Liebert® NXL™ UPS Installation Manual – 250-400kVA, 60Hz, Three-Phase, Single-Module and Multi-Module Units CONTACTING EMERSON NETWORK POWER® FOR SUPPORT To contact Emerson Network Power Liebert® Services for information or repair service in the United States, call 1-800-LIEBERT (1-800-543-2378). Liebert Services offers a complete range of start-up services, repair services, preventive maintenance plans and service contracts. For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services, if available in your area. For areas not covered by Emerson Network Power Liebert Services, the authorized distributor is responsible for providing qualified, factory-authorized service. For LGS to assist you promptly, please have the following information available: Part numbers: _________________________________________________________________ Serial numbers:________________________________________________________________ Rating: _______________________________________________________________________ Date purchased: _______________________________________________________________ Date installed:_________________________________________________________________ Location: ______________________________________________________________________ Input voltage/frequency: ________________________________________________________ Output voltage/frequency: ______________________________________________________ Battery reserve time:___________________________________________________________ Product Warranty Registration To register for warranty protection, visit the Service and Support section of our Web site at: www.liebert.com Click on Product Registration and fill out the form. TABLE OF CONTENTS CONTACTING EMERSON NETWORK POWER® FOR SUPPORT . . . . . . . . . . . . . . INSIDE FRONT COVER IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.0 SINGLE-MODULE AND MULTI-MODULE MECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . .3 1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.2 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.3 Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3.1 1.3.2 1.4 UPS Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.4.1 1.4.2 1.4.3 1.4.4 1.4.5 Moving the Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Raised Floor Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Kick Plate Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Special Considerations for 1+N Parallel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 5 5 5 5 1.5 System Composition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.6 Cable Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.0 UPS ELECTRICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 2.1 External Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.2 Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2.2.1 2.2.2 2.3 Sizing the Input Breaker Feeding a Liebert NXL UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Power Cable Connection Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Control Cable and Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.3.1 2.3.2 Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Multi-Module Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2.4 Digital LBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 2.5 Configuring Neutral and Ground Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 2.5.1 2.5.2 2.5.3 2.5.4 2.5.5 Four-Wire Input connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Three-Wire Input Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preferred Grounding Configuration, Battery Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Multi-Module Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . High Resistance Ground Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 16 16 17 17 2.6 Grounding Diagrams, Single- and Multi-Module Systems . . . . . . . . . . . . . . . . . . . . . . . . . . 17 3.0 OPTIONAL EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 3.1 Single-Module System Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 3.1.1 3.1.2 3.1.3 3.1.4 3.2 Matching Maintenance Bypass Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Temperature Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Load Bus Synch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote Alarm Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 20 20 20 Communication and Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 3.2.1 3.2.2 3.2.3 Alber Monitoring System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Programmable Relay Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Input Contact Isolator Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 i 4.0 INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 5.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42 APPENDIX A - CABINET INTERCONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A50 FIGURES Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 Figure 23 Figure 24 Figure 25 Figure 26 Figure 27 Figure 28 Figure 29 Figure 30 Figure 31 Figure 32 Figure 33 Figure 34 Figure 35 Figure 36 Figure 37 Cabinet arrangement—Liebert NXL single-module, battery cabinets, maintenance bypass cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Cabinet arrangement—Liebert NXL 400kVA, 575-600V multi-module and battery cabinets . . . 7 Cabinet grounding plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Kick plate and filter locations, typical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 External Interface Board connections layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Inter-Module Communication Board wiring diagram—Multi-modules . . . . . . . . . . . . . . . . . . . . 15 Inter-Module Communication Board wiring diagram—Digital LBS . . . . . . . . . . . . . . . . . . . . . . . 15 Grounding diagram, three-wire single-module system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Grounding diagram, four-wire single-module system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Grounding diagram, three-wire multi-module system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Grounding diagram, four-wire multi-module system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Control wiring, Programmable Relay Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Programmable relay board dialog box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Input contact isolator dialog box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Optional Input Contact Isolator Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Outline drawing, 250kVA, 480V Liebert NXL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Outline drawing, 250kVA, 575/600V; and 300kVA, 480/575/600V Liebert NXL . . . . . . . . . . . . . 26 Outline drawing, 400kVA, 480V Liebert NXL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Outline drawing, 400kVA, 575V/600V Liebert NXL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Outline drawing, 400kVA, 575V/600V Liebert NXL with DC I/O cabinet . . . . . . . . . . . . . . . . . . 29 Main components, 250kVA, 480V Liebert NXL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Main components, 250kVA, 575/600V, and 300kVA, 480/575/600V Liebert NXL . . . . . . . . . . . . 31 Main components, 400kVA, 480V Liebert NXL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Main components, 400kVA, 575V/600V Liebert NXL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Main components, 400kVA, 575V/600V Liebert NXL with DC I/O cabinet . . . . . . . . . . . . . . . . . 34 Input/output conduit detail drawing, 250-300kVA, all voltages, Liebert NXL . . . . . . . . . . . . . . . 35 Input/output terminal detail, 400kVA, 480V Liebert NXL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Input/output terminal detail, 400kVA, 575V/600V Liebert NXL. . . . . . . . . . . . . . . . . . . . . . . . . . 37 Input/output terminal detail, 400kVA, 575V/600V Liebert NXL with DC I/O cabinet . . . . . . . . 38 Top cable entry routing and installation order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Bottom cable entry routing and installation order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Single-input busbar arrangement—250-400kVA units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Low-voltage cable entry—250-400kVA units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Inverter overload data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Bypass overload data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Cabinet interconnection cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Cabinet interconnection cabling (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 ii TABLES Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Table 16 Table 17 Table 18 UPS input dry contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UPS control with battery cabinet or module battery disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . UPS control contacts with global maintenance bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UPS control contacts to remote status panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parallel from UPS module Inter-Module Communication Board to other Inter-Module Communication Board in system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wire size, length for digital LBS connection of UPS Inter-Module Communication Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programmable Relay Board pinout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Contact Isolator Board pre-assigned values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Contact Isolator Board control wiring connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liebert NXL UPS specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current ratings—rectifier input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current ratings—bypass input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current ratings—output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current ratings—battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Recommended conduit and cable sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Recommended lug sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Recommended torque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cabinet interconnection cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii 13 13 13 14 14 15 21 24 24 42 44 44 44 44 45 49 49 52 iv Important Safety Instructions IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation of your Liebert NXL UPS.Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel. ! WARNING Risk of electrical shock. Can cause personal injury or death. This UPS has several circuits that are energized with high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters before working within the UPS. Check for voltage with both AC and DC voltmeters before making contact. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the UPS or preparing the UPS for installation. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires. Extreme caution is required when performing installation and maintenance. Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system. Observe all safety precautions in this manual before handling or installing the UPS system. Observe all precautions in the Operation and Maintenance Manual, SL-25425, before as well as during performance of all maintenance procedures. Observe all DC safety precautions before working on or near the DC system. ! WARNING Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death. Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The UPS module weight ranges from 3965 to 6380 lb. (1768 to 2894kg). Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times. Slots at the base of the modules cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit. Read all of the following instructions before attempting to move, lift, remove packaging from or preparing unit for installation. ! WARNING Risk of electrical shock and fire. Can cause equipment damage, personal injury or death. Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high potential electric charges may exist at the capacitor banks and at the DC connections. All wiring must be installed by a properly trained and qualified electrician. All power and control wiring must comply with all applicable national, state and local codes. One person should never work alone, even if all power is disconnected from the equipment. A second person should be standing by to assist and to summon help in case of an accident. 1 Liebert® NXL™ Important Safety Instructions NOTE Materials sold hereunder cannot be used in the patient vicinity (e.g., use where UL, cUL or IEC 60601-1 is required). Medical applications such as invasive procedures and electrical life support equipment are subject to additional terms and conditions. NOTICE This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communication. Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense. Liebert® NXL™ 2 Single-Module and Multi-Module Mechanical Installation 1.0 SINGLE-MODULE AND MULTI-MODULE MECHANICAL INSTALLATION 1.1 Introduction This following section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert NXL uninterruptible power supply and related equipment. This chapter is a guide to general procedures and practices that should be observed by the installing personnel. The particular conditions of each site will determine the applicability of such procedures. ! WARNING Risk of electrical shock. Can cause injury or death. Special care must be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400VDC and is potentially lethal. NOTICE All equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation. NOTICE Three-phase input supply required. The standard Liebert NXL UPS is suitable for connection to three-phase, four-wire (+ Earth) TN-C, TN-S, IT-G, IT-IG or, three-phase, three-wire plus ground, IT-UG. If using with IT Power system, a 4-pole disconnect device must be included as part of building installation. NOTICE Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer. 1.2 Preliminary Checks Before installing the UPS, please carry out the following preliminary checks: • Visually examine the UPS equipment for transit damage, both internally and externally. Report any damage to the shipper immediately. • Verify that the correct equipment is being installed. The equipment supplied has an identification tag on the back of the main door reporting: the type, size and main calibration parameters of the UPS. • Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system. 3 Liebert® NXL™ Single-Module and Multi-Module Mechanical Installation 1.3 Environmental Considerations 1.3.1 UPS Room The UPS module is intended for indoor installation and should be located in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range (see Environmental Parameters in Table 10). The Liebert NXL UPS is cooled with the aid of internal fans. To permit air to enter and exit and prevent overheating or malfunctioning, do not cover the ventilation openings. NOTE To ensure proper airflow, the unit must be installed only on a solid surface made of a noncombustible material, such as concrete. The Liebert NXL UPS is equipped with air filters located behind the front doors. A schedule for inspection of the air filters is required. The period between inspections will depend upon environmental conditions. When bottom entry is used, the conduit plate must be installed. NOTE The UPS is suitable for mounting on concrete or other non-combustible surface only. 1.3.2 Storage Should the equipment not be installed immediately, it must be stored in a room for protection against excessive humidity and or heat sources (see Environmental Parameters in Table 10). 1.4 Positioning The cabinet is structurally designed to handle lifting from the base. Access to the power terminals, auxiliary terminals blocks and power switches is from the front. The door can be opened to give access to the power connections bars, auxiliary terminal blocks and power isolators. Front door can be opened at 180° for more flexibility in installations. NOTE The UPS must be placed a solid surface. There must be no openings in the surface except those required for conduit landing areas. All provided kick plates must be installed. 1.4.1 Moving the Cabinets The route to be travelled between the point of arrival and the unit’s position must be planned to make sure that all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check that doorways, lifts, ramps, etc. are adequate and that there are no impassable corners or changes in the level of corridors). Ensure that the UPS weight is within the designated surface weight loading (kg/cm2) of any handling equipment. For weight details, see Table 10. The UPS can be handled with a forklift or similar equipment. Ensure any lifting equipment used in moving the UPS cabinet has sufficient lifting capacity. When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15-degree tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath the unit. Handling with straps is not authorized. Liebert® NXL™ 4 Single-Module and Multi-Module Mechanical Installation ! WARNING Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death. Because the weight distribution in the cabinet is uneven, use extreme care while handling and transporting. Take extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The UPS module weight ranges from 3965 to 6380 lb. (1768 to 2894kg). Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times. 1.4.2 Clearances The Liebert NXL has no ventilation grilles at either side or at the rear of the UPS. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important to leave a distance of 24" (610mm) between the top of the UPS and any overhead obstacles to permit adequate circulation of air coming out of the unit. 1.4.3 Raised Floor Installations If the equipment is to be located on a raised floor it should be mounted on a pedestal suitably designed to accept the equipment point loading. Refer to the base view to design this pedestal. The top of pedestal must be solid. NOTE The UPS must be placed on a solid surface. There must be no openings in the surface except those required for conduit landing areas. All provided kick plates must be installed. 1.4.4 Kick Plate Installation Kick plates must be installed. If the unit is to be installed in a position that does not permit access to the rear kick plates, then kick plates must be installed before the unit is placed in its final position. 1.4.5 Special Considerations for 1+N Parallel Systems Consider the grounding configuration of your system before finalizing module placement See 2.5 Configuring Neutral and Ground Connections. Emerson Network Power recommends matching the impedance in the bypass path of paralleled systems as closely as possible. The impedance mismatch can be minimized by controlling the wiring length of each unit. The design and the layout of the UPS system and associated panels and cabling should be examined closely to ensure that cable lengths and impedances are closely matched. The Liebert 1+N UPS module is supplied with a sharing reactor to minimize the impact of cable impedance mismatch. The cabling impedance must be carefully controlled to ensure good bypass current sharing. For Liebert NXL Systems, the cabling impedances must be within 10% from maximum to minimum. If the cabling impedances need to be greater than 10%, contact your Emerson representative to calculate whether the system will result in an overload condition when operating on bypass. When bringing the 1+N system online for the first time or after removing one unit, Emerson recommends checking the bypass current mismatch. To check the bypass current mismatch: 1. Place a load on the bypass of each UPS module. 2. View the output current of each unit. The accuracy of the currents displayed on the UPS module is sufficient for this check. If the mismatch is greater than 10%, the bypass impedances must be balanced or the load must be limited to less than the maximum rating. 5 Liebert® NXL™ Single-Module and Multi-Module Mechanical Installation 1.5 System Composition A UPS system can comprise a number of equipment cabinets, depending on the individual system design requirements, e.g. UPS cabinet, battery cabinet, maintenance bypass cabinet. In general, all the cabinets used in a particular installation are of the same height. Refer to the drawings provided in 4.0 - Installation Drawings for the positioning of the cabinets as shown in Figures 1 and 2. 1.6 Cable Entry Cables can enter the UPS cabinet from bottom or top into the Input/Output (I/O) section of the unit, see the figures in 4.0 - Installation Drawings. Figure 1 Cabinet arrangement—Liebert NXL single-module, battery cabinets, maintenance bypass cabinet Applicable to: 250 - 400 kVA 480V, 250 - 300 kVA 575/600V except without Maintenance Bypass Cabinet The side panels and hangers must be removed before the cabinets can be bolted together. Additional Battery Cabinet(s) Additional Battery Cabinet(s) Liebert® NXL™ Battery Cabinet Liebert NXL UPS Liebert NXL UPS Maintenance Bypass Cabinet Battery Cabinet Liebert NXL UPS Liebert NXL UPS Liebert NXL UPS 6 Note: If a maintenance bypass cabinet is used, it must be installed on the right side of the Liebert NXL UPS Maintenance Bypass Cabinet Battery Cabinet Additional Battery Cabinet(s) Single-Module and Multi-Module Mechanical Installation Figure 2 Cabinet arrangement—Liebert NXL 400kVA, 575-600V multi-module and battery cabinets The side panels and hangers must be removed before the cabinets can be bolted together. Liebert NXL UPS DC I/O Section I/O Bypass Section Battery Cabinet Battery Cabinet Liebert NXL UPS 7 Liebert® NXL™ UPS Electrical Installation 2.0 UPS ELECTRICAL INSTALLATION This chapter provides guidelines for qualified installers who must have knowledge of local wiring practices pertaining to the equipment to be installed. ! WARNING Risk of electrical shock. Can cause injury or death. The UPS contains high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters before working within the UPS. