LITTELFUSE V302AS32

AS Series
Data Sheet
[ /Title
(AS
Series)
/Subject
(High
Energy
MetalOxide
Arreste
r
Blocks
)
/Autho
r ()
/Keywords
(TVS,
Transient
Suppression,
Protection,
Arreste
r,
Lightning
Protection,
January 1998
File Number
2492.4
High Energy Metal-Oxide Arrester Blocks
Features
The AS Series of Arrester blocks is primarily designed to be
used as the surge suppression element within a lightning
arrester assembly. These arrester blocks provide the high
peak surge current and energy ratings required for the
protection of high voltage AC power utility distribution
systems. Typically, these devices are placed within a special
arrester housing provided by the customer, and stacked to
achieve the necessary continuous working voltage ratings
for the specific application. (See the CA or NA series of
Varistor discs for lower voltage and energy applications.)
• Provided in Disc Form for Unique Packaging by
Customer
• Electrode Finish Enables Pressure Contact for Stacking
Application
• Available Disc Sizes: 32mm, 42mm and 60mm Diameter
• No Follow Current
• High Surge Current Capability
• Conforms to IEC 99-4 and ANSI/IEEE C62.11 Industry
Standards
• Characterized for Lightning Arrester Parameters
Applications
• Lightning Protection of Electrical AC Distribution
Transformers and Systems
d
de
n
e
–
mm
ns
o
g
c
i
e
s
s
tR
Ha
De
s
w
No
e
d
rie
rN
ue
Se
t
o
n
t
i
F
en
nt
uc
m
o
d
e
c
o
c
Pr
Dis epla
n
e
R
Be
No
h
t
Wi
• Arrester Assemblies of the Porcelain Polymeric,
“Under-oil” and Metal Clad Variety
Packaging
AS SERIES
OBSOLETE
PART
8-3
1-800-999-9445 or 1-847-824-1188 | Copyright
© Littelfuse, Inc. 1998
AS Series
Absolute Maximum Ratings
For ratings of individual members of a series, see Device Ratings and Specifications chart
AS SERIES
UNITS
3.00 to 6.00
kV
2.55 to 5.10
kV
Peak Pulse Current (ITM) for 4/10 µs Current Wave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
65 to 100
kA
Energy Rating for 2ms Current Wave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 to 12
kJ
60
oC
Rated Voltage
AC Voltage Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Steady State Applied Voltage
AC Voltage (MCOV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transient
Operating Ambient Temperature (TA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STORAGE AND HANDLING NOTES:
1. Arrester blocks should be stored in a moisture free environment at all times.
2. Use caution during handling to prevent damage or chipping of edges of the arrester blocks.
CAUTION: Stresses above those listed in “Absolute Maximum Ratings” may cause permanent damage to the device. This is a stress only rating and operation of the
device at these or any other conditions above those indicated in the operational sections of this specification is not implied.
Device Ratings and Specifications
25oC Unless Otherwise Specified
PART NUMBER
PARAMETER
V302AS32
V402AS32
V502AS32
V602AS32
V302AS42
V402AS42
V502AS42
V402AS60
UNITS
Rated Voltage (RMS)
3.0
4.0
5.0
6.0
3.0
4.0
5.0
4.0
kV
Maximum Continuous
Operating Voltage (MCOV)
2.55
3.40
4.25
5.1
2.55
3.40
4.25
3.40
kV
Reference Current, IREF
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
mA
Minimum Reference
Voltage, VREF
3.12
4.16
5.20
6.24
3.12
4.16
5.20
4.16
kVRMS
Nominal Discharge
Current, IP (8/20µs)
5.0
5.0
5.0
5.0
10.0
10.0
10.0
10.0
kA
Residual Voltage (Max) at
IP
9.8
13.1
16.3
19.6
10.0
13.3
16.7
12.5
kV
Energy Rating at 60oC
(2ms)
2.2
2.9
3.6
4.3
3.5
4.7
5.8
12.0
kJ
Peak Current, 4/10µs at
60oC (Note 4)
65.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
kA
Maximum Steep Current
Residual Voltage at 5kA
(1/20µs)
11.3
15.0
18.8
22.5
-
-
-
-
kV
Maximum Steep Current
Residual Voltage at 10kA
(1/20µs)
-
-
-
-
11.5
15.3
19.2
14.4
kV
Maximum Dissipation
Power at MCOV
0.23
0.30
0.38
0.45
0.36
0.48
0.60
0.50
W
Maximum Conduction
Current at MCOV
75.0
75.0
75.0
75.0
110.0
110.0
110.0
140.0
µA
OBSOLETE
PART
NOTES:
3. In addition to above standard types, custom ratings and dimensions can be provided.
4. Parts should be wrapped using a secondary insulating film or encased by polymeric housing.
8-4
AS Series
Performance Curves
35
PEAK RESIDUAL VOLTAGE (kV)
PER UNIT OF RATED VOLTAGE
1.3
1.25
1.2
1.15
1.1
1.05
1
0.1
1
10
100
1000
30
25
15
10
5
0
0.001
10000
V602AS32
V502AS32
V402AS32
V302AS32
20
0.01
TIME (s)
FIGURE 1. TEMPORARY OVERVOLTAGE CAPABILITY (TOV)
FOR AS SERIES ARRESTERS
PEAK RESIDUAL VOLTAGE (kV)
PEAK RESIDUAL VOLTAGE (kV)
20
25
15
10
5
0
0.001
10,000 100,000
FIGURE 2. V-I CHARACTERISTIC AS32 SIZE
30
20
1000
100
1
10
0.1
PEAK IMPULSE CURRENT (A)
15
OBSOLETE
PART
V502AS42
V402AS42
V302AS42
0.01
100
1000
1
10
0.1
PEAK IMPULSE CURRENT (A)
10,000 100,000
FIGURE 3. V-I CHARACTERISTIC AS42 SIZE
8-5
10
V402AS60
5
0
0.001
0.01
1000
100
1
10
0.1
PEAK IMPULSE CURRENT (A)
10,000 100,000
FIGURE 4. V-I CHARACTERISTIC AS60 SIZE
AS Series
Dimensions
PASSIVATION COLLAR
TYPICAL THICKNESS = 0.07mm
ELECTRODE
OF SPRAYED
ALUMINUM
PARTICLES
FACE CAMBER
= 0.15mm MAX
ELECTRODE
= 0.10mm TYPICAL
∅D
H
OBSOLETE
PART
DIMENSIONS (IN MILLIMETERS)
PART NUMBER
PARAMETER
Diameter (∅D)
Min
Max
Height (H)
Min
Max
V302AS32
V402AS32
V502AS32
V602AS32
V302AS42
V402AS42
V502AS42
V402AS60
UNITS
32.3
32.3
32.3
32.3
40.9
40.9
40.9
60.0
mm
33.7
33.7
33.7
33.7
42.3
42.3
42.3
62.0
mm
20.0
27.0
34.0
41.0
20.0
27.0
34.3
35.3
mm
21.5
28.5
35.5
42.5
21.5
28.5
35.8
36.8
mm
Ordering Information
VXXX ASXX TYPES
AS SERIES
V
30
2
AS
60
VARISTOR
TECHNOLOGY
DIAMETER SIZE (mm)
MCOV BASE VALUE
ARRESTER SERIES
MCOV DECADE MULTIPLIER
8-6