omron.com

Solid-state Timer
H3Y
CSM_H3Y_DS_E_7_1
Miniature Timer Compatible with the MY
Relay
LR
• Semi-multi power supply voltage.
• Large transparent time setting knob facilitates time setting.
A flat-blade and Phillips screwdriver can also be used for
time setting.
• Pin configuration compatible with MY Power Relay.
• LED indication for power and output statuses.
• Conforms to EMC standards.
• Conforms to EN61812-1 and approved by UL and CSA.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Ordering Information
Operation/
resetting system
Time-limit contact
Time ranges
Supply voltage
Mounting
Surface/DIN-track
mounting
(with socket)
Time-limit operation/ DPDT (for power
self-resetting
switching)
0.04 s to 3 h
4PDT
24, 100 to 120, 200 to 230 VAC H3Y-2
(50/60 Hz);
12, 24, 48, 125, 100 to
H3Y-4 (See note 3.)
110 VDC
Surface mounting
(with PCB terminals)
H3Y-2-0
H3Y-4-0 (See note 3.)
Note: 1. Specify both the model number, supply voltage, and rated time when ordering.
Ex. H3Y-2 100 to 120 VAC 0.5 s
Rated time
Supply voltage
2. Sockets and Hold-down Clips are not included with the H3Y. They must be ordered separately.
3. Use the H3Y-4 or H3Y-4-0 Series when switching micro loads.
■ Accessories (Order Separately)
Adapter, Mounting Plate, Clip
Socket
Name/specification
Timer
Model
Flush mounting adapter
Y92F-78
Mounting
Plate for
Socket
For 1 Socket
PYP-1
For 18
Sockets
PYP-18
Clip
For PYF@A
Y92H-3
For PY@ and
PYF@M
Y92H-4
Contact
Square Sockets
Model
Pin
Connection
Terminal
DIN track
mounting
DPDT
H3Y-2
8-pin
H3YN-2@
Back
Solder
Connecting terminal
DIN track
mounting
4PDT
PYF08A
DIN track
Front
mounting
PYF08A-E
Connecting (Fingersafe tyape)
Screw
mounting
Note: For details, refer to Safety Precautions.
Model
PYF08F
PY08
PYF14A
Front
DIN track
Connecting mounting
H3Y-4
14-pin
PYF14A-E
H3YN-4@
(Fingersafe tyape)
Back
Solder
Connecting terminal
PY14
Note: 1. Cannot be used with the H3Y-@-0 (PCB terminals).
2. The PYF@@A-E has a finger-protection structure. Round crimp
terminals cannot be used. Use forked crimp terminals.
3. For details, refer to Socket and DIN Track Products.
1
H3Y
Specifications
■ Time Ranges
Rated time
0.5 s
Time setting range
0.04 to 0.5 s
Rated time
3 min
Time setting range
0.1 to 3 min
1s
0.1 to 1 s
5 min
0.2 to 5 min
5s
0.2 to 5 s
10 min
0.5 to 10 min
10 s
0.5 to 10 s
30 min
1 to 30 min
30 s
1.0 to 30 s
60 min
2 to 60 min
60 s
2.0 to 60 s
3h
0.1 to 3 h
120 s
5.0 to 120 s
---
---
■ Ratings
Item
H3Y-2(-0)/H3Y-4(-0)
Rated supply voltage (See note 6, 7.) 24, 100 to 120 (50/60 Hz), 200 to 230 VAC (50/60 Hz) (See note 1.), 12, 24, 48, 125, 100 to 110 VDC
(See notes 2 and 3.)
Operating voltage range
All rated voltages except 12 VDC: 85% to 110% of rated supply voltage
12 VDC: 90% to 110% of rated supply voltage (See note 4.)
Reset voltage
10% min. of rated supply voltage (See note 5.)
