LIEBERT® APM™ 3-PHASE UPS: 15-90KVA/KW, 60HZ, 208-600VAC, SINGLE & DUAL INPUT - SITE PLANNING DATA The UPS must be fed from a solidly grounded wye or delta AC source. Not for use with impedance-grounded systems, corner-grounded or high leg delta systems. For these applications, an isolation transformer must be installed between the AC feed and the UPS. BYPASS DISTRIBUTION CABINET (Optional; see Note 7) * SYSTEM AC INPUT 4 WIRE + GRD MBB BIB (OPTIONAL) 54 POLE SEE NOTE 6 MIB AC OUTPUT 208V 4 WIRE + GND BIB Bypass Isolation Breaker MBB Maintenance Bypass Breaker MIB Maintenance Isolation Breaker * External Overcurrent Protection by others STATIC BYPASS Field-supplied wiring NOTES 1. Install in accordance with national and local electrical codes. 2. Input and bypass must share the same single source. 3. A neutral is required from the system AC input source. A full capacity neutral conductor is recommended. Grounding conductors are recommended. 4. UPS system input and output cables must be run in separate conduits. 5. Control wiring must be run in separate conduits. 6. Optional 54 pole, 225A for 45kVA frame only or optional 54 pole, 400A for 90kVA frame only. UAM01004 7. Transformer available 480V or 600V input. Rev. 0 UPS CABINET BATTERY 1 Notes for Tables 1. 2. 3. 4. 5. 6. 7. Nominal (Nom) current is based on full rated output load at nominal input voltage. Maximum (Max) current (125% of nominal) is short duration for battery recharge conditions. UPS input and bypass cables must be run in separate conduit from output cables. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2. Nominal rectifier AC input current (considered continuous) is based on full rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered non-continuous). Continuous and non-continuous currents are defined in NEC 215. Nominal AC output current (considered continuous) is based on full rated output load. Output breakers are either supplied by the customer or by using the optional Liebert Bypass Distribution Cabinet. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Neutral conductors to be sized for full capacity per NEC 310-15 (b)(4). References are per NEC 2008. Wiring requirements: AC Input: 3-phase, 4-wire, plus ground AC Output: 3-phase, 3- or 4-wire, plus ground Table 1 All wiring is to be in accordance with national and local electric codes. Minimum access clearance is 36" (914mm) front; ventilation clearance is 24" (610mm) above and 12" (305mm) in the rear. Top or bottom cable entry through removable access plates. Punch plate to suit conduit size, then replace. Control wiring and power wiring must be run in separate conduit. Dimensions shown include an internal battery (45kVA frame only). Weights shown do not include an internal battery nor optional cabinets or features. When a Liebert Bypass Distribution Cabinet is not used, the customer must supply the input circuit breaker with a 120VAC shunt trip. The shunt trip drive capability is 8A. 10. 11. 12. 13. 14. Additional Notes • If site configuration includes a backup emergency generator, it is recommended that the engine generator set be properly sized and equipped for a UPS application. Generator options would typically include an isochronous governor (generator frequency regulation) and a UPS-compatible regulator (generator voltage regulation). Consult generator manufacturer for required generator options and sizing. • If site configuration includes an automatic transfer switch, refer to Liebert Power Line titled “Criteria for Application of Automatic Transfer Switches (ATS) With Uninterruptible Power Supply (UPS) Systems,” publication 91K-PLT-48-02. It is also recommended that the transfer switch be equipped with auxiliary contacts to provide a UPS “on generator” signal. Consult transfer switch manufacturer for required transfer switch options and sizing. • If site configuration requires an external isolated maintenance bypass circuit, it should be noted that utility AC input might not be in phase with the UPS AC output. Consult an Emerson sales representative or applications engineer. Site Planning Data - 15-90kVA, 60Hz, 208VAC, Single Input UPS Rating Voltage AC Input Current, A kVA 8. 