Moore 340 Pressure Transmitter-Controller
FEATURES & BENEFITS
Silicon-based MycroSENSORTM provides exceptional performance
Built-in PID controller reduces hardware and wiring
per loop costs
Rotatable NEMA 4X/6P, IP66/68 housing and rotatable Smart Display (shown on the next page) deliver
long, trouble-free operation and maximum flexibility in mounting options
10 segment characterizer linearizes non-linear flow
elements and valves
SmartDisplay in engineering units affords greater operator understanding
ABS/FM/CSA/CENELEC/SAA approvals ensure safe
operation in various high industrial stress environments
Americas +1 215 646 7400 ext. 6613
Re-ranging in engineering units, such as GPM, delivers easy configuration changes
The ability to make on-line zero calibration adjustments without removing pressure simplifies maintenance and calibrations
Asia Pacific +65 299 6051
Europe +44 1935 706262
XTC Transmitters - Pressure
Fully interchangeable components (shown on the
next page) result in fewer spare parts and reduced
inventory costs
Built-in common x1/2, x3/2, or x5/2 transfer functions,
totalizer, and process alarms reduce the need for additional loop components
73
DESCRIPTION
XTC transmitter-controllers offer an integral PID controller to deliver process sensing and control capabilities in a
single instrument and eliminate the need for a separate
controller to handle basic PID loops. Thus, using XTCs in
a control application reduces the number of necessary devices, while minimizing wiring costs via a direct connection from the transmitter to the final control element.
XTC Transmitters - Pressure
Additional proven features include the silicon-based dual
element capacitive pressure MycroSENSOR and the hermetically sealed pressure capsule, which combine to deliver high performance with minimal maintenance.
XTC models include differential gauge, absolute, and
flanged level differential pressure transmitters, which can
all be remotely re-ranged, calibrated, and configured via a
number of HARTTM devices. These include control systems, panelboard instruments, and universal handhelds.
XTC accessories include the Moore XTC communicator,
a handheld configuration terminal, PC-based configuration software, and remote diaphragm seals.
Unique Features of the XTC
H
74
Moore Process Automation Solutions
www.moore-solutions.com
MODELS
Model 340D Differential Pressure
Transmitter-Controller
Spans from 0.2" H 2O to 450 PSID (0.05 to 3100
KPA)
Standard Hastelloy-C diaphragms and 316SS wetted parts (Ranges D & F)
1/4" NPTF or 1/2" NPTF process connection
Suitable for DP, level, and flow applications
XTC Transmitters - Pressure
Model 340A/G Absolute or Gauge Pressure
Transmitter-Controller
10" H2O Abs to 450 PSIA (2.5 to 3100 KPA abs)
10" H2O to 5500 PSIG (2.5 to 37920 KPA)
Standard Hastelloy-C diaphragms and 316SS
wetted parts
1/2" NPTF process connection
Suitable for pressure applications
Model 340F Flanged Level
Transmitter-Controller
10" H2O to 450 PSI (2.5 to 3100 KPA)
Standard 316SS diaphragms and wetted parts
Standard ANSI and DIN flanges
Suitable for level and flanged pressure applications
Model 340 Transmitter-Controller with
Sterling Output
0.035% of Reading Accuracy
Available in DP, GP, and flanged and level configurations
Suitable for HTG and other critical applications
Americas +1 215 646 7400 ext. 6613
Asia Pacific +65 299 6051
Europe +44 1935 706262
75
PROCESS CONNECTIONS
Model 340 Transmitter-Controller with
Tantalum Diaphragms
Available in DP, GP, and AP configurations
XTC Transmitters - Pressure
Suitable for harsh process fluids
Model 340 Transmitter-Controller with
Remote Diaphragm Seals
Available in various materials and process connections including threaded, flanged, weld-in, and
sanitary
Model 340D Differential Transmitter-Controller
with Integral Orifice Assemblies
Six integral orifice sizes
316 SS construction
1/2" NPTF process connection
“Wet” calibrations available
Suitable for low-flow applications
Model 340D Differential Transmitter-Controller
with Integral 3-Valve Manifold
Factory mounted
316SS or CS construction
76
Moore Process Automation Solutions
www.moore-solutions.com
SPECIFICATIONS
PERFORMANCE SPECIFICATIONS
Reference conditions: Zero-based, positive spans, ambient temperature 23ºC, D/A trim values equal to span end
points, Silicone fill, standard diaphragms, 1 second damping.
