Solid State Relays with Failure Detection Function
G3PC
CSM_G3PC_DS_E_1_2
Refer to Safety Precautions for All Solid State Relays.
Detects failures in SSR used for heater
temperature control and simultaneously
outputs alarm signal. This SSR supports the
safe design of heater control systems, and
contributes to maintenance improvements
by the user.
• Main detection items:
SSR short-circuits and SSR open-circuits
• Alarm output possible to NPN/PNP-input devices.
• The failure-detection function is built-in and power is supplied
from the main circuit power supply making wiring simple.
• Slim design (width: 22.5 mm) incorporating a heat sink.
• In addition to screw mounting, DIN track mounting is also
possible.
• Certified by EC, UL, and CSA.
Model Number Structure
■ Model Number Legend
G3PC-@@@-@
1
2 3 4
5
1. Basic Model Name
G3PC:
SSR with Failure Detection Function
2. Rated Load Power Supply Voltage
2:
100 to 240 VAC
3. Rated Load Current
20:
20 A (carry current)
4. Terminal Type
B:
Screw terminals
5. Certification
VD:
Certified by UL, CSA, and VDE
Ordering Information
■ List of Models
Insulation method
Phototriac coupler
Zero cross function
Yes
Indicators
Yes
(See page 5)
Rated output load
20 A, 100 to 240 VAC
(resistive load: AC, Class1)
Model number
G3PC-220B-VD
Note: When ordering, specify the rated input voltage.
■ Accessories (Order Separately)
Name
Mounting Track
Dimensions
50 cm (l) × 7.3 mm (t)
Model number
PFP-50N
1 m (l) × 7.3 mm (t)
PFP-100N
1 m (l) × 16 mm (t)
PFP-100N2
1
G3PC
Specifications
■ Ratings (at an Ambient Temperature of 25°C)
Detection Power Supply
Main Circuit
Rated power supply voltage
100 to 240 VAC (50/60 Hz)
Rated load voltage
100 to 240 VAC (50/60 Hz)
Operating voltage range
75 to 264 VAC (50/60 Hz)
Operating voltage range
75 to 264 VDC (50/60 Hz)
Current consumption
15 mA AC max. (at 200 VAC)
Applicable load current
20 A (Ta = 40)
Minimum load current
0.1 A
Inrush current resistance (peak value)
220 A (60 Hz, 1 cycle)
Operating Circuit
2
Input method
Voltage input
Permissible (I t)
260 A2s
Applicable load
(with Class-1 AC resistive load)
4 kW (at 200 VAC)
Rated input voltage
12 to 24 VDC
Operating input voltage
range
9.6 to 30 VDC
Must operate voltage
9.6 VDC max.
Must release voltage
1 VDC min.
Output OFF collector voltage
30 VDC max.
Input current
7 mA DC max. (at rated input voltage)
Maximum carry current
0.1 A
Output form
Independent NPN open collector
Alarm Output
■ Characteristics
Operate time
1/2 of load power source cycle + 1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Main circuit
Alarm output
Output ON voltage drop
1.6 V rms max.
OFF leakage current
10 mA max. (at 200 VAC)
Output ON voltage drop
1.5 V max.
OFF leakage current
0.1 mA max.
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to10 Hz, 0.35-mm single amplitude
Shock resistance
Destruction: 294 m/s2
Ambient temperature
Operating: −20 to 60°C (with no icing or condensation)
Storage: −30 to 70°C (with no icing or condensation)
Ambient humidity
45% to 85%
Weight
Approx. 300 g
Certified standards
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3); Certified by VDE
EMC
Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2
Engineering Data
Ta = +25°C
8
The figure will be less than 1/2 the rated
value for repetitive input.
25
20
Input impedance
6
15
4
One Cycle Surge Current:
Non-repetitive
Inrush current (A. Peak)
10
Load Current vs.
Ambient Temperature
Load current (A)
Input impedance (kΩ)
Input current (mA)
Input Voltage vs. Input
Current
Input Voltage vs. Input
Impedance
250
200
150
10
100
5
50
Input current
2
0
0
10
20
30
40
Input voltage (V)
-20
0
20
40
60
80
100
Ambient temperature (°C)
0
10
30 50
100
300 500 1,000 3,000 5,000
Energized time (ms)
2
G3PC
Operation
■ Failure Detection Function
Conditions for SSR Failure Detection
Failure mode
(See note 1.)
Operating input (between
terminals A1 and A2)
Detection time
Alarm display
(See note 3.)
SSR short-circuit
OFF
0.5 s max. (See note 2.)
Red
Open collector transistor
output
SSR half-wave short-circuit OFF
SSR open-circuit
Alarm display (between
terminals X1 and X2)
(See note 3.)