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the UPS or preparing the UPS for installation. 2.1 External Protective Devices For safety, it is necessary to install circuit breakers in the input AC supply and external battery system. Given that every installation has its own characteristics, this section provides guidelines for qualified installation personnel with knowledge of operating practices, regulatory standards and the equipment to be installed. External overcurrent protection must be provided. See Table 10 - Liebert NXL UPS specifications for overload capacity. Dual Input When wiring the UPS with a separate rectifier and bypass input, each input must be protected separately. Size the breakers according to the input currents shown in Table 10. Liebert® NXL™ 8 UPS Electrical Installation 2.2 Power Cables The UPS requires both power and control cabling. All control cables, whether shielded or not, should be run separate from the power cables in metal conduits or metal ducts which are electrically bonded to the metalwork of the cabinets to which they are connected The cable design must comply with the voltages and currents in Table 10, follow local wiring practices and take into consideration the environmental conditions (temperature and physical support media), room temperature and conditions of installation of the cable and system’s overload capacity (see 5.0 - Specifications). For cable entry terminal, refer to Figures 26 28 and 29. ! WARNING Risk of electrical shock. Can cause injury or death. Before cabling the UPS, ensure that you are aware of the location and operation of the external isolators that connect the UPS input/bypass supply to the power distribution panel. Check that these supplies are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation. NOTICE For dual input operation ensure that any busbars between the bypass and the rectifier input are removed. When sizing battery cables, a maximum volt drop of 2VDC is permissible at the current ratings given in Table 14. The following are guidelines only and superseded by local regulations and codes of practice where applicable: • Take special care when determining the size of the neutral cable (grounded conductor), because current circulating on the neutral cable may be greater than nominal current in the case of nonlinear loads. Refer to the values in Table 10. • The grounding conductor should be sized according to the fault rating, cable lengths, type of protection, etc. The grounding cable connecting the UPS to the main ground system must follow the most direct route possible. • Consideration should be given to the use of paralleled smaller cables for heavy currents, as this can ease installation considerably. • AC and DC cables must be run in conduits according to local codes, national codes and standard best practices. This will prevent creation of excess EMI fields. 2.2.1 Sizing the Input Breaker Feeding a Liebert NXL UPS The rectifier nominal input current value (Table 11) is based on providing enough power to operate the inverter at full rated load when the input voltage is nominal. The published rectifier maximum input current value is based on the maximum input current limit setting of 125%. The recommended input breaker ampacity is based on the NEC calculation for a branch circuit with the current limit set at the maximum value. The calculation for an 80% rated breaker is 125% of the nominal current (continuous) plus 100% of the difference between the nominal and the maximum currents (non-continuous). The calculation for a 100% rated breaker is 100% of the nominal current (continuous) plus 100% of the difference between the nominal and maximum currents (noncontinuous). The rectifier input current limit can be adjusted from 25% to 125% of the nominal value. This setting is accessible only to a factory-trained service engineer. The effect of changing this setting is similar to that of changing the setting of the trip unit on a solid-state circuit breaker. With a lower current limit setting, the calculation for the branch circuit will result in a lower value. The input current limit should not be set less than 105% of the current needed to support the inverter at full load for normal operation. This results in sufficient power to recharge the battery in a reasonable time and to operate over the published input voltage range. 9 Liebert® NXL™ UPS Electrical Installation 2.2.2 Power Cable Connection Procedure The rectifier input, bypass, output and battery power cables (all require lug type terminations) are connected to busbars situated in the I/O section as shown in Figures 26 through 31. Equipment Ground The equipment ground busbar is located in the I/O section as shown in Figures 26 through 31. The grounding conductor must be connected to the ground busbar and bonded to each cabinet in the system. All cabinets and cabling should be grounded in accordance with local regulations. NOTE Proper grounding reduces problems in systems caused by electromagnetic interference. ! WARNING Failure to follow adequate grounding procedures can result in electric shock hazard to personnel, or the risk of fire, should a ground fault occur. All operations described in this section must be performed by properly trained and qualified electricians or technical personnel. If any difficulties are encountered, contact Emerson® Network Power Liebert Services. See the back page of this manual for contact information. The grounding and neutral bonding arrangement must be in accordance with local and national codes of practice. Once the equipment has been positioned and secured, connect the power cables as described below (refer to the appropriate cable connection drawing in 4.0 - Installation Drawings): 1. Verify that the UPS equipment is isolated from its external power source and all the UPS power isolators are open. Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation. 2. Open exterior and interior panels on the front of the I/O. 3. Connect the ground and any necessary main bonding jumper to the equipment ground busbar located in the I/O section. 4. Make power connections and tighten the connections to the proper torque according to one of the two procedures below, depending on the type of installation: Ensure correct phase rotation. • Top Cable Entry (see Figures 19, 20, 25, 28, 29 and 30) • Bottom Cable Entry (see Figures 19, 20, 25, 28, 29 and 31) Top Cable Entry When making the power connections for top cable entry, the recommended order of pulling and installing cables is to start from the top connections to the bottom connections. The cables must be routed around the fault braces (see Detail in Figure 30). This is to prevent the cables from contacting other busbars. The recommended conduit layout is shown in Figure 26. Bottom Cable Entry When making the power connections for bottom cable entry, the recommended order of pulling and installing cables is to start from the bottom connections to the top connections. The cables must be routed around the fault braces (see Detail in Figure 31). This is to prevent the cables from contacting other busbars. The recommended conduit layout is shown in Figure 26. NOTE For a single input configuration, linking busbars must be installed between the bypass and the rectifier input. ! WARNING Risk of electrical shock. Can cause injury or death. If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, ensure that the system output cables are safely isolated at their termination. Liebert® NXL™ 10 UPS Electrical Installation ! WARNING Risk of electrical shock. Can cause injury or death. When connecting the cables between the battery extremities to the circuit breaker always connect the circuit breaker end of the cable first. 5. For control connection details, see 2.3 - Control Cable and Communication. NOTE If fault bracing brackets were removed during installation, they MUST be replaced. 6. Close and secure the interior and exterior doors. Figure 3 Cabinet grounding plates Note location of larger cutouts. Orient ground plate as shown. A Detail A Grounding plates are installed at each shipping split. Figure 4 Mounting Hardware (Supplied) Kick plate and filter locations, typical KICKPLATE G KICKPLATE REAR D FRONT KICKPLATE KICKPLATE DETAIL D INSTALL M6X25 BOLT, LCKW AND WSHR (4) PLACES, FRONT SIDE E DETAIL E F INSTALL M6X25 BOLT, LCKW AND WSHR (2) PLACES, EACH SIDE DETAIL G INSTALL M6X60 BOLT, LCKW AND WSHR (2) PLACES, FRONT SIDE INSTALL M6X25 BOLT, LCKW AND WSHR (4) PLACES, REAR SIDE NOTE Kick plates must be installed. If the unit is to be installed in a position that does not permit access to rear kick plates, then kick plates must be installed before the unit is placed in its final position. 