Digital Output
Range D,F,G:
± 0.075% of Reading or 0.015% of URL,
whichever is greater
Sterling Units:
± 0.035 % of Reading or 0.006% of URL,
whichever is greater
Ambient Temperature Effect
Models 340A, 340G, 340D
Ranges A-B:
±(0.175% URL + 0.075% span) per 28oC
(50oF)
Ranges D-G:
±(0.075% URL + 0.075% span) per 28oC
(50oF)
Model 340F
Ranges D-F2:
±(0.075% URL + 0.075% span + 1.5" H2O)
per 28º C (50ºF)
Humidity
0-100% relative humidity, non-condensing
Vibration Effect
Less than ±0.05% of maximum span per G for 0 to
60 Hz in any axis up to 2 Gs max.
Power Supply Effect
Less than 0.005% of output span per volt
EMI/RFI Susceptibility
Less than 0.25% of max. span at 30 V/m,
30 MHz - 1 GHz
ESD Susceptibility
IEC severity level 4, 15 kV
Static Pressure Effect (340D)
Range Span Error Correctable To:4
B 0.2% per 100psi
D 0.2% per 1000psi
F 0.2% per 1000psi
NOTES:
(1)
Accuracy includes the effects of linearity, hysteresis and repeatability.
(2) Specifications for 3" & 4" flange size only. For smaller flange
sizes, consult Moore.
(3) Limit to 85oC (185oF) in vacuum service.
(4) Zero effect eliminated at operating pressure.
XTC Transmitters - Pressure
Accuracy1,2
Analog Output
Range A:
±0.2% of calibrated span for spans from 1:1 to
2:1 of URL
±(0.174 + 0.013[URL/Span]) % of calibrated
span for spans from 2:1 to 25:1 of URL
Range B:
± 0.1% of calibrated span for spans from 1:1
to 2.5:1 of URL
± (0.043 + 0.0228 [URL/span]) % of calibrated span for spans from 2.5:1 to 20:1 of
URL
Range D,F,G:
±0.1% of calibrated span for spans from 1:1 to
10:1 of URL
±(0.028 + 0.0072 [URL/span]) % calibrated
span for spans from 10:1 to 45:1 of URL
Stability
Zero Stability:
Range A: ±0.1% of URL for 6 months
Ranges B-G: ±0.1% of URL for 12 months
Span Stability: No Measurable Span Drift
Temperature Limits
Sensor Assembly3:
Silicon: -40 to 125ºC (-40 to 257ºF)
Inert Fill: 0 to 85ºC (32 to 185ºF)
Paratherm: -20 to 125ºC (-4 to 257ºF)
Electronics: -40 to 85ºC (-40 to 185ºF)
Americas +1 215 646 7400 ext. 6613
Asia Pacific +65 299 6051
Europe +44 1935 706262
77
FUNCTIONAL SPECIFICATIONS
Range and Sensor Limits
Model 340A, 340D, 340F, 340G
XTC Transmitters - Pressure
Range
Min.
Span
340A
340D
LRL/URL
340F
340G
A
0.20" (.05KPA)
NA
-2/5" (5/1.25KPA)
NA
NA
B
0.75" (0.185KPA)
NA
-15/15" (-3.7/3.7KPA)
NA
NA
D
10" (2.5KPA)
0/450" (0/112.5KPAabs)
-450/450" (-112.5/112.5KPA)
-450/450" (-112.5/112.5KPA)
-407/450" (-101/112.5KPA)
F
12.6psi (87KPA)
0/450psia (0/3045KPAabs)
-150/450psi (-689/3100KPA)
-150/450psi (-689/3100KPA)
-14.7/450psig (-101/3100KPA)
G
300psi (2068KPA)
NA
NA
NA
0/5500psig (0/37920KPA)
Zero Elevation and Suppression
The range may be set anywhere between the LRL
and URL of the transmitter, as long as the
calibrated span does not exceed the minimum
allowable span (see Range table). Zero and
span in the XTC are non-interactive.
