Liebert APM UPS 15-90kVA 60Hz Single Dual Input Site Planning Data (R03/14) (SL-25605)

LIEBERT® APM™ 3-PHASE UPS: 15-90KVA/KW, 60HZ, 208-600VAC, SINGLE & DUAL INPUT - SITE PLANNING DATA
The UPS must be fed from a solidly
grounded wye or delta AC source. Not for
use with impedance-grounded systems,
corner-grounded or high leg delta systems. For these applications, an isolation
transformer must be installed between
the AC feed and the UPS.
BYPASS DISTRIBUTION CABINET
(Optional; see Note 7)
* SYSTEM
AC INPUT
4 WIRE + GRD
MBB
BIB
(OPTIONAL)
54 POLE
SEE NOTE 6
MIB
AC OUTPUT
208V
4 WIRE + GND
BIB Bypass Isolation Breaker
MBB Maintenance Bypass Breaker
MIB Maintenance Isolation Breaker
* External Overcurrent Protection by others
STATIC BYPASS
Field-supplied wiring
NOTES
1. Install in accordance with national and local electrical codes.
2. Input and bypass must share the same single source.
3. A neutral is required from the system AC input source.
A full capacity neutral conductor is recommended.
Grounding conductors are recommended.
4. UPS system input and output cables must be run
in separate conduits.
5. Control wiring must be run in separate conduits.
6. Optional 54 pole, 225A for 45kVA frame only or
optional 54 pole, 400A for 90kVA frame only.
UAM01004
7. Transformer available 480V or 600V input.
Rev. 0
UPS CABINET
BATTERY
1
Notes for Tables
1.
2.
3.
4.
5.
6.
7.
Nominal (Nom) current is based on full rated output load at nominal input voltage.
Maximum (Max) current (125% of nominal) is short duration for battery recharge
conditions.
UPS input and bypass cables must be run in separate conduit from output cables.
Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
Nominal rectifier AC input current (considered continuous) is based on full
rated output load. Maximum current includes nominal input current and
maximum battery recharge current (considered non-continuous). Continuous
and non-continuous currents are defined in NEC 215.
Nominal AC output current (considered continuous) is based on full rated
output load. Output breakers are either supplied by the customer or by using
the optional Liebert Bypass Distribution Cabinet.
Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized
ground conductors are recommended. Neutral conductors to be sized for full
capacity per NEC 310-15 (b)(4). References are per NEC 2008.
Wiring requirements: AC Input:
3-phase, 4-wire, plus ground
AC Output: 3-phase, 3- or 4-wire, plus ground
Table 1
All wiring is to be in accordance with national and local electric codes.
Minimum access clearance is 36" (914mm) front; ventilation clearance is 24" (610mm)
above and 12" (305mm) in the rear.
Top or bottom cable entry through removable access plates. Punch plate to suit conduit
size, then replace.
Control wiring and power wiring must be run in separate conduit.
Dimensions shown include an internal battery (45kVA frame only).
Weights shown do not include an internal battery nor optional cabinets or features.
When a Liebert Bypass Distribution Cabinet is not used, the customer must supply the
input circuit breaker with a 120VAC shunt trip. The shunt trip drive capability is 8A.
10.
11.
12.
13.
14.
Additional Notes
• If site configuration includes a backup emergency generator, it is recommended that the
engine generator set be properly sized and equipped for a UPS application. Generator
options would typically include an isochronous governor (generator frequency regulation)
and a UPS-compatible regulator (generator voltage regulation). Consult generator
manufacturer for required generator options and sizing.
• If site configuration includes an automatic transfer switch, refer to Liebert Power Line titled
“Criteria for Application of Automatic Transfer Switches (ATS) With Uninterruptible Power
Supply (UPS) Systems,” publication 91K-PLT-48-02. It is also recommended that the
transfer switch be equipped with auxiliary contacts to provide a UPS “on generator” signal.
Consult transfer switch manufacturer for required transfer switch options and sizing.
• If site configuration requires an external isolated maintenance bypass circuit, it should be
noted that utility AC input might not be in phase with the UPS AC output. Consult an
Emerson sales representative or applications engineer.
