CC-1138-10

1138 SERIES
LOAD
LINE
Operating Voltage = 250/480 V~, 50 / 60 Hz
Operating Voltage = 125/208 V~, 50 – 400 Hz
Operating Current = 10, 15 Amp / Phase
Temperature Range = -20 TO 50 Deg. C
Diel. Withstand (L-CASE) = 1500 V~ FOR 1 MIN.
Diel. Withstand (L-L) = 1500 Vdc For 1 Min.
Leakage Current = 3.8 ma @ 250 V~, 60 Hz
Discharge Volt after 1.0 second = 24 V Max.
Maximum Capacitance each line to case = 0.02 u F
Calculated MTBF = 639,726 hours GB @ 30oC
L1
1
1
2
2
3
3
N
N
GRD
Order P/N:
GRD
10 Amp: CC-1138-10
15 Amp: CC-1138-15
INSERTION LOSS vs FREQUENCY
1138 SERIES
The 1138 series is a 3 phase WYE filter. This series is
designed to be used with military systems which are requires to meet the conducted emissions of MIL STD 461C / CE03.
Minor modifications can be done to adjust the filter configuration in order to meet any special environmental or
vibration specifications.