Download

Solid State Relays
G3FM
CSM_G3FM_DS_E_5_2
100-μA-max. Leakage Current, No Bleeder
Resistor Required
• Reduces wiring work by 60% when combined with the PFY-08PU Push-In Plus Socket (according to actual OMRON measurements).
• 1 mA to 500 mA micro-load switching.
• Switch to both AC and DC with no polarity.
• Switch for a wide range of voltages; 19.2 to 264 VAC, 19.2 to
125 VDC.
• Switch full- and half-wave rectifier AC loads.
• Same sizes and terminal arrangements as OMRON Power
Relay MY Series.
• Switch MY Series (without bleeder resistor).
• Superior surge absorption with a built-in varistor.
• Optimum SSR to control minute load, valves, and solenoids.
Note: The socket is optional.
Refer to Safety Precautions for All Solid State
Relays.
Model Number Structure
■ Model Number Legend
G3FM-@@@@@
1
2 3 4 5 6
1. Basic Model Name
G3FM:
Solid State Relay
2. Rated Load Power Supply Voltage
2:
200 VAC
3. Rated Load Current
R5:
0.5 A
4. Terminal Type
S:
Plug-in terminals
5. Zero Cross Function
L:
Not equipped with zero cross function
6. Operation Indicator
N:
Equipped with operation indicator
Ordering Information
■ List of Models
Isolation
Photo-voltage coupler No
Zero cross
function
Indicator
Yes
Rated output load
0.5 A at 24 to 240 VAC
0.5 A at 24 to 110 VDC
Rated input voltage
5 VDC
Model
G3FM-2R5SLN
12 VDC
24 VDC
Note: When ordering, specify the rated input voltage.
1
G3FM
■ Accessories (Order Separately)
Connection Sockets
Classification
Front-mounting
Back-mounting
Terminal type
Appearance
Model
Screw terminals
(finger protection structure)
PYF08A-E
Screw terminals
(finger protection structure)
PYF08A-N
Screw terminals
PYF08A
Push-In Plus terminal blocks
(Socket combination)
PYF-08-PU
Relays with PCB Terminals
PY08-02
Refer to Common Socket and DIN Track Products for details on Connection Sockets and DIN Track products (sold separately) of your OMRON
website.
Refer to PYF@@-PU/P2RF-@@-PU for details on A Push-In Plus Terminal Block Socket of your OMRON website.
Hold-down Clips
Applicable Socket
Classification
Hold-down Clips
Terminal type
Model
For front-mounting
Screw terminals (finger protection structure)
Screw terminals
PYF08A
For back-mounting
Relays with PCB Terminals
PY08-02
Model *
PYF08A-E and PYF08A-N
PYC-A1
PYC-P
* PYC-A1 is provided with two clips.
DIN Track Mounting Parts
Classification/
division
For front-mounting
Type
DIN Tracks
Appearance
Model
Shallow type, total length: 1 m
PFP-100N
Shallow type, total length: 0.5 m
PFP-50N
Deep type, total length: 1 m
PFP-100N2
End Plate
PFP-M
Spacer
PFP-S
2
G3FM
Specifications
■ Ratings (at an Ambient Temperature of 25°C)
Model
Input
Rated
voltage
G3FM-2R5SLN
Operating
voltage
Output
Impedance
Voltage levels
Must
operate
voltage
Applicable load
Must release Rated load
voltage
voltage
5 VDC
4 to 6 VDC
250 Ω±20%
4 VDC max.
12 VDC
9.6 to
14.4 VDC
600 Ω±20%
9.6 VDC
max.
24 VDC
19.2 to
28.8 VDC
1.2 kΩ±20%
19.2 VDC
1 VDC min.
24 to
240 VAC
24 to
110 VDC
Load
voltage
range
19.2 to
264 VAC
19.2 to
125 VDC
Load
current
1 to
500 mA
at 40°C
Inrush
current
6A
(10 ms)
■ Characteristics
Operate time
5 ms max.
Release time
10 ms max.
Output ON voltage drop
3 V (RMS) max.
Leakage current
0.1 mA max. (at 200 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
1,500 VAC, 50/60 Hz for 1 min
Vibration resistance
10 to 55 to 10 Hz, 0.75-mm single amplitude
Shock resistance
Ambient temperature
1,000 m/s2
Operating: –30°C to 80°C (with no icing or condensation)
Storage: –30°C to 100°C (with no icing or condensation)
Ambient humidity
Operating: 45% to 85%
Weight
Approx. 50 g
Engineering Data
Load Current vs. Ambient Temperature
Characteristics
One Cycle Surge Current:
Non-repetitive
Non-repetitive (Keep the inrush current to
half the rated value if it occurs repetitively.)
G3FM-2R5SLN
Load current (A)
Inrush current (A. Peak)
G3FM-2R5SLN
Ambient temperature (°C)
Energized time (ms)
3
G3FM
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■ Relay
Terminal
Arrangement/Internal
Connections (Bottom View)
1
28 max.
4
5
21.5 max.
9
36.5 max.
42.5 max.
13
8
Load
Input
−
−
Load
Load power supply
12
14
+
Input voltage
+
■ Accessories (Order Separately)
Connection Socket
Hold-down Clips
DIN Track Mounting Parts
Refer to Products Related to Common Sockets and DIN Tracks for precautions on the applicable Sockets of your OMRON website.
Refer to PYF-@@-PU/P2RF-@@-PU for precautions on Push-In Plus Terminal Block Sockets of your OMRON website.
Safety Precautions
Be sure to read 'the Common Precautions' in the website at the following URL:
http://www.ia.omron.com/.
Refer to the Common Solid State Relay Precautions for common precautions of your OMRON website.
Refer to Products Related to Common Sockets and DIN Tracks for precautions on the applicable Sockets of your
OMRON website.
Refer to PYF-@@-PU/P2RF-@@-PU for precautions on Push-In Plus Terminal Block Sockets of your OMRON website.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
4
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2016.6
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2016 All Right Reserved.