1600
Electronic Damping (Digital Filter)
Adjustable between 0 and 30 seconds
Transmitter Outputs
Each transmitter has:
LOOP
RESISTANCE
(OHMS)
1. Analog, Two-Wire 4-20mA
2. Digital, HART Communications
3. Optional Transient Suppressor
700
OPERATING
REGION
250
0
10
15
Power Supply Requirements
Minimum Terminal to Terminal Compliance
Voltage: +10 Vdc
Maximum Terminal to Terminal Voltage: +42 Vdc
Maximum Load: RL = 50*(Supply Voltage)
- 500 Ohms1
24
42
POWER SUPPLY (Vdc)
Maximum Working Pressure2
Range
340A
340D
340G
340F
A
NA
+/-60 psi 3 (+/-413KPA)
NA
NA
B
NA
+/-100 psi3 (+/-689KPA)
NA
NA
D
250psi (1.72MPA)
+/-4000 psi (+/-27.6MPA)
250 psi (1.72MPA)
Per Flange
F
1500psi (10.3MPA) +/-4000 psi (+/-27.6MPA)
1500 psi (10.3MPA)
Per Flange
G
NA
9,000 psi(SS only 62.0MPA)
NA
NA
NOTES:
(1) To ensure digital communications, HART requires the loop
resistance to remain between 250 and 1100 Ohms. HART
also imposes the following requirements on the loop power
supply:
Ripple: 0.2 Vp-p, 47-125 Hz
Noise: 0.6 mV RMS maximum
Impedance: 10 Ohms maximum
78
(2) The Maximum Working Pressure (MWP) is defined as the
maximum pressure which can be applied to the cell without
damage, static or otherwise.
(3) 340D Range A and Range B sensors have a body rating of
+/- 4000 psi; however, no over pressure protection is employed in these units thereby limiting the MWP to +/- 100
psi.
Moore Process Automation Solutions
www.moore-solutions.com
Flange Rating
Standard Class
ANSI
ANSI
DIN
DIN
Carbon Steel Rating Stainless Steel Rating
150#
300#
PN 10/16
PN 25/40
285 psi 1
740 psi1
16 bar2
40 bar2
275 psi1
720 psi1
16 bar2
40 bar2
Local Indication
Optional 4 1/2 Digit SmartDisplay
MECHANICAL SPECIFICATIONS
Dimensions
See Installation Drawings (Pages 97-99)
Weight3
340A/G4 4 lbs
340D 7 lbs
340F 20 lbs
NOTES:
Electronics Housing
Epoxy Powder Coated, Low Copper Cast
Aluminum
316 SS (optional)
NEMA 4X/6P (IP66/68)
(2) 1/2" -14 NPTF Electrical Conduit
Entrances (M20 x 1.5 optional)
(1)
At 100ºF (38ºC), the rating decreases with increasing
temperature.
(2)
At 120ºC, the rating decreases with increasing temperature.
(3) Weights approximate.
(4) 340A/G with tantalum diaphragm: 7 lbs.
Process Wetted Parts
Various Materials Available
NACE MR0175 compliant with options as noted in
the model number breakdown.
Americas +1 215 646 7400 ext. 6613
Hazardous Area Classification/Approvals6
Approved
ABS Type approved
FM/CSA Approval:
Intrinsically Safe:
Class I, Div. 1, Groups A, B, C, & D
Class II, Div. 1, Groups E, F, & G
Class III, Div. 1
Explosion Proof:
Class I, Div. 1, Groups B, C, & D
Class II, Div. 1, Groups E, F, & G
Class III, Div. 1
Non-Incendive:
Class I, Div. 2, Groups A, B, C, & D
CENELEC Approval:
Intrinsically Safe: EEx ia IIC T6, T5, T4
Explosion Proof: EEx d [ia] ia, IIC T47
BASEEFA Approval:
Non-Incendive: Exn IIC T6
SAA Approval:
Intrinsically Safe: Ex ia IIC T6
Explosion Proof: Ex d IIB T6
Non-Incendive: Ex n DIP IIC T6
XTC Transmitters - Pressure
Surge Protection
(with optional Transient Suppressor)
Maximum clamping voltage (either loop terminal
to enclosure)
DC: 68V
100 kV per microsecond AC surge: 70V peak
1000 kV per microsecond AC surge: 120V peak
Transient surge current
Up to 5000 amp for 20 microseconds, repeated
strikes
Turn-On Time
The transmitter will begin operating within 5
seconds after power is applied. The transmitter will perform within specifications
within 60 seconds after power is applied.