11 Liebert® NXL™ UPS Electrical Installation 2.3 Control Cable and Communication Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system (external battery circuit breaker), communicate with a personal computer or provide alarm signaling to external devices, or for Remote Emergency Power Off (REPO). The External Interface Board, arranged for this purpose, is next to the option box in the Rectifier section (refer to 4.0 Installation Drawings). The contacts are rated for 250VAC @ 2A. Figure 5 External Interface Board connections layout MAINT BYP ENABLE TB0821 ACT FILT TB035 CNTL P0831 P66C P99C AUX SPARE TEMP P0832 P0801 BATT GND FLT TB0815 EXTERNA L CAN MOB TB0811 MIB TB0830 ACT FILT STATUS TB0810 TB0816 RIB ON GEN P0808 TB0823 TB0829 EPO STATUS OPT PS TB1154B EXTERNA L CAN INT BATT CAN TB0813 TB0819 MBB BYP CNTL TB0817 BIB RECT CNTL J5 TB0820 TB0818 REPO FORM C KEY STATUS INV CNTRLN REPO J4 BATT MTR TB1156 OP TB0826 TB0824 Liebert® NXL™ EXT BATT CAN TB0812 TB0825 LBS VO LTAGE TB1154A 12 UPS Electrical Installation 2.3.1 Dry Contacts NOTE If connection to more than one module is required, use a separate contact for each module. Table 1 UPS input dry contacts Terminal Block Item Remote EPO Input Form C On Generator Input Form C Table 2 TB0816 1 REPO Switch, normally open contact 2 REPO Switch, common contact 3 REPO Switch, normally closed contact, set jumper J5: 1-2 to enable, 2-3 to disable 1 On Generator switch, closed = On Generator 2 On Generator switch, common 3 On Generator switch, closed = Not On Generator Wire Size/ Max Length 14AWG/ 500ft. (150m). UPS control with battery cabinet or module battery disconnect Terminal Block Item CAN Bus and 24V Power Supply Table 3 TB0824 Connects to (Description of External Item) Pin TB1154A Connects to (Description of External Item) Pin 1 Battery Interface Board TB1154-1 2 Battery Interface Board TB1154-2 3 Battery Interface Board TB1154-3 4 Battery Interface Board TB1154-4 Wire Size/ Max Length 18 AWG 1000ft. (300m). UPS control contacts with global maintenance bypass Terminal Block Item Maintenance Isolation Breaker (MIB) Form C 1 TB0811 Maintenance Bypass Breaker (MBB) Form C 1 Maintenance Bypass Enable Form C 1 Remote EPO Input 1 Key Status Input 1, 3 Module Output Breaker (MOB) Form C 2 TB0813 TB0821 TB0825 TB0820 TB0815 Connects to (Description of External Item) Pin 1 CB aux. contact, closed = CB is closed 2 CB aux. contact, common 3 CB aux. contact, closed = CB is open 1 CB aux. contact, closed = CB is closed 2 CB aux. contact, common 3 CB aux. contact, closed = CB is open 1 Maintenance Bypass Cabinet, closed = load not on inverter 2 Maintenance Bypass Cabinet, common 3 Maintenance Bypass Cabinet, closed = load on inverter 1 REPO Switch, normally open contact 2 REPO Switch, common contact 1 Key status switch, closed = key removed 2 Key status switch, common 3 Key status switch, closed = key inserted 1 CB aux. contact, closed = CB is closed 2 CB aux. contact, common 3 CB aux. contact, closed = CB is open Wire Size/ Max Length 14AWG/500ft. (150m) 14AWG/500ft. (150m) 14AWG/500ft. (150m) 14AWG/500ft. (150m) 14AWG/500ft. (150m) 14AWG/500ft. (150m) 1. For 1+N systems with a maintenance Bypass, these Aux contacts must be run to each module from an isolated source. 2. For 1+N systems, these breaker Aux contact go to the UPS that it is associated with. 3. Key Status Input can be either Form-C, N.O. or N.C. contact. 13 Liebert® NXL™ UPS Electrical Installation Table 4 UPS control contacts to remote status panel Terminal Block Item CAN Bus and 24V Power Supply 2.3.2 TB0829 Pin Connects to (Description of External Item) 1 Remote Status Panel TB-2 2 Remote Status Panel TB-1 3 Remote Status Panel TB-3 4 Remote Status Panel TB-4 Wire Size/ Max Length 18 AWG/1000ft. (300m) Multi-Module Communication Paralleling cables that connect the module to the system are connected to terminals P3101 and P3103 on the Inter-Module Communication (IMC) board (refer to 4.0 - Installation Drawings). Table 5 Parallel from UPS module Inter-Module Communication Board to other Inter-Module Communication Board in system Terminal Designation From To Signal Name Wire Size/ Max Length Primary Connections P3101-1 P3101-1 Share CAN +24V P3101-2 P3101-2 Share CAN common P3101-3 P3101-3 System CAN +24V P3101-4 P3101-4 System CAN common P3101-5 P3101-5 SER synch CAN+24V P3101-6 P3101-6 SER synch CAN common P3101-7 P3101-7 Ground - Drain Wire P3101-14 P3101-14 Ground P3101-8 P3101-8 PWM synch CAN +24V P3101-9 P3101-9 PWM synch CAN common P3101-10 P3101-10 MMS synch CAN +24V P3101-11 P3101-11 MMS synch CAN common 1000ft. (300m) Redundant Connections P3103-1 P3103-1 Redundant share CAN +24V P3103-2 P3103-2 Redundant share CAN common P3103-3 P3103-3 Redundant system CAN +24V P3103-4 P3103-4 Redundant system CAN common P3103-5 P3103-5 Redundant SER synch CAN +24V P3103-6 P3103-6 Redundant SER synch CAN common P3103-7 P3103-7 Ground - Drain Wire P3103-14 P3103-14 Ground P3103-8 P3103-8 Redundant PWM synch CAN +24V P3103-9 P3103-9 Redundant PWM synch CAN common P3103-10 P3103-10 Redundant MMS synch CAN +24V P3103-11 P3103-11 Redundant MMS synch CAN common 1. 2. 3. 4. 5. 1000ft. (300m) Belden 810x or Belden 89901 cables are the only approved cables. Belden 89901 cable can be used for underground installations. If using multiple parallel cables for each run, all cables must be run in the same conduit. Each cable group should be run in a separate grounded conduit to ensure redundancy. The maximum lengths must include all the parallel cables from the first module to the last module. The primary and redundant cable lengths can be counted separately. 6. The ground pins on the Inter-Module Communication Board (Pins 7 and 14) are connected together on the board. If using cable with only one (1) drain wire, then connect the ground (drain wire) to Pin 7. 7. Care must be taken to prevent the drain wire from touching any other component in the module. 8. Attach control wires to the side of the control door where the Inter-Module Board (IMC) is attached. Do not run wires across the IMC board. Liebert® NXL™ 14 UPS Electrical Installation Figure 6 Inter-Module Communication Board wiring diagram—Multi-modules IMC 02-806730-xx P3103 P3101 UPS 1 2.4 IMC 02-806730-xx P3103 IMC 02-806730-xx P3101 P3103 P3101 UPS 3 UPS 2 Digital LBS The Load Bus Sync interface enables independent UPS units to remain in sync when operating on battery or when supplied by unsynchronized input sources. Digital LBS cables that connect the module to the system are connected to terminals P3108 and P3109 on the Inter-Module Communication (IMC) board. See Figure 7. Table 6 Wire size, length for digital LBS connection of UPS Inter-Module Communication Boards Terminal Designation From To Wire Size/ Max Length Signal Name Digital LBS from UPS inter-module communication board to other UPS inter-module communication board P3108-1 P3108-1 LBS Synch CANH P3108-2 P3108-2 LBS Synch CANL P3108-3 P3108-3 Ground - Drain Wire 3000ft (900m) Redundant Digital LBS from UPS Inter-Module Communication Board to Other UPS Inter-Module Communication Board P3109-1 P3109-1 Redundant LBS Synch CANH P3109-2 P3109-2 Redundant LBS Synch CANL P3109-3 P3109-3 Ground - Drain Wire 1. 2. 3. 4. 5. 6. Figure 7 3000ft (900m) Belden 810x or Belden 89901 cables are the only approved cables. Each cable group should be run in a separate grounded conduit to ensure redundancy. The maximum lengths must include all the LBS cables from the first module to the last module. The primary and redundant cable lengths can be counted separately. Belden 89901 cable can be used for underground installations. Attach the control wire to the side of the control door where the Inter-Module Board (IMC) is attached. Do not run wires across the IMC board. Inter-Module Communication Board wiring diagram—Digital LBS IMC 02-806730-xx UPS 1 P3108 P3109 IMC 02-806730-xx UPS 2 15 P3108 P3109 IMC 02-806730-xx P3108 P3109 UPS 3 Liebert® NXL™ UPS Electrical Installation 2.5 Configuring Neutral and Ground Connections Improper grounding is the largest single cause of UPS installation and startup problems. Grounding techniques vary significantly from site to site, depending on several factors. Proper grounding should be based on NEC Section 250, but safe and proper equipment operation requires further enhancements. The following pages detail recommendations for grounding various system configurations to ensure optimal UPS system performance. ! CAUTION The UPS ground lug must be solidly connected to the service entrance ground by an appropriately sized wire conductor per NEC Article 250. Each conduit or raceway containing phase conductors must also contain a ground wire, both for UPS input and output, which are solidly connected to the ground terminal at each termination point. Conduit-based grounding systems tend to degrade over time. Therefore, using conduit as a grounding conductor for UPS applications may degrade UPS performance and cause improper UPS operation. 2.5.1 Four-Wire Input connections The UPS module main input and bypass input are connected to a grounded service. In this configuration, the UPS module is not considered a separately derived source. The UPS module output neutral is solidly connected to the building service neutral, which is bonded to the grounding conductor at the service entrance equipment. Advantages of this configuration include: • A measure of common-mode noise attenuation, since the isolation (common-mode rejection) occurs as close to the load as practical (i.e., at the PDU). • The UPS module can be located remotely from the PDU without compromising common-mode noise performance. • By using UPS modules with 480VAC input and output and creating 208VAC at the PDU, smaller and less costly power feeders can be used and less voltage drop (as a percent of nominal) occurs. 2.5.2 Three-Wire Input Connections This configuration must NOT be used when single-phase loads are directly connected to the UPS. The UPS output transformer is considered a separately derived source. The UPS module neutral is bonded to the UPS ground, which is connected to a local grounding electrode in accordance with NEC 250-26. Please note that this configuration represents a price/performance trade-off. Whenever the UPS module transfers to or from bypass, two AC sources (input and bypass) are briefly connected together and circulating current must flow. In this configuration, the current flows through the ground path, possibly tripping ground fault interrupters (GFIs) and distorting the bypass waveform reference. Proper adjustment of ground fault interrupters is necessary to avoid unwanted tripping. The time delay should be set to at least 0.2 seconds to prevent tripping when the UPS performs a transfer or retransfer operation. NOTICE Risk of improperly set ground fault interrupters. Can cause equipment damage. Failure to set the ground fault interrupters properly could cause loss of power to the critical load. 2.5.3 Preferred Grounding Configuration, Battery Systems Open-rack battery systems, depending on local code requirements and customer preference, are normally: • Floating (ungrounded) OR • Center-tapped and floating Battery cabinet systems must be connected as floating (ungrounded) systems. Liebert® NXL™ 16 UPS Electrical Installation Center-tapped or grounded battery systems are not possible with battery cabinet systems. Whether the battery system is open-rack or cabinet, the metal rack parts or cabinet must be grounded to the UPS module ground bus. 2.5.4 Multi-Module Systems For both N+1 and 1+N systems, the neutrals of all UPS modules in the system must be connected together inside the switchgear or parallel cabinet. The neutral conductors must be rated for 20% of phase conductor current minimum. Site and load conditions will determine if larger neutrals are required. For Multi-Module systems using a 3-wire bypass, the Neutral-Ground bond must be made at the common neutral connection point in the switchgear or parallel cabinet. 