Spec Sheet MTU 12V0183 GS400 (400 kW Standby)

GAS GENERATOR SET
MTU 12V0183 GS400
400 kWe /60 Hz /Standby
208 - 600V
Reference MTU 12V0183 GS400 (355kWe) for Prime Rating Technical Data
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
Natural Gas
Ratings: Amps
Natural Gas
Ratings: kW/kVA
LP Gas
Ratings: Amps
LP Gas
Ratings: kW/kVA
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V**
1
1
60
208V**
3
0.8
60
240V**
3
0.8
60
480V**
3
0.8
60
600V**
3
0.8
60
1604
1388
1203
601
481
385/385
400/500
400/500
400/500
400/500
1187
1023
887
443
355
285/285
295/368
295/368
295/368
295/368
760
574RSL4037
130 °C/40 °C
1500
572RSL4029
130 °C/40 °C
1500
572RSL4029
130 °C/40 °C
1500
572RSL4029
130 °C/40 °C
1080
433RSS4266
130 °C/40 °C
12 LEAD ZIG-ZAG
12 LEAD LOW WYE
12 LEAD HI DELTA
12 LEAD HI WYE
4 LEAD WYE
* Consult the factory for alternate configuration.
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
// Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
// UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
// Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
// Power Rating
- Accepts Rated Load in One Step Per NFPA 110
2
/ // /
MTU 12V0183 GS400 (400 kWe) - Standby
STANDARD FEATURES*
// // // // // // // // MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
21.9 L Turbo Engine Charge Air Cooling
- 21.9 Liter Displacement
- 4-Cycle
3-Way Catalyst
Optional Fuel System: NG and LP Vapor Dual Fuel
Engine-generator resilient mounted
Complete Range of Accessories
Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- PMG (Permanent Magnet Generator) supply to regulator
- 300% Short Circuit Capability
// Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine Driven Fan
// STANDARD EQUIPMENT*
// Engine
Air Cleaner
Oil Pump
Oil Drain Extension & S/O Valve
Full Flow Oil Filter
Jacket Water Pump
Thermostats
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 24V
Governor – Electronic Isochronous
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 24V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
// Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for
up to 10 seconds
Self Ventilated and Drip-proof
Superior Voltage Waveform
Digital, Volts-per-hertz Regulator
±1% Voltage Regulation No Load to Full Load
Brushless Alternator with Brushless Pilot Exciter
4 pole, Rotating Field
130 °C Maximum Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-phase Voltage Sensing
100% of Rated Load - One Step
5% Maximum Total Harmonic Distortion
// Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows®-Based Software
Multilingual Capability
Remote Communications to RDP-110 Remote Annunciator
Programmable Input and Output Contacts
UL Recognized, CSA Certified, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
3
/ // /
MTU 12V0183 GS400 (400 kWe) - Standby
APPLICATION DATA
// Engine
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Maximum Power (NG): kWm (bhp)
Maximum Power (LP): kWm (bhp)
Speed Regulation
Air Cleaner
// // Doosan
21.9L CAC
4-Cycle
12-V
21.9 (1,338)
12.8 (5.04)
14.2 (5.59)
10.5:1
1,800
Bosch
456 (612)
351 (471)
±0.5%
Dry
NG
At 100% of Power Rating: m3/hr (ft3/hr) 119.8 (4,230)
At 75% of Power Rating: m3/hr (ft3/hr)
93.4 (3,297)
At 50% of Power Rating: m3/hr (ft3/hr)
65.5 (2,314)
// Cooling - Radiator System
NG and LPG
50 (122)*
Ambient Capacity of Radiator: °C (°F)
Maximum Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM)
Heat Radiated to Ambient: kW (BTUM)
Fan Power: kW (hp)
0.12 (0.5)
660 (174)
453 (25,760)
118.2 (6,720)
31.3 (42)
47.1 (12.4)
52.3 (11.5)
291 (64)
* Installation of enclosures reduces the ambient capacity of the cooling
system by 1 °C (1.8 °F). Gravity exhaust louvers reduce ambient
capacity of the cooling system by an additional 3 °C (5.5 °F).
// Air Requirements
Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
// LPG
39.9 (1,407)
34 (1,200)
22.9 (808)
Liquid Capacity (Lubrication)
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
// Fuel Consumption (NG-1000 BTU/ft3 / LP-2500 BTU/ft3)
24
1,050
Fuel Inlet
Fuel Supply Connection Size
Fuel Supply Pressure: mm H20 (in. H20)
3” NPT
178–279 (7–11)
NG and LPG
24.6 (841)
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Cooled Unit: **m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Gen-set Heat for a
Max of 25 °F Rise: *m3/min (SCFM)
1,333 (40,000)
429 (15,160)
* Air density = 1.184 kg/m (0.0739 lbm/ft )
** At 0.25 kPa (1 in. H20) static pressure and 52 °C (125 °F) at radiator
3
// 3
Exhaust System
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
Temp: m3/min (CFM)
Maximum Allowable
Back Pressure: kPa (in. H20)
NG and LPG
582 (1,080)
72.2 (2,550)
2.5 (10.25)
4
/ // /
MTU 12V0183 GS400 (400 kWe) - Standby
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
4,369 x 2,760 x 2,413 mm (172 x 108.63 x 95 in)
Weight (dry)
5,228 kg (11,500 lb)
SOUND DATA
Unit Type
Level 0: Open Power Unit dB(A)
Standby Full Load (NG)
86.2
Standby Full Load (LP)
85.3
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
Fuel Type
Natural Gas
Liquid Propane
THC + NOx
0.39
0.06
RATING DEFINITIONS AND CONDITIONS
CO
0.1
0.25
All units are in g/hp-hr and are EPA weighted cycle values.
Emission levels of the engine may vary with ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation, etc.
The data was obtained in compliance with US EPA regulations.
C/F = Consult Factory/MTU Onsite Energy Distributor
N/A = Not Available
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Ambient capability factor at 984 ft (300 m). Consult your
local MTU Onsite Energy Power Generation Distributor for
other altitudes.
// Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload
capability for this rating. Ratings are in accordance with
ISO 3046-1, BS 5514, and AS 2789. Average load
factor: ≤ 85%.
// Deration Factor:
Production tolerances in engines and installed components
can account for power variations. Altitude, temperature and
excessive exhaust and intake restrictions should be applied
to power calculations. Consult your local MTU Onsite Energy
Power Generation Distributor for derations.
// © MTU Onsite Energy. Subject to alteration due to technological advances. OE 23 477 (72 3E) 2015-03
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.