Process Connections
Model 340A/G5
(1) 1/2" NPTF, no vent/drain (External block and
bleed may be purchased separately)
Model 340D
(2) 1/4" NPTF with vent/drains
(1/2" NPTF with optional process adapters)
Model 340F
High Pressure Side: Per flange size and rating
selected
Low Pressure Side: 1/4" NPTF with vent/drain
(1/2" NPTF with process adapter provided)
(5) 340A/G Transmitters with tantalum diaphragms are
differential style units. Process connections are similar to
340D. See drawings.
(6) Consult Moore for information on additional approvals.
(7) Consult Moore for information on special power
requirements for EExd models.
Asia Pacific +65 299 6051
Europe +44 1935 706262
79
MODEL NUMBER
XTC Transmitters - Pressure
Absolute Pressure
340A Absolute Pressure Transmitter-Controller
Input Range: Span Limits, Min/Max
D 10/450" H2O abs (2.5/112.5 KPA abs)
F 12.6/450 psia (87/3100 KPA abs)
Output
B 4-20 mAdc with HART Protocol 1
C 4-20 mAdc with HART Protocol & Integral Transient Suppressor
D Direct Connection to Model 348 Field Mounted Controller or Spare Capsule
Process Diaphragm
H Hastelloy C-2761,3
S 316L SS
B Hastelloy C-276 with 1 Remote Seal (Specify AA for Body Parts)
Body Parts
Wetted
Process Connection
AA 316SS
1/2" NPT1
BA Hastelloy-C276 1/2" NPT
Fill Fluid
B Silicone DC2001
C Inert
D Paratherm
Output Indicator
5 4-1/2 Digit Digital SmartDisplay
N Not Required 5
Standard Options
X Oxygen Cleaned
Y Special Features4
N Not Required5
Mounting Bracket
1 2" Pipe Mount Bracket with SS Hardware
2 Universal Bracket
3 2" Pipe Mount 316SS Bracket
N Not Required 5
Housing
1 Aluminum 1/2" - 14 NPT1
2 Aluminum M20 x 1.56
3 316 SS 1/2" - 14 NPT
4 316 SS M20 x 1.5
N Not Required5
Hazardous Area Classification
2 CSA/CRN
3 FM/CSA All1
M CENELEC EEx d [ia] ia14
R SAA All & ABS Type Approved14
L CENELEC EExia & BASEEFA Ex N
N Non-Approved 5
W FM/CSA All & ABS Type Approved
340A F
B
H AA B
5
N N 1
3
Sample Model Number
See notes on page 95.
80
Moore Process Automation Solutions
www.moore-solutions.com
Differential Pressure
340D
D B H AA B
5
N
1
1
3
XTC Transmitters - Pressure
340D Differential Pressure Transmitter-Controller
Input Range: Span Limits, Min/Max
A 0.2/5 "H2O (0.05/1.25 KPA) 10 (Remote seals not available with this range.)
B 0.75/15 "H 2O (0.185/3.7 KPA)2 (Matched remote seals only with this range.)
D 10/450 "H 2O (2.5/112.5 KPA)2
F 12.6/450 psi (87/3100 KPA)2
Output
B 4-20 mAdc with HART Protocol 1,2
C 4-20 mAdc with HART Protocol & Integral Transient Suppressor
D Direct Connection to Model 348 Field Mounted Controller or Spare Capsule
Process Diaphragm
H Hastelloy C-2762,3,8,11
S 316L SS2,7
A Hastelloy C-276 with 2 Remote Seals9,11
B Hastelloy C-276 with 1 Remote Seal on high side9,12
C Hastelloy C-276 with 1 Remote Seal on low side9,12
Body Parts
Wetted
Vent/Drain
Process Conn.
