R48-3500e Rectifier Data Sheet​

DC Power for
Business-Critical Continuity™
eSure™ Rectifier
R48-3500e
Key Features
 3500 Watt high-efficiency
rectifier designed for -48V DC
power applications
 Optimized depth –
reduced footprint allows
installation in short-depth
racks and cabinets
 DSP (Digital Signaling
Processor) – means fewer
components, optimized
operation and active load
sharing for increased reliability
In addition to reducing power consumption and
lowering operating cost, eSure™ high-efficiency
rectifiers offer superior performance and
uncompromised reliability.
Description
The eSure™ R48-3500e high-efficiency rectifier is designed to convert standard AC
supply voltages into stable nominal -48V DC voltage that is adjustable to application
needs. The R48-3500e is a constant power rectifier designed with the latest patented switchmode technology, using DSP (Digital Signaling Processor) functionality for
efficient operation.
For a higher load capacity, rectifiers can be connected in parallel, and intelligent
control can be added with the help of a separate controller.
 Compliant with global
standards – delivers quality,
performance and reliability no
matter what the application or
location demands
 High efficiency, approaching
97% – reduces power
consumption for lower
operating costs
 Hot pluggable – facilitates
future extensions
 Wide input voltage range to
operate in the most
demanding environments
where input voltage changes
Sure™ Rectifier
Effi iency Curve
 Wide temperature operating
range (-40°C / -40°F to +75°C /
167°F) to meet the harshest
climatic environment
requirements
2012.10
1
eSure™ Rectifier R48-3500e
Control and Monitoring
Rectifier Alarm and Signaling
Visual Indications
Environmental
Temperature Range, Operating
Temperature Range, Storage
Relative Humidity
Altitude
120
100
80
60
40
20
0
-40
-20
0
See diagram
73A
7.3 to 73A
96.5% peak
<2 mV; <32 dBrnc
See diagram
Mechanics
Dimensions (H x W x D)
Weight
132 x 85.3 x 287mm / 5.2 x 3.36 x 11.3 inches
3.5kg / 7.7Ibs
Other Parts
Controller Units
See separate ACU/ACU+ and SCU/SCU+ datasheets
40
60
80
100
Output Power vs. Input Voltage
and Vo > 48V at Temp <45°C
Alarm and status reported via CAN bus to system controller
Green LED:
Normal Operation
Yellow LED:
Alarm
Red LED:
Failure
Flashing Red LED:
Fan Failure
Safety
20
Temperature (C°)
-42 to -58 V DC
3500W@Vout >48VDC
-40 to +75°C, -40 to +167°F
-40 to +70°C, -40 to +158°F
0 to 95%
2000 m, 6560 ft at full power
ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B,
Telcordia GR-1089-CORE class B
IEC 60950, EN 60950, UL 60950
EMC
Output Power vs. Temperature
at 264 ≥ Vin ≥176Vac
% of max output power
DC Output
Output Voltage, Adjustment Range
Output Power
Output Power,
Derated for Input Voltage
Output Current
Output Current Limit Set Point
Efficiency
Psophometric Noise (system)
Temperature Derating
200 to 250 VAC
85 to 300 VAC
45 to 65 Hz
22.5A
0.99
<5% from 50 to 100% of rated load
120
100
80
60
40
20
0
0
50
100
150
200
250
300
350
Input Voltage (VAC)
Output voltage vs. Output current
at max. output power 3500 W
Output Voltage (V)
AC Input
Input Voltage, Nominal
Input Voltage, Permitted Variation
Line Frequency
Max Input Current
Power Factor
THD (Total Harmonic Distortion)
Diagrams
% of max output power
Technical Specifications
70
60
50
40
30
20
10
0
0
10 15 20
25 30 35 40
45
50 55
60 65 70
75
Output Current (A)
Ordering Information
Model Number
1R483500E2
Description
Rectifier 48V, 3500W
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power Energy Systems North America 2012.
Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson® and Consider it Solved are service marks and trademarks of Emerson Electric Co.
EnergyMaster™, eSure™, NetPerform™, NetReach™, NetSpan™, NetSure® and NetXtend ™ are trademarks of Emerson Network Power Energy Systems North America.
2
2012.10