Power consumption
100 to 120 VAC:
200 to 230 VAC:
24 VAC:
12 VDC:
24 VDC:
48 VDC:
100 to 110 VDC:
125 VDC:
Control outputs
Relay ON: Approx. 1.8 VA (1.6 W) at 120 VAC, 60 Hz
Relay OFF: Approx. 1 VA (0.6 W) at 120 VAC, 60 Hz
Relay ON: Approx. 2.2 VA (1.8 W) at 230 VAC, 60 Hz
Relay OFF: Approx. 1.5 VA (1.1 W) at 230 VAC, 60 Hz
Relay ON: Approx. 1.8 VA (1.4 W) at 24 VAC, 60 Hz
Relay OFF: Approx. 0.3 VA (0.2 W) at 24 VAC, 60 Hz
Relay ON: Approx. 1.1 W at 12 VDC
Relay OFF: Approx. 0.1 W at 12 VDC
Relay ON: Approx. 1.1 W at 24 VDC
Relay OFF: Approx. 0.1 W at 24 VDC
Relay ON: Approx. 1.2 W at 48 VDC
Relay OFF: Approx. 0.3 W at 48 VDC
Relay ON: Approx. 1.6 W at 110 VDC
Relay OFF: Approx. 0.4 W at 110 VDC
Relay ON: Approx. 1.6 W at 125 VDC
Relay OFF: Approx. 0.4 W at 125 VDC
H3Y-2(-0):
5 A at 250 VAC, resistive load (cosφ = 1)
The minimum applicable load is 1 mA at 5 VDC (P reference value).
Contact materials : Ag
H3Y-4(-0):
3 A at 250 VAC, resistive load (cosφ = 1)
The minimum applicable load is 1 mA at 1 VDC (P reference value).
Contact materials : Au-clad + Ag-alloy
Note: 1.
2.
3.
4.
Do not use the output from an inverter as the power supply. Refer to Safety Precautions for All Times for details.
With DC ratings, single-phase full-wave rectified power sources may be used.
Only the H3Y-2 and H3Y-2-0 Series include 2-VDC models.
Use the Timer within 90% to 110% of the rated supply voltage (95% to 110% for 12 VDC) when using it continuously under an ambient
operating temperature of 50°C.
5. Set the reset voltage as follows to ensure proper resetting.
100 to 120 VAC:10 VAC max.
200 to 230 VAC:20 VAC max.
100 to 110 VDC:10 VDC max.
6. Refer to Safety Precautions for All Times when combining the Timer with an AC 2-wire proximity sensor.
7. A diode to prevent reverse voltages is provided only on models with a DC power supply.
2
H3Y
■ Characteristics
Accuracy of operating time
±1% FS max. (0.5 s range: ±1%±10 ms max.)
Setting error (see note 1)
±10%±50 ms FS max.
Reset time
Min. power-opening time: 0.1 s max. (including halfway reset)
Reset voltage
10% max. of rated supply voltage
Influence of voltage (see note 1)
±2% FS max.
Influence of temperature (see note 1) ±2% FS max.
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying
metal parts) (see note 2)
2,000 VAC, 50/60 Hz for 1 min (between operating power circuit and control output) (see note 2)
2,000 VAC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model) (see note 2)
1,500 VAC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance
Destruction: 10 to 55 Hz, 0.75-mm single amplitude
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude
Shock resistance
Destruction: 1,000 m/s2 (approx. 100G)
Malfunction: 100 m/s2 (approx. 10G)
Ambient temperature
Operating:
Storage:
–10°C to 50°C (with no icing)
–25°C to 65°C (with no icing)
Ambient humidity
Operating:
35% to 85%
Life expectancy
Mechanical:10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
H3Y-2: 500,000 operations min. (5 A at 250 VAC, resistive load at 1800 operations/h)
H3Y-4: 200,000 operations min. (3 A at 250 VAC, resistive load at 1800 operations/h)
Impulse withstand voltage
Between power terminals:
3 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1 kV for 12 VDC, 24 VDC, 48 VDC
Between exposed non-current-carrying metal parts:
4.5 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1.5 kV for 12 VDC, 24 VDC, 48 VDC
Noise immunity
±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity
Destruction: 8 kV
Malfunction: 4 kV
Enclosure rating
IP40
Weight
Approx. 50 g
EMC
(EMI)
Emission Enclosure:
Emission AC Mains:
(EMS)
Immunity ESD:
Immunity RF-interference:
Immunity Burst:
Immunity Surge:
Immunity Conducted Disturbance:
Immunity Voltage Dip/Interruption:
Approved standards
UL508, CSA C22.2 No. 14, Lloyds, CCC
Conforms to EN61812-1 and IEC60664-1. (2.5 kV/2 for H3Y-2/-2-0, 2.5 kV/1 for H3Y-4/-4-0)
Output category according to EN60947-5-1.