AA
316SS
End
1/2 NPT1,2
AB
316SS
Side (top)
1/2 NPT
AC
316SS
Side (bottom)
1/2 NPT
AD
316SS
Side (dual)
1/2 NPT
AE
316SS
End
1/4 NPT
AF
316SS
Side (top)
1/4 NPT
AG
316SS
Side (bottom)
1/4 NPT
AH
316SS
Side (dual)
1/4 NPT
BA
Hastelloy C-276 End
1/2 NPT
BB
Hastelloy C-276 Side (top)
1/2 NPT
BC
Hastelloy C-276 Side (bottom)
1/2 NPT
BD
Hastelloy C-276 Side (dual)
1/2 NPT
BE
Hastelloy C-276 End
1/4 NPT
BF
Hastelloy C-276 Side (top)
1/4 NPT
BG
Hastelloy C-276 Side (bottom)
1/4 NPT
BH
Hastelloy C-276 Side (dual)
1/4 NPT
RR
Remote Seals
Fill Fluid
B Silicone DC2001,2
C Inert11
D Paratherm 11
Output Indicator
5 4-1/2 Digit Digital SmartDisplay 2
N Not Required5
Standard Options
D B7M Bolts3
E B8M Bolts17
X Oxygen Cleaned
Y Special Features4
N Not Required2,5
Mounting Bracket
1 2" Pipe Mount Bracket with SS Hardware2
2 Universal Bracket
3 2" Pipe Mount 316SS Bracket
N Not Required5
Housing
1 Aluminum 1/2" - 14 NPT1,2
2 Aluminum M20 x 1.5 6
3 316 SS 1/2" - 14 NPT
4 316 SS M20 x 1.5
N Not Required 5
Hazardous Area Classification
2 CSA/CRN
3 FM/CSA All1,2
M CENELEC EEx d [ia] ia14
R SAA All & ABS Type Approved
L CENELEC EExia & BASEEFA
N Non-Approved
W FM/CSA All & ABS Type Approved
Sample Model Number
See notes on page 85.
Americas +1 215 646 7400 ext. 6613
Asia Pacific +65 299 6051
Europe +44 1935 706262
81
XTC Transmitters - Pressure
Flanged Level
340F Flanged Level Transmitter-Controller
Input Range: Span Limits, Min./Max.
D 10/450 "H 2O (2.5/112.5 KPA)2
F 12.6/450 psi (87/3100 KPA)2
Output
B 4-20 mAdc with HART Protocol 1,2
C 4-20 mAdc with HART Protocol & Integral Transient Suppressor
Body Parts
High Side Dia/Wetted Low Side Dia/Wetted
Extension Length
A0 316SS
Hastelloy C-276/316SS Flush Mount1,2
A2 316SS
Hastelloy C-276/316SS 2"15
A4 316SS
Hastelloy C-276/316SS 4"15
A6 316SS
Hastelloy C-276/316SS 6"15
B0 Hastelloy C-276
Hastelloy C-276/316SS Flush Mount
B2 Hastelloy C-276
Hastelloy C-276/316SS 2"15
B4 Hastelloy C-276
Hastelloy C-276/316SS 4"15
B6 Hastelloy C-276
Hastelloy C-276/316SS 6"15
C0 Monel
Hastelloy C-276/316SS Flush Mount
C2 Monel
Hastelloy C-276/316SS 2"15
C4 Monel
Hastelloy C-276/316SS 4"15
C6 Monel
Hastelloy C-276/316SS 6"15
D0 Tantalum
Hastelloy C-276/316SS Flush Mount
G0 316SS
Remote Seal
Flush Mount
G2 316SS
Remote Seal
2"15
G4 316SS
Remote Seal
4"15
G6 316SS
Remote Seal
6"15
Mounting Flange
Size
Rating
Material
Size
Rating
Material
A 2"
150#
CS
J 3"
150#
SS2
B 2"
300#
CS
K 3"
300#
SS
C 3"
150#
CS 2
L 4"
150#
SS
D 3"
300#
CS
M 4"
300#
SS
E 4"
150#
CS
N 50mm
10/16 Bar
CS
F 4"
300#
CS
P 50mm
25/40 Bar
CS
G 2"
150#
SS
Q 80mm
10/16 Bar
CS
H 2"
300#
SS
R 80mm
25/40 Bar
CS
Fill Fluid
High Side
Low Side
B Silicone DC200
Silicone DC2001,2
C Fluorolube
Inert
D NEOBEE
Paratherm
E Silicone DC550
Silicone DC200
F Silicone DC704
Silicone DC200
G Syltherm 800
Silicone DC200
Output Indicator
5 4-1/2 Digit Digital Smart Display2
N Not Required
Standard Options
D B7M Bolts3
E B8M Bolts17
X Oxygen Cleaned
Y Special Features4
N Not Required2
Mounting Bracket
N Not Required
Housing
1 Aluminum 1/2" - 14 NPT1,2
2 Aluminum M20 x 1.5 6
3 316 SS 1/2" - 14 NPT
4 316 SS M20-1.5
Hazardous Area Classification
2 CSA/CRN
3 FM/CSA All1,2
M CENELEC EEx d [ia] ia14
R SAA All & ABS Type Approved
L CENELEC EExia & BASEEFA Type N
N Non-Approved
W FM/CSA All & ABS Type Approved
340FD B A0 C B
See notes on page 85.
