnetic interference will occur with the built-in permanent magnet
and the contact switching capacity will be decreased.
• Models for AC loads do not contain a permanent magnet.
• When mounting a P7MF-06(-D) Front-mounting Socket to a DIN
Track, attach PFP-M End Plates on both sides of the Socket to
prevent it from moving.
Conditions for Gang Mounting Relays
Socket
Back-Connecting
Socket
Front-Connecting
Socket
Models for
10A
DC Loads
❍
❍
Models for
15A
AC Loads
❍
*
Rated current
of Relay
Applied current (A)
* Gang mounting of the Front-Mounting Sockets is not possible if the
contact carry current exceeds 10A.Provide space on both the right
and left sides of the Sockets.
The mounting pitch is given in the following diagram.
20
15
10
5
0
0
10
20
30
40
50
Mounting interval (mm)
Mounting interval
Wiring
• The contact terminals on Models for DC Loads (i.e., models with
“X” in the model number) have polarity. Wiring with incorrect
polarity may result in inability to turn OFF the Relay or loss of
functionality.
• Wire models with built-in operation indicators with the correct coil
polarity (DC operating coil).
10
Operating Environment
Do not use the Relay in environments with combustible gas. Doing so
may result in explosion due to arcing.
Storage
Gang Mounting
Relay
• Turn OFF the power supply before operating the test button.
Always return the test button to the original position after you use it.
• Do not use the test button as a switch.
• The durability of the test button is 100 operations minimum.
Models for DC Loads (i.e., models with “X” in the model number) are
magnetized because they have a built-in magnet to deflect and
extinguish the arc. Do not install the Relay near IC cards or other
items that may be adversely affected by magnetism.
Usage
Use the Relay mounted in the P7M-06P or P7MF-06(-D) Socket.
MK-S(X)
Warranty and Application Considerations
Read and Understand this Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or
other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
11
OMRON Corporation
Industrial Automation Company
Control Devices Division H.Q.
Strategy Planning Division
Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
Tel: (81) 75-344-7109/Fax: (81) 75-344-7149
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
Authorized Distributor:
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
OMRON Industrial Automation Global: www.ia.omron.com
© OMRON Corporation 2008 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
CSM_5_2_1015
Printed in Japan
Cat. No. J175-E1-02
0809