LIEBERT® NXL™, 250-400KVA, SINGLE-MODULE SYSTEM - SITE PLANNING DATA Table 1 Site planning data—250-400kVA UPS Rating kVA kW AC Input/Output Voltage, VAC 250 225 480 Input Isolation Transformer Rectifier AC Input Current Bypass/Output AC Output Current Nom Max Nom 312 389 301 250 225 575 260 326 251 250 225 600 250 312 241 300 270 480 371 464 361 300 270 575 308 386 301 300 270 600 296 369 289 400 360 480 497 621 481 400 360 575 419 524 402 400 360 600 401 502 385 See Notes below: * NO — 1,4,5,7,8,9,11,12 Maximum Battery Current at End of Discharge (A) Maximum Heat Dissipation Full Load, BTU/h (kW) 53,592 (15.7) 615 Dimensions WxDxH, in. (mm) Approximate Weight Unpacked, lb. (kg) 71.8x33.5x76.8 (1823x850x1950) 3965 (1798) 53,662 (15.7) 61,890 (18.1) 730 2,3,5,7,8,9,11,12 4975 (2257) 78.5x33.5x76.8 (1993x850x1950) 64,311 (18.8) 4840 (2195) 5440 (2468) 980 74,173 (21.7) 78.5x39.4x76.8 (1993x1000x1950) 6280 (2849) 990 86,265 (25.3) 114.5x39.4x76.8 * (2908x1000x1950) 6925 (3141) 6,8,9,11,12 — — — Deduct 16.1 inches (409mm) when battery cabinets are attached. Notes for Table 1 1. 2. 3. 4. 5. 6. Nominal rectifier AC input current (considered continuous) is based on full rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current limits are defined in NEC 100. Maximum input current is controlled by current limit setting which is adjustable. Values shown for maximum setting are 125% of nominal input current. Nominal AC output current (considered continuous) is based on full rated output load. Maximum current includes nominal output current and overload current for 10 minutes. Bypass AC input current (considered continuous) is based on full rated output load. Emerson recommends that feeder protection (by others) for the rectifier AC input and the bypass AC input be provided by separate overcurrent protection devices. UPS output load cables must be run in separate conduit from input cables. Power cable from module DC bus to battery should be sized for a total maximum 2.0 volt line drop (power cable drop plus return cable drop as measured at the module) at maximum discharge current. 7. Grounding conductors to be sized per NEC 250-95. Neutral conductors to be sized for full capacity—per NEC 310-16, Note 10—for systems with 4-wire loads and 20% minimum capacity for 3-wire loads. 8. Rectifier AC Input: 3-phase, 3-wire, plus ground AC Output to Load: 3-phase, 3- or 4-wire, plus ground Bypass AC Input: 3-phase, 3- or 4-wire, plus ground Module DC Input from Battery: 2-wire (positive and negative), plus ground 9. All wiring is to be in accordance with National and Local Electrical Codes. 10. Minimum overhead clearance is 2 ft. (0.6m) above the UPS. 11. Top or bottom cable entry through removable access plates. Cut plate to suit conduit size. 12. Control wiring and power cables must be run in separate conduits. Control wiring must be stranded tinned conductors. 13. 10% maximum reflected input harmonic current and 0.92 lagging input power factor at full load. 1 Liebert® NXL™, 250-400kVA, Single-Module System - Site Planning Data Maintenance Bypass Panel (Option) MBB 2 MIB 3 5 AC Output To load UPS Module 4 5 3 Bypass AC input 4 5 BFB 1 Rectifier AC input DC Bus CB1 Battery System 6 CB2 6 MBD The Liebert NXL is compatible with high resistance ground systems. See your local Emerson representative for details. © 2008 Liebert Corporation Technical Support / Service United States All rights reserved throughout the world. Specifications subject to change without notice. 1050 Dearborn Drive 800-543-2378 ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. [email protected] P.O. Box 29186 Web site: www.liebert.com SL-25510_REV3_02-14 2 Columbus, OH 43229