48 Volt Module With DuraBlue - Datasheet

DATASHEET
NEW 48V MODULE
FEATURES AND BENEFITS*
TYPICAL APPLICATIONS
Up to 1,000,000 duty cycles or
10 year DC life
48V DC working voltage
Active cell balancing
Temperature output
Overvoltage outputs available
High power density
Extreme Vibration Environment
Compatible
Hybrid vehicles
Rail
Heavy industrial equipment
UPS systems
PRODUCT SPECIFICATIONS
ELECTRICAL
Rated Capacitance
BMOD0165 P048 C01
165 F
1
Minimum Capacitance, initial1
165 F
Maximum Capacitance, initial
198 F
Maximum ESR DC, initial
1
6.0 mΩ
1
Test Current for Capacitance and ESR DC
100 A
1
Rated Voltage
Stored Energy
48 V
53 Wh
4
Absolute Maximum Voltage
51 V
2
Absolute Maximum Current
1,900 A
Maximum Series Voltage
750 V
Capacitance of Individual Cells8
3,000 F
Stored Energy, Individual Cell8
3.0 Wh
Number of Cells
18
TEMPERATURE
Operating Temperature (Cell Case Temperature)
Minimum
-40oC
Maximum
65oC
Storage Temperature (Stored Uncharged)
Minimum
-40oC
Maximum
70oC
*Results may vary. Additional terms and conditions, including the limited warranty, apply at the time of purchase.
See the warranty details for applicable operating and use requirements.
Page 1
Document number: 3000685.3
maxwell.com
DATASHEET
NEW 48V MODULE
PRODUCT SPECIFICATIONS (Cont’d)
PHYSICAL
BMOD0165 P048 C01
Mass, typical
14.2 kg
Power Terminals
M8/M10
Recommended Torque - Terminal
20 Nm (M8)/30 Nm (M10)
Vibration Specification
ISO 16750-3, Table 12
Shock Specification
IEC 60068-2-27, -29
Environmental Protection
IP65
Cooling
Natural Convection
MONITORING / CELL VOLTAGE MANAGEMENT
Internal Temperature Sensor3
NTC Thermistor (10 kΩ)
Temperature Interface
Analog
Cell Voltage Monitoring3
Overvoltage Alarm (open collector)
Connector (Mating)
Deutsch DTM04-4P, Amphenol ATM04-4P
Cell Management System
CMS 2.0
SAFETY
Short Circuit Current, typical
(Current possible with short circuit from rated voltage. Do not use as an operating
current.)
8,100 A
Certifications
RoHS, UL810a (50 volts)
High-Pot Test9
2,500 VDC
Page 2
Document number: 3000685.3
maxwell.com
DATASHEET
NEW 48V MODULE
TYPICAL CHARACTERISTICS
THERMAL CHARACTERISTICS
BMOD0165 P048 C01
Thermal Resistance (Rca, All Cell Cases to Ambient), typical
5
0.40oC/W
Thermal Capacitance (Cth), typical
13,000 J/oC
Maximum Continuous Current (∆T = 15 °C)5
(BOL, Beginning of Life)
79 A, RMS
Maximum Continuous Current (∆T = 40 °C)5
(BOL, Beginning of Life)
130 A, RMS
LIFE
DC Life at High Temperature1
(held continuously at Rated Voltage and Maximum Operating Temperature)
1,500 hours
Capacitance Change
20%
ESR Change
100%
(% decrease from minimum initial value)
(% increase from maximum initial value)
Projected DC Life at 25°C1
10 years
(held continuously at Rated Voltage)
Capacitance Change
20%
ESR Change
100%
(% decrease from minimum initial value)
(% increase from maximum initial value)
Projected Cycle Life at 25°C1,6,7
1,000,000 cycles
Capacitance Change
20%
ESR Change
100%
Test Current
100 A
(% decrease from minimum initial value)
(% increase from maximum initial value)
Shelf Life
4 years
(Stored uncharged at 25°C)
Page 3
Document number: 3000685.3
maxwell.com
DATASHEET
NEW 48V MODULE
ESR AND CAPACITANCE VS TEMPERATURE
180%
Capacitance
DC ESR
Percentage change from value at 25°C
170%
160%
150%
140%
130%
120%
110%
100%
90%
80%
-60
-40
-20
0
20
40
60
80
Temperature (°C)
NOTES
1. Capacitance and ESRDC measured at 25°C using
specified test current per waveform below.