82
H0
H2
H4
H6
J0
J2
J4
J6
K0
N0
N2
N4
N6
Q0
Q2
Q4
Q6
R0
5
N N 1
High Side
Dia/Wetted
Hastelloy C-276
Hastelloy C-276
Hastelloy C-276
Hastelloy C-276
Monel
Monel
Monel
Monel
Tantalum
Hastelloy C-276
Hastelloy C-276
Hastelloy C-276
Hastelloy C-276
Monel
Monel
Monel
Monel
Tantalum
S
T
U
V
W
X
Y
Z
Size
100mm
100mm
50mm
50mm
80mm
80mm
100mm
100mm
3 Sample Model Number
Moore Process Automation Solutions
www.moore-solutions.com
Low Side
Dia/Wetted
Remote Seal
Remote Seal
Remote Seal
Remote Seal
Remote Seal
Remote Seal
Remote Seal
Remote Seal
Remote Seal
Hastelloy C-276
Hastelloy C-276
Hastelloy C-276
Hastelloy C-276
Hastelloy C-276
Hastelloy C-276
Hastelloy C-276
Hastelloy C-276
Hastelloy C-276
Extension
Length
Flush Mount
2"15
4"15
6"15
Flush Mount
2"15
4"15
6"15
Flush Mount
Flush Mount
2"15
4"15
6"15
Flush Mount
2"15
4"15
6"15
Flush Mount
Rating
Material
10/16 Bar CS
25/40 Bar CS
10/16 Bar S S
25/40 Bar S S
10/16 Bar S S
25/40 Bar S S
10/16 Bar S S
25/40 Bar S S
Gauge Pressure
340G F
B H AA B
5
N
1
1
3
XTC Transmitters - Pressure
340G Gauge Pressure Transmitter-Controller
Input Range: Span Limits, Min/Max
D 10/450 "H 2O (2.5/112.5 KPA)2
F 12.6/450 psig (87/3100 KPA) 2
G 300/5500 psig 2008/37920 KPA) 2
Output
B 4-20 mAdc with HART Protocol 1,2
C 4-20 mAdc with HART Protocol & Integral Transient Suppressor
D Direct Connection to Model 348 Field Mounted Controller or Spare Capsule
Process Diaphragm
H Hastelloy C-2761,2,3
S 316L SS
B Hastelloy C-276 with 1 Remote Seal (Specify AA for Body Parts)
Body Parts
Wetted
Process Connection
AA 316SS
1/2" NPT1,2
BA Hastelloy C-276
1/2" NPT
Fill Fluid
B Silicone DC2001,2
C Inert
D Paratherm
Output Indicator
5 4-1/2 Digit Digital SmartDisplay2
N Not Required 5
Standard Options
X Oxygen Cleaned
Y Special Features4
N Not Required 5
Mounting Bracket
1 2" Pipe Mount Bracket with SS Hardware2
2 Universal Bracket
3 2" Pipe Mount 316SS Bracket
N Not Required 5
Housing
1 Aluminum 1/2" - 14 NPT1,2
2 Aluminum M20 x 1.5 6
3 316 SS 1/2" - 14 NPT
4 316 SS M20 x 1.5
N Not Required 5
Hazardous Area Classification
2 CSA/CRN
3 FM/CSA All1,2
M CENELEC EEx d [ia] ia14
R SAA All & ABS Type Approved
L CENELEC EExia & BASEEFA
N Non-Approved 5
W FM/CSA All & ABS Type Approved
Sample Model Number
See notes on page 85.