9. kW Input Output Nom. Max. Battery Rec. Nom. Max. OPD VDC Discharge AC Output Mechanical Data System OCPD (45 and 90 kVA) Dimensions Heat Dis. Cooling Air (customersupplied) OPD WxDxH, in. (mm) 45kVA Frame 90kVA Frame BTU/hr (kWH) CFM (m3/hr) Current, A Nom. Unit Weight, lb. (kg) 15 15 208 208 45 56 70 288 67 42 60 866 (394) 796 (362) 3,759 (1.1) 102 (173) 30 30 208 208 90 112 125 288 135 83 125 942 (428) 872 (396) 7,753 (2.21) 204 (346) 45 45 208 208 134 167 200 288 202 125 200 60 60 208 208 179 223 250 288 269 167 225 75 75 208 208 224 279 350 288 335 208 90 90 208 208 268 334 400 288 404 250 1 2, 3, 5, 8,12 6 4 See Notes for Tables (above): 1, 3, 8,12 1,3,8,12 200A/ with 120VAC/ shunt trip 1018 (463) 948 (431) 11,383 (3.34) 306 (519) NA 1024 (465) 15,130 (4.43) 408 (692) 300 NA 1100 (500) 18,853 (5.52) 510 (865) 350 NA 1176 (535) 22,518 (6.6) 612 (1038) 400A/ with/ 120VAC/ shunt trip 14 14 — — 15 31.8x39.5x78.7 (800x1000x2000) 6 13 2 Table 2 Site Planning Data - 15-90kVA, 60Hz, 480VAC, Single Input UPS Rating Voltage AC Input Current, A kVA kW Input Output Nom. Max Battery Rec. Nom Max. OPD VDC Discharge AC Output Mechanical Data Current, A Nom. Unit Weight, lb. (kg) Cooling Air Dimensions Heat Dis. OPD WxDxH, in. (mm) 45kVA Frame 90kVA Frame BTU/hr (kWH) CFM (m3/hr) 15 15 480 208 19 24 30 288 67 42 60 NA 1728 (785) 14,642 (4.3) 102 (173) 30 30 480 208 39 49 60 288 135 83 125 NA 1804 (820) 16,587 (4.9) 204 (346) 45 45 480 208 58 73 90 288 202 125 1880 (855) 20,217 (5.9) 306 (519) 60 480 208 78 98 125 288 269 167 200 31.8x39.5x78.7 225 (800x1000x2000) NA 60 NA 1956 (889) 23,964 (7.0 408 (692) 75 75 480 208 97 121 150 288 335 208 300 NA 2032 (924) 27,687 (8.1) 510 (865) 90 90 480 208 116 145 175 288 404 250 350 NA 2108 (958) 31,352 (9.2) 612 (1038) 1 2, 3, 5, 8,12 6 4 1, 3, 8,12 1, 3, 8, 12 6 14 14 — — See Notes for Tables (p. 2): Table 3 UPS Rating 13 System OCPD (45 and 90 kVA) (customersupplied) 100A with 120VAC shunt trip 200A with 120VAC shunt trip 15 Site Planning Data - 15-90kVA, 60Hz, 600VAC, Single Input Voltage AC Input Current, A Input Output Nom. Max Battery Max. Rec. Nom OPD VDC Discharge AC Output Mechanical Data System OCPD (45 and 90 kVA) Dimensions Heat Dis. Cooling Air (customerOPD WxDxH, in. (mm) 45kVA Frame 90kVA Frame BTU/hr (kWH) CFM (m3/hr) supplied) Current, A Nom. Unit Weight, lb. (kg) kVA kW 15 15 600 208 16 20 25 288 67 42 60 NA 1743 (792) 12,350 (3.6) 102 (173) 30 30 600 208 31 39 50 288 135 83 125 NA 1819 (827) 16,344 (4.7) 204 (346) 45 45 600 208 47 59 70 288 202 125 200 NA 1895 (861) 19,974 (5.8) 306 (519) 60 60 600 208 62 78 100 288 269 167 225 NA 1971 (896) 23,721 (6.9) 408 (692) 75 75 600 208 78 98 125 288 335 208 300 NA 2047 (930) 27,444 (8.0) 510 (865) 90 90 600 208 93 116 150 288 404 250 350 NA 2123 (965) 31,109 (9.1) 612 (1038) 1 2,3,5,8,12 6 4 1,3,8,12 1,3,8,12 6 14 14 — — See Notes for Tables (p. 2): 31.8x39.5x78.7 (800x1000x2000) 13 3 100A with 120VAC shunt trip 150A with 120VAC shunt trip 15 Table 4 Site Planning Data - 15-90kVA, 60Hz, 208VAC, Dual Input UPS Rating Voltage 208VAC Bypass Input AC Rectifier Input Current, A kVA kW Input Output Battery AC Output Current