EN61812-1
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61812-1
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
IEC61000-4-6
IEC61000-4-11
Note: 1. Add ±10 mS to the above value for the 0.5-S range model.
2. Terminal screw sections are excluded.
3
H3Y
Engineering Data
H3Y-2, H3Y-2-0
Switching operations (×103)
250 VAC, cosφ = 1
24 VDC, cosφ = 1
Switching operations (×103)
H3Y-2, H3Y-2-0
Load current (A)
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
Load current (A)
Reference: A maximum current of 0.6 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both
cases, a life of 100,000 operations can be expected.The minimum
applicable load is 1 mA at 5 VDC (P reference value).
H3Y-4, H3Y-4-0
250 VAC, cosφ = 1
24 VDC, cosφ = 1
Load current (A)
Switching operations (×103)
Switching operations (×103)
H3Y-4, H3Y-4-0
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
Load current (A)
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both
cases, a life of 100,000 operations can be expected.The minimum
applicable load is 1 mA at 1 VDC (P reference value).
Operation
■ Timing Chart
H3Y-2, H3Y-2-0
NC
H3Y-4, H3Y-4-0
NC
4
H3Y
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■ Timers
H3Y-2
H3Y-4
28 max.
28 max.
6.3
6.3
6.4
21.5
max.
6.4
21.5
max.
(63.0)
(63.0)
H3Y-2-0
H3Y-4-0
28 max.
28 max.
6.3
6.3
21.5
max.
(60.7)
21.5
max.
(60.7)
Mounting Holes
Pin 1
Mounting Holes
Pin 1
Eight,
1.3-dia. holes
Fourteen,
1.3-dia. holes
5
H3Y
■ Accessories (Order Separately)
Use the PYF@A, PY@, PY@-02, or PY@QN(2) to mount the H3Y. When ordering any one of these sockets, replace “@” with “08” or “14.”
Track Mounting/Front Connecting Sockets
PYF08A
Two, 4.2 × 5
mounting holes
Eight, M3 × 8
sems
6
Terminal Arrangement
(Top View)
3.4
Mounting Holes
Two, 4.5 dia.
M4 or M3
H3Y
Series
35.4
72 max.
90.5
86.6
59±0.3
4
PYF@A
6
23 max.
15±0.2
16.5
30 max.
PYF14A
Two, 4.2 × 5
mounting holes
Terminal Arrangement
(Top View)
3.4
6
Fourteen, M3 × 8
sems
Mounting Holes
Two, 4.5 dia.
M4 or M3
35.4
72 max.
59±0.3
4
29.5 max.
22±0.2
6
16.5
30 max.
PYF08A-N
Terminal Arrangement
22 max.
4
1
42
12
8
5
44
14
42
4
44
8
Mounting Holes
(for Surface Mounting)
12
1
14
5
3.2 dia.
66.5 max.
3.6 dia.
19.8
PYF-08A-N
41
11
12
9
9
12
41
A2
A2
A1
14
14
13
11
14 14 13
A2 A2 A1
30 max.