2.5.5 High Resistance Ground Systems The Liebert NXL is compatible with High Resistance Ground Systems. See your local Emerson representative for details. 2.6 Grounding Diagrams, Single- and Multi-Module Systems Figure 8 Grounding diagram, three-wire single-module system UPS Source N N G Grounding diagram, four-wire single-module system UPS Source BPSS N N G G 17 To connect equipment Figure 9 G To connect equipment BPSS Liebert® NXL™ UPS Electrical Installation Switchgear UPS #1 N Source G N UPS #2 G N G UPS #3 Grounding for 1+N systems is wired exactly the same. Liebert® NXL™ 18 N N G G To connect equipment Figure 10 Grounding diagram, three-wire multi-module system UPS Electrical Installation Figure 11 Grounding diagram, four-wire multi-module system Switchgear BPSS N Source G To connect equipment UPS #1 UPS #2 N BPSS G N G UPS #3 BPSS 19 N N G G Liebert® NXL™ Optional Equipment 3.0 OPTIONAL EQUIPMENT 3.1 Single-Module System Options 3.1.1 Matching Maintenance Bypass Cabinet A matching Liebert NXL Maintenance Bypass cabinet is available. See Maintenance Bypass Cabinet Installation Manual (SL-24532) for more details. 3.1.2 Battery Temperature Sensor The optional external battery temperature sensor kit, supplied separately from the battery circuit breaker, contains one probe and one temperature transport board. 3.1.3 Load Bus Synch An optional Load Bus Synch (LBS) system can be used to synchronize two Liebert NXL UPSs or an Liebert NXL UPS to a Liebert Series 610 UPS. 3.1.4 Remote Alarm Panel The remote alarm panel has LED alarm lights. An audible alarm sounds upon any alarm condition. The surface- or flush-mounted NEMA 1 enclosed panel indicates: Load on UPS, Load on Bypass, Battery Discharging, Low Battery Warning, Overload Warning, Ambient Overtemp Warning, UPS Alarm Condition and New Alarm Condition (for a second UPS alarm condition). 3.2 Communication and Monitoring • • • • 3.2.1 Liebert IntelliSlot™ Unity Card Alber Battery Monitoring System Programmable Relay Board Input Contact Isolator Board Alber Monitoring System The matching Liebert NXL Battery Cabinet allows installing an optional Alber Battery monitoring system in the cabinet. The Alber Battery Monitoring by Liebert continuously checks all critical battery parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic tests of internal resistance of each battery will verify the battery’s operating integrity. Additional capabilities include automatic internal DC resistance tests and trend analysis providing the ability to analyze performance and aid in troubleshooting. Liebert® NXL™ 20 Optional Equipment 3.2.2 Programmable Relay Board The Programmable Relay Board (PRB) provides a means to trigger an external device when an event occurs in the Liebert NXL. Each PRB has eight channels. Each channel has Form-C dry contacts rated at 1A @ 30VDC or 125VAC @ 0.45A. Any alarm/event can be programmed to any channel or channels. Up to four (4) events can be programmed to a relay. If multiple events are grouped to one relay, group the events logically to simplify troubleshooting when an event is triggered. The same alarm/event can be programmed to more than one channel. Up to two Programmable Relay Boards can be installed in the Liebert NXL for a total of 16 channels. Programming is performed through the HMI touchscreen display. NOTE Up to two (2) PRB’s can be installed in the Liebert NXL. Figure 12 Control wiring, Programmable Relay Board 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 J71 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 J72 1 2 3 1 2 3 4 5 6 7 8 9 10111213141516 J73 J74 1. 2. 3. 4. 5. 6. Customer control wiring connection points are terminals 1 through 15. (Pin 16 not used on J71, J72, and J73.) Programmable Relay Board option includes eight signal channels with two Form-C dry contacts per channel (see Table 7). All control wiring (by others) must be run separate from power wiring. Control wiring runs should not be combined in the same conduit. Contact ratings: 1A @ 30VDC or 125VAC @ 0.45A Maximum cable length 500 ft. (152m) with #16AWG and flexible stranded cable. All wiring must be in accordance with national and local electrical codes. Table 7 Terminal Block Programmable Relay Board pinout Channel CH1 J71 CH2 CH3 J72 CH4 CH5 CH6 TB3 J74 CH7 CH8 A B A B A B A B A B A B A B A B Pin No. Common Normally Closed Normally Open 1-3 4-6 7-9 10-12 13-15 1-3 4-6 7-9 10-12 13-15 1-3 4-6 7-9 10-12 13-15 1-3 1 4 7 10 13 1 4 7 10 13 1 4 7 10 13 1 2 5 8 11 14 2 5 8 11 14 2 5 8 11 14 2 3 6 9 12 15 3 6 9 12 15 3 6 9 12 15 3 Note: Pin 16 not used on J71, J72, and J73. 21 Liebert® NXL™ Optional Equipment Configuring the Programmable Relay Board Settings 1. Press Internal Option Settings from the Config menu. 2. Press which Programmable Relay Board will be configured. The Programmable Relay Board dialog box is displayed. 3. Press the Relay channel 4. Press up to four (4) events. Selected events will show up under Relay 1 Assignment. NOTE To deselect an event, click on the event. 5. Repeat Steps 3 and 4 for each relay. 6. Press SAVE to keep the settings. Figure 13 Programmable relay board dialog box • Assignment—0 to 4 event (default: 0) • Delay, sec—0 to 99.9 (default: 0) 3.2.3 Input Contact Isolator Board The Input Contact Isolator Board (ICI) provides a Liebert NXL module interface for up to eight external user alarm or message inputs to be routed through the NXL’s alarm network. The eight contacts are normally open dry contacts. When a contact closes, an event is triggered. NOTE Up to two (2) ICI’s can be installed in a Liebert NXL. The Input Contact Isolator options are configured through the Input Contact Isolator dialog box, which is accessed from the Internal Option Settings under the Config dialog box on the HMI touchscreen display. The Input Contact Isolator dialog box contains eight choices to match the eight channel input board. You can label each button to identify the event associated with the contact. When the dialog box is accessed, each button flashes to display the Input Contact Isolator number and the user entered label. This label also appears in the Display Panel when an event related to an Input Isolator Connector is triggered. Liebert® NXL™ 22 Optional Equipment The Input Contact Isolator dialog box allows you to: • Label the input contact assignments for your setup. • Set the delay for an external event triggering an alarm. • Review the isolator contact assignments, once the labels are entered. The delay allows setting the number of seconds that a condition must exist before it will trigger an alarm. To configure the Input Contact Isolator relays: 1. Press Internal Option Settings from the Config menu. 2. Press which Input Contact Isolator is to be configured. The Input Contact Isolator dialog box is displayed. Figure 14 Input contact isolator dialog box • • • 3. Assignment—Custom, Pre-assigned (default: “Input Contact” XY) Delay, sec—0 to 99.9 (default: 0) Message—Custom: 0-19 characters To assign labels for each channel: a. Press Pre-assigned for default labels on Channels 1-6 (See Table 8) b. For Custom labels 1. Press Custom to unique labels. 2. Click on Input Contact XX button. A keyboard is displayed to allow naming alarms. 3. Enter the name of the alarm set for that input. For example, a fan problem could be indicated by naming the button FAN. 4. Press OK on the keyboard to keep your label. 4. Press DELAY. a. A keypad is displayed prompting you for a delay time, in seconds, for a condition to exist before the alarm is triggered. b. Enter the delay value. The range for the values are from 0 (zero) to 99.9 seconds. c. Press OK on the keypad to keep your setting. The value you entered is displayed in the field adjacent to the corresponding input contact. 5. Repeat Steps 3 and 4 for each input contact. 23 Liebert® NXL™ Optional Equipment 6. Press SAVE after you have configured all input contacts. Be sure to press Save even if you have accessed this dialog only to change a setting. 7. This information is not saved if control power is removed. Table 8 Input Contact Isolator Board pre-assigned values Channel Number ICI #1 Pre-Assigned Label ICI #2 Pre-Assigned Label 1 2 3 4 5 6 7 8 Reduced Rect ILimit Reduced Batt ILimit Stop Battery Charge Inhibit Rect Restrt Inhibit Byp Restrt Inhibit Inv Restrt Input Trap Filter Disconnect Suspend ECO Mode Stop Battery Charge Stop Battery Charge Stop Battery Charge Stop Battery Charge Stop Battery Charge Stop Battery Charge Inhibit IP Standby Figure 15 Optional Input Contact Isolator Board Table 9 No Customer Connection Input Contact Isolator Board control wiring connections Input Contact 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 J51 2 3 4 1. 2. 3. 4. 5. 6. Customer control wiring connection points are terminals 1 through 16 (see Table 9). Customer provided normally open dry contacts for user alarm messages. All control wiring (by others) must be run separate from power wiring. Control wiring runs should not be combined in the same conduit. Signal voltage: 100mA @ 12VDC. Maximum cable length 500 ft. (152m) with #16AWG and flexible stranded cable. All wiring must be in accordance with national and local electrical codes. Liebert® NXL™ 24 5 6 7 8 Pin No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Installation Drawings 4.0 INSTALLATION DRAWINGS Figure 16 Outline drawing, 250kVA, 480V Liebert NXL 57.5" (1460mm) 64.2" (1630mm) Cable Entry Conduit Plte See Detail A TOP VIEW (Doors Open) 71.8" (1824mm) 15" (380mm) 2.2 (57mm) Outside Panel 33.5" (850mm) .9" (23mm) Outside Panel 21.4" (544mm) Power Cable Conduit Plate Control Cable Conduit Plate 6.9" (175mm) 76.8" (1950mm) FRONT CONDUIT DETAIL A 11.4" (290mm) RIGHT SIDE FRONT Cable Entry Conduit Plate See Detail B Control Cable Conduit Plate Power Cable Conduit Plate 7.3" (185mm) BOTTOM 10.4" (264mm) 1.7" (43mm) Outside Frame 2.5" (64mm) To Outside 7.1" (180mm) .2" (5mm) 21.9 (556mm) 11.9" (302mm) Notes 1. All dimensions are in inches (mm). CONDUIT 2. 24" minimum clearance above unit required for air exhaust. DETAIL B 3. Keep cabinet within 15 degrees of vertical while handling. 4. Top and bottom cable entry available through removable conduit plates. Remove, punch to suit conduit size and replace. 5. Unit bottom is structurally adequate for forklift handling. 6. Control wiring and power wiring must be run in separate conduits. 