Site Planning Data - 15-90kVA, 60Hz, 208VAC, Single Input
UPS Rating
Voltage
AC Input
Current, A
kVA
8.
9.
kW
Input Output Nom.
Max.
Battery
Rec. Nom.
Max.
OPD VDC Discharge
AC Output
Mechanical Data
System OCPD
(45 and 90 kVA)
Dimensions
Heat Dis.
Cooling Air
(customersupplied)
OPD WxDxH, in. (mm) 45kVA Frame 90kVA Frame BTU/hr (kWH) CFM (m3/hr)
Current, A
Nom.
Unit Weight, lb. (kg)
15
15
208
208
45
56
70
288
67
42
60
866 (394)
796 (362)
3,759 (1.1)
102 (173)
30
30
208
208
90
112
125
288
135
83
125
942 (428)
872 (396)
7,753 (2.21)
204 (346)
45
45
208
208
134
167
200
288
202
125
200
60
60
208
208
179
223
250
288
269
167
225
75
75
208
208
224
279
350
288
335
208
90
90
208
208
268
334
400
288
404
250
1
2, 3, 5, 8,12
6
4
See Notes for Tables
(above):
1, 3, 8,12 1,3,8,12
200A/
with
120VAC/
shunt trip
1018 (463)
948 (431)
11,383 (3.34)
306 (519)
NA
1024 (465)
15,130 (4.43)
408 (692)
300
NA
1100 (500)
18,853 (5.52)
510 (865)
350
NA
1176 (535)
22,518 (6.6)
612 (1038)
400A/
with/
120VAC/
shunt trip
14
14
—
—
15
31.8x39.5x78.7
(800x1000x2000)
6
13
2
Table 2
Site Planning Data - 15-90kVA, 60Hz, 480VAC, Single Input
UPS Rating
Voltage
AC Input
Current, A
kVA
kW
Input Output Nom.
Max
Battery
Rec. Nom
Max.
OPD VDC Discharge
AC Output
Mechanical Data
Current, A
Nom.
Unit Weight, lb. (kg)
Cooling Air
Dimensions
Heat Dis.
OPD WxDxH, in. (mm) 45kVA Frame 90kVA Frame BTU/hr (kWH) CFM (m3/hr)
15
15
480
208
19
24
30
288
67
42
60
NA
1728 (785)
14,642 (4.3)
102 (173)
30
30
480
208
39
49
60
288
135
83
125
NA
1804 (820)
16,587 (4.9)
204 (346)
45
45
480
208
58
73
90
288
202
125
1880 (855)
20,217 (5.9)
306 (519)
60
480
208
78
98
125
288
269
167
200 31.8x39.5x78.7
225 (800x1000x2000)
NA
60
NA
1956 (889)
23,964 (7.0
408 (692)
75
75
480
208
97
121
150
288
335
208
300
NA
2032 (924)
27,687 (8.1)
510 (865)
90
90
480
208
116
145
175
288
404
250
350
NA
2108 (958)
31,352 (9.2)
612 (1038)
1
2, 3, 5, 8,12
6
4
1, 3, 8,12
1, 3, 8, 12
6
14
14
—
—
See Notes for Tables (p. 2):
Table 3
UPS Rating
13
System OCPD
(45 and 90 kVA)
(customersupplied)
100A
with 120VAC
shunt trip
200A
with 120VAC
shunt trip
15
Site Planning Data - 15-90kVA, 60Hz, 600VAC, Single Input
Voltage
AC Input
Current, A
Input Output Nom.
Max
Battery
Max.
Rec. Nom
OPD VDC Discharge
AC Output
Mechanical Data
System OCPD
(45 and 90 kVA)
Dimensions
Heat Dis.
Cooling Air
(customerOPD WxDxH, in. (mm) 45kVA Frame 90kVA Frame BTU/hr (kWH) CFM (m3/hr)
supplied)
Current, A
Nom.