Americas +1 215 646 7400 ext. 6613
Asia Pacific +65 299 6051
Europe +44 1935 706262
83
XTC Transmitters - Pressure
Sterling High Performance
340 Sterling Performance Transmitter-Controller
Type and Input Range: Span Limits, Min/Max
DD
Differential
10/450 "H 2O (2.5/112.5 KPA)
FD
Flanged Level 10/450 "H 2O (2.5/112.5 KPA)
GF
Gauge
12.6/450 psi (87/3100 KPA)
Output
E 4-20 mAdc High Performance Output with HART Protocol
Process Diaphragm
H Hastelloy C-276
Body Parts
Wetted
Process Conn.
Type
DA
316SS
1/2" NPT
D
DB
316SS
1/4" NPT
D
GA
316SS
1/2" NPT
G
FA
CS
2", 150#, CS
F
FB
CS
2", 300#, CS
F
FC
CS
3", 150#, CS
F
FD
CS
3", 300#, CS
F
FE
CS
4", 150#, CS
F
FF
CS
4", 300#, CS
F
FG
SS
2", 150#, SS
F
FH
SS
2", 300#, SS
F
FI
SS
3", 150#, SS
F
FJ
SS
3", 300#, SS
F
FK
SS
4", 150#, SS
F
FL
SS
4", 300#, SS
F
Fill Fluid
B Silicone DC2001
Output Indicator
5 4-1/2 Digit Digital Smart Display
N Not Required
Standard Options
D B7M Bolts3
E B8M Bolts17
X Oxygen Cleaned
Y Special Features4
N Not Required
Mounting Bracket
1 2" Pipe Mount Bracket with SS Hardware
2 UniversalBracket
3 2" Pipe Mount 316SS Bracket
N Not Required
Housing
1 Aluminum 1/2" - 14 NPT1
2 Aluminum M20 x 1.5 6
3 316 SS 1/2" - 14 NPT
4 316 SS M20 x 1.5
Hazardous Area Classification
2 CSA/CRN
3 FM/CSA All10
M CENELEC EEx d [ia] ia14
R SAA All & ABS Type Approved
L CENELEC EExia & BASEEFA Type N
N Non-Approved
W FM/CSA All & ABS Type Approved
340 DD E H DA B
5
N N
1
3
Sample Model Number
See notes on page 85.
84
Moore Process Automation Solutions
www.moore-solutions.com
Tantalum Diaphragms
340 DB B T TE B N N N
1
3
Sample Model Number
NOTES:
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
XTC Transmitters - Pressure
340 Absolute, Gauge & Differential Pressure Transmitter-Controllers with Tantalum Diaphragms
Type and Input Range: Span Limits, Min/Max
Type
Span Limits, Min/Max.
DD
Differential
10/450 "H2O (2.5/112.5 KPA)
GD
Gauge
10/450 "H2O (2.5/112.5 KPA)
GF
Gauge
12.6/450 psi (87/3100 KPA)
AD
Absolute
10/450 "H2O Abs (2.5/112.5 KPA)
AF
Absolute
12.6/450 psia (87/3100 KPA)
Output
B 4-20 mAdc with HART Protocol 1
C 4-20 mAdc with HART Protocol & Integral Transient Suppressor
D Direct Connection to Model 348 Field Mounted Controller or Spare Capsule
Diaphragm
T Tantalum
Body Parts
Hi Side
Lo Side
Use with
TB
Hastelloy-C
316SS
A, G
TC
Hastelloy-C
Hastelloy-C D
TD
Monel
316SS
A, G1
TE
Monel
Monel
D1
Fill Fluid
B Silicone DC200
C Inert13
Output Indicator
5 4-1/2 Digit Digital SmartDisplay
N Not Required
Standard Options
D B7M Bolts3
E B8M Bolts17
X Oxygen Cleaned
Y Special Features4
N Not Required5
Mounting Bracket
1 2" Pipe Mount Bracket with SS Hardware
2 Universal Bracket
3 2" Pipe Mount 316SS Bracket
N Not Required 5
Housing
1 Aluminum 1/2" - 14 NPT1
2 Aluminum M20 x 1.56
3 316 SS 1/2" - 14 NPT
4 316 SS M20 x 1.5
N Not Required 5
Hazardous Area Classification
2 CSA/CRN
3 FM/CSA All1
M CENELEC EEx d [ia] ia14
R SAA All & ABS Type Approved
L CENELEC EExia & BASEEFA
N Non-Approved
W FM/CSA All & ABS Type Approved
Standard for all ranges.