PYF14A-N
Terminal Arrangement
4
3
42
32
8
7
44
34
2
1
22
12
6
5
24
14
42
4
44
8
32
3
34
7
22
2
24
6
12
1
14
5
Mounting Holes
(for Surface Mounting)
Two, 3.5 dia.
66.5 max.
PYF-14A-N
41
31
21
12
11
10
A2
A2
A1
11
14
14
13
9
30 max.
29.5 max.
12 11 10 9
41 31 21 11
13
14 14
A2 A2
20.8
A1
6
H3Y
PYF08A-E
Two, 4.2 × 5
mounting holes
(Top View)
Two, 4.5 dia.
M4 or M3
Eight, M3 × 8
sems
72 max.
23 max.
31 max.
PYF14A-E
(Top View)
Two, 4.2 × 5
mounting holes
Two, 4.5 dia.
M4 or M3
Eight, M3 × 8
sems
72 max.
29.5 max.
31 max.
Back Connecting Sockets
PY08, PY14
Terminal Arrangement
(Bottom View)
Eight, 3 × 1.2 dia. holes
only for PY08 (Fourteen,
3 × 1.2 dia. holes)
24 max.
0.3
2.7
21.4+0.2
0
25.5 29.5
max. max.
59.3
H3Y
Series
25.8+0.2
0
2.6
7.7
PY08
20 max.
Terminal Arrangement
(Bottom View)
24 max.
22 max.
25 max. *
(See
note)
PY14
PY@, PY@-02,
PY@QN(2)
PY08QN, PY14QN
PY08QN(2), PY14QN(2)
2.7
Panel Cutout
29.5 max.
1×1
**
41.5 max.
(see note)
Note: With PY@QN(2), dimension * should read
20 max. and dimension ** 36.5 max.
PY08-02, PY14-02
4.3
2.7
PY14QN
PY14QN(2)
Terminal Arrangement
(Bottom View)
22 max.
0.3
PY08QN
PY08QN(2)
25.5 29.5
max. max.
2
16.5 max.
PY08-02
PY14-02
7
H3Y
Socket Mounting Plates (t = 1.6)
Applicable socket
For mounting 1 socket
PY08, PY14, PY08QN(2), PY14QN(2)
PYP-1
For mounting 18 sockets
PYP-18
Note: PYP-18 may be cut to any desired length.
PYP-1
PYP-18
Two, 3.4-dia. holes
Relay Hold-down Clips
Y92H-3
Y92H-4
Y92H-3 for
PYF@A Socket
(Set of Two Clips)
Y92H-4 for
PY@ Socket
9R
5 max.
30.5
24.5
53
2.5
20
(84°)
33.7
4.5
1.2
4.5
Mounting Track
End Plate
PFP-100N/PFP-50N (see note 1)
PFP-M
1000 (500) (See note 2)
Note: 1. Meets DIN EN50022
2. This dimension applies to PFP-50N.
Spacer
PFP-S
8
H3Y
Installation
■ Connection
H3Y-2, H3Y-2-0
H3Y-4, H3Y-4-0
Connect the DC power supply to
terminals 13 and 14 according
to the polarity marks.
(Bottom View)
Connect the DC power supply to
terminals 13 and 14 according to
the polarity marks.
(Bottom View)
9
H3Y
Safety Precautions
Refer to Safety Precautions for All Timers.
Warning Indications
CAUTION
Indicates a potentially hazardous situation
which, if not avoided, may result in minor
or moderate injury or in property damage.
Precautions for
Safe Use
Supplementary comments on what to do
or avoid doing, to use the product safely.
Precautions for
Correct Use
Supplementary comments on what to do
or avoid doing, to prevent failure to
operate, malfunction or undesirable effect
on product performance.
Meaning of Product Safety Symbols
Precautions for Safe Use
Confirm that the setting dial, indicators and plastic parts are
operating normally. Depending on the operating environment, the
setting dial, indicators and plastic parts may deteriorate faster than
expected, causing the indicators to fail. Periodically perform
inspections and replacements.