ON
SSR half-wave open-circuit ON
Note: 1. The contents of each of the above failure modes is as follows:
SSR short-circuit: SSR output circuit remains in the ON state.
SSR half-wave short-circuit: SSR output circuit remains in the ON state in one direction.
SSR open-circuit: SSR output circuit remains in the OFF state.
SSR half-wave open-circuit: SSR output circuit remains in the OFF state in one direction.
In addition to the failure modes listed above, detection of circuit disconnections for the load circuit is also possible. (As a rough guide,
circuit disconnection will be detected if the load impedance is greater than or equal to 1 MΩ.)
2. The same power supply is used for both the detection and for the output circuit and so detection is not performed during power
interruptions.
3. If power supply (terminal 3) is in the open state, the SSR will still turn ON and OFF in the same way but the failure detection function and
alarm display will not operate properly.
Connection Diagrams (Main Circuit)
The following diagrams show the applicable load connection configurations for SSR failure detection.
Single Phase
3-phase Star
Connection
G3PC
G3PC
3-phase Delta
Connection (3-phase,
2-wire Switching)
G3PC
G3PC
G3PC
G3PC
3-phase V
Connection
G3PC
G3PC
Heater
er
at
er
He
at
He
er
at
He
er
er
er
at
at
at
He
He
He
Heater
Heater
Note: 1. With 3-phase connection, so that the power supply voltage is applied between the G3PC’s terminals 1/L1 and 3, connect the desired
phase to terminal 3.
2. When grounding to a neutral point with a three-phase start connection, an overvoltage will be applied to the G3PC if the neutral point
becomes disconnected, possibly causing product failure. Make sure the connection to the neutral point is secure.
3. Detection is not possible for the heater indicated with an asterisks with a three-phase delta connection.
Timing Chart
SSR failure detection
SSR ON normally
Main circuit power
supply (load side)
SSR OFF normally
SSR short-circuit
Reset (See note.)
SSR open-circuit
Circuit disconnection detection on the load side
Reset (See note.)
Load circuit disconnection
Reset (See note.)
Operating input
(between terminals
A1 and A2)
Input LED
(yellow)
Load current
RDY/ALM LED
(Green:
; Red:
)
Alarm output
(between terminals
X1 and X2)
Note: After failure detection, if the detection conditions differ to the conditions given under Conditions for SSR Failure Detection, alarm output is
reset.
3
G3PC
Dimensions
G3PC-220B-VD
Mounting Holes
130 max.
Terminal cover
114.4
22.5 max.
Tow, 4.6 dia.
13
Three, 4.5 dia. or M4
13.5
68
100 max.
90±0.2 80
8.5x3
= 25.5
4.5
90±0.3
4.6x5.6 elliptic hole
Note The above diagram is
for when the terminal
cover is open.
84.2
13±0.3
Note The above diagram is
for when the terminal
cover is closed.
Accessories (Order Separately)
Mounting Tracks
PFP-100N, PFP-50N
PFP-100N2
16
7.3±0.15
4.5
4.5
35±0.3
25
25
15 25 10 25
1,000(500)
(500) 10
1,000
(see
note)
(see note)
27±0.15
15 (5)
(see note)
35±0.3 27 24
15 25
10
25
25
1,000
10
25 15
1
29.2
1.5
Note Values in parentheses indicate dimensions for the
PFP-50N.
4
G3PC
Installation
■ External Specifications
Appearance
Terminal Arrangement
Terminal name
Terminal number
Main circuit terminals 1/L1, 2/T1
(output)
1/L1
Screw size
M4
3
RDY/ALM
Detection power sup- 3
ply terminal (input)
A1(IN+)
Operating circuit terminals (input)
A1, A2
Alarm output terminals (output)
X1, X2
INPUT
A2(IN−)
M3.5
X1(ALM+)
X2(ALM−)
2/T1
Indicators
Name
Status indicators
Input indicator
Symbol
Color
Meaning
RDY
Green
SSR normal
ALM
Red
SSR failure detection
and circuit
disconnection
detection
INPUT
Yellow
Operating
Note: The same indicator is used as both the power supply indicator
and the alarm indicator.
■ Connection Example
(See note 1.)
Display Labels
L1
1
AC
3
Voltage output for Temperature
Controller, sequencer
A1
12 to 24
VDC
IN
A2
X1
Input for Temperature
Controller, sequencer
ALM
X2
30 VDC
min.
2
T1
(See note 2.)
Heater
Note: 1. If the detection power supply terminal (terminal 3) is not connected, failure detection is not performed and so be sure to connect this
terminal.
2. If the load is connected to terminal 1/L1, failure detection may not operate correctly and so connect the load to terminal 2/T1.
3. With inductive loads (relay coil, etc.), connect back-current prevention diodes to both sides of the load.
5
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2009.1
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2009 All Right Reserved.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2009.1
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2009 All Right Reserved.