Stock model selection.
NACE MR0175 compliance requires this option.
Please describe the modification or provide a quotation
reference number.
Required selection for OUTPUT option “D”, direct connection
to the Moore 348.
Not available with FM/CSA approvals.
Standard on Input Ranges A & B.
Standard on Input Ranges D & F.
Must specify Body Parts code “RR”.
Americas +1 215 646 7400 ext. 6613
(10)
(11)
(12)
(13)
(14)
Must select Body Parts “AA”.
Not available with Input Range “A”.
Not available with Input Range “A” or “B”.
Available with Body Parts “TD” or “TE” only.
CENELEC EExd & SAA units are only available with OUTPUT
code “B”.
(15) 2" flanges with an extension or not available.
(16) 3" and 4" flanges with an extension will fit into Schedule 80
and larger i.d. pipes.
(17) B8M (316SS) bolting may have a reduced pressure rating.
Consult Moore for information.
Asia Pacific +65 299 6051
Europe +44 1935 706262
85
MODEL DIFFERENCES &
MODIFICATIONS
If no range is selected, the instrument will be calibrated as
follows:
Range Code
A
B
D
F
G
Default Calibration
Common modifications can be specified by selecting a Y
in the Special Features category and describing the modification. Always consult your salesperson before ordering a modification.
-0.5 to 0.5 "H2O
0 to 10 "H2O
0 to 100 "H2O (or "H2O abs)
0 to 100 PSI (or PSIA)
0 to 1000 PSIG
XTC Transmitters - Pressure
TRANSMITTER COMPONENTS
86
Moore Process Automation Solutions
www.moore-solutions.com
INSTALLATION DRAWINGS
XTC Transmitters - Pressure
Models 340A and Model 340G
Americas +1 215 646 7400 ext. 6613
Asia Pacific +65 299 6051
Europe +44 1935 706262
87
XTC Transmitters - Pressure
Model 340D and Models 340A and 340G with Tantalum Diaphragms
88
Moore Process Automation Solutions
www.moore-solutions.com
Flange Dimensions
SIZE
DIM
“D”
2"-150#
2"-300#
3"-150#
3"-300#
4"-150#
4"-300#
DIM
“T”
DIM
“RF”
BOLT BOLT
DIA. NO.
6.00
6.50
7.50
8.25
9.00
10.00
(152.40)
(165.10)
(190.50)
(209.55)
(228.60)
(254.00)
4.75 (120.65)
5.00 (127.00)
6.00 (152.40)
6.625 (168.28)
7.50 (190.50)
7.875 (200.03)
0.75
0.88
0.94
1.13
0.94
1.25
(19.05)
(22.23)
(23.81)
(28.58)
(23.81)
(31.75)
5/8
5/8
0.06 (1.58) 5/8
3/4
5/8
3/4
4
8
4
8
8
8
6.50
6.50
7.87
7.87
8.66
9.25
(165.00)
(165.00)
(200.00)
(200.00)
(220.00)
(235.00)
4.92
4.92
6.30
6.30
7.09
7.48
0.71
0.79
0.79
0.94
0.79
0.94
(18.00)
(20.00)
(20.00)
(24.00)
(20.00)
(24.00)
M16
M16
0.12 (3.00) M16
M16
M16
M20
4
4
8
8
8
8
(125.00)
(125.00)
(160.00)
(160.00)
(180.00)
(190.00)
FLANGE
PER
ANSI B16.5
DIN 2526
TYPE C
EXTENSION LENGTH
(Not available on 2" or 50mm flanges.)
DIM
“L”
0
(0.00)
2.00
(50.80)
4.00
(101.60)
6.00
(152.40)
Model 340F Flange Mounted Transmitter
Americas +1 215 646 7400 ext. 6613
Asia Pacific +65 299 6051
Europe +44 1935 706262
DIM
“ED”
1.95
1.95
2.81
2.81
3.70
3.70
(49.53
(49.53)
(71.37)
(71.37)
(93.98)
(93.98)
Consult
Moore
XTC Transmitters - Pressure
50MM-10/16 BAR
50MM-25/40 BAR
80MM-10/16 BAR
80MM-25/40 BAR
100MM-10/16 BAR
100MM-25/40 BAR
DIM
“BC”
89