7. All wiring is to be in accordance with national and local electrical codes 8. Width dimension is with side panels. Subtract 1.4" (35mm) for dimensions with both side panels removed. U40-2C-1001 9. Depth dimension includes the front door and rear panel. Rev. 6 10. Refer to technical information drawing for 250kVA/225kW UPS. 25 12.1" (307mm) 2.6 (66mm) Outside Frame Liebert® NXL™ Installation Drawings Figure 17 Outline drawing, 250kVA, 575/600V; and 300kVA, 480/575/600V Liebert NXL Cable Entry Conduit Plate See Detail A 63.8" (1620mm) TOP VIEW (Doors Open) 78.5" (1994mm) 2.2" (57mm) Outside Panel 15" (380mm) .9" (23mm) Outside Panel 33.5" (850mm) 21.4" (544mm) Power Cable Conduit Plate 6.9" (175mm) Control Cable Conduit Plate 76.8" (1950mm) 12.1 (307mm) CONDUIT DETAIL A FRONT RIGHT SIDE 11.4" (290mm) FRONT Cable Entry Conduit Plate See Detail B Control Cable Conduit Plate Power Cable Conduit Plate 7.3" (185mm) BOTTOM VIEW Notes: 1. All dimensions are in inches (mm). 2.24" minimum clearance above unit required for air exhaust. 3. Keep cabinet within 15 degrees of vertical while handling. 4. Top and bottom cable entry available through removable conduit plates. Remove, punch to suit conduit size and replace. 5. Unit bottom is structurally adequate for forklift handling. 6. Control wiring and power wiring must be run in separate conduits. 7. All wiring is to be in accordance with national and local electrical codes. 8. Width dimension is with side panels. Subtract 1.4" (35mm) for dimensions with both side panels removed. 9. Depth dimension includes the front door and rear panel. 10. Refer to technical information drawing for 250kVA 575V or 600V UPS. Liebert® NXL™ 26 10.4" (264mm) 1.7" (43mm) Outside Frame 2.5" (64mm) to Outside 7.1" (180mm) .2" (5mm) 21.9" (556mm) 11.9" (302mm) CONDUIT DETAIL B U40-2C-1006 Rev. 2 2.6" (66mm) Outside Frame Installation Drawings Figure 18 Outline drawing, 400kVA, 480V Liebert NXL 15.0" (380mm) 2.2" (57mm) Outside of Panel Cable Entry Conduit Plate See Detail A 69.5" (1766mm) .9" (23mm) Outside Panel Power Cable Conduit Plate 27.3" (693mm) Top View (Doors Open) Control Cable Conduit Plate 6.9" (175mm) 39.4" (1000mm) 78.5" (1994mm) CONDUIT DETAIL A 12.1" (307mm) 76.8" (1950mm) 11.4" (290mm) 1.7" (43mm) Outside Frame 2.5" (64mm) To Outside 7.1" (180mm) FRONT VIEW .2" (5mm) RIGHT SIDE VIEW FRONT Control Cable Conduit Plate Cable Entry Conduit Plate See Detail B Power Cable Conduit Plate 7.3" (185mm) 11.1" (281mm) 27.8" (706mm) 11.9" (302mm) 2.6" (66mm) CONDUIT BOTTOM VIEW Outside Frame Note: DETAIL B 1. All dimensions are in inches (mm). 2. 24" (610) minimum clearance above unit required for air exhaust and 36" (914) front access required for service. 3. Keep cabinet within 15 degrees of vertical while handling. 4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace. 5. Unit bottom is structurally adequate for forklift handling. 6. Control wiring and power wiring must be run in separate conduits. 7. All wiring is to be in accordance with national and local electrical codes. 8. Width dimension includes side panels. Subtract 1.4" (35mm) when removing both side panels. 9. Depth dimension includes the front door and rear panel. U40-4C-1001 10. See technical information drawing for shipping weights. Rev. 5 27 Liebert® NXL™ Installation Drawings Figure 19 Outline drawing, 400kVA, 575V/600V Liebert NXL Cable Entry Conduit Plate Actual Usable Area 10.2" x 34.2" (260mm x 870mm) 75.3" (1912mm) TOP VIEW 76.8" (1950mm) UPS Cabinet I/O Bypass Cabinet 61.8" (1570mm) 36.6" (930mm) 39.4" (1000mm) 98.4" (2500mm) FRONT VIEW RIGHT SIDE VIEW FRONT Outside Frame 2.9" (74mm) FRONT To Outside Cable Entry Conduit Plate See Detail A Cable Entry Conduit Plate Actual Usable Area 12.8" x 34.2" (325mm x 870mm) BOTTOM VIEW NOTE: 1. All dimensions are in inches (mm). 2. 24" (610) minimum clearance above unit required for air exhaust, and 36" (914) front access required for service. 3. Keep cabinet within 15 degrees of vertical while handling. 4. Top and bottom cable entry available through removable access plates. Remove punch to suit conduit size and replace. 5. Unit bottom is structurally adequate for forklift handling. 6. Control wiring and power wiring must be run in separate conduits. 7. All wiring is to be in accordance with national and local electrical codes 8. Width dimension includes one side panel. Subtract 0.7" (17mm) when removing the side panel. 9. Depth dimension includes the front door and rear panel. 10. See technical information drawing for shipping weights. Liebert® NXL™ 28 Detail A I/O Bypass Cabinet Bottom Cable Entry U40-4C-1006 Rev. 2 3.1" (80mm) Installation Drawings Figure 20 Outline drawing, 400kVA, 575V/600V Liebert NXL with DC I/O cabinet Cable Entry Conduit Plate Actual Usable Area 10.2" x 34.2" (260mm x 870mm) (Service) Access Plate 12" x 12.3" (305mm x 312mm) 19.2" (488mm) Cable Entry Conduit Plate Actual Usable Area 12.1" (307mm) 75.3" (1912mm) TOP VIEW 76.8" (1950mm) DC I/O Cab. UPS Cabinet I/O Bypass Cabinet 77.9" (1978mm) 36.6" (930mm) 114.5" (2908mm) RIGHT SIDE VIEW FRONT VIEW Outside 3.1" Frame (80mm) FRONT To Outside 2.9" (74mm) Outside Frame FRONT To Outside 2.5" (64mm) Cable Entry Conduit Plate Actual Usable Area 12.8" x 34.2" (325mm x 870mm) Cable Entry Conduit Plate Actual Usable Area 9.2" x 34.2" (233mm x 870mm) 39.4" (1000mm) DETAIL A DC I/O Cabinet Bottom Cable Entry DETAIL B I/O Bypass Cabinet Bottom Cable Entry FRONT 3.1" (80mm) Note: 1. All dimensions are in inches (mm]. 2. 24" (610) minimum clearance above unit required for air exhaust and 36" (914) front access required for service. 3. Keep cabinet within 15 degrees of vertical while handling. 4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace. 5. Unit bottom is structurally adequate for forklift handling. 6. Control wiring and power wiring must be run in separate conduits. 7. All wiring is to be in accordance with national and local electrical codes. 8. Width dimension includes side panels. Subtract 1.4" (35mm) when removing both side panels. 9. Depth dimension includes the front door and rear panel. 10. See technical information drawing for shipping weights. Cable Entry Conduit Plate See Detail B Cable Entry Conduit Plates See Detail A U40-4C-1008 Rev. 2 BOTTOM VIEW 29 Liebert® NXL™ Installation Drawings Figure 21 Main components, 250kVA, 480V Liebert NXL HMI Keylock or EMO Button (Optional) Liebert IntelliSlot Housings HMI Screen External Interface Board (EIB) Module Output Circuit Breaker (CB2) Main Input Circuit Breaker (CB1) Back Feed Breaker (BFB) Option Box (6 Slots Available) Input/Output Cabinet Doors and Inner Skins Removed Liebert® NXL™ 30 U40-2C-1000 Rev. 4 Installation Drawings Figure 22 Main components, 250kVA, 575/600V, and 300kVA, 480/575/600V Liebert NXL HMI Screen HMI Keylock or EMO Button (Optional) Liebert IntelliSlot Housings External Interface Board (EIB) Module Output Circuit Breaker (CB2) Back Feed Breaker (BFB) Main Input Circuit Breaker (CB1) Option Box (6 Slots Available) Input/Output Cabinet Doors and Inner Skins Removed 31 U40-3C-1000 Rev. 5 Liebert® NXL™ Installation Drawings Figure 23 Main components, 400kVA, 480V Liebert NXL HMI Keylock or EMO Button (Optional) HMI Screen Liebert IntelliSlot Housings External Interface Board (EIB) Module Output Circuit Breaker (CB2) Main Input Circuit Breaker (CB1) Back Feed Breaker (BFB) Option Box (6 Slots Available) Input/Output Cabinet Doors and Inner Skins Removed Liebert® NXL™ 32 U40-4C-1000 Rev. 3 Installation Drawings Figure 24 Main components, 400kVA, 575V/600V Liebert NXL HMI Screen External Interface Board (EIB) Backfeed Breaker (BFB) Main Input Circuit Breaker (CB1) Module Output Circuit Breaker (CB2) DC Negative Busbar DOORS REMOVED DC Positive Busbar Liebert IntelliSlot Housings Bypass Input & Neutral Busbars Output & Neutral Busbars Rectifier Input Busbars Ground Busbar DOORS AND INNER SKINS REMOVED 33 U40-4C-1005 Rev. 0 Liebert® NXL™ Installation Drawings Figure 25 Main components, 400kVA, 575V/600V Liebert NXL with DC I/O cabinet HMI Screen Backfeed Breaker (BFB) External Interface Board (EIB) Main Input Circuit Breaker (CB1) Module Output Circuit Breaker (CB2) DOORS REMOVED Liebert IntelliSlot Housings Bypass Input & Neutral Busbars DC Positive Busbar Output & Neutral Busbars DC Negative Busbar Rectifier Input Busbars Ground Busbar Ground Busbar DOORS AND INNER SKINS REMOVED Liebert® NXL™ 34 U40-4C-1007 Rev. 0 Installation Drawings Figure 26 Input/output conduit detail drawing, 250-300kVA, all voltages, Liebert NXL DC 3" Conduit, 2 Places Input 3.5" Conduit, 2 Places Output 3.5" Conduit, 2 Places Input 3.5" Conduit, 2 Places DC 3" Conduit, 2 Places Output 3.5" Conduit, 2 Places Low Voltage 1.5" Conduit FRONT TOP VIEW Low Voltage 1" Conduit, 14 Places Low Voltage 1.5" Conduit FRONT BOTTOM VIEW Extended position 76.8" (1950mm) See Detail D For DC Busbars Bypass Neutral DC Positive DC Negative Ground Bus (Top Entry) See Note 6 See Detail D For Input Busbars 59.4" (1509mm) 56.4" (1432mm) UPS Input 52.9" (1343mm) 49.4" (1255mm) 46.4" (1178mm) 43.4" (1102mm) B D 31.4" (797mm) 28.4" (721mm) 25.4" (645mm) Output Inner Panel Removed For Clarity 21.9" (556mm) Ground Bus (Bottom Entry) A C Output Neutral FRONT Ø .56" (14mm) Typical .87" (22mm) 1.75 .87" (44mm) Typical (22mm) 1.75 1.75 (44mm) (44mm) Typical Typical .98" (25mm) (Top Entry) 1.10" (28mm) DETAIL A RIGHT SIDE VIEW 1.75 (44mm) (Bottom Typical Entry) .0" (0mm) Ø .56" (14mm) Typical Ø .56" (14mm) Typical 1.75 (44mm) Typical DETAIL C Notes: DETAIL B 1. All dimensions are in inches (mm). 1.75 2. 24" (610) minimum clearance above unit required for air exhaust, (44mm) and 36" (914) front access required for service. Typical 3. Keep cabinet within 15 degrees of vertical while handling. (Bottom 4. Top and bottom cable entry available through removable Entry) access plates. Remove punch to suit conduit size and replace. 5. Unit bottom is structurally adequate for forklift handling. .88" x .56" Slot 6. These brackets can be removed during installation but must be (22mm x 14mm) replaced after installation. 6 Places 7. Control wiring and power wiring must be run in separate conduits. Each Bar 8. All wiring is to be in accordance with national and local electrical codes. 35 1.75 (44mm) Typical (Top Entry) DETAIL D Ø .56" (14mm) Typical U40-3E-1400 Rev. 3 Liebert® NXL™ Installation Drawings Figure 27 Input/output terminal detail, 400kVA, 480V Liebert NXL DC (2) 3" Conduit Bypass (2) 3.5" Conduit Ø.56 (14)Typ. Output (2) 3.5" Conduit .87 (22) .98 (25) Input (2) 3" Conduit Input (2) 3" Conduit Output (2) 3.5" Conduit Bypass (2) 3.5" Conduit 1.75 (44) Typ. .87 (22) DC (2) 3" Conduit 1.1 (28) DETAIL A Low Voltage 1.5" Conduit 1.75 (44) Typ. (Bottom (Entry) Low Voltage (14) 1" Conduit Low Voltage (14) 1" Conduit 1.75 (44) Typ.