2. Absolute maximum voltage, non-repeated. Not to
exceed 1 second.
3. Please refer to module user manual for additional
technical details.
½ CV2
4. Estored = 3,600
5. ∆T=IRMS2 x ESR x Rca
6. Cycle using specified test current per waveform
below.
7. Cycle life varies depending upon application-specific
characteristics. Actual results will vary.
Page 4
Document number: 3000685.3
maxwell.com
8. Per United Nations material classification UN3499, all
Maxwell ultracapacitors have less than 10 Wh capacity
to meet the requirements of Special Provisions
361. Both individual ultracapacitors and modules
composed of those ultracapacitors shipped by
Maxwell can be transported without being treated
as dangerous goods (hazardous materials) under
transportation regulations.
9. Duration = 60 seconds. Not intended as an operating
parameter.
DATASHEET
NEW 48V MODULE
This document has not been finalized or approved for release as a formal datasheet. This document has been provided as a courtesy only and for engineering
assessment purposes and the information within this document should not be relied upon in making decisions regarding this product.
BMOD0165 P048 C01
W
L
H2
Part Description
BMOD0165 P048 C01
L (max)
H1
Dimensions (mm)
W (max)
H1 (max)
418
194
179
H2 (max)
Package Quantity
157
1
Product dimensions are for reference only unless otherwise identified. Product dimensions and specifications may change without notice.
Please contact Maxwell Technologies directly for any technical specifications critical to application. All products featured on this datasheet are covered by the following
U.S. patents and their respective foreign counterparts: 6643119, 7180726, 7295423, 7342770, 7352558, 7384433, 7440258, 7492571, 7508651, 7580243, 7791860, 7816891,
7859826, 7883553, 7935155, 8072734, 8098481, 8279580, and patents pending.
Maxwell Technologies, Inc.
Global Headquarters
3888 Calle Fortunada
San Diego, CA 92123
USA
Tel: +1 (858) 503-3300
Fax: +1 (858) 503-3301
Maxwell Technologies SA
Route de Montena 65
CH-1728 Rossens
Switzerland
Tel: +41 (0)26 411 85 00
Fax: +41 (0)26 411 85 05
Maxwell Technologies, GmbH
Leopoldstrasse 244
80807 Münich
Germany
Tel: +49 (0)89 / 4161403 0
Fax: +49 (0)89 / 4161403 99
Maxwell Technologies
Shanghai Trading Co., Ltd
Unit A2BC, 12th Floor
Huarun Times Square
500 Zhangyang Road, Pudong
Shanghai 200122, P.R. China
Phone: +86 21 3852 4000
Fax: +86 21 3852 4099
MAXWELL TECHNOLOGIES, MAXWELL, MAXWELL CERTIFIED INTEGRATOR, ENABLING ENERGY’S FUTURE, BOOSTCAP, C CELL, D CELL and their respective
designs and/or logos are either trademarks or registered trademarks of Maxwell Technologies, Inc. and may not be copied, imitated or used, in whole or in
part, without the prior written permission from Maxwell Technologies, Inc. All contents copyright © 2015 Maxwell Technologies, Inc. All rights reserved. No
portion of these materials may be reproduced in any form, or by any means, without prior written permission from Maxwell Technologies, Inc.
Page 5
Document number: 3000685.3
maxwell.com
Maxwell Technologies Korea Co., Ltd
Room 1524, D-Cube City
Office Tower, 15F #662
Gyeongin-Ro, Guro-Gu,
Seoul, Korea 152-706
Phone: +82 10 4518 9829