Rec. Nom. Max OPD Nom Mechanical Data Current, A Rec. Nom Max. OPD VDC Discharge Nom. OPD Dimensions WxDxH, in. (mm) Unit Weight, lb. (kg) 45kVA Frame 90kVA Frame Input CB Cooling Air (customerHeat Dis. 3 BTU/hr (kWH) CFM (m /hr) supplied) 15 15 208 208 45 56 70 42 60 288 67 42 60 866 (394) 796 (362) 3,759 (1.1) 102 (173) 30 30 208 208 90 112 125 84 110 288 135 83 125 942 (428) 872 (396) 7,753 (2.21) 204 (346) 45 45 208 208 134 167 200 126 175 288 202 125 200 60 208 208 179 223 250 168 225 288 269 167 31.8x39.5x78.7 1018 (463) 948 (431) 11,383 (3.34) 225 (800x1000x2000) NA 1024 (465) 15,130 (4.43) 306 (519) 60 75 75 208 208 224 279 350 210 300 288 335 208 300 NA 1100 (500) 18,853 (5.52) 510 (865) 90 90 208 208 268 334 400 252 350 288 404 250 350 NA 1176 (535) 22,518 (6.6) 612 (1038) 1 2,3,5, 8,12 6 — — 4 1,3,8,12 1,3, 8,12 6 14 14 — — See Notes for Tables (p. 2): Table 5 13 408 (692) 200A with 120VAC shunt trip 400A with 120VAC shunt trip 15 Site Planning Data - 15-90kVA, 60Hz, 480VAC, Dual Input UPS Rating Voltage 208VAC Bypass Input AC Input Current, A Input Output Nom. Battery Current Max Rec. OPD Nom 42 AC Output Mechanical Data Current, A Byp. Nom Max. OPD VDC Discharge 90kVA Frame Input CB Heat Dis. Cooling Air (customerBTU/hr (kWH) CFM (m3/hr) supplied) kVA kW 15 15 480 208 19 24 30 30 30 480 208 39 49 60 84 110 288 135 83 125 45 45 480 208 58 73 90 126 175 288 202 125 200 NA 1956 (889) 23,964 (7.0 408 (692) — NA 2032 (924) 27,687 (8.1) 510 (865) — NA 2108 (958) 31,352 (9.2) 612 (1038) — 14 14 — — 15 60 288 67 Nom. Unit Weight, lb. (kg) Dimensions 45kVA OPD WxDxH, in. (mm) Frame 42 60 60 60 480 208 78 98 125 168 225 288 269 167 31.8x39.5x78.7 225 (800x1000x2000) 75 75 480 208 97 121 150 210 300 288 335 208 300 90 90 480 208 116 145 175 252 350 288 404 250 350 1 2,3,5,8,12 6 — — 4 1,3,8,12 1,3,8,12 6 See Notes for Tables (p. 2): 4 1728 (785) 14,642 (4.3) 102 (173) — NA 1804 (820) 16,587 (4.9) 204 (346) — NA 1880 (855) 20,217 (5.9) 306 (519) — NA 13 Table 6 Site Planning Data - 15-90kVA, 60Hz, 600VAC, Dual Input UPS Rating Voltage 208VAC Bypass Input AC Input Current, A Input Output Nom. Battery Current Max Rec. OPD Nom 42 AC Output Mechanical Data Current, A Byp. Nom Max. OPD VDC Discharge Unit Weight, lb. (kg) Dimensions OPD WxDxH, in. (mm) 90kVA Frame NA 1743 (792) 12,350 (3.6) 102 (173) — kVA kW 15 15 600 208 16 20 25 30 30 600 208 31 39 50 84 110 288 135 83 125 NA 1819 (827) 16,344 (4.7) 204 (346) — 45 45 600 208 47 59 70 126 175 288 202 125 200 1895 (861) 19,974 (5.8) 306 (519) — 60 60 600 208 62 78 100 168 225 288 269 167 31.8x39.5x78.7 225 (800x1000x2000) NA NA 1971 (896) 23,721 (6.9) 408 (692) — 75 75 600 208 78 98 125 210 300 288 335 208 300 NA 2047 (930) 27,444 (8.0) 510 (865) — 90 90 600 208 93 116 150 252 350 288 404 250 350 NA 2123 (965) 31,109 (9.1) 612 (1038) — 1 2,3,5,8,12 6 — — 4 1,3,8,12 1,3,8,12 6 14 14 — — 15 See Notes for Tables (p. 2): Table 7 60 288 Nom. Input CB Heat Dis. Cooling Air (customerBTU/hr (kWH) CFM (m3/hr) supplied) 45kVA Frame 67 42 60 13 UPS currents and terminals—Input (for dual-input unit only, 208V operation) Maximum Recommended Lug (T&B) Unit Rating Nom. Input Current Max. Input Current OCP Device Rating Bolt Size 75°C Wire Current, tot Wire Compression Lug Two Hole 3/8" Bolt Mechanical Lug Two Hole 3/8" Bolt 15 45 56 70 M10 (3/8") 130 (1) #1 54857BE 32209 30 90 112 125 M10 (3/8") 150 (1) 1/0 54860BE 32209 45 134 167 200 M10 (3/8") 200 (1) 3/0 54864BE 32211 60 179 223 250 M10 (3/8") 300 (2) 1/0 54860BE 32209 75 224 279 350 M10 (3/8") 350 (2) 2/0 54862BE 32209 90 268 334 400 M10 (3/8") 460 (2) 4/0 54866BE 32211 Table 8 UPS currents and terminals—Bypass input (for