(Top (Entry) BOTTOM VIEW TOP VIEW 76.8 (1950) Bypass Neutral DC Positive Dc Negative Ground Bus Location (Top Entry) DETAIL 59.4 (1509) 56.4 (1432) 1.75 (44) 52.9 (1343) Typ. 49.4 (1255) 46.4(1178) 43.4 (1102) .56 40.4 (1026) (14)Typ. 37.4 (950) 34.4 (874) 31.4(797) 28.4 (721) 25.4 (645) 21.9 (556) B See Note 6 Bypass Input Rectifier Input D Output Inner Panel Removed For Clarity A Ground Bus (Bottom Entry) Output Neutral 0 FRONT Liebert® NXL™ RIGHT SIDE VIEW 36 1.75 (44) Typ. DETAIL C 1.75 (44) Typ. (Top (Entry) 1.75 (44) Typ. (Bottom (Entry) C NOTES 1. All dimensions are in inches (mm). 2. 24" minimum clearance above unit required for air exhaust. 3. Keep cabinet within 15 degrees of vertical. 4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace. 5. Unit bottom is structurally adequate for forklift handling. B Ø .56 (14)Typ. .88 x .56 Slot 6 Places DETAIL Each Bar D Ø .56 (14)Typ. 6. These brackets can be removed during installation but must be replaced after installation. 7. Control wiring and power wiring must be run in separate conduits. 8. Unless otherwise noted, use copper or aluminum conductors suitable for at least 75°C. 9. All wiring is to be in accordance with national and local electrical codes. Installation Drawings Figure 28 Input/output terminal detail, 400kVA, 575V/600V Liebert NXL BOTTOM Cable Entry Conduit Plate 12.8" x 33.9" (325mm x 861mm) FRONT TOP Cable Entry Conduit Plate 12.6" x 37" (320mm x 940mm) Bypass Input and Neutral See Detail A 3.1" (80mm) Typ. Between Busbars 51.4" (1305mm) Output and Neutral See Detail B Ground See Detail D 32.9" (835mm) 15.6" (396mm) RIGHT SIDE VIEW 3.1" (80mm) Typ. Between Busbars Ø .512" (13mm) Typ. DETAIL A Detail A & B: Suitable for two-hole lugs (3 each) at 1.75" spacing between hole centers and 1.75" max. tongue width. 15.2" (385mm) Rectifier Input See Detail C FRONT Ø .512" (13mm) Typ. DETAIL B Ø.563" (014mm) Typ. Notes: 1.75" (44mm) 1.75" (44mm) 1. All dimensions are in inches (mm). 2. 24" minimum clearance above unit is required. 3. Keep cabinet within 15 degrees of vertical. 2.56" 0.87" (22mm) 4. Top and bottom cable entry available through removable (65mm) Typ 0.99" (25mm) access plates. Remove and punch to suit conduit size 1.1" (28mm) and replace. DETAIL D 5. Unit bottom is structurally adequate for forklift handling. Ø .512" 6. These brackets can be removed during installation but must (13mm) Typ. U40-4E-1408 be replaced after installation. DETAIL C Rev. 0 7. Control wiring and power wiring must be run in separate conduits 8. All wiring is to be in accordance with national and local electrical codes. 37 Liebert® NXL™ Installation Drawings Figure 29 Input/output terminal detail, 400kVA, 575V/600V Liebert NXL with DC I/O cabinet FRONT Ø.563" (014mm) Typ. 1.75" (44mm) Cable Entry Conduit Plate 9.2" x 17.1" (233 x 435mm) 2 Places 2" (51mm) Typ. Cable Entry Conduit Plate 20.6" x 15" (524 x 381mm) BOTTOM DETAIL A DC POSITIVE Ø.563" (014mm) Typ. 1.75" (44mm) FRONT TOP 2" (51mm) Typ. DETAIL B DC NEGATIVE Ø.563" (014mm) Typ. 1.75" (44mm) DC Positive See Detail A 1.75" (44mm) DETAIL C DC Negative See Detail B 47.1" (1197mm) Ground See Detail C 35.3" (897mm) 24.5" (622mm) FRONT LEFT SIDE VIEW Liebert® NXL™ 38 GROUND NOTES 1. All dimensions are in inches (mm). 2 .24" minimum clearance above unit is required. 3 . Keep cabinet within 15 degrees of vertical. 4. Top and bottom cable entry available through removable access plates. Remove and punch to suit conduit size and replace. 5. Unit bottom is structurally adequate for forklift handling. 6. These brackets can be removed during installation but must be replaced after installation. 7. Control wiring and power wiring must be run in separate conduits 8. All wiring is to be in accordance with national and local electrical codes. U40-4E-1407 Rev. 0 Installation Drawings Figure 30 Top cable entry routing and installation order FOR UNIT RATINGS 250kVA- 480/575/600V 300kVA- 480/575/600V 400kVA- 480V Output Conduit Input Conduit Bypass Conduit DC Conduit DC (Positive) DC (Negative) DC (Positive) DC (Negative) Ground (Top Entry) Bypass Neutral Bypass Neutral Fault Brace Bypass Input Fault Brace Rectifier Input Fault Brace Output Bypass Input Bypass Input (Phase C) Fault Brace Bypass Input Rectifier Input (Phase C) Fault Brace Rectifier Rectifier Input Input Fault Brace Output OUTPUT Output (Phase C) Ground (Bottom Entry) Output Neutral Output Neutral FRONT VIEW SIDE VIEW Recommended cable installation order : 1. DC Power 2. Bypass Neutral 3. Bypass Input Power (Phases A-B-C) 4. Rectifier Input Power (Phases A-B-C) 5. Output Power (Phases A-B-C) 6. Output Neutral 7. Ground The cables must be routed around the fault braces to prevent the cables from coming in contact with other busbars. 39 Liebert® NXL™ Installation Drawings Figure 31 Bottom cable entry routing and installation order FOR UNIT RATINGS 250kVA- 480/575/600V 300kVA- 480/575/600V 400kVA- 480V DC (Positive) DC (Negative) Ground (Top Entry) DC (Positive) DC (Negative) Bypass Neutral Bypass Neutral Fault Brace Bypass Input Fault Brace Rectifier Input Fault Brace Output Bypass Input Fault Brace Bypass Input Bypass Input (Phase C) Fault Brace Rectifier Input Rectifier Input Rectifier Input (Phase C) Fault Brace Output Output (Phase C) Output Ground (Bottom Entry) Output Neutral Output Neutral DC Conduit FRONT VIEW Output Conduit Input Conduit Bypass Conduit SIDE VIEW Recommended cable installation order : 1.) Output Neutral 2.) Output Power (Phases A-B-C) 3.) Rectifier Input Power (Phases A-B-C) 4.) Bypass Input Power (Phases A-B-C) 5.) Bypass Neutral 6.) DC Power 7.) Ground The cables must be routed around the fault braces to prevent the cables from coming in contact with other busbars. Liebert® NXL™ 40 Installation Drawings Figure 32 Single-input busbar arrangement—250-400kVA units 12 x4 13 x4 11 13 x4 14 x8 15 x4 3 Places Isometric View 250, 300 and 400kVA Units Not all parts shown for clarity Figure 33 Low-voltage cable entry—250-400kVA units REMOVE PLATES FLIP PLATES INSTALL Low-voltage cables can be install through the top of each unit. The entry conduit landing plate is shipped inverted. To install, remove conduit plate, flip and reinstall. Removal of side plate is for access to pull wires. 41 Liebert® NXL™ Specifications 5.0 SPECIFICATIONS Table 10 Liebert NXL UPS specifications 250kVA 480V 250kVA 575/600V 300kVA 480V Input Parameters Input Voltage to Rectifier, VAC Input Voltage to Bypass, VAC 400kVA 480V 400kVA 575/600V 480/575/600V 3-phase, 3-wire 480/575/600V 3-phase, 3-wire +10% to -15 -15% to -20% * -20% to -30% ** <-30% *** 60 Input Voltage Range, VAC Input Frequency, Hz Permissible Input Frequency Range, Hz Reflected Input THDi at Nominal Voltage at Full Load, % Power Walk-In, sec Bypass Neutral Current Battery & DC Parameters Battery Type Nominal Battery Bus, VDC Battery Float Voltage, VDC Minimum End of Discharge Voltage, VDC DC Ripple Voltage in Float & Const V Ch. Mode, % Temperature Compensated Battery Charging Output Parameters Inverter Type Output Power, kW Output Voltage, VAC Output Voltage Regulation, % Output Voltage Regulation (100% Unbalanced Load) Output Frequency, Hz Output Frequency Regulation, % Output THDv Linear Load at Nominal Voltage, % Output THDv at Nominal Voltage Including a 100kVA Non Linear Load per EN 62040-3, % Capacity to Handle High Crest Factor Load Capacity to handle Step Load, % Transient Recovery (linear loads), % Unbalance Loads Current Capacity 300kVA 575/600V 55 to 65 <10% with 6-pulse & Passive Filter 1 to 30 (selectable) in 1 sec. Increment 1.7 times full-phase current VRLA (Valve Regulated Lead Acid) or (FLA) Flooded Lead Acid 480V 540V 384V (for VRLA / Flooded Lead Acid) <1 (RMS value) < 3,4% Vpp Standard (with temperature probe) 225 IGBT-based Sine-Sine PWM Controlled 270 480V 3-ph, 4-w < 1% (3-phase RMS average) < 2% (3-phase RMS average) 60 ± 0.1 <2% 2.5% (max) 3:1 0-100 or 100-0 Within 5% peak-to-peak in one line cycle. 100% of nominal phase current * The UPS will operate at full load, but the battery charge will either be reduced or off (depending on input current). ** The UPS will operate at full load, but UPS may source share with the batteries (depending on input current). *** UPS will be in Battery mode Liebert® NXL™ 42 360 400kVA 575/600V with DC I/O Cabinet Specifications Table 10 Liebert NXL UPS specifications (continued) 250kVA 480V Capacity to Handle Leading PF Load 0.9 lag to Nom at 0.95 Lead at 0,9 Lead Voltage Displacement, ° el Overload Conditions, % FL Physical Parameters and Standards, in (mm) 71.8 Width, With Side Panels 1 (1823) 33.5 Depth 2 (850) Height SMS Weight, Unpacked, lb. (kg) 3965 approximate (1798) 1+N Weight, Unpacked, lb. (kg) 4040 approximate (1833) Max heat Dissipation, Full Load, <54,000 BTU/hr (kW) (15.8) Cooling Air CFM Color Front Door Opening (for serviceability) Degree of Protection for UPS Enclosure Minimum Clearance, Top, in (mm) Minimum Clearance, Back, in (mm) Minimum Clearance, Sides, in (mm) Location of Cable Entrance Standards and Conformities Environmental Parameters Storage Temperature Range, °F (°C) Operating Temperature Range, °F (°C) Acoustical Noise, dBA Relative Humidity Maximum Altitude Above MSL, ft (m) 250kVA 575/600V 300kVA 480V 300kVA 575/600V 400kVA 480V 400kVA 575/600V 400kVA 575/600V with DC I/O Cabinet Subject to Max. kW rating Subject to Max. kW rating Subject to 12.5% kW derate or same Rating and 50°F (10°C) Temp. Derate 120° ±1° el (with 100% unbalanced load) 105% for 85 minutes 110% for 60 minutes 125% for 10 minutes 150% for 1 minute 98.4 (2500) 114.5 (2908) 7945 (3604) 8045 (3649) <86,300 (25.3) 7092 8275 (3754) 8375 (3799) <86,300 (25.3) 78.5 (1993) 39.4 (1000) 5440 4840 (2468) (2195) 5515 4915 (2502) (2229) <54,000 <62,000 (15.8) (18.2) 5894 76.8 (1950) 5440 6280 (2468) (2849) 5515 6380 (2502) (2894) <64,500 <74,500 (18.9) (21.8) Black (ZP-7021) More than 180° IP 20 (with and without front door open) 24 (610) 0 0 Top or Bottom UL 1778, 4th Ed; CSA 22.2 107.3; FCC Part 15, Class A FCC, Class A—Standard; IEC62040-2, Level 4, Criteria A EN61000-4-3, Level 3, Criteria A; EN61000-4-6, Level 4, Criteria A; EN61000-2-2, Criteria A EN61000-4-4, Level 4, Criteria A ANSI C62.41, Category A3 &B3; IBC 2012/CBC 2010 ISTA Procedure 1H; WEEE -13 to 158 (-25 to 70) 32 to 104 (0 to 40) (UPS) 68 95% or less Non-Condensing (Operating and Non-Operating) 4920 (1500) (as per IEC 62040/3) - 1% Max kW derate / 328 rise between 4921-9842 (100m rise between 1500-3000m) 1. Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels. 2. Depth dimensions include the front door and rear panel. 