Unit Weight, lb. (kg)
kVA
kW
15
15
600
208
16
20
25
288
67
42
60
NA
1743 (792)
12,350 (3.6)
102 (173)
30
30
600
208
31
39
50
288
135
83
125
NA
1819 (827)
16,344 (4.7)
204 (346)
45
45
600
208
47
59
70
288
202
125
200
NA
1895 (861)
19,974 (5.8)
306 (519)
60
60
600
208
62
78
100
288
269
167
225
NA
1971 (896)
23,721 (6.9)
408 (692)
75
75
600
208
78
98
125
288
335
208
300
NA
2047 (930)
27,444 (8.0)
510 (865)
90
90
600
208
93
116
150
288
404
250
350
NA
2123 (965)
31,109 (9.1)
612 (1038)
1
2,3,5,8,12
6
4
1,3,8,12
1,3,8,12
6
14
14
—
—
See Notes for Tables (p. 2):
31.8x39.5x78.7
(800x1000x2000)
13
3
100A
with 120VAC
shunt trip
150A
with 120VAC
shunt trip
15
Table 4
Site Planning Data - 15-90kVA, 60Hz, 208VAC, Dual Input
UPS
Rating
Voltage
208VAC
Bypass Input
AC Rectifier Input
Current, A
kVA
kW
Input
Output
Battery
AC Output
Current
Rec.
Nom. Max OPD
Nom
Mechanical Data
Current, A
Rec. Nom
Max.
OPD VDC Discharge
Nom.
OPD
Dimensions
WxDxH,
in. (mm)
Unit Weight, lb. (kg)
45kVA
Frame
90kVA
Frame
Input CB
Cooling Air (customerHeat Dis.
3
BTU/hr (kWH) CFM (m /hr) supplied)
15
15
208
208
45
56
70
42
60
288
67
42
60
866 (394)
796 (362)
3,759 (1.1)
102 (173)
30
30
208
208
90
112
125
84
110
288
135
83
125
942 (428)
872 (396)
7,753 (2.21)
204 (346)
45
45
208
208
134
167
200
126
175
288
202
125
200
60
208
208
179
223
250
168
225
288
269
167
31.8x39.5x78.7 1018 (463) 948 (431) 11,383 (3.34)
225 (800x1000x2000)
NA
1024 (465) 15,130 (4.43)
306 (519)
60
75
75
208
208
224
279
350
210
300
288
335
208
300
NA
1100 (500) 18,853 (5.52)
510 (865)
90
90
208
208
268
334
400
252
350
288
404
250
350
NA
1176 (535)
22,518 (6.6)
612 (1038)
1
2,3,5,
8,12
6
—
—
4
1,3,8,12
1,3, 8,12
6
14
14
—
—
See Notes for Tables (p. 2):
Table 5
13
408 (692)
200A with
120VAC
shunt trip
400A with
120VAC
shunt trip
15
Site Planning Data - 15-90kVA, 60Hz, 480VAC, Dual Input
UPS Rating
Voltage
208VAC
Bypass Input
AC Input
Current, A
Input Output Nom.
Battery
Current
Max
Rec.
OPD
Nom
42
AC Output
Mechanical Data
Current, A
Byp. Nom
Max.
OPD VDC Discharge
90kVA
Frame
Input CB
Heat Dis.
Cooling Air (customerBTU/hr (kWH) CFM (m3/hr) supplied)
kVA
kW
15
15
480
208
19
24
30
30
30
480
208
39
49
60
84
110
288
135
83
125
45
45
480
208
58
73
90
126
175
288
202
125
200
NA
1956 (889)
23,964 (7.0
408 (692)
—
NA
2032 (924)
27,687 (8.1)
510 (865)
—
NA
2108 (958)
31,352 (9.2)
612 (1038)
—
14
14
—
—
15
60
288
67
Nom.