dual-input units, 208V operation) Maximum Recommended Lug (T&B) Unit Rating Nom. Input Current OCP Device Rating Bolt Size 75°C Wire Current, tot Wire Compression Lug Two Hole 3/8" Bolt 15 42 60 M10 (3/8") 130 (1) #1 54857BE Mechanical Lug Two Hole 3/8" Bolt 32209 30 84 110 M10 (3/8") 150 (1) 1/0 54860BE 32209 45 126 175 M10 (3/8") 175 (1) 2/0 54862BE 32209 60 168 225 M10 (3/8") 230 (1) 4/0 54866BE 32211 75 210 300 M10 (3/8") 300 (2) 1/0 54860BE 32209 90 252 350 M10 (3/8") 350 (2) 2/0 54862BE 32209 5 Table 9 UPS currents and terminals—Output 208V Maximum Recommended Lug (T&B) Unit Rating Nom. Output Current OCP Device Rating Bolt Size 75°C Wire Current tot Wire Compression Lug Two Hole 3/8" Bolt Mechanical Lug Two Hole 3/8" Bolt 15 42 60 M10 (3/8") 130 (1) #1 54857BE 32209 30 83 125 M10 (3/8") 150 (1) 1/0 54860BE 32209 45 125 200 M10 (3/8") 175 (1) 2/0 54862BE 32209 60 167 225 M10 (3/8") 230 (1) 4/0 54866BE 32211 75 208 300 M10 (3/8") 300 (2) 1/0 54860BE 32209 90 250 350 M10 (3/8") 350 (2) 2/0 54862BE 32209 Table 10 UPS currents and terminals—Battery (288V string) Maximum Recommended Lug (T&B) Unit Rating Battery Current OCP Device Rating Bolt Size 75°C Wire Current, tot Wire Compression Lug Two Hole 3/8" Bolt Mechanical Lug Two Hole 3/8" Bolt 15 67 80 M10 (3/8") 130 (1) #1 54857BE 32209 30 135 150 M10 (3/8") 175 (1) 2/0 54862BE 32209 45 202 225 M10 (3/8") 230 (1) 4/0 54866BE 32211 60 269 300 M10 (3/8") 300 (2) 1/0 54860BE 32209 75 336 350 M10 (3/8") 400 (2) 3/0 54864BE 32211 90 404 450 M10 (3/8") 460 (2) 4/0 54866BE 32211 6 General Specifications INPUT Voltage 208/120, 220/127VAC, 50/60Hz, 3-phase, 4-wire plus ground Voltage Range Without Derating +15%, -20% Frequency Range 40-70Hz Current Distortion 3% maximum reflected THD at full load Current Walk-In 5-35 seconds to full load (adjustable) Power Factor 0.99 full load, 0.98 half load ENVIRONMENTAL Operating Temperature UPS: 32° to 104°F (0-40°C); Battery: 68° to 86°F (20-30°C) Non-Operating Temperature -4° to 158°F (-20° to 70°C) Relative Humidity 0-95% non-condensing Operating Altitude Up to 3,300 ft. (1,000m) without derating Acoustical Noise Less than 57 dBA typical (45kVA), 60 dBA typical (90kVA) 3.3 ft. (1m) from the unit Internal Battery Battery Time (Minutes) Battery Code 15kVA 30kVA HX100-FR FX 30 12 6 1056 (480) HX150-FR HX 53 21 12 1248 (567) Model 45kVA Added Battery Weight lb. (kg) 7 OUTPUT Voltage 208/120, 220/127VAC, 50/60Hz, 3-phase, 3- or 4-wire plus ground Voltage Adjustment Range ±5% Voltage Regulation ±1% for balanced load ±5% for 100% unbalanced load Dynamic Regulation ±5% deviation for 100% load step ±1% for loss or return of AC input Transient Response Time Recover to ±5% of output voltage within 1/2 cycle THD For linear loads, 1% THD; Less than 4% THD for 100% nonlinear loads without kVA/kW derating Phasing Balance 120° ±1° for balanced load 120° ±1.5° for 100% unbalanced load Frequency Regulation ±0.1% (single Liebert FlexPower™ assembly) ±0.25% (six Liebert FlexPower assemblies) Load Power Factor Range 0.7 lagging to 0.9 leading without derating Overload 100% load, continuous; 110% load, 60 minutes; 125% load, 10 minutes; 150% load, 60 seconds, with true sinusoidal waveform STANDARDS Listed to UL 1778 UPS standards, and CSA certified. Meets current requirements for safe high performance UPS operation. © 2010 Liebert Corporation Technical Support / Service United States All rights reserved throughout the world. Specifications subject to change without notice. 1050 Dearborn Drive 800-543-2378 ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. [email protected] P.O. Box 29186 SL-25605_REV7_03-14 Web site: www.liebert.com 8 Columbus, OH 43229