43 Liebert® NXL™ Specifications Table 11 Current ratings—rectifier input UPS Rating kVA kW Voltage, VAC Nominal Current Maximum Current 250 225 480 312 389 250 225 575 260 326 250 225 600 250 312 300 270 480 371 464 300 270 575 308 386 300 270 600 295 368 400 360 480 497 621 400 360 575 419 524 400 360 600 401 502 Table 12 Current ratings—bypass input UPS Rating kVA kW Voltage, VAC Nominal Current 250 250 250 300 300 300 400 400 400 225 225 225 270 270 270 360 360 360 480 575 600 480 575 600 480 575 600 301 251 241 361 301 289 481 402 385 Table 13 Current ratings—output UPS Rating Voltage, Nominal kVA kW VAC Current 250 250 250 300 300 300 400 400 400 225 225 225 270 270 270 360 360 360 Table 14 480 575 600 480 575 600 480 575 600 301 251 241 361 301 289 481 402 385 Notes on Tables 1. Nominal input current (considered continuous) is based on full-rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are defined in NEC 100. 2. Maximum input current is controlled by the current limit setting, which is adjustable. Values shown are for a maximum setting of 125%. The standard factory setting is 125%. If a smaller input feed breaker is used, the input current limit must be adjusted accordingly. 3. For units with an input transformer, the Rectifier Input Feed Breaker must be set to handle the Liebert NXL transformer inrush of up to eight times the nominal current. 4. For breaker coordination while the module is overloaded, see the currentversus-time values on the overload curves, Figures 34 and 35. 5. The battery current is at an EOD voltage of 1.61 volts/cell. Current ratings—battery UPS Rating kVA kW AC Input/Output Voltage, VAC Maximum Battery Current at EOD 250 300 400 400 225 270 360 360 480, 575 and 600 480, 575 and 600 480 600 615 730 980 990 Liebert® NXL™ 44 Specifications Table 15 Recommended conduit and cable sizes UPS Rating kVA kW 250 225 250 Voltage (VAC) (# of conduits); size of conduits; # -size of phase cables per conduit; size of cable for ground per conduit Copper Conductors Aluminum Conductors 480 (2) 2C 3-250kcmil, #3AWG (2) 2C 3-350kcmil, #1AWG 225 575 (2) 1.5C 3-#4/0AWG, #3AWG (2) 1.5C 3-250kcmil, #1AWG 250 225 600 (2) 1.5C 3-#4/0AWG, #3AWG (2) 1.5C 3-250kcmil, #1AWG 300 270 480 (2) 2C 3-350kcmil, #2AWG (2) 2.5C 3-500kcmil, #1/0AWG 300 270 575 (2) 2C 3-250kcmil, #3AWG (2) 2.0C 3-350kcmil, #1AWG 300 270 600 (2) 1.5C 3-#4/0AWG, #3AWG (2) 2.0C 3-300kcmil, #1AWG 400 360 480 (2) 2.5C, 3-500kcmil, #1/0AWG (2) 2.5C 3-750kcmil, #3/0AWG 400 360 575 (2) 2.5C 3-350kcmil, #2AWG (2) 2.5C 3-500kcmil, #1/0AWG 400 360 600 (2) 2.5C 3-350kcmil, #2AWG (2) 2.5C 3-500kcmil, #1/0AWG Bypass Input UPS Rating kVA kW Voltage (VAC) 250 225 250 (# of conduits); size of conduits; # -size of phase cables per conduit; #-size of neutral cables per conduit; size of cable for ground per conduit Copper Conductors Aluminum Conductors 480 (2) 2.5C 3-250kcmil, 2-#4/0AWG, #3AWG (2) 2.5C 3-350kcmil, 2-#250kcmil, #1AWG 225 575 (2) 2C 3-#4/0AWG, 2-#2/0AWG, #4AWG (2) 2.0C 3-250kcmil, 2-#4/0AWG, #2AWG 250 225 600 (2) 2C 3-#4/0AWG, 2-#2/0AWG, #4AWG (2) 2.0C 3-250kcmil, 2-#4/0AWG, #2AWG 300 270 480 (2) 2.5C 3-350kcmil, 2-#4/0AWG, #3AWG (2) 2.5C 3-500kcmil, 2-300kcmil, #1AWG 300 270 575 (2) 2.5C 3-250kcmil, 2-#4/0AWG, #3AWG (2) 2.5C 3-350kcmil, 2-250kcmil, #1AWG 300 270 600 (2) 2C 3-#4/0AWG, 2-#4/0AWG, #4AWG (2) 2.5C 3-300kcmil, 2-250kcmil, #2AWG 400 360 480 (3) 3.5C, 3-600kcmil, 2-500kcmil, #1/0AWG (2) 3.5C 3-750kcmil, 2-500kcmil, #1/0AWG 400 360 575 (2) 2.5C 3-#4/0AWG, 2-#4/0AWG, #2AWG (2) 3C 3-300kcmil, 2-300kcmil, #1/0AWG 400 360 600 (2) 2.5C 3-#4/0AWG, 2-#4/0AWG, #2AWG (2) 3C 3-300kcmil, 2-300kcmil, #1/0AWG Output UPS Rating kVA kW Voltage (VAC) 250 225 250 (# of conduits); size of conduits; # -size of phase cables per conduit; #-size of neutral cables per conduit; size of cable for ground per conduit Copper Conductors Aluminum Conductors 480 (2) 2.5C 2-250kcmil, 2-#4/0AWG, #3AWG (2) 2.5C 3-350kcmil, 2-#250kcmil, #1AWG 225 575 (2) 2C 3-#4/0AWG, 2-#2/0AWG, #4AWG (2) 2.0C 3-250kcmil, 2-#4/0AWG, #2AWG 250 225 600 (2) 2C 3-#4/0AWG, 2-#2/0AWG, #4AWG (2) 2.0C 3-250kcmil, 2-#4/0AWG, #2AWG 300 270 480 (2) 2.5C 3-350kcmil, 2-#4/0AWG, #3AWG (2) 2.5C 3-500kcmil, 2-300kcmil, #1AWG 300 270 575 (2) 2.5C 3-250kcmil, 2-#4/0AWG, #3AWG (2) 2.5C 3-350kcmil, 2-250kcmil, #1AWG 300 270 600 (2) 2C 3-#4/0AWG, 2-#4/0AWG, #4AWG (2) 2.5C 3-300kcmil, 2-250kcmil, #2AWG 400 360 480 (3) 3.5C, 3-600kcmil, 2-500kcmil, #1/0AWG (2) 3.5C 3-750kcmil, 2-500kcmil, #1/0AWG 400 360 575 (2) 2.5C 3-#4/0AWG, 2-#4/0AWG, #2AWG (2) 3C 3-300kcmil, 2-300kcmil, #1/0AWG 400 360 600 (2) 2.5C 3-#4/0AWG, 2-#4/0AWG, #2AWG (2) 3C 3-300kcmil, 2-300kcmil, #1/0AWG Battery UPS Rating (# of conduits); size of conduits; # -size of phase cables per conduit; size of cable for ground per conduit kVA kW Copper Conductors Aluminum Conductors 250 225 (2) 2C 2-600kcmil, #1/0AWG (2) 2.5C 2-750kcmil, #3/0AWG 300 270 (2) 2.5C 2-750kcmil, #1/0AWG (3) 2.0C 2-500kcmil, #3/0AWG 400 360 (3) 2C, 2-500kcmil, #2/0AWG (3) 2.0C 2-600kcmil, #4/0AWG 45 Liebert® NXL™ Specifications Table 15 Recommended conduit and cable sizes Bonding UPS Rating Main Bonding Jumper/Grounding Electrode Conductor kVA kW Copper Conductors Aluminum Conductors 250 225 (1) #1/0AWG/ (1) #1/0AWG (1) #1/0AWG/ (1) #1/0AWG 300 270 (1) #2/0AWG/ (1) #2/0AWG (1) #2/0AWG/ (1) #2/0AWG 400 360 (1) #2/0AWG/ (1) #2/0AWG (1) #2/0AWG/ (1) #2/0AWG 1. Recommended cable sizes are 167°F (75°C) (THW) wire at 86°F (30°C) ambient. Unless otherwise noted, use copper or aluminum conductors suitable for at least 75°C. 2. For continuous operations not at 86°F (30°C), recommend that the site planner choose the appropriate cable type based on the particular installation requirements. 3. Conduit size is based on FMC type conduit with two neutral conductors rated at 200% of phase. Liebert® NXL™ 46 Time, seconds 47 0 500 1000 1500 2000 1500 3000 3500 4000 4500 5000 5000 Continuous 100 110 3748 1363 120 937 600 130 394 250 150 60 40 Load, Percent 140 159 100 160 25 15 6 4 180 Time, seconds 170 10 2 190 1 0.5 200 Specifications Figure 34 Inverter overload data Liebert® NXL™ Liebert® NXL™ 48 Continuous 110 120 3000 600 130 394 110% Load - 15,000 Seconds 0 100 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 250 140 159 150 60 40 25 160 Load, Percent 100 15 6 180 4 2 Time, Seconds 170 10 190 1 0.5 200 Specifications Figure 35 Bypass overload data Time, Seconds Specifications Table 16 Recommended lug sizes Cable Size T&B Copper One Hole T&B Copper Two Hole T&B Aluminum One Hole T&B Aluminum Two Hole #8AWG 54930BE 54850BE 60104-TB — #6AWG 54905BE 256-30695-868 60109-TB — #4AWG 54906BE 256-30695-733 60114-TB — #2-3AWG 54942BE 54811BE 60120 — #1AWG 54947BE 54857BE 60126 — #1/0AWG 54950BE 256-30695-593 60132 — #2/0AWG 54951BE 54862BE 60138 60238 #3/0AWG 54965BE 54864BE 60144 60244 #4/0AWG 54970BE 54866BE 60150 60250 250kcmil 54913BE 54868BE 60156 60256 300kcmil 54914BE 54870BE 60162 60262 350kcmil 54915BE 54872BE 60165 60267 400kcmil 54916BE 54874BE 60168 60269 500kcmil 54918BE 54876BE 60171 60273 600kcmil 54920BE 54878BE 60176 60275 750kcmil 54922BE 54880BE 60178 60277 Table 17 Recommended torque values Grade 5 Steel – Unified Thread System Torque Units - lbf.*in. Fastener Finish => Size 1/4 5/16 3/8 7/16 1/2 9/16 Threads/ Inch, Tpi Plain Steel No Washer/ Flat Washer Class 8.8 Steel – Metric Thread System Torque Units - N*m Fastener Finish => Zinc Plating Lock Washer No Washer/ Flat Washer Lock Thread Washer Size Pitch Tp 20 101 — 91 — 28 116 — 104 — 18 209 224 188 203 24 231 246 208 223 16 370 392 333 355 24 420 442 378 400 14 593 — 534 — 20 662 — 596 — 13 904 934 814 844 20 1,020 1,050 918 948 12 1,305 — 1,175 — 18 1,456 — 1,310 — M5 M6 M8 M10 M12 M14 49 Plain Steel No Washer/ Flat Washer Zinc Plating Lock Washer No Washer/ Flat Washer Lock Washer 0.8 6.1 — 5.5 — 0.5 6.9 — 6.2 — 1 10 — 9 — 0.75 11 — 10 — 1.25 25 — 23 — 1 27 — 24 — 1.5 50 64 45 59 1.25 53 67 47 61 1.75 87 128 78 119 1.25 95 136 86 127 2 139 — 125 — 1.5 151 — 136 — Liebert® NXL™ Liebert® NXL™ 50 CB2 and Neutral Output Connection These cables already connected to CB2/Neutral Ouput when shipped. Connect to junction busbars, based on labels (A, B, C, N). Detail A Typical Cabinet-to-Cabinet Bolting M10 x 25 Bolt M10 Split Lock Washer M10 Large Flat Washer Rectifier Input Busbars Phase C Rectifier Input Busbars Phase B Rectifier Input Busbars Phase A Detail B CB1 Input Connection These cables already connected to CB1 input when shipped. Connect to rectifier input busbars, based on labels (A,B,C). I/O Bypass Cabinet Install M10 Large Flat Washer (2) M10 Belleville Washers M10 Nut Torque to 240 in-lb. (27Nm) (3) Places UPS Cabinet Install M10 Large Flat Washer (2) M10 Belleville Washers M10 Nut Torque to 240 in-lb. (27Nm) (5) Places Phase C Junction Busbar Phase B Junction Busbar Phase A Junction Busbar Neutral Junction Busbar DC I/O Cabinet 608841P1 Pg. 1, Rev. 0 Route these cables through the glastic part Specifications APPENDIX A - CABINET INTERCONNECTION Figure 36 Cabinet interconnection cabling Power Supply EIB Board Fuses F42, F43 Fan Interface Board DC I/O CABINET UPS CABINET Fan 13, Fan14 Load V/I Board 51 608841P1 Pg. 2, Rev. 0 CT7, CT8, CT9 behind this glastic plate BPSS Board BYP_PS_B BYP_PS_C I/O BYPASS CABINET Liebert IntelliSlot Bay Specifications Figure 37 Cabinet interconnection cabling (continued) Liebert® NXL™ Specifications Table 18 Cabinet interconnection cabling Cable Part # Cabinet Start Connector Label Cabinet Finish Connector Label These Cables Already Connected to UPS 606986G1 I/O Bypass - IntelliSlot PIN1, PIN2 UPS - EIB Board IntelliSlot 606980G3 I/O Bypass - BPSS Board P0500 UPS - UPSC Board P0500 606985G1 I/O Bypass - BPSS Board P0501 UPS - UPSC Board P0501 607080G1 I/O Bypass - BPSS Board P44 UPS - Power Supply P44 I/O Bypass - BFB BYP_PS_B UPS - F42 F42-1 I/O Bypass - BFB BYP_PS_C UPS - F43 F43-1 I/O Bypass - CT7 X1, X2 UPS - Load V/I Board P0713 I/O Bypass - CT8 X1, X2 UPS - Load V/I Board P0714 I/O Bypass - CT9 X1, X2 UPS - Load V/I Board P0715 I/O Bypass - Fan13 CONNECTOR1 UPS - Fan Interface Board P1005 I/O Bypass - Fan14 CONNECTOR2 UPS - Fan Interface Board P1006 These Cables Already Connected to I/O Bypass 607011G1 607024G1 607045G1 Source: 608841P1, Rev. 0 Liebert® NXL™ 52 Technical Support / Service Web Site www.liebert.com Monitoring [email protected] 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets [email protected] 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246 Locations While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2013 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572 SL-25420_REV15_09-15 Emerson Network Power Division: Liebert Web: www.emerson.com www.EmersonNetworkPower.com