We recommend that you use a surge absorber if surge voltages may occur.
When you dispose of the Timer, do so according to all local
ordinances for processing industrial waste.
Precautions for Correct Use
When selecting a control output, use the H3Y-2 for switching ON and
OFF the power and the H3Y-4 for switching ON and OFF the minute
load.
Used for general prohibitions for which there is no
specific symbol.
The operating voltage will increase when using the H3Y in any place
where the ambient temperature is more than 50°C. Supply 90% to
110% of the rated voltages (at 12 VDC: 95% to 110%) when
operating at 45°C or higher.
Use to indicate prohibitions when there is a risk of
minor injury from electrical shock or other source if
the product is disassembled.
Do not leave the H3Y in time-up condition for a long period of time
(for example, more than one month in any place where the ambient
temperature is high), otherwise the internal parts (aluminum
electrolytic capacitor) may become damaged. Therefore, the use of
the H3Y with a relay as shown in the following circuit diagram is
recommended to extend the service life of the H3Y.
Used for general mandatory action precautions for
which there is no specified symbol.
CAUTION
Risk of fire and explosion due to arcing and relay heat
generation that accompanies switching. Do not use in an
environment where flammable or explosive gas is present.
Auxiliary relay such as MY Relay
Do not connect the H3Y as shown in the following circuit diagram on
the right hand side, otherwise the H3Y’s internal contacts different
from each other in polarity may become short-circuited.
Correct
The service life of the output relay varies widely
depending on switching capacity and switching
conditions. Use only within the rated load and
electrical life count, based on actual conditions of use.
Risk of contact sticking and burning if used past the
service life. Always use a load current that does not
exceed the rating, and if a heater is used, use a thermal switch in the
load circuit.
Incorrect
L2
L1
L2
L1
Use the following safety circuit when building a self-holding or selfresetting circuit with the H3Y and an auxiliary relay, such as an MY
Relay, in combination.
Do not remove the outer casing.
: H3Y
In rare circumstances there is a risk of slight electrical
shock, fire, or device damage. Do not disassemble,
modify, repair, or otherwise touch the inside.
Auxiliary relay:
MY Relay
Do not use the H3Y in places where there is excessive dust,
corrosive gas, or direct sunlight.
Tighten the screws for the lead wires to the Socket to
the following torque.
PYF Socket: 0.78 to 1.18 N·m
This is the recommended range when crimp terminals
are used.
If the screws are not tightened sufficiently on Frontconnecting Sockets, the lead wires may come off, connection failure
may cause abnormal heating, or fires may occur.
If they are tightened excessively, the screw threads may be
damaged.
Do not mount more than one H3Y closely together, otherwise the
internal parts may become damaged. Make sure that there is a
space of 5 mm or more between any H3Y Models next to each other
to allow heat radiation.
The internal parts may become damaged if a supply voltage other
than the rated ones is imposed on the H3Y. When more than 100 V is
applied to 12- or 24-VDC models, the internal element (varistor) may
break.
Always use the same type of wire.
Installation
There are no restrictions on the installation orientation. Install the
Timer securely.
10
H3Y
Precautions for EN61812-1
Conformance
The H3Y as a built-in timer conforms to EN61812-1 provided that the
following conditions are satisfied.
Handling
Wiring
Before dismounting the H3Y from the socket, make sure that no
voltage is imposed on any terminal of the H3Y.
The power supply for the H3Y must be protected with equipment
such as a breaker approved by VDE.
Basic insulation is ensured between the H3Y’s operating circuit and
control output.
Insulation requirement:
Overvoltage category II,
pollution degree 1 (H3Y-4/-4-0),
pollution degree 2 (H3Y-2/-2-0)
(with a clearance of 1.5 mm and a
creepage distance of 2.5 mm at 240 VAC)
Output terminals next to each other on the H3Y-4 or H3Y-4-0 must
have the same polarity.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
11
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2014.9
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2014 All Right Reserved.