Unit Weight, lb. (kg)
Dimensions
45kVA
OPD WxDxH, in. (mm) Frame
42
60
60
60
480
208
78
98
125
168
225
288
269
167
31.8x39.5x78.7
225 (800x1000x2000)
75
75
480
208
97
121
150
210
300
288
335
208
300
90
90
480
208
116
145
175
252
350
288
404
250
350
1
2,3,5,8,12
6
—
—
4
1,3,8,12
1,3,8,12
6
See Notes for Tables (p. 2):
4
1728 (785)
14,642 (4.3)
102 (173)
—
NA
1804 (820)
16,587 (4.9)
204 (346)
—
NA
1880 (855)
20,217 (5.9)
306 (519)
—
NA
13
Table 6
Site Planning Data - 15-90kVA, 60Hz, 600VAC, Dual Input
UPS Rating
Voltage
208VAC
Bypass Input
AC Input
Current, A
Input Output Nom.
Battery
Current
Max
Rec.
OPD
Nom
42
AC Output
Mechanical Data
Current, A
Byp. Nom
Max.
OPD VDC Discharge
Unit Weight, lb. (kg)
Dimensions
OPD WxDxH, in. (mm)
90kVA
Frame
NA
1743 (792)
12,350 (3.6)
102 (173)
—
kVA
kW
15
15
600
208
16
20
25
30
30
600
208
31
39
50
84
110
288
135
83
125
NA
1819 (827)
16,344 (4.7)
204 (346)
—
45
45
600
208
47
59
70
126
175
288
202
125
200
1895 (861)
19,974 (5.8)
306 (519)
—
60
60
600
208
62
78
100
168
225
288
269
167
31.8x39.5x78.7
225 (800x1000x2000)
NA
NA
1971 (896)
23,721 (6.9)
408 (692)
—
75
75
600
208
78
98
125
210
300
288
335
208
300
NA
2047 (930)
27,444 (8.0)
510 (865)
—
90
90
600
208
93
116
150
252
350
288
404
250
350
NA
2123 (965)
31,109 (9.1)
612 (1038)
—
1
2,3,5,8,12
6
—
—
4
1,3,8,12
1,3,8,12
6
14
14
—
—
15
See Notes for Tables (p. 2):
Table 7
60
288
Nom.
Input CB
Heat Dis.
Cooling Air (customerBTU/hr (kWH) CFM (m3/hr) supplied)
45kVA
Frame
67
42
60
13
UPS currents and terminals—Input (for dual-input unit only, 208V operation)
Maximum Recommended Lug (T&B)
Unit Rating
Nom. Input Current
Max. Input Current
OCP Device Rating
Bolt Size
75°C Wire
Current, tot
Wire
Compression Lug
Two Hole 3/8" Bolt
Mechanical Lug
Two Hole 3/8" Bolt
15
45
56
70
M10 (3/8")
130
(1) #1
54857BE
32209
30
90
112
125
M10 (3/8")
150
(1) 1/0
54860BE
32209
45
134
167
200
M10 (3/8")
200
(1) 3/0
54864BE
32211
60
179
223
250
M10 (3/8")
300
(2) 1/0
54860BE
32209
75
224
279
350
M10 (3/8")
350
(2) 2/0
54862BE
32209
90
268
334
400
M10 (3/8")
460
(2) 4/0
54866BE
32211
Table 8
UPS currents and terminals—Bypass input (for dual-input units, 208V operation)
Maximum Recommended Lug (T&B)
Unit Rating
Nom. Input Current
OCP Device Rating
Bolt Size
75°C Wire Current, tot
Wire
Compression Lug
Two Hole 3/8" Bolt
15
42
60
M10 (3/8")
130
(1) #1
54857BE
Mechanical Lug
Two Hole 3/8" Bolt
32209
30
84
110
M10 (3/8")
150
(1) 1/0
54860BE
32209
45
126
175
M10 (3/8")
175
(1) 2/0
54862BE
32209
60
168
225
M10 (3/8")
230
(1) 4/0
54866BE
32211
75
210
300
M10 (3/8")
300
(2) 1/0
54860BE
32209
90
252
350
M10 (3/8")
350
(2) 2/0
54862BE
32209
5
Table 9
UPS currents and terminals—Output 208V
Maximum Recommended Lug (T&B)
Unit Rating
Nom. Output Current
OCP Device Rating
Bolt Size
75°C Wire Current tot
Wire
Compression Lug
Two Hole 3/8" Bolt
Mechanical Lug
Two Hole 3/8" Bolt
15
42
60
M10 (3/8")
130
(1) #1
54857BE
32209
30
83
125
M10 (3/8")
150
(1) 1/0
54860BE
32209
45
125
200
M10 (3/8")
175
(1) 2/0
54862BE
32209
60
167
225
M10 (3/8")
230
(1) 4/0
54866BE
32211
75
208
300
M10 (3/8")
300
(2) 1/0
54860BE
32209
90
250
350
M10 (3/8")
350
(2) 2/0
54862BE
32209
Table 10
UPS currents and terminals—Battery (288V string)
Maximum Recommended Lug (T&B)
Unit Rating
Battery Current
OCP Device Rating
Bolt Size
75°C Wire Current, tot
Wire
Compression Lug
Two Hole 3/8" Bolt
Mechanical Lug
Two Hole 3/8" Bolt
15
67
80
M10 (3/8")
130
(1) #1
54857BE
32209
30
135
150
M10 (3/8")
175
(1) 2/0
54862BE
32209
45
202
225
M10 (3/8")
230
(1) 4/0
54866BE
32211
60
269
300
M10 (3/8")
300
(2) 1/0
54860BE
32209
75
336
350
M10 (3/8")
400
(2) 3/0
54864BE
32211
90
404
450
M10 (3/8")
460
(2) 4/0
54866BE
32211
6
General Specifications
INPUT
Voltage
208/120, 220/127VAC, 50/60Hz, 3-phase, 4-wire plus ground
Voltage Range Without Derating
+15%, -20%
Frequency Range
40-70Hz
Current Distortion
3% maximum reflected THD at full load
Current Walk-In
5-35 seconds to full load (adjustable)
Power Factor
0.99 full load, 0.98 half load
ENVIRONMENTAL
Operating Temperature
UPS: 32° to 104°F (0-40°C); Battery: 68° to 86°F (20-30°C)
Non-Operating Temperature
-4° to 158°F (-20° to 70°C)
Relative Humidity
0-95% non-condensing
Operating Altitude
Up to 3,300 ft. (1,000m) without derating
Acoustical Noise
Less than 57 dBA typical (45kVA), 60 dBA typical (90kVA)
3.3 ft. (1m) from the unit
Internal Battery
Battery Time (Minutes)
Battery
Code
15kVA
30kVA
HX100-FR
FX
30
12
6
1056 (480)
HX150-FR
HX
53
21
12
1248 (567)
Model
45kVA
Added Battery Weight
lb. (kg)
7
OUTPUT
Voltage
208/120, 220/127VAC, 50/60Hz, 3-phase, 3- or 4-wire plus ground
Voltage Adjustment Range
±5%
Voltage Regulation
±1% for balanced load
±5% for 100% unbalanced load
Dynamic Regulation
±5% deviation for 100% load step
±1% for loss or return of AC input
Transient Response Time
Recover to ±5% of output voltage within 1/2 cycle
THD
For linear loads, 1% THD; Less than 4% THD for 100% nonlinear loads without kVA/kW derating
Phasing Balance
120° ±1° for balanced load
120° ±1.5° for 100% unbalanced load
Frequency Regulation
±0.1% (single Liebert FlexPower™ assembly)
±0.25% (six Liebert FlexPower assemblies)
Load Power Factor Range
0.7 lagging to 0.9 leading without derating
Overload
100% load, continuous;
110% load, 60 minutes; 125% load, 10 minutes;
150% load, 60 seconds, with true sinusoidal waveform
STANDARDS
Listed to UL 1778 UPS standards, and CSA certified. Meets current requirements for safe high performance UPS operation.
© 2010 Liebert Corporation
Technical Support / Service
United States
All rights reserved throughout the world. Specifications subject to change without notice.
1050
Dearborn Drive
800-543-2378
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks or registered trademarks of their respective owners. [email protected] P.O. Box 29186
SL-25605_REV7_03-14
Web site: www.liebert